Installation Instructions
Specifications
Normal Operating Voltage: 15 to 32 VDC
EOL Resistance: 3.9K ohms
Maximum IDC Resistance: 25 Ohms
External Supply Voltage (between Terminals T3 and T4)
DC Voltage: 18-28 volts power limited
Ripple Voltage: 0.1 Volts RMS maximum
Current: 90mA per module
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Noncondensing
Dimensions: 41/ 2” H x 4” W x 11/4” D (Mounts to a 4” square by 21/ 8” deep box.)
Accessories: SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system
will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The MMF-302 Interface Module is intended for use in addressable two-wire systems, where the individual address of each module
is selected using the built-in rotary switches. This module allows addressable panels to interface and monitor two-wire conventional
smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel.
All two-wire detectors being monitored must be UL compatible with this module. The MMF-302 has a panel controlled LED indicator
and can be used to replace an M302 module in existing systems.
Compatibility Requirements
To ensure proper operation, these modules shall be connected to listed compatible system control panels only.
Mounting
The MMF-302 mounts directly to 4” square electrical boxes (see Figure 2A). The box must have a minimum depth of 21 /8”. Surface
mounted electrical boxes (SMB500) are available.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power-limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully
remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
9 67 8 9
0
5 10
8 4 11 1 0
3 12 1
10
2
9
11
8
13
4 5 6 7 15 1 1 12
2
4 5 67
8 4 3
0
9 3
7 1 0 15 14 2 1
8 4
10
2
3
9
9
11
8
0
4 5 6 7 15 1 1 12
2
NS 1
4 5 67
8 4 3
TENS 9 3
7 ES
S
TE
8 4
6789 DR
3
9
0
2
NS 1
7 S
6 AD
TE
ES
5
3
DR
6 3
0
6
2
AD
1
ES
3
5
0
2
ON
1
5 ES
4 ON
3
5 2
10
4
ONES
LOOP ADDRESS
A78-2318-07 A78-2611-12
A78-2610-10
Figure 1. Controls and indicators: Figure 2A. Module mounting Figure 2B:
F300-03-00 1 I56-1192-02
Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161
Figure 3. Interface two-wire conventional detectors, NFPA Style B (Class B):
COMMUNICATION LINE CONNECT MODULES TO LISTED
32 VDC MAX. COMPATIBLE FIRE LITE CONTROL PANELS ONLY.
TWISTED PAIR
IS RECOMMENDED
)—( )—(
TO NEXT FROM PANEL OR
)+( )+(
DEVICE PREVIOUS DEVICE
INTERFACE
MODULE
TERMINAL WIRING MUST BE POWER LIMITED.
9 0
4
5
67 8 9
10
11
)—(
8 3 12
1
7
2 13
1 0 15 14 2 )+(
TENS
5
6789 )—(
6 4 3
3 )+( LISTED BATTERY-BACKUP SWITCHED
5 2 4
3.9K EOL ONES
10 DC POWER SUPPLY.
LOOP ADDRESS
RESISTOR
(INCLUDED)
A2143-10
+ +
POWER TO THE INTERFACE MODULE
MUST BE EXTERNALLY SWITCHED TO
— — RESET THE DETECTORS. A CRF-300
RELAY CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
POWER SUPPLY - SEE FIGURE 5.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
OPTIONAL BRANCH CIRCUIT
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. TO NEXT INTERFACE MODULE.
INSTALL DETECTORS PER MANUFACTURER’S MODULE SUPERVISES SUPPLY
INSTALLATION INSTRUCTIONS. VOLTAGE AND DETECTOR LOOP. A78-2394-18
9 67 8 9
0
5 10 )—(
8 4 11 1
3 12
3.9K EOL RESISTOR 2 13 )+(
7 1 0 15 14 2
REQUIRED AT TERMINALS TENS
5
6789 )—(
6 3
8 & 9 (INCLUDED) 3
4
)+(
A2143-10 5 2
10
4 LISTED BATTERY-BACKUP, SWITCHED
ONES
LOOP ADDRESS
DC POWER SUPPLY.
+ +
POWER TO THE INTERFACE MODULE
— — MUST BE EXTERNALLY SWITCHED TO
RESET THE DETECTORS. A CRF-300
RELAY CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
POWER SUPPLY - SEE FIGURE 5.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS. OPTIONAL BRANCH CIRCUIT
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. TO NEXT INTERFACE MODULE.
INSTALL DETECTORS PER MANUFACTURER’S MODULE SUPERVISES SUPPLY
INSTALLATION INSTRUCTIONS. VOLTAGE AND DETECTOR LOOP.
A78-2395-18
)–( )–(
TO NEXT FROM PANEL OR
DEVICE )+( )+( PREVIOUS DEVICE
RELAY
CONTROL
MODULE
A78-2396-10
F300-03-00 2 I56-1192-02
©1999 Fire•Lite Alarms, Inc.