Flow temperature_1
11004 Desired T 50 °C
11175 Heat curve 0.9
11177 Temp. min. 40 °C (10)
11178 Temp. max. 80 °C
11253 Des. flow T 10 °C
11300 High supp. T X2 150 °C
11301 High T max Y2 95 °C
11302 Low supply T X1 70 °C
11303 Low T max Y1 80 °C (50)
11400 Y1 80 °C (150)
11401 Y2 65 °C (150)
11402 Y3 60 °C (150)
11403 Y4 55 °C (150)
11404 Y5 50 °C (150)
11405 Y6 40 °C (150)
Page 1 / 11
Return limit_1
Optimization_1
Control Parameter_1
Application_1
Page 2 / 11
11022 P exercise 0s
11023 M exercise 0
11052 DHW priority 0
11077 P frost T 2 °C
11078 P heat T 20 °C
11093 Frost pr. T 10 °C
11141 Ext. input 0
11142 Ext. mode 0
11189 Min. act. time 10
11500 Send desired T 1
Schedule_1 (3110)
Holiday1_1 (10714)
Holiday2_1 (10721)
Holiday3_1 (10728)
Holiday4_1 (10735)
Alarm1_1
10643 Digital S9 1
11147 Upper difference 0K
11148 Lower difference 0K
11149 Delay 10 m
11150 Lowest temp. 30 °C
Page 3 / 11
Alarm2_1
Alarm3_1
General_1
4201 Mode
Flow temperature_2
Return limit_2
12030 Limit 60 °C
12035 Infl. - max. 0
12036 Infl. - min. 0
12037 Adapt. time 25 s
12085 Priority 0
12256 S6 Sensor reference 60 °C
Control Parameter_2
Application_2
12022 P exercise 0s
12023 M exercise 0
12077 P frost T 2 °C
12078 P heat T 20 °C
12093 Frost pr. T 10 °C
12141 Ext. input 0
12142 Ext. mode 0
12189 Min. act. time 3
12500 Send desired T 1
Anti-bacteria_2
12122 Day: 0
12123 Start time 0
12124 Duration 120 m
12125 Desired T 9 °C
Schedule_2 (3210)
Holiday1_2 (10742)
Holiday2_2 (10749)
Holiday3_2 (10756)
Holiday4_2 (10763)
Alarm1_2
General_2
4202 Mode
General_3
General_4
Input_config
CommonHoliday_1 (10700)
CommonHoliday_2 (10707)
CommonHoliday_3 (10770)
CommonHoliday_4 (10777)
Pump control_1
10603 Digital S7 0
11310 Retry time 20 m
11311 Change, duration 2
11312 Change time 12
11313 Stab. time 15 s
11314 Chan.-over time 0 s (5)
11315 Circ. pumps 0
Refill water_1
Page 7 / 11
11316 Alarm handling 1
11320 P exercise 0s
11321 Pressure, des. 3 bar
11322 Pressure, diff. 1.5 bar
11323 Time-out 1m
11324 Refill water 0
11326 No. of pumps 1
11327 Input type 0
11600 Pressure 0 bar
11609 Low Y 0 bar
11610 High Y 20 bar
Pump control_2
10623 Digital S8 0
12310 Retry time 20 m
12311 Change, duration 2
12312 Change time 12
12313 Stab. time 15 s
12314 Chan.-over time 0 s (5)
12315 Circ. pumps 0
Pressure1
Pressure2
Pressure3
Pressure4
Pressure5
Page 8 / 11
General_5
General_6
ECL_alarm
ECL_system
1 System Command 0
8 Build no. 11356
19 Code no. 3040
34 Hardware 18692
35 Software 527
36 Serial no. 402980
38 Modbus addr. 1
39 Baud 38 (0)
2048 ECL 485 addr. 15
2049 Modbus bias. 0
2050 Language 1
2097 Wink 0
2099 Production week 5650
10198 Aut. daylight 1
60058 Backlight 5
60059 Contrast 3
ECL_Extension
Ethernet
Page 9 / 11
258 Address type 1
278 IP 1 192.168.101.100
282 Gateway IP 1 192.168.101.1
286 Net Mask 1 255.255.255.0
2152 Inbound accept 2 (0)
2153 Portal encryption 1 (0)
2160 ECL Portal 0
2161 Connection status 0
2162 Portal status 0
2165 Server name, char 1 ecl.portal.danfoss.ro
2230 Password, char 1 ----
2240 DNS IP1 1 192.168.1.1
2244 DNS IP2 1 208.67.222.222
Raw_sensor
SCADA_override
M-bus Config
ECL_system_ex
4236 AccumulatedPulse 1 0
4238 AccumulatedPulse 2 0
4240 AccumulatedPulse 3 0
Page 11 / 11