You are on page 1of 1

Tests and Test Results on Cable As per EED-50-12 & EED-50-13

Sample: 7PX0.60 SQ MM (As per EED-50-12 Rev.-2)

Sr. No. Tests Test Method Test Instrument Calibration Due Date Test-1 Test-2 Test-3 Test-4 Test-5

1 Construction,Dimensions & Thickness


(a) Dia of Strand (mm) 0.205 0.207 0.208 0.205 0.210
(b) Conductor Dia (mm) 0.980 1.000 1.030 1.050 0.990
(c )Insulation Thickness (mm) Vernier Caliper 0.710 0.725 0.850 0.900 0.860
IS-10810 01.05.2024
(d) Core Dia. (mm) Micrometer 2.440 2.460 2.500 2.540 2.580
(e ) Dia of Screen wire (mm) 0.198 0.200 0.196 0.199 0.200
(f) Laid up Screened core Diameter (mm) 11.790 11.800 11.820 11.850 11.920
(g) Sheath Thickness (mm) 1.850 1.925 2.000 2.100 2.280
(h) Dia over Sheath (mm) 16.880 16.950 17.200 17.440 17.350
IS-10810
2 Insulation Resistance Million Mega ohm meter 03.05.2024 3000 3100 3250 3700 3975
Part-43
IS-10810 Dig. Micro Ohm Meter
3 Conductor Resistance 05.05.2024 26.100 26.500 26.720 26.841 27.050
Part-5 Digital Hygrometer
4 Hot Set Test
IS-10810 Hot Set (Temperature Indicator
02.05.2024
(a) Under Load Part-30 With Sensor) 26.650 25.200 26.300 25.500 26.550
(b) After Cooling 1.820 2.100 1.950 2.600 2.300

5 Tensile Strength
IS-10810
Tensile Testing M/c 01.05.2024
(a) Tensile Strength (Insulation) Part-7 14.210 13.500 14.500 13.600 14.300
(c ) Tensile Strength (Sheath) 12.240 13.500 12.800 13.600 13.800

6 Elongation
IS-10810
Tensile Testing M/c 01.05.2024
(b) % Elongation (Insulation) Part-7 278.500 260.000 265.500 280.200 275.500
(d) % Elongation (Sheath) 320.000 280.000 310.000 275.000 280.000
IS-10810
7 High Voltage Test AC High Voltage Tester 03.05.2024 2 Kv. For 5 Min. (Withstood)
Part-45

You might also like