You are on page 1of 10

Energy 36 (2011) 520e529

Contents lists available at ScienceDirect

Energy
journal homepage: www.elsevier.com/locate/energy

Comparative study of power converter topologies and control strategies for the
harmonic performance of variable-speed wind turbine generator systems
R. Melício a, b, V.M.F. Mendes c, J.P.S. Catalão a, b, *
a
Department of Electromechanical Engineering, University of Beira Interior, R. Fonte do Lameiro, 6201-001 Covilha, Portugal
b
Center for Innovation in Electrical and Energy Engineering, Instituto Superior Técnico, Technical University of Lisbon, Av. Rovisco Pais, 1049-001 Lisbon, Portugal
c
Department of Electrical Engineering and Automation, Instituto Superior de Engenharia de Lisboa, R. Conselheiro Emídio Navarro, 1950-062 Lisbon, Portugal

a r t i c l e i n f o a b s t r a c t

Article history: Power converters play a vital role in the integration of wind power into the electrical grid. Variable-speed
Received 6 March 2010 wind turbine generator systems have a considerable interest of application for grid connection at
Received in revised form constant frequency. In this paper, comprehensive simulation studies are carried out with three power
3 October 2010
converter topologies: matrix, two-level and multilevel. A fractional-order control strategy is studied for
Accepted 6 October 2010
Available online 11 November 2010
the variable-speed operation of wind turbine generator systems. The studies are in order to compare
power converter topologies and control strategies. The studies reveal that the multilevel converter and
the proposed fractional-order control strategy enable an improvement in the power quality, in
Keywords:
Wind energy
comparison with the other power converters using a classical integer-order control strategy.
Power converters  2010 Elsevier Ltd. All rights reserved.
Transient analysis
Power quality

1. Introduction it possible to implement more complex control algorithms and thus


allowing the optimization of the performance of a wind turbine [10].
Wind power industry and the construction of wind farms are The variable-speed WTG systems are implemented with either
undergoing rapid development [1,2]. In Portugal, the total installed doubly fed induction generators (DFIGs) [11] or full-power
renewable energy capacity reached 9321 MW in June 2010, of converters. At the moment, substantial documentation exists on
which wind power capacity is responsible for 3802 MW, and modeling and control issues for the DFIG wind turbine. But this is
continues growing. not the case for wind turbines with full-power converter and
As wind energy is increasingly integrated into power systems, permanent magnet synchronous generator (PMSG) [12]. Indeed,
the stability of already existing power systems is becoming permanent magnet machines appear more and more promising,
a concern of utmost importance [3]. Also, network operators have having higher ratio of power to weight, reliability, and efficiency
to ensure that consumer power quality is not compromised. Hence, than electrically excited machines [13].
the total harmonic distortion (THD) should be kept as low as In this paper, a variable-speed WTG system is considered with
possible, improving the quality of the energy injected into the PMSG and three power converter topologies: matrix, two-level and
electrical grid [4]. The new technical challenges emerging due to multilevel. Also, a fractional-order control strategy is proposed.
increased wind power penetration imply research of more accurate Accordingly, comprehensive simulation studies are carried out in
modeling and control of wind turbine generator (WTG) systems. order to adequately assess the harmonic behavior of the electric
Power converters play a vital role in the integration of wind current injected into the electrical grid, taking into account three
power into the electrical grid [5]. Power converters allow for vari- power converter topologies and both fractional-order and integer-
able-speed operation of the wind turbine [6e8], and enhanced order controllers.
power extraction [9]. The use of power electronics components has This paper is organized as follows. Section 2 presents the
resulted in the creation of extra degrees of freedom thereby making modeling for the WTG system with different topologies for the
power converters, namely matrix, two-level and multilevel
converters. Section 3 provides the fractional-order control strategy.
* Corresponding author. Department of Electromechanical Engineering, Univer-
Section 4 presents the harmonic assessment by Discrete Fourier
sity of Beira Interior, R. Fonte do Lameiro, 6201-001 Covilha, Portugal. Tel.: þ351
275 329914; fax: þ351 275 329972. Transform (DFT) and THD. Section 5 provides the simulation
E-mail address: catalao@ubi.pt (J.P.S. Catalão). results. Finally, Section 6 outlines the conclusions.

0360-5442/$ e see front matter  2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.energy.2010.10.012
R. Melício et al. / Energy 36 (2011) 520e529 521

Nomenclature Jg Moment of inertia for the rotor of the generator


Tdg Resistant torque in the generator bearing
Pt Mechanical power of the wind turbine Tag Resistant torque due to the viscosity of the airflow in
r Air density the generator
A Area covered by the rotor blades Tg Electric torque
u Wind speed value upstream of the rotor if Equivalent rotor current
cp Power coefficient M Mutual inductance.
q Pitch angle of the rotor blades p Number of pairs of poles
l Tip speed ratio id, iq Stator currents
ut Rotor angular speed at the wind turbine Ld, Lq Stator inductances
Jt Moment of inertia for the rotor of the wind turbine Rd, Rq Stator resistances
Tt Mechanical torque u d , uq Stator voltages
Tdt Resistant torque in the wind turbine bearing Rn Resistance of the electric grid
Tat Resistant torque in the hub and blades due to the Ln Inductance of the electric grid
viscosity of the airflow ufk Voltage at the filter
Tts Torque of the torsional stiffness uk Voltage at the electric grid
ug Rotor angular speed at the generator

2. Modeling usually sufficient to consider the mechanical drive train as a single-


mass shaft model because shaft oscillations of the WTG system are
2.1. Wind turbine not reflected to the grid due to the fast active power control [15].
However, when the system response to heavy disturbances is
The mechanical power Pt of the wind turbine is given by: analyzed, the rotor must be approximated by at least a two-mass
model [16]. One mass represents the wind turbine moment of
1 inertia, and the other mass represents the generator moment of
Pt ¼ rAu3 cp (1)
2 inertia.
The computation of the power coefficient cp requires the use of The equations for modeling the mechanical drive train are given
blade element theory and the knowledge of blade geometry. These by:
complex issues are normally empirical considered. In this paper,
dut 1
the wind turbine used corresponds to the one with the numerical ¼ ðTt  Tdt  Tat  Tts Þ (6)
approximation developed in [14], where the power coefficient is dt Jt
given by:
  dug 1 
151 ¼ Tts  Tdg  Tag  Tg (7)
 13:2 e18:4=li dt Jg
2:14
cp ¼ 0:73  0:58q  0:002q (2)
li
Hence, a two-mass model for the mechanical drive train, given by
where Eqs. (6) and (7), is considered in this paper.

1
li ¼ (3) 2.3. Generator
1 0:003
 
ðl  0:02qÞ q3 þ 1
The generator considered in this paper is a PMSG. The equations
for modeling a PMSG can be found in the literature [17]. Using the
The power coefficient is a function of the pitch angle q of rotor
motor machine convention, the following equations in the dq-
blades and of the tip speed ratio l, which is given by:
plane, based on Park (deq) transformation, are considered:
wt D
l ¼ (4) did 1 
2u ¼ u þ p ug L q i q  R d i d (8)
dt Ld d
From (2), for a null pitch angle, the maximum power coefficient
and the optimal tip speed ratio are respectively: cpmax ¼ 0:4412;
diq 1h   i
lopt ¼ 7:057. ¼ uq  pug Ld id þ Mif  Rq iq (9)
The mechanical torque Tt of the wind turbine is given by: dt Lq
The electric power Pg is given by:
Pt
Tt ¼ (5)   T
wt
Pg ¼ ud uq uf id iq if (10)
This mechanical torque is responsible for the movement of the
In order to avoid demagnetization of permanent magnet in the
mechanical drive train.
PMSG, a null stator current id ¼ 0 is imposed [18].
2.2. Mechanical drive train
2.4. Matrix converter
A way to model a mechanical drive train of a WTG system is to
model the rotor as a number of equivalent discrete masses con- Matrix converters have many advantages, which are well
nected together by springs and dampers. When the simulated documented in the literature [19]. The matrix converter is an
applications are limited to the impact of wind fluctuations, it is ACeAC converter, with nine bidirectional commanded insulated
522 R. Melício et al. / Energy 36 (2011) 520e529

gate bipolar transistors (IGBTs) Sij. It is connected between a first- 2.5. Two-level converter
order filter and a second-order filter. The first order filter is con-
nected to a PMSG, while the second order filter is connected to an The two-level converter is an AC/DC/AC converter, with six
electrical grid. A three-phase active symmetrical circuit in series unidirectional commanded IGBTs Sik used as a rectifier, and with the
models the electrical grid. The configuration of the simulated WTG same number of unidirectional commanded IGBTs used as an
system with matrix converter [20] is shown in Fig. 1. inverter. The rectifier is connected between the PMSG and a capac-
The IGBTs commands Sij in function of the on and off states are itor bank. The inverter is connected between this capacitor bank and
given by: a second order filter, which in turn is connected to an electric grid.
 The groups of two IGBTs linked to the same phase constitute a leg k
1; ðonÞ of the converter.
Sij ¼ ; i; j˛f1; 2; 3g (11)
0; ðoffÞ The configuration of the simulated WTG system with two-level
converter [24] is shown in Fig. 2.
subject to the following constraints:
For the switching function of each IGBT, the switching variable
X
3 gk is used to identify the state of the IGBT i in the leg k of the
Sij ¼ 1; i˛ 1; 2; 3 (12) converter. The index i with i˛f1; 2g identifies the IGBT. The index k
j¼1 with k˛f1; 2; 3g identifies a leg for the rectifier and k˛f4; 5; 6g
identifies the inverter one. The two conditions [25] for the
X
3 switching variable of each leg k are given by:
Sij ¼ 1; j˛ 1; 2; 3 (13)

i¼1 1; ðS1k ¼ 1 and S2k ¼ 0Þ
gk ¼ ; k˛f1; .; 6g (16)
The vector of output phase voltages is related to the vector of 0; ðS1k ¼ 0 and S2k ¼ 1Þ
input phase voltages through the command matrix [21], as given by: The topological restriction [25] for the leg k is given by:
2 3 2 32 3 2 3
vA S11 S12 S13 va va X
2
4 vB 5 ¼ 4 S21 S22 S23 54 vb 5 ¼ ½S4 vb 5 (14) Sik ¼ 1; k˛ 1; .; 6 (17)
vC S31 S32 S33 vc vc i¼1

Each switching variable depends on the conduction and blockade


The vector of input phase currents is related to the vector of
states of the IGBTs.
output phase currents through the command matrix [21], as given
The voltage vdc is modeled by the state equation given by:
by:
!
dvdc 1 X
3 X
6
½ ia ib ic T ¼ ½ST ½ iA iB iC T (15) ¼ gk ik  gk ik (18)
dt C
k¼1 k¼4
Hence, the matrix converter is modeled by Eqs. (11)e(15).
Two distinct advantages arise from this topology, the converter Hence, the two-level converter is modeled by Eqs. (16)e(18).
requires no bulky energy storage or DC-link, and control is per- Two-level converters generate an output voltage with two
formed on just one converter [9]. The converter is smaller, lighter values (levels) with respect to the negative terminal of the capac-
and more reliable than conventional converters. itor. Hence, two voltage levels lead to the production of lower
Because of these characteristics matrix converters are thought power quality waveforms [26] causing more harmonic distortion in
to be a good alternative for variable-speed operation of WTGs [22]. comparison with multilevel converters.
Nevertheless, industrial wide use of matrix converter is still very
limited due to strong undesirable characteristics: its sensitivity to 2.6. Multilevel converter
distortion in input power supply due to the lack of reactive
component in the power circuit, and its sensitivity to the rapidly The multilevel converter is an AC/DC/AC converter, with twelve
fluctuating input voltage frequency when used in WTGs [23]. unidirectional commanded IGBTs Sik used as a rectifier, and with

Fig. 1. WTG system with matrix converter.


R. Melício et al. / Energy 36 (2011) 520e529 523

Fig. 2. WTG system with two-level converter.

the same number of unidirectional commanded IGBTs used as an With the two upper IGBTs in each leg k (S1k and S2k) of the
inverter. The rectifier is connected between the PMSG and converter it is associated a switching variable F1k and also for the
a capacitor bank. The inverter is connected between this capacitor two lower IGBTs (S3k and S4k) it is associated a switching variable
bank and a second order filter, which in turn is connected to an F2k , respectively given by:
electric grid. The groups of four IGBTs linked to the same phase
constitute a leg k of the converter. gk ð1 þ gk Þ gk ð1  gk Þ
F1k ¼ ; F2k ¼ ; k˛ 1; .; 6 (21)
The configuration of the simulated WTG system with multilevel 2 2
converter [27] is shown in Fig. 3. Each switching variable depends on the conduction and blockade
For the switching function of each IGBT, the switching variable states of the IGBTs.
gk is used to identify the state of the IGBT i in the leg k of the The voltage vdc is the sum of the voltages vC1 and vC2 in the
converter. The index i with i˛f1; 2; 3; 4g identifies the IGBT. The capacity banks C1 and C2, modeled by the state equation:
index k with k˛f1; 2; 3g identifies the leg for the rectifier and
! !
k˛f4; 5; 6g identifies the inverter one. dvdc 1 X
3 X
6
1 X
3 X
6
The three valid conditions [28] for the switching variable of each ¼ F1k ik  F1k ik þ F2k ik  F2k ik
dt C1 C2
leg k are given by: k¼1 k¼4 k¼1 k¼4

8 (22)
< 1; ðS1k and S2k Þ ¼ 1 and ðS3k or S4k Þ ¼ 0
gk ¼ 0; ðS2k and S3k Þ ¼ 1 and ðS1k or S4k Þ ¼ 0 ; k˛f1;.;6g Hence, the multilevel converter is modeled by Eqs. (19)e(22).
: Multilevel converters, and specifically three-level converters,
1; ðS3k and S4k Þ ¼ 1 and ðS1k or S2k Þ ¼ 0
are a good tradeoff solution between performance and cost in high-
(19) power systems [29]. Multilevel converters are, however, limited by
The topological restriction for the leg k is given by: the following drawbacks: voltage unbalances, high component
count, and increased control complexity [30]. A critical issue in
ðS1k $S2k Þ þ ðS2k $S3k Þ þ ðS3k $S4k Þ ¼ 1; k˛f1; .; 6g (20) three-level converters is the design of the DC-link capacitors. Thus,
special attention should be paid to the unbalance in the voltage of

Fig. 3. WTG system with multilevel converter.


524 R. Melício et al. / Energy 36 (2011) 520e529

the capacitors in three-level converters, which may produce Table 2


a malfunction of the control. Output voltage vectors selection for the multilevel converter, for vC1 > vC2.

sb ysa 2 1 0 1 2
2.7. Electric grid 2 25 25 12 7 7
1 24 13 13;6 6 8
0 19 18 1;14;27 5 9
A three-phase active symmetrical circuit in series models the 1 20 17 17;2 2 4
electric grid. The phase currents injected in the electric grid are 2 21 21 16 3 3
modeled by the state equation given by:

difk 1 
paper, m is assumed as a real number that satisfies the restrictions
¼ ufk  Rn ifk  uk ; k ¼ f4; 5; 6g (23)
dt Ln 0 < m < 1. Also, it is assumed that a ¼ 0. The following convention
m m
is used: 0 D
t hDt .
3. Control strategy
The other approach is GrünwaldeLetnikov definition of frac-
tional-order integral, given by:
3.1. Fractional-order controller
ta
A control strategy based on fractional-order PIm controllers is m
Xh G m
ð þ rÞ
a Dt f ðtÞ ¼ lim hm f ðt  rhÞ (28)
proposed for the variable-speed operation of wind turbines with h/0
r¼0
r! GðmÞ
PMSG/full-power converter topology. Fractional-order controllers
are based on fractional calculus theory, which is a generalization of while the definition of fractional-order derivatives is:
ordinary differentiation and integration to arbitrary (non-integer)
ta
order [31]. Recently, applications of fractional calculus theory in X
m m
h Gðm þ 1Þ
practical control field have increased significantly [32]. Fractional- a Dt f ðtÞ ¼ lim h ð  1Þr f ðt  rhÞ (29)
h/0
r¼0
r!Gðm  r þ 1Þ
order calculus used in mathematical models can improve the design,
properties and controlling abilities in dynamical systems [33]. An important property revealed by the RiemanneLiouville and
The fractional-order derivative or integral can be denoted by GrünwaldeLetnikov definitions is that while integer-order opera-
m
a general operator a Dt [34], given by: tors imply finite series, the fractional-order counterparts are
8 m defined by infinite series [33,34]. This means that integer operators
>
> d ; <ðmÞ > 0
>
> dt m are local operators in opposition with the fractional operators that
>
>
>
< 1; <ðmÞ ¼ 0 have, implicitly, a memory of the past events.
m
a Dt ¼ > Z t (24) The design of a fractional-order controller has the advantage of
>
> entailing more criterion than the classical one, augmenting the
> m
> ðdsÞ ; <ðmÞ < 0
>
> freedom for imposing an enhanced behavior [35]. A fractional-
:
a order controller has a dynamical behavior described by a fractional
differential integral equation with a derivative or an integral having
where m is the order of the derivative or the integral, <ðmÞ is the real
at least a non-integer order.
part of the m.
The differential equation of the fractional-order PIm controller,
The mathematical definition of fractional derivatives and inte-
0 < m < 1 in time domain, is given by:
grals has been the subject of several descriptions. The most
frequently encountered definition is called RiemanneLiouville m
f ðtÞ ¼ Kp eðtÞ þ Ki D
t eðtÞ (30)
definition, in which the fractional-order integral is given by:
where f(t) is the output of the controller, e(t) is the input error, Kp is
Zt the proportional constant, and Ki is the integration constant. Taking
m 1
a Dt f ðtÞ ¼ ðt  sÞm1 f ðsÞ ds (25) m ¼ 1, in (30), a classical PI controller is obtained.
GðmÞ
a The transfer function of the fractional-order PIm controller, using
the Laplace transform in (30), is given by:
while the definition of fractional-order derivatives is given by:
2 t 3 GðsÞ ¼ Kp þ Ki sm (31)
n Z
m 1 d 4 f ð sÞ
a Dt f ðtÞ ¼ ds 5 (26) The fractional-order PIm controller is more flexible than the classical
Gðn  mÞ dt n ðt  sÞmnþ1
a PI controller, because it has one more adjustable parameter, which
can reflect the intensity of integration.
where:
ZN 3.2. Converters control
GðxÞh yx1 ey dy (27)
0 Power converters are variable structure systems, because of the
on/off switching of their IGBTs. As mentioned previously, the
is the Euler’s Gamma function, a and t are the limits of the opera-
tion, and m is the number identifying the fractional order. In this Table 3
Output voltage vectors selection for the multilevel converter, for vC1 < vC2.
Table 1
Output voltage vectors selection for the two-level converter.
sb ysa 2 1 0 1 2
2 25 25 12 7 7
sb ysa 1 0 1 1 24 26 26;11 11 8
1 4 4;5 5 0 19 23 1;14;27 10 9
0 6 0;7 1 1 20 22 22;15 15 4
1 2 3;2 3 2 21 21 16 3 3
R. Melício et al. / Energy 36 (2011) 520e529 525

Fig. 4. Diagram of a WTG with two-level converter employing fractional-order controllers.

controllers used in the converters are fractional-order PIm control- At the simulation level, a practical implementation of the switching
lers. Pulse width modulation (PWM) by space vector modulation strategy considered in Eq. (33) could be accomplished by using
(SVM) associated with sliding mode (SM) is used for controlling the hysteresis comparators.
converters. The output voltages of matrix converter are switched discontin-
Sliding mode control presents special interest for systems with uous variables. If high enough switching frequencies are considered
variable structure, such as switching power converters, guaran- (much higher than the input and output matrix converter funda-
teeing the choice of the most appropriate space vectors. The aim is mental frequencies), it is possible to assume that in each switching
to let the system slide along a predefined sliding surface by period Ts, the average value of the output voltages is nearly equal to
changing the system structure. their reference average value. Hence, the following equality is
The sliding mode control presents attractive features such as assumed:
robustness to parametric uncertainties of the wind turbine and the
generator as well as to electrical grid disturbances [21,36]. ðnþ1ÞT
Z s
The power semiconductors present physical limitations that 1
vab dt ¼ v*ab (34)
have to be considered during design phase and during simulation Ts
nTs
study. Particularly, they cannot switch at infinite frequency. Also,
for finite values of the switching frequency, for instances, 2 kHz, Similar to output voltages, the input current average value is nearly
5 kHz or even 10 kHz, an error on the electric currents will exist equal to their reference average value. Hence, the following
between the reference value and the control value. Let eab be the equality is also assumed:
error on the electric currents in the ab-plane, based on Concordia
ða  bÞ transformation, in order to guarantee that the system slides ðnþ1ÞT
Z s
along the sliding surface Sðeab ; tÞ. It has been proven that it is 1
necessary to ensure that the state trajectory near the surfaces iq dt ¼ i*q (35)
Ts
verifies the stability conditions [21] given by: nTs

  The outputs of the hysteresis comparators are the integer vari-


 dS eab ; t ables sab ¼ ðsa ; sb Þ [21]. For the matrix converter, the voltage
S eab ; t <0 (32) variables sa and sb assume values in the set U given by:
dt
in practice the sliding surface is chosen in a way of letting a small U˛f1; 0; 1g (36)
error 3 > 0 for Sðeab ; tÞ to be allowed, due to power semiconductors
switching only at finite frequency. Consequently, the switching in
practice strategy is given by: Table 5
First harmonic and third harmonic of the current injected into the electrical grid for
  the matrix converter e case study 1.
3 < S eab ; t < þ3 (33) Wind PIm controller PI controller
speed
First Third First Third
(m/s)
harmonic (%) harmonic (%) harmonic (%) harmonic (%)

Table 4 2.5 87.92 1.89 87.22 2.10


WTG system data. 5.0 88.10 1.78 87.90 1.91
7.5 88.15 1.59 88.04 1.64
Turbine moment of inertia 2500  103 kg m2 10.0 88.41 1.30 88.11 1.46
Turbine rotor diameter 49 m 12.5 88.50 1.24 88.30 1.37
Hub height 45 m 15.0 88.63 1.16 88.42 1.21
Tip speed 17.64e81.04 m/s 17.5 88.80 1.11 88.50 1.18
Rotor speed 6.9e31.6 rpm 20.0 88.80 1.11 88.50 1.18
Generator rated power 900 kW 22.5 88.80 1.11 88.50 1.18
Generator moment of inertia 100  103 kg m2 25.0 88.80 1.11 88.50 1.18
526 R. Melício et al. / Energy 36 (2011) 520e529

3.5 2.5

3
2
2.5
↓ Classical PI controllers
1.5
THD (%)

THD (%)
2
↑ Fractional PI controllers
1.5
1 ↓ Classical PI controllers

1
0.5
0.5 ↑ Fractional PI controllers

0 0
2.5 10 17.5 25 2.5 10 17.5 25
Wind speed (m/s) Wind speed (m/s)

Fig. 5. THD of the current injected into the electrical grid for the matrix converter e Fig. 6. THD of the current injected into the electrical grid for the two-level converter e
case study 1. case study 1.

The current variables sq in dq coordinates assume values in the The difference between the voltage vdc and the reference voltage
set U given by: v*dc is processed by the PIm controller in order to determine the
reference stator currents. The difference between the stator current
U˛f1; 1g (37) and the reference stator current is the error eab to be subjected to
For the two-level converter, the voltage variables sa and sb the output voltage vectors selection for the two-level converter,
assume values in the set U given by: Table 1, after being processed by the hysteresis comparator given by
(33). The sliding mode control is a lower level of control as it is
U˛f1; 0; 1g (38) normally envisaged with the PI controller.

The appropriate vector selection in order to ensure stability for the 4. Harmonic assessment
two-level converter is shown in Table 1.
For the multilevel converter, the voltage variables sa and sb The harmonic behavior computed by the DFT is given by:
assume values in the set U given by:
X
N1
U˛f  2; 1; 0; 1; 2g (39) XðkÞ ¼ ej2pkn=N xðnÞ for k ¼ 0; .; N  1 (40)
n¼0
In this control strategy, only when vC1 svC2 a new vector is selected.
The appropriate vector selection in order to ensure stability for the where x(n) is the input signal, a complex number giving the
multilevel converter is shown in Table 2, for vC1 > vC2, and in amplitude and phase of the different sinusoidal components of x
Table 3, for vC1 < vC2. (n).
The control strategy for the WTG using PIm controllers has In order to evaluate the harmonic content of the current injected
a block diagram, for example, as illustrated for the configuration in the electrical grid, the THD is considered. The harmonic behavior
with a two-level converter shown in Fig. 4. computed by the THD is given by:
The design of PIm controllers follows the tuning rules in [37].
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
P50
Power electronic converters are modeled as a pure delay [38] and 2
the left-over dynamics are modeled with a second order equivalent H ¼ 2 XH
THD ð%Þ ¼ 100 (41)
transfer function, following the identification of a step response. XF

Table 6 Table 7
First harmonic and third harmonic of the current injected into the electrical grid for First harmonic and third harmonic of the current injected into the electrical grid for
the two-level converter e case study 1. the multilevel converter e case study 1.

Wind PIm controller PI controller Wind PIm controller PI controller


speed speed
First Third First Third First Third First Third
(m/s) (m/s)
harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%)
2.5 93.20 1.61 92.83 1.78 2.5 93.90 1.57 93.35 1.60
5.0 93.80 0.97 93.10 1.42 5.0 94.07 1.42 94.00 1.48
7.5 94.20 0.89 93.30 0.94 7.5 94.19 0.83 94.06 0.88
10.0 94.30 0.27 93.40 0.30 10.0 94.38 0.33 94.14 0.47
12.5 94.30 0.27 93.50 0.30 12.5 94.78 0.27 94.28 0.30
15.0 94.30 0.27 93.50 0.30 15.0 94.94 0.23 94.45 0.26
17.5 94.40 0.27 93.50 0.30 17.5 95.18 0.23 94.63 0.26
20.0 94.40 0.27 93.50 0.30 20.0 95.18 0.23 94.82 0.26
22.5 94.40 0.27 93.50 0.30 22.5 95.20 0.23 94.82 0.26
25.0 94.40 0.27 93.50 0.30 25.0 95.24 0.23 94.82 0.26
R. Melício et al. / Energy 36 (2011) 520e529 527

2.5 10

2 8

← Classical PI controllers
1.5 ← Fractional PI controllers 6
THD (%)

THD (%)
↓ Classical PI controllers

1 4
↑ Fractional PI controllers

0.5 2

0 0
2.5 10 17.5 25 2.5 10 17.5 25
Wind speed (m/s) Wind speed (m/s)

Fig. 7. THD of the current injected into the electrical grid for the multilevel converter e Fig. 8. THD of the current injected into the electrical grid for the matrix converter e
case study 1. case study 2.

Table 5 shows that the first harmonic never decreases while the
where XH is the root mean square (RMS) value of the individual
third harmonic never increases when the wind speed increase, due
harmonic components of the signal, and XF is the RMS value of the
to the respective increase in the rotor speed. Also, it is shown by
fundamental component.
comparison of the fractional-order PIm controller with the PI
Standards such as IEEE-519 [39] impose limits for different order
controller that the former improves the value for the first harmonic
harmonics and the THD. The limit is 5% for THD. Hence, IEEE-519
and consequently reduces the value for the third harmonic. This is
standard is used in this paper as a guideline for comparison
an advantage of the PIm controller.
purposes.
The THD of the output current for the WTG system with the
matrix converter is shown in Fig. 5.
5. Simulation results Fig. 5 shows that the THD with the PIm controller is never worst
than that with the PI controller, which is a consequence of what is
The mathematical models for the WTG system with the matrix, shown in Table 5.
two-level and multilevel power converter topologies were imple- The first harmonic and the third harmonic of the current
mented in Matlab/Simulink. In this paper it is assumed that m ¼ 1/2 injected into the electrical grid, computed by the DFT, for the WTG
for the fractional-order controller. The WTG system considered has system with the two-level converter is shown in Table 6.
a rated electrical power of 900 kW. The operational region of the A comparison between Table 5 and Table 6 reveals a better
WTG system was simulated for wind speed range from 2.5e25 m/s. performance for the two-level converter, which is able to achieve
Table 4 summarizes the WTG system data. enhanced values for the harmonics. Also, it is shown by comparison
of the fractional-order PIm controller with the PI controller that the
5.1. Case study 1 d ideal sinusoidal voltage waveforms on the former has advantage.
network The THD of the output current for the WTG system with the
two-level converter is shown in Fig. 6.
The simulation results for a network modeled as a three-phase Fig. 6 shows that the THD with the PIm controller is lesser than
active symmetrical circuit in series, with ideal sinusoidal voltage that with the PI controller, which is again a consequence of what is
waveforms of 850 V at 50 Hz, were carried out. shown in Table 6.
The first harmonic and the third harmonic of the current The first harmonic and the third harmonic of the current
injected into the electrical grid, computed by the DFT, for the WTG injected into the electrical grid, computed by the DFT, for the WTG
system with the matrix converter is shown in Table 5. system with the multilevel converter is shown in Table 7.

Table 8 Table 9
First harmonic and third harmonic of the current injected into the electrical grid for First harmonic and third harmonic of the current injected into the electrical grid for
the matrix converter e case study 2. the two-level converter e case study 2.

Wind PIm controller PI controller Wind PIm controller PI controller


speed speed
First Third First Third First Third First Third
(m/s) (m/s)
harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%) harmonic (%)
2.5 86.67 4.99 86.30 5.10 2.5 90.58 4.80 89.67 4.50
5.0 87.59 4.94 87.67 5.02 5.0 90.97 4.59 90.67 4.68
7.5 87.99 4.82 87.84 4.95 7.5 91.09 3.42 90.92 3.49
10.0 88.04 4.77 87.84 4.95 10.0 91.17 3.42 91.03 3.49
12.5 88.16 4.71 87.84 4.95 12.5 91.15 3.42 91.03 3.49
15.0 88.16 4.71 88.05 4.91 15.0 91.14 3.43 91.03 3.51
17.5 88.23 4.68 88.11 4.89 17.5 91.10 3.43 90.96 3.51
20.0 88.23 4.68 88.11 4.89 20.0 91.10 3.43 90.96 3.51
22.5 88.23 4.68 88.11 4.89 22.5 91.10 3.43 90.96 3.51
25.0 88.23 4.68 88.11 4.89 25.0 91.10 3.43 90.96 3.51
528 R. Melício et al. / Energy 36 (2011) 520e529

9 10

7.5
8

6
6
THD (%)

THD (%)
4.5
↓ Classical PI controllers
4
3 ↓ Classical PI controllers
↑ Fractional PI controllers
2
1.5 ↑ Fractional PI controllers

0 0
2.5 10 17.5 25 2.5 10 17.5 25
Wind speed (m/s) Wind speed (m/s)

Fig. 9. THD of the current injected into the electrical grid for the two-level converter e Fig. 10. THD of the current injected into the electrical grid for the multilevel converter
case study 2. e case study 2.

Comparisons among Tables 5, 6 and 7 reveal a better perfor- The first harmonic and the third harmonic of the current
mance for the multilevel converter, which is able to achieve the injected into the electrical grid, computed by the DFT, for the WTG
best values for the harmonics. Again it is shown by comparison of system with the two-level converter is shown in Table 9. The THD of
the fractional-order PIm controller with the PI controller that the the output current for the WTG system with the two-level
former has advantage. converter is shown in Fig. 9.
The THD of the output current for the WTG system with the The first harmonic and the third harmonic of the current
multilevel converter is shown in Fig. 7. injected into the electrical grid, computed by the DFT, for the WTG
Comparisons between Figs. 5e7 reveal a better performance for system with the multilevel converter is shown in Table 10. The THD
the multilevel converter, which is able to achieve the smallest of the output current for the WTG system with the multilevel
values for the THD. converter is shown in Fig. 10.
The fractional-order control strategy provides better results As in the first case study, the fractional-order control strategy
comparatively to a classical integer-order control strategy, in what provides better results comparatively to a classical integer-order
regards the harmonic performance computed by DFT and THD. The control strategy in what regards the harmonic performance and THD.
THD of the output current is lower than 5% limit imposed by IEEE- But, the harmonics are worst than what is reveled in the first case
519 standard [39], for all power converter topologies considered. study due to the greater influence of the third harmonic component.
The presence of the energy-storage elements, in comparison
5.2. Case study 2 e non-ideal sinusoidal voltage waveforms on the with the matrix converter, and the increasing number of voltage
network levels, in comparison with the two-level converter, allows the WTG
system with the multilevel converter to achieve the best harmonic
The simulation results for a network modeled as a three-phase performance. Also, it has been shown that non-ideal sinusoidal
active symmetrical circuit in series, with 850 V at 50 Hz and 5% of voltage waveforms on the network affect the current THD from the
third harmonic component, were carried out. converters.
The first harmonic and the third harmonic of the current
injected into the electrical grid, computed by the DFT, for the WTG 6. Conclusions
system with the matrix converter is shown in Table 8. The THD of
the output current for the WTG system with the matrix converter is The paper studies a control strategy based on fractional-order
shown in Fig. 8. controllers for the variable-speed operation of WTG systems.
Comprehensive simulation studies are carried out with three
Table 10
topologies for the power converters, namely matrix, two-level and
First harmonic and third harmonic of the current injected into the electrical grid for multilevel converters. Two case studies are presented, considering
the multilevel converter e case study 2. ideal and non-ideal sinusoidal voltage waveforms on the network.
Wind PIm controller PI controller
For all power converter topologies considered, the harmonic
speed performance and THD revealed that the power quality injected into
First Third First Third
(m/s) the electrical grid is enhanced using the fractional-order control
harmonic (%) harmonic (%) harmonic (%) harmonic (%)
strategy in comparison with a classical integer-order control
2.5 87.90 4.94 87.62 4.99
5.0 88.00 4.92 87.77 4.95 strategy. Also, the comparative study illustrates that the best
7.5 93.80 2.44 93.51 2.91 harmonic performance is achieved using a WTG system with the
10.0 93.90 2.11 93.72 2.34 multilevel converter.
12.5 94.11 2.10 93.90 2.33
15.0 94.65 2.10 94.10 2.33
17.5 94.77 2.10 94.26 2.33
References
20.0 94.93 2.10 94.45 2.33
22.5 95.02 2.10 94.76 2.33 [1] Saheb-Koussa D, Haddadi M, Belhamel M, Hadji S, Nouredine S. Modeling and
25.0 95.02 2.10 94.76 2.33 simulation of the fixed-speed WECS (wind energy conversion system):
application to the Algerian Sahara area. Energy 2010;35(10):4116e25.
R. Melício et al. / Energy 36 (2011) 520e529 529

[2] Fusco F, Nolan G, Ringwood JV. Variability reduction through optimal combina- [21] Pinto S, Silva J. Sliding mode direct control of matrix converters. IET Electr
tion of wind/wave resources e an Irish case study. Energy 2010;35(1):314e25. Power Appl 2007;1(3):439e48.
[3] Ullah NR, Thiringer T. Variable speed wind turbines for power system stability [22] Cardenas R, Pena R, Wheeler P, Clare J. Reactive power capability of WECS
enhancement. IEEE Trans Energy Convers 2007;22(1):52e60. based on matrix converter. Electron Lett 2008;44(11):674e6.
[4] Carrasco JM, Franquelo LG, Bialasiewicz JT, Galvan E, Guisado RCP, Prats AM, [23] Jia S, Wang X, Tseng KJ. Matrix converters for wind energy systems. In:
et al. Power-electronic systems for the grid integration of renewable energy Proceedings of the second IEEE conference on industrial electronics applica-
sources: a survey. IEEE Trans Ind Electron 2006;53(4):1002e16. tions, Harbin, China; 2007. p. 488e94.
[5] Blaabjerg F, Chen Z, Kjaer SB. Power electronics as efficient interface in [24] Melício R, Mendes VMF, Catalão JPS. A pitch control malfunction analysis for
dispersed power generation systems. IEEE Trans Power Electron 2004;19(5): wind turbines with permanent magnet synchronous generator and full-
1184e94. power converters: proportional integral versus fractional-order controllers.
[6] Lin W-M, Hong C-M, Cheng F-S. Fuzzy neural network output maximization control Electr Power Compon Syst 2010;38(4):387e406.
for sensorless wind energy conversion system. Energy 2010;35(2):592e601. [25] Silva JF, Pinto SF. In: Rashid MH, editor. Control methods for switching power
[7] Lin W-M, Hong C-M. Intelligent approach to maximum power point tracking converters. New York: Power Electronics Handbook; 2007. p. 935e98.
control strategy for variable-speed wind turbine generation system. Energy [26] Babaei E, Hosseini SH, Gharehpetian GB, Haque MT, Sabahi M. Reduction of dc
2010;35(6):2440e7. voltage sources and switches in asymmetrical multilevel converters using
[8] Lin W-M, Hong C-M, Cheng F-S. On-line designed hybrid controller with a novel topology. Electr Power Syst Res 2007;77(8):1073e85.
adaptive observer for variable-speed wind generation system. Energy 2010;35 [27] Melício R, Mendes VMF, Catalão JPS. Power converter topologies for wind
(7):3022e30. energy conversion systems: integrated modeling, control strategy and
[9] Baroudi JA, Dinavahi V, Knight AM. A review of power converter topologies for performance simulation. Renew Energy 2010;35(10):2165e74.
wind generators. Renew Energy 2007;32(14):2369e85. [28] Barros JD, Silva JF. Optimal predictive control of three-phase NPC multilevel
[10] Camblong H, Tapia G, Rodríguez M. Robust digital control of a wind turbine converter for power quality applications. IEEE Trans Ind Electron 2008;55(10):
for rated-speed and variable-power operation regime. IEE Proc Control Theory 3670e81.
Appl 2006;153(1):81e91. [29] Alepuz S, Busquets-Monge S, Bordonau J, Gago J, Gonzalez D, Balcells J.
[11] Fernandez LM, Garcia CA, Jurado F. Comparative study on the performance of Interfacing renewable energy sources to the utility grid using a three-level
control systems for doubly fed induction generator (DFIG) wind turbines inverter. IEEE Trans Ind Electron 2006;53(5):1504e11.
operating with power regulation. Energy 2008;33(9):1438e52. [30] Portillo RC, Prats MM, León JI, Sanchez JA, Carrasco JM, Galván E, et al.
[12] Hansen AD, Michalke G. Modelling and control of variable-speed multi-pole Modeling strategy for back-to-back three-level converters applied to high-
permanent magnet synchronous generator wind turbine. Wind Energy power wind turbines. IEEE Trans Ind Electron 2006;53(5):1483e91.
2008;11(5):537e54. [31] Podlubny I. Fractional-order systems and PI-lambda-D-mu-controllers. IEEE
[13] Li H, Chen Z. Design optimization and site matching of direct-drive permanent Trans Autom Control 1999;44(1):208e14.
magnet wind power generator systems. Renew Energy 2009;34(4):1175e84. [32] Li W, Hori Y. Vibration suppression using single neuron-based PI fuzzy
[14] Slootweg JG, de Haan SWH, Polinder H, Kling WL. General model for repre- controller and fractional-order disturbance observer. IEEE Trans Ind Electron
senting variable speed wind turbines in power system dynamics simulations. 2007;54(1):117e26.
IEEE Trans Power Syst 2003;18(1):144e51. [33] Cao JY, Cao BG. Design of fractional order controllers based on particle swarm
[15] Slootweg JG, de Haan SWH, Polinder H, Kling WL. Aggregated modelling of wind optimization. In: Proceedings of the first IEEE conference on industrial elec-
parks with variable speed wind turbines in power system dynamics simulations. tronics and applications, Singapore; May 2006.
In: Proc. 14th power systems computation conference Sevilla, Spain; 2002. [34] Calderón AJ, Vinagre BM, Feliu V. Fractional order control strategies for power
[16] Poller MA. Doubly-fed induction machine models for stability assessment of electronic buck converters. Signal Process 2006;86(10):2803e19.
wind farms. In: Proceedings of IEEE Bologna Power Technology Conference, [35] Biswas A, Das S, Abraham A, Dasgupta S. Design of fractional-order (PID mu)-
Bologna, Italy; 2003. D-lambda controllers with an improved differential evolution. Eng Appl Artif
[17] Ong C-M. Dynamic simulation of electric machinery: using Matlab/Simulink. Intell 2009;22:343e50.
New Jersey: Prentice-Hall; 1998. p. 259e350. [36] Beltran B, Ahmed-Ali T, Benbouzid MEH. Sliding mode power control of
[18] Senjyu T, Tamaki S, Urasaki N, Uezato K. Wind velocity and position sensorless variable-speed wind energy conversion system. IEEE Trans Energy Convers
operation for PMSG wind generator. In: Proceedings of the fifth international 2008;23(2):551e8.
conference on power electronics and drive systems, Singapore; 2003. p. 787e92. [37] Maione G, Lino P. New tuning rules for fractional PI-alfa controllers. Nonlinear
[19] Cárdenas R, Peña R, Wheeler P, Clare J, Asher G. Control of the reactive power Dynamics 2007;49(1e2):251e7.
supplied by a WECS based on an induction generator fed by a matrix [38] Chinchilla M, Arnaltes S, Burgos JC. Control of permanent-magnet generators
converter. IEEE Trans Ind Electron 2009;56(2):429e38. applied to variable-speed wind energy systems connected to the grid. IEEE
[20] Melício R, Mendes VMF, Catalão JPS. Fractional-order control and simulation Trans Energy Convers 2006;21(1):130e5.
of wind energy systems with PMSG/full-power converter topology. Energy [39] IEEE guide for harmonic control and reactive compensation of static power
Convers Manage 2010;51(6):1250e8. converters, IEEE Standard 519-1992.

You might also like