ELECTRICAL CORE TEST REPORT Report No: PDC/001
Thi sto be completed vhen conlutng ir-house tests and examinaten of equipment by planned Makenance Systems and
folowing repair or overhaul of equipment
Equipments tobe tested in accordance wit the requirements of MCA DO18
(The intial and Peredie Examination Testing and Certification of Dhing Pit and Equipment)
TEST TYPE | 6 MONTHLY : VISUAL EXAMINATION & FUNCTION TEST
EQUIPMENT | MODEL. 3007A _INSULATION-CONTINUITY TESTER / KYORITSU
TOOATION SAT CONTROL ROOM,
DETAILS OF ELECTRICAL CORE TEST
CORE ID NO. ‘CORE FUNCTION. ‘CONTINUITY RESISTANCE PASSIFAIL
1 [BULL HORN L oK OK
2 BULL HORN N OK OK
3 [ait PHONE L OK OK
4 JAIR PHONE N OK OK
8 [CALL BUTTON L OK OK
6 JCAL BUTTON N oK OK
7 INTERNAL CAMERA L OK OK
8 INTERNAL CAMERA N OK OK
8 INTL CAM POWER: L OK OK
10__|INTLCAMPOWER N OK OK
11 [Sensor4 L OK OK
12___|[sensor1 N OK OK
[Halin Corporate Senices Pte Ua TNICA DOT March, 2008
[rest Procedures Reference Detal Shoet
Date of Test SEPTEMBER, 08 Tovation Newt Test Due
[Tested by Witnessed by
Sionature Signature
Name Name
Designation: TECHNICIAN Designation: TECHNICIAN~~ Hallin
ELECTRICAL CORE TEST REPORT Report No; DDC/002
‘This is fo be completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
{oliowing repair or overhaul of equipment
Equipment isto be tested in accordance with the requirements of IMCA DO18
(The Intial and Peviodie Examination Testing and Certification of Diving Plant and Equipment)
TEST TYPE | 6 MONTHLY : VISUAL EXAMINATION & FUNCTION TEST
equipment | MODEL3007A —_INSULATION-CONTINUITY TESTER / KYORITSU
LOCATION SAT GONTROL ROOM
DETAILS OF ELECTRICAL CORE TEST
[CORE ID NO [CORE FUNCTION ‘CONTINUITY, RESISTANCE, PASSIFAIL
19 [OsHLIGHT1,.2.3 te ‘OK
20 [OFHLIGHT1,.2.3 N OK
21 BK LIGHT L5,6,7.8 L OK
2 |B/KUGHTL 56.78 N OK
23 (B/KUGHTR 12.34 L OK
24 (B/KLIGHTR 1.2.3.4 N oK
25 [SCRUBBER 3,46, L OK
26 [SCRUBBERL3,46 N OK
29 [SCRUBBER 1,2,5 L OK
20 [SCRUBBER R 1,25 N OK
a HouLsa4 L OK
22 |HcuLaaa N OK
a3 [HCUL182 L OK
34 |HouL1a2 N OK
[Halin Corporate Services Pre Lid THGAD 018 > March, 2007
[Test Procedures Reference Delail Shoo!
Date of Test SEPTEMBER 08 Tocation Next Test Due
[Tested by Witnessed by
Signature Signature
Name NameELECTRICAL CORE TEST REPORT
‘This is tobe completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
following repair or overhaul of equipment
Equipment is tobe tested in accordance with the requirements of IMCA D018
—~= Hallin
(The Intel and Periodic Examination Testing and Certification of Diving Piet and Equipment)
Report No
TEST TYPE | 6 MONTHLY: VISUAL EXAMINATION & FUNCTION TEST
equipment | MODEL3007A —_INSULATION-CONTINUITY TESTER / KYORITSU
LOCATION SAT CONTROL ROOM,
DETAILS OF ELECTRICAL CORE TEST
CORE 1D NO | CORE FUNCTION ‘CONTINUITY RESISTANCE PASS/FAIL
Lu a v
N a v
L Q v
N a v
L a v
N a v
[Falin Corporate Services Pte Lid TCAD O18 —- March, 2001
[Test Procedures Reference Deiail Sheet
Date of Test Location Next Test Due
[Tasted by Witnessed by
Signature Signature
Name Name
Designation “TECHNICIAN Designation _: TECHNICIAN.—~> Hallin
ELECTRICAL CORE TEST REPORT Report No: TUP/O0%
‘Tis isto be completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
following repair or overhaul of equipment
Equipment i to be tested in accordance with the requirements of INCA D018
(The intial and Periocic Examination Testing and Cextficaton of Diving Plent and Equipment)
TEST TYPE | 6 MONTHLY : VISUAL EXAMINATION & FUNCTION TEST
EQUIPMENT | MODEL 007A _INSULATION-CONTINUITY TESTER / KYORITSU
TOGATION SAT CONTROL ROOM
DETAILS OF ELECTRICAL CORE TEST
CORE ID NO ‘GORE FUNCTION. CONTINUITY RESISTANCE PASS/FAIL
1 [BULL HORN’ L OK ‘OK
2 BULL HORN. N OK OK
3 [spt L OK ‘OK
4 SPT. N OK OK
5 CaLL BUTTON iy OK OK
6 CALL BUTTON N OK OK
7 [air PHONE L OK OK
8 [AIR PHONE N OK OK
9 [CAMERA L oK OK
10 CAMERA L OK OK
a CAMERA N OK OK
72 ‘[sensort k OK OK
13 [sensor1 N OK OK
alin Engineering Services Pte Lid TCAD O18 + March, 2001
[Test Provedures Reference etal Sheet
[Date of Tost SEPTEMBER 08 Tocation Next Test Due
Tested by Witnessed by
[Signature Signature
Name Name
Designation _: TECHNICIAN Designation _: TECHNICIANELECTRICAL CORE TEST REPORT
‘This is tobe completed when conducting in-house tests and examination of equipment by planned Mainlenance Systems and
{allowing repair or overhaul ef equipment
Equipment isto be tested in accordance with the requirements of IMCA D018
~~ Hallin
(The initial and Pesiocic Examination Testing and Certification of Diving Plan and Equioment)
Report No: TUPIO02
TESTTYPE | 6 MONTHLY: VISUAL EXAMINATION & FUNCTION TEST
equipment | MODEL3007A —_INSULATION-CONTINUITY TESTER / KYORITSU
TOGATION SAT CONTROL ROOM
DETAILS OF ELECTRICAL CORE TEST
[CORE ID NO | CORE FUNCTION CONTINUITY, [RESISTANCE PASSIFAIL,
19 fOsHUIGHT 1, OK ‘OK
20 [ov HLIGHT 4, OK ‘OK
21 O/H LIGHT 1) OK OK
22 |O/HLIGHT 1, OK OK
23 |scrUBBER OK OK
24 [SCRUBBER OK 0K
25 [SCRUBBER OK OK
26 [SCRUBBER OK OK
Ed Hou OK 0K
28 |Hcu ok OK
22 |Hcu OK ‘OK
30 [HcU OK OK
[Halin Engineering Services Ple Lid TCAD O18 March, 2007
[Test Procedures Referance Detail Sheet
Date of Tet SEPTEMBER ,08 Tocation Next Test Due
[Tasted by Witnessed by
Signature Signature
Name Name
[Designation _: TECHNICIAN Designation _: TECHNICIAN<> Hallin
ELECTRICAL CORE TEST REPORT
“This isto be completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
following repair or overhaul of equipment
Equipment is to be tested in accordance with the requirements of IMCA DO18
(he intial and Periodic Examination Testing and Cerifcetion of Diving Pint and Equipment)
Report No; HRC/001
TEST TYPE | 6 MONTHLY : VISUAL EXAMINATION & FUNCTION TEST
EQUIPMENT | MODEL.3007A —_INSULATION-CONTINUITY TESTER / KYORITSU
TOCATION __ FLYAWAY CONTROL ROW.
DETAILS OF ELECTRICAL CORE TEST
‘CORE ID NO ‘CORE FUNCTION ‘CONTINUITY RESISTANCE PASSIFAIL,
1 BULL HORN L OK OK
2 [BULL HORN N OK OK
3 CALL BUTTON. L OK OK
4 [CALL BUTTON N OK OK
5 Jai PHONE: L OK OK
6 [AIR PHONE: N OK OK
7 ser L OK ‘OK
8 [ser N OK OK
8 CAMERA L OK OK
10 CAMERA u OK OK
1" JCAMERA N OK OK
3 [SENSOR 1 L OK OK
14 [SENSOR 1 N OK OK
[Malin Corporate Services Pte Lid TCAD O18: March, 2007
[Test Procedures Reference Detail Sheet
Date of Test SEPTEMBER, 2008 Tocation Next Test Due
[Tested by ‘Winessed by
Signature Signature
Name Name
[Designation _: TECHNICIAN Designation _: TECHNICIANELECTRICAL CORE TEST REPORT
‘This sta be completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
following reper or overhaul of equipment
Equipments tobe tested in accordance with the requirements of IMCA D018
~~ Hallin
Report No: HRC/002
(The Inttal and Periodic Examination Testing and Certification of Diving Plan and Equipment)
TeSTTYPE | 6 MONTHLY: VISUAL EXAMINATION & FUNCTION TEST
equipment | MODEL.2007A _INSULATION-CONTINUITY TESTER / KYORITSU
LOCATION HRC CHAMBER
DETAILS OF ELECTRICAL CORE TEST
CORE ID NO | CORE FUNCTION CONTINUITY RESISTANCE PASS/FAIL
19 [OVERHEAD LIGHT 1 L OK OK
20 [OVERHEAD LIGHT 1 N OK OK
21 OVERHEAD LIGHT 2 L OK OK
22 JOVERHEAD LIGHT 2 N OK OK
23 |OVERHEAD LIGHT 3 L OK OK
24 [OVERHEAD LIGHT 3 N OK OK
25 [SX BUNK LIGHT L OK OK
26 [SX BUNK LIGHT N OK OK
27 [SCRUBBER 18.2 L OK OK
28 [SCRUBBER 182 N OK OK
20 [SCRUBBERS a4 L OK OK
30 [SCRUBBER 3&4 N OK OK
34 SCRUBBER 5 & 6 L OK OK
32 [SCRUBBERS 86 N OK OK
33 |SENSOR2 L OK OK
34 [SENSOR2 N OK OK
36 _|SENSOR3 L OK OK
36___|SENSORS N OK OK
Halin Corporate Services Pte Lid THOAD O18 March, 2007
Test Procedures Reference etal Sheet
[Date of Test SEPTEMBER, 2008 Tocation Naxt Test Due
Tasted by Witnessed by.
Signature Signature
Name Name
[Designation _: TECHNICIAN Designation _: TECHNICIAN—~ > Hallin
ELECTRICAL CORE TEST REPORT Report No: DIVEIO0!
“This sto be competed when conducting l-house tests and examination of equipment by planned Maintenance Systems and
following repair or overhaul of equipment
Equipment isto be tested in accordance withthe requirements of MCA DO18
(The intial anc Pesodle Examination Testing and Certcation of Diving Plant and Equipment)
TEST TYPE | 6 MONTHLY : VISUAL EXAMINATION & FUNCTION TEST
EQUIPMENT | MODEL3007A _INSULATION-CONTINUITY TESTER / KYORITSU
TOCATION DIVE CONTROL ROOW,
DETAILS OF ELECTRICAL CORE TEST
‘CORE IDNO ‘CORE FUNCTION. ‘CONTINUITY RESISTANCE PASSIFAIL
1 |CALL BUTTON L OK OK
2 [CALL BUTTON N OK OK
3 BULL HORN L OK OK
4 [BULL HORN N OK ok
5 [ser L oK OK
6 [ser N OK OK
7 JowveR 1 EAR L ok OK
8 DIVER 1 EAR N OK OK
8 JoivER 1 mic. L OK OK
10 [overs mic N OK OK
1" [DIVER 2 EAR & oK OK
12 [DIVER2 EAR N OK OK
13 [pveramic L OK OK
14 [pver2mic N OK OK
16 _ [DIVERS EAR L OK OK
16 [DIVERS EAR N OK OK
17 |pweRsmic ks OK OK
18 [DveRsmic N OK OK
[Halin Corporate Senioes Ple Lid THEA DOT = March, 2007
[Test Procedures Reference Det Sheet
[Date of Test SEPTEMBER 2008 Tecation Newt Test bus
Tested by ‘Winessed by
[signature Signature
IName Name
[Designation
TECHNICIAN
Designation: TECHNICIAN—~> Hallin
ELECTRICAL CORE TEST REPORT Reporte DNE/02
‘This fo be completed when conducting in-house tests and examination of equipment by planned Maintenance Systems and
fellowing epeir or overhaul of equipment
Equipment is tobe tested in accordance withthe requirements of IMCA D018
(The intial end Periocic Examination Testing and Cetication of Diving Plant and Equipment)
rest TPE | 6 MONTHLY: VISUAL EXAMINATION & FUNCTION TEST
lequipment | MODEL 30078 _INSULATION-CONTINUITY TESTER / KYORITSU
TOCATION DIVE CONTROL ROOM
DETAILS OF ELECTRICAL CORE TEST
[COREIDNO | CORE FUNCTION ‘CONTINUITY RESISTANCE PASS/FAIL,
25 (BELLINT'LOAMERA LL OK OK
26 (BELLINT'LCAMERA LL OK OK
27 |BELLINT'LCAMERA ON OK OK
28 |DWERT CAMERA L OK OK
29 [DIVER 1 CAMERA L OK OK
30 [DIVER 1 CAMERA N OK OK
3 [DVER2 CAMERA L OK OK
32 [DIVER 2 CAMERA u OK OK
33 [DIVER 2 CAMERA N OK OK
34 [HEATER L OK OK
35 (HEATER N OK OK
41 [SCRUBBER 1 L OK OK
42 [SCRUBBER N OK OK
43 [SCRUBBER2 L OK OK
44 [ScRUBBER2 N OK OK
45 —_(EXT/LIGHT 182 L OK OK
46 [ext/uGHT1a2 N OK OK
47__[ext/ucuT3a4 L OK OK
43 [ext/uGHT3a4 N ‘OK
ain Corporate Senvoee Pte Ld INCA D O18: March, 207
[rest Procedures Reference Detail Sheet
[Date of Test SEPTEMBER 2008 Tosation Nex Test Due
Tested by Roproved by
ses Signature
IName Name
[Designation = TECHNICIAN, Designation _: TECHNICIAN—~> Hallin
ELECTRICAL CORE TEST REPORT Report No: DIVEIO03
‘This isto be completed when conducting i-house tests and examination of equipment by planned Maintenance Systems and a
{alloning reper or overhaul of equipment
Equipment isto be tected in accordance with the requirements of INCA O18
(The Ia and Periodic Examination Testing and Certification of Diving Plant and Equipment)
TEST TYPE | 6MONTHLY: VISUAL EXAMINATION & FUNCTION TEST
EQUIPMENT | MODEL 3007A _INSULATION-CONTINUITY TESTER / KYORITSU
TOCATION DIVE CONTROL ROOM:
DETAILS OF ELECTRICAL CORE TEST
CORE ID NO | CORE FUNCTION ‘CONTINUITY RESISTANCE PASSIFAIL
49 [DIVERHATLIGHT 1 L OK oK
50 [DVERHATLIGHT 1 N OK oK
51 DIVER HAT LIGHT 2 L oK OK
62 |DIVERHATLIGHT2 N OK OK
53 [DIVERHATLIGHT3 L oK OK
84 [DIVERHATLIGHT3 N OK OK
[Halin Gorporale Senices Pie Lid TCAD O18 = March, 2007
[rest Procedures Reference Detal Shoot
[Date of Test SEPTEMBER 2007 Tocation Net Test Dus
ested by ‘Approved by
[Signature Signature
IName Name
[Designation : TECHNICIAN Designation _: TECHNICIAN,