You are on page 1of 1

REV 2 2 2 2 2 2

NOTE
HMI
A = Action Alarm
DO = Display Only
RO = Remote Only
PLC
CONTROL ACTIONS:
I = Initiate (causes indicated SD or ESD) Plus sign (+) indicates variance from SD or ESD actions
R = Reset (resets SD or ESD)
CL = Close
OP = Open
M0 = Manual Mode 0% Output
SD = Shutdown (reset required) P&ID 11X75 11X75 11X76 11X80 11X85 11X85
SP = Stop (Normal, no reset required to re-start)
ST = Start
TE = Time Delay Energize
TD = Time Delay De-Energize
DE = De-Energized
EN = Energized
P = Permissive (must be satisfied before output can be energized, or sequence can start, after shutdown or stopped condition)

FAIL ACTIONS:
FO = Valve Fails Open
FC = Valve Fails Closed SUCTION VALVE AC-11X85 RUN RECYCLE VALVE M-11X75 RUN AC-11X78 RUN H-11X75C RUN
DESCRIPTION SOLENOID COMMAND SOLENOID COMMAND COMMAND COMMAND
I/O TYPE:
DI = Digital Input

P&ID 11X75

P&ID 11X76

P&ID 11X80

P&ID 11X85
DO= Digital Output
AI = Analog Input
AO = Analog Output
TC = Thermocouple
RTD = Resistive Thermal Device
MBS = MODBUS Comms
ECOMM = Ethernet/IP Comms
SMC = Smart Motor Control Ethernet/IP Comms
DEVICE XY-11X75 XC-11X85 XY-11X81 XC-11X76 XC-11X78 XC-11X75C

NOTES:
FAIL ACTION FC FO
1. CAUSE AND EFFECT PORTRAYS A RUNNING AND FULLY LOADED COMPRESSOR.
2. TIMER SET AT 10 MINUTE

I/O TYPE DO DO DO DO DO D0

TRANSMITTER SCALING AND SETPOINTS PLC CARD / POINT Local:5:O.Data.6 Local:6:O.Data.0 Local:5:O.Data.5 Local:6:O.Data.2 Local:6:O.Data.3 Local:5:O.Data.13

ALARM
MIN. MAX PLC TAG
REV HMI TRAIN AREA P&ID NO. DEVICE I/O TYPE UNITS CONDITION / PLC CARD / POINT DESCRIPTION XY-11X75 XC-11X85 XY-11X81 XC-11X76 XC-11X78 XC-11X75C COMMENTS
VALUE VALUE PLC
SETPOINT
ALARM
GENERAL
2 N/A XS11X75S DI Local:4:I.Data.1 UCP ESD FROM SIS XS11X75S.Shutdown CL SP OP SP SP SP
2 N/A XI-11X75 DI Local:3:I.Data.29 REMOTE STOP FROM DCS XI11X75.Shutdown CL SP OP SP SP SP
2 N/A HS-11X75 DI Local:4:I.Data.0 UCP E-STOP BUTTON HS11X75.Shutdown CL SP OP SP SP SP
2 N/A M-11X75 DI Local:3:I.Data.17 MAIN MOTOR RUNNING UNLOADED TIME EXPIRED MotorRunUnldFail.Shutdown CL SP OP SP SP SP
2 N/A TIT-11X75 RTD DEG F <3% 0 100 Local:10:I.Ch0Data UCP TEMPERATURE OUT OF RANGE TIT11X75.OOR CL SP OP SP SP SP

P&ID 11X75
2 11X75 LSHH-11680 DI Local:3:I.Data.27 1ST STAGE SCRUBBER LEVEL HI HI LSHH11X80.Shutdown CL SP OP SP SP SP
2 11X75 PIT-11X82 AI PSI 170 0 800 Local:1:I.Ch01Data 1ST STAGE SUCTION BOTTLE PRESSURE LO LO PIT11X82.LLShutdown CL SP OP SP SP SP
2 11X75 PIT-11X82 AI PSI 400 0 800 Local:1:I.Ch01Data 1ST STAGE SUCTION BOTTLE PRESSURE LO LO PIT11X82.LLShutdown CL SP OP SP SP SP
2 11X75 PIT-11X82 AI PSI <3% 0 800 Local:1:I.Ch01Data 1ST STAGE SUCTION BOTTLE PRESSURE OUT OF RANGE PIT11X82.OOR CL SP OP SP SP SP
2 11X75 PIT-11X84 AI PSI 300 0 1000 Local:1:I.Ch02Data 1ST STAGE DISCHARGE BOTTLE PRESSURE LO LO PIT11X84.LLShutdown CL SP OP SP SP SP
2 11X75 PIT-11X84 AI PSI 670 0 1000 Local:1:I.Ch02Data 1ST STAGE DISCHARGE BOTTLE PRESSURE HI HI PIT11X84.HHShutdown CL SP OP SP SP SP
2 11X75 PIT-11X84 AI PSI <3% 0 1000 Local:1:I.Ch02Data 1ST STAGE DISCHARGE BOTTLE PRESSURE LO LO PIT11X84.OOR CL SP OP SP SP SP
2 11X75 VT-11X85 AI "/SEC 0.6 0 2 Local:1:I.Ch05Data AC-11685 VIBRATION HI HI VT11X85.HHShutdown CL SP OP SP SP SP
2 11X75 VT-11X85 AI "/SEC <3% 0 2 Local:1:I.Ch05Data AC-11685 VIBRATION OUT OF RANGE VT11X85.OOR CL SP OP SP SP SP
2 11X75 TE-11X80 RTD DEGF 15 0 250 Local:11:I.Ch0Data 1ST STAGE SCRUBBER TEMPERATURE LO LO TE11X80.LLShutdown CL SP OP SP SP SP
2 11X75 TE-11X80 RTD DEGF 160 0 250 Local:11:I.Ch0Data 1ST STAGE SCRUBBER TEMPERATURE HI HI TE11X80.HHShutdown CL SP OP SP SP SP
2 11X75 TE-11X80 RTD DEGF <3% 0 250 Local:11:I.Ch0Data 1ST STAGE SCRUBBER TEMPERATURE OUT OF RANGE TE11X80.OOR CL SP OP SP SP SP
2 11X75 AC-11X85 DI Local:3:I.Data.10 AFTERCOOLER FAN MOTOR FAIL AC11X85.Fail CL SP OP SP SP SP

P&ID 11X76
2 11X76 LSHH-11X90 DI Local:3:I.Data.28 2ND STAGE SCRUBBER LEVEL HI HI LSHH11X90.Shutdown CL SP OP SP SP SP
2 11X76 PIT-11X94 AI PSI 170 0 250 Local:1:I.Ch04Data 2ND STAGE DISCHARGE BOTTLE PRESSURE LO LO PIT11X94.LLShutdown CL SP OP SP SP SP
2 11X76 PIT-11X94 AI PSI 1150 0 250 Local:1:I.Ch04Data 2ND STAGE DISCHARGE BOTTLE PRESSURE HI HI PIT11X94.HHShutdown CL SP OP SP SP SP
2 11X76 PIT-11X94 AI PSI <3% 0 250 Local:1:I.Ch04Data 2ND STAGE DISCHARGE BOTTLE PRESSURE OUT OF RANGE PIT11X94.OOR CL SP OP SP SP SP
2 11X76 TE-11X90 RTD DEG F 30 0 350 Local:11:I.Ch2Data 2ND STAGE DISCHARGE BOTTLE TEMPERATURE LO LO TE11X90.LLShutdown CL SP OP SP SP SP
2 11X76 TE-11X90 RTD DEG F 160 0 350 Local:11:I.Ch2Data 2ND STAGE DISCHARGE BOTTLE TEMPERATURE HI HI TE11X90.HHShutdown CL SP OP SP SP SP
2 11X76 TE-11X90 RTD DEG F <3% 0 350 Local:11:I.Ch2Data 2ND STAGE DISCHARGE BOTTLE TEMPERATURE OUT OF RANGE TE11X90.OOR CL SP OP SP SP SP
2 11X76 TE-11X96 RTD DEG F 165 0 350 Local:11:I.Ch4Data AC-11X95 OUTLET TEMPERATURE HI HI TE11X96.HHShutdown CL SP OP SP SP SP
2 11X76 TE-11X96 RTD DEG F <3% 0 350 Local:11:I.Ch4Data AC-11X95 OUTLET TEMPERATURE OUT OF RANGE TE11X96.OOR CL SP OP SP SP SP
2 11X76
P&ID 11X80
2 11X80 VT-11X76A AI "/SEC 0.5 0 2 Local:1:I.Ch12Data M-11X76 DE VIBRATION HI HI VT11X76A.HHShutdown CL SP OP SP SP SP
2 11X80 VT-11X76A AI "/SEC <3% 0 2 Local:1:I.Ch12Data M-11X76 DE VIBRATION OUT OF RANGE VT11X76A.OOR CL SP OP SP SP SP
2 11X80 VT-11X76B AI "/SEC 0.6 0 2 Local:1:I.Ch13Data M-11X76 NDE VIBRATION HI HI VT11X76B.HHShutdown CL SP OP SP SP SP
2 11X80 VT-11X76B AI "/SEC <3% 0 2 Local:1:I.Ch13Data M-11X76 NDE VIBRATION OUT OF RANGE VT11X76B.OOR CL SP OP SP SP SP
2 11X80 TE-11X83 RTD DEGF 320 0 350 Local:11:I.Ch1Data STAGE 1 DISCHARGE TEMPERATURE HI HI TE11X83.HHShutdown CL SP OP SP SP SP
2 11X80 TE-11X83 RTD DEGF <3% 0 350 Local:11:I.Ch1Data STAGE 1 DISCHARGE TEMPERATURE OUT OF RANGE TE11X83.OOR CL SP OP SP SP SP
2 11X80 TE-11X93 RTD DEGF 320 0 350 Local:11:I.Ch3Data STAGE 2 DISCHARGE TEMPERATURE HI HI TE11X93.HHShutdown CL SP OP SP SP SP
2 11X80 TE-11X93 RTD DEGF <3% 0 350 Local:11:I.Ch3Data STAGE 2 DISCHARGE TEMPERATURE OUT OF RANGE TE11X93.OOR CL SP OP SP SP SP
2 11X80 TE-11X75A TC DEGF 230 0 250 Local:9:I.Ch0Data C-11X75 THROW 1 BRG TEMPERATURE HI HI TE11X75A.HHShutdown CL SP OP SP SP SP
2 11X80 TE-11X75A TC DEGF <3% 0 250 Local:9:I.Ch0Data C-11X75 THROW 1 BRG TEMPERATURE OUT OF RANGE TE11X75A.OOR CL SP OP SP SP SP
2 11X80 TE-11X75B TC DEGF 230 0 250 Local:9:I.Ch1Data C-11X75 THROW 2 BRG TEMPERATURE HI HI TE11X75B.HHShutdown CL SP OP SP SP SP
2 11X80 TE-11X75B TC DEGF <3% 0 250 Local:9:I.Ch1Data C-11X75 THROW 2 BRG TEMPERATURE OUT OF RANGE TE11X75B.OOR CL SP OP SP SP SP
2 11X80 M-1X75 DI Local:3:I.Data.17 MAIN MOTOR FAIL M1XX75.Fail CL SP OP SP SP SP

P&ID 11X85
2 11X85 LSLL-11X75 DI Local:3:I.Data.26 COMPRESSOR OIL LEVEL LO LO LSLL11X75.Shutdown CL SP OP SP SP SP
2 11X85 FSLL-11X75 DI Local:3:I.Data.16 C-11X75 FLOW SWITCH LO LO FSLL11X75.Shutdown CL SP OP SP SP SP
2 11X85 VT-11X75A AI "/SEC 0.6 0 2 Local:1:I.Ch07Data C-11X75 DE VIBRATION HI HI VT11X75A.HHShutdown CL SP OP SP SP SP
2 11X85 VT-11X75A AI "/SEC 0 2 Local:1:I.Ch07Data C-11X75 DE VIBRATION OUT OF RANGE VT11X75A.OOR CL SP OP SP SP SP
2 11X85 PIT-11X75A AI PSI 45 0 100 Local:1:I.Ch09Data C-11X75 PRESSURE LO LO PIT11X75A.LLShutdown CL SP OP SP SP SP
2 11X85 PIT-11X75A AI PSI 0 100 Local:1:I.Ch09Data C-11X75 PRESSURE OUT OF RANGE PIT11X75A.OOR CL SP OP SP SP SP
2 11X85 TE-11X78A RTD DEGF 150 0 250 Local:11:I.Ch5Data AC-11X78 OUTLET TEMPERATURE LO LO TE11X78A.LLShutdown CL SP OP SP SP SP
2 11X85 TE-11X78A RTD DEGF 190 0 250 Local:11:I.Ch5Data AC-11X78 OUTLET TEMPERATURE HI HI TE11X78A.HHShutdown CL SP OP SP SP SP
2 11X85 TE-11X78A RTD DEGF 0 250 Local:11:I.Ch5Data AC-11X78 OUTLET TEMPERATURE OUT OF RANGE TE11X78A.OOR CL SP OP SP SP SP
2 11X85 AC-11X78 DI Local:3:I.Data.19 LUBE OIL COOLER FAN FAIL E11X78.Fail CL SP OP SP SP SP
2 11X85 H-11X75C DI Local:3:I.Data.22 HOT START FAIL H11X75C.Fail CL SP OP SP SP SP

DATE REV BY: DESCRIPTION APPROVED BY: BY: TREVOR FEDYK


04-Oct-22 2 TWF ASBUILT DATE: OCT 04., 2022
RECYCLE COMPRESSOR UNIT NO. 11675 DOCUMENT NO.
B-SID14918-IE-1941 REV.2