Professional Documents
Culture Documents
Handbook Sprinkler System
Handbook Sprinkler System
1723 and consisted of a cast of water, a chamber of gun powder, and a system
of fuses. In about 1852 the perforated pipe system represented the first form of a
sprinkler system used in the United States. In 1874, Henry S. Parmelee of New Haven,
Connecticut, patented the first practical automatic sprinkler.
C.J.H. Woodbury of the Boston Manufacturers Mutual Fire Insurance
Company & F.E. Cabot of the Boston Board of Fire Underwriters completed a study
on the performance of the sprinklers for the Factory Mutual Fire Insurance Company in
1884. This study was the basis for the first set of rules for the installation of Automatic
Sprinkler systems that were developed by John Wormald of the Mutual Fire Insurance
Corporation of Manchester, England in 1885. In 1887, similar rules were prepared in the
United States by the Factory Improvement Committee of the New England Insurance
Exchange.
In 1895, the commercial growth and development of sprinkler systems was so
rapid that a number of different installation rules had been adopted by various insurance
organizations. These problems lead to the creation of NFPA 13 and the formation of the
NATIONAL FIRE PROTECTION ASSOCIATION in 1896.
As has been the case for over 100 years, the intent of the NFPA is to provide a
means for analyzing sprinkler system information and presenting it a form that
will lead into effective system designs & installations. This task continues to
become increasingly demanding as scientific and other discoveries generate
information at an increasingly accelerated rate. In response to these challenges, NFPA
expanded the scope of NFPA 13 so that it is the most comprehensive document
addressing sprinkler systems.
NFPA 13:1.2.1
“The purpose of this standard shall be to provide a reasonable degree of protection for life and
property from fire through standardization of design, installation, and testing requirements for
sprinkler systems, including private fire service mains, based on sound engineering principles,
test data, and field experience.”
“As an installation standard, NFPA 13 DOES NOT specify the buildings or structures that require
sprinkler systems. The purpose of NFPA 13 is to provide for the proper DESIGN & INSTALLATION
of the sprinkler system and to specify acceptable system components when a sprinkler system is
required. In other words, NFPA 13 specifies HOW to properly design & install a sprinkler system
using the proper components. The standard DOES NOT identify when the system is required.”
Cross
Main
#
A sprinkler system employing automatic sprinklers that are attached to a piping system
containing water and connected to a water supply that contains air that might or might
not be under pressure, with a supplemental detection system installed in the same
areas as the sprinklers.
# #
Preaction systems operate in several of ways and perform a variety of functions: (1)
Non-Interlocking; (2) Single Interlocked; (3) Double Interlocked. The detection system
may be hydraulic, pneumatic or electric and maybe actuated by manual, fixed
temperature rate of rise or other means. Detection system operates before the sprinkler
fuses and gives an alarm.
$ (
A sprinkler designed to be installed in such a way
that the water spray is directed upwards against the
deflector.
#
A sprinkler having special deflectors that are designed to discharge
most of the water away from the nearby wall in a pattern resembling
one-quarter or a sphere, with a small portion of the discharge directed at
the wall behind the sprinkler.
)$
A sprinkler designed for use in light & ordinary hazard,
commercial occupancies such as banks, hotels,
shopping malls, schools hospitals, etc. Sprinklers that
have a thermal element with an RTI of 50 (meter-
seconds)1/2 or more.
# $ *#
A type of fast-response sprinkler that have a thermal element with
an RTI of 50 (meter-seconds)1/2 or more. And is listed for its
capability to provide fire suppression of specific high-challenge fire
hazards.
+ , #
A sprinkler which coverage is up to 400 ft2 for light & ordinary
hazard & 196 ft2 for extra hazard. Their use is especially
advantageous as a means of decreasing the number of sprinklers to
protect occupancies requiring an area/density application of water.
#
A recessed sprinkler with cover plates. These are decorative
sprinklers featuring a flat cover plate designed to conceal the
sprinkler. It is the best choice for architecturally sensitive areas
such as hotel lobbies, office buildings, churches & restaurants.
#
A type of specific application control mode sprinkler that is capable
of producing characteristic large water droplets and that is listed for
its capability to provide fire control of specific high-challenge fire
hazards. In some cases, they can provide an economic advantage
by eliminating in-rack sprinklers.
'!
#
A type of fast-response sprinkler that has been
specifically investigated for its ability to enhance
survivability in the room of fire origin and is listed for
use in the protection of dwelling units.
NFPA 13: 6.2.3.1 The K-factor, relative discharge, and NFPA 13: 6.2.5.1 Automatic sprinklers shall have their frame
marking identification for sprinklers having different orifice sizes arms, deflector, coating material, or liquid bulb colored in
shall be in accordance with Table 6.2.3.1. accordance with the requirements of Table 6.2.5.1.
!" " "
COMMODITY REFERENCES:
* NFPA 13: A.5.6.3 to A.5.6.4.1 – Examples of Commodity Class
* NFPA 13: 5.6.4 – Classification of Plastics, Elastomers, and Rubber. Plastics, lastomers, and rubber (classified as Group
A, Group B, or Group C)
* NFPA 13: 5.6.2 – Pallet Types:
\ # " 6
* # 14 11/3/4/3/1/1 The water supply requirement for sprinklers only shall be calculated from
the density/area curves of Figure 11.2.3.1.5.
* # 14 7/3/1 The maximum floor area on any one floor to be protected by sprinklers supplied by
any one sprinkler system riser or combined system riser shall be as follows:
(1) Light hazard — 52,000 ft2 (4831 m2)
(2) Ordinary hazard — 52,000 ft2 (4831 m2)
(3) Extra hazard : (a) Pipe schedule — 25,000 ft2 (2323 m2)
(b) Hydraulically calculated — 40,000 ft2 (3716 m2)
(4) Storage — High-piled storage (as defined in 3.3.12) and storage covered by other NFPA
standards — 40,000 ft2 (3716 m2)
* # 14 7/8/3/3/3 The maximum area of coverage of any sprinkler shall not exceed 400 ft2 (36 m2).
* # 14 7/8/4/3/1 The distance from sprinklers to walls shall not exceed one-half of the allowable
maximum distance between sprinklers.
* # 14 7/9/4/4 Minimum Distances from Walls. Sprinklers shall be located a minimum of 4 in.
(102 mm) from a wall.
* # 14 7/9/3/3/1: The maximum allowable protection area of coverage for a sprinkler (As) shall
be in accordance with the value indicated in Table 8.6.2.2.1(a) through Table 8.6.2.2.1(d).
COVERAGE SPACING
2
* Light Hazard : 18.6 m (pipe schedule) 4.6 m
2
: 20.9 m (hydraulically calculated) 4.6 m
2
* Ordinary Hazard : 12.1 m 4.6 m
2
* Extra Hazard : 8.4 m (pipe schedule) 3.7 m
2
: 9.3 m (hydraulically calculated 3.7 m
w/ density >= 0.25)
2
: 12.1 m (hydraulically calculated 4.6 m
w/ density <= 0.25)
* # 7/19/3/8/1 A listed check valve shall be installed in each fire department connection.
* # 14 9/4/1/1 Aboveground Pipe or tube shall meet or exceed one of the standards in Table
6.3.1.1 or be in accordance with 6.3.6.
* Welded & Seamless Steel Pipe ANSI / ASTM A 53
* Electric Resistance-Welded Steel Pipe ANSI / ASME B36.10M ASTM A 135
* Seamless Copper Water Tube ASTM B 88
* # 14 15/1/1: Listing. Underground Piping Materials shall be listed for fire protection service or
shall comply with the standards in Table 10.1.1.
* Ductile Iron, Steel, Concrete, Plastic (PVC), & Copper AWWA / ASTM
* # 14 11/3/3/1 Table 11.2.2.1 shall be used in determining the minimum water supply requirements for
light and ordinary hazard occupancies protected by systems with pipe sized according to the pipe schedules of
Section 14.5.
\ & "
* # 14 13/4/1/3/1 Sprinkler protection criteria for the storage of materials on racks shall be in
accordance with 12.3.2 or 12.3.3 for storage up to 25 ft (7.6 m), and 12.3.4 and 12.3.5 for storage
over 25 ft (7.6 m).
* # 14 1;/;/;/7/1 Minimum operating pressure of any sprinkler shall be 7 psi (0.5 bar).
* # 14 1;/8/3/1/1 Unless permitted by 14.5.2.1.2 or 14.5.2.1.3, branch lines shall not exceed
eight sprinklers on either side of a cross main.
* # 14 1;/8/3/1/3 Where more than eight sprinklers on a branch line are necessary, lines shall
be permitted to be increased to nine sprinklers by making the two end lengths 1 in. (25.4 mm) and 1¼
in. (33 mm), respectively, and the sizes thereafter standard.
* # 14 1;/8/3/1/4 Ten sprinklers shall be permitted to be placed on a branch line, making the
two end lengths 1 in. (25.4 mm) and 1¼ in. (33 mm), respectively, and feeding the tenth sprinkler by a
2½-in. (64-mm) pipe.
* # 14 9/1/4 " / System
components shall be rated for the maximum system
working pressure to which they are exposed but shall
not be rated at less than 175 psi (12.1 bar) for
components installed aboveground and 150 psi (10.4
bar) for components installed underground.
* # 14 1;/8/1/4 The number of automatic
sprinklers on a given pipe size on one floor shall
not exceed the number given in 14.5.2, 14.5.3,
or 14.5.4 for a given occupancy.
\ < # " => * & !"
* #
“The SUM of all of the Sprinkler Flows at the remotest area.”
$ #
“Pressure needed at the Sprinklers to ensure that they FLOW at
the required level”
• PN = (Q / K)2
where:
PN = End-Head Pressure in PSI
Q = Remotest Sprinkler Flow in GPM
K = Sprinkler K-Factor in GPM / (PSI)1/2
“Pressure needed to OVERCOME the effects of Gravity”
• Pe = 0.434 X (H)
where:
Pe = Elevation Pressure in PSI
H = Elevation Difference Between Remotest
Sprinkler & Water Source in FEET
“Pressure needed to OFFSET the losses caused by the water
flowing through the system Pipes, Valves, and Fittings”
* # 14 # ?#
\ < # " => "@!
* # 14 1;/;/4/1/1 Table 14.4.3.1.1 shall be used to determine the equivalent length of pipe
for fittings and devices unless manufacturer's test data indicate that other factors are appropriate.
* # 14 1;/;/;/;/9
The calculated pressure at each
sprinkler shall be used to determine
the discharge flow rate for that
particular sprinkler.
Notes:
1. Do not include fitting loss for straight-
through flow in a tee or cross.
2. Include pipe, fittings, and devices
such as valves, meters, flow switches
in pipes 2 in. or less in size, and
strainers, and calculate elevation
changes that affect the sprinkler
discharge.
3. Use the equivalent feet value for the
standard elbow on any abrupt 90-
degree turn, such as the screw-type
pattern.
4. Friction loss shall be excluded for the
fitting directly connected to a
sprinkler.
5. Calculate the loss for a tee or a cross
where flow direction change occurs
based on the equivalent pipe length
of the piping segment in which the
fitting is included.
\ "& ! @! &
,
Area Description : TEXTILE WAREHOUSE / MANUFACTURING
Commodity : Textile Products in Pallet (Stockpiles < 3.7 m Height)
Dimension : 80 m (L) X 30 m (W) X 10 m (H)
Determine : Pump Capacity, # of Sprinklers Required, Size / Quantity of
Alarm Check Valve Assembly, & Water Tank Capacity
$
(1.0) Design Basis:
Hazard Classification : Ordinary Hazard Grp. 2 - NFPA 13: Annex A.5.3.1
Area of Sprinkler Operation : 1, 500 ft2 (139 m2) - NFPA 13: 11.2.3.2.1.1
Design Density : 0.20 gpm / ft2 - NFPA 13: 11.2.3.2.1.1
Sprinkler Coverage (As) : 12 m2 – NFPA 13: 8.6.2.2.1
= 340.83 GPM
Hose Stream Demand / Allowance – (QH):
QH = Inside (Hose Cabinets) + Outside (Hydrants)
= 250 GPM – NFPA 13: Table 11.2.3.1.1
TOTAL SYSTEM FLOW DEMAND = Qs + QH = 590.83 GPM say 750 GPM
(6.0) Required No. of Riser / Alarm Check Valve Ass’y. – NFPA 13: 8.2.1(2)
= Area of the Warehouse = (80m X 30m) = 1 SET
Max. Area per Riser 4831 m2
(7.0) Water Tank Capacity = System Demand Flow X Duration – NFPA 13: Table 11.2.3.1.1
= 750 GPM X 60 MINS. (minimum)
= 45,000 Galons
$ #