Item #______________________________________

Quantity____________________________________
C.S.I. Section 11400

CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
DISHWASHER

STANDARD FEATURES MODEL


■ 202 racks per hour ❑ CL44eN-BAS – Dishwasher
■ Opti-RinSe system

■ Rapid return conveyor drive mechanism OPTIONS AT EXTRA COST


■ Insulated hinged double doors with door ❑ Stainless steel pressure-less 15/30 KW booster
interlock switches heater
■ 19.5 inch chamber height opening ❑ Higher than standard chamber
■ Top mounted micro-processer control module
■ Energy saver mode
ACCESSORIES
■ Dirty water indicator
❑ Stainless steel vent hoods
■ Manager activated low temperature alert
❑ Direct drive unloader
■ NSF rated configurable Pot and Pan dwell mode
❑ Side loader
■ Configurable “intelligent” smart delime alert,
determined by water hardness test at installation ❑ Blower-dryer
■ Service diagnostics ❑ Drain water tempering kit (Drain water t­ empering
kit comes standard on the DWER or
■ NAFEM Data Protocol compliant models)
■ Computational fluid dynamic designed self- ❑ Flanged feet kit (requires two kits)
aligning wash manifolds
Specifications, Details and Dimensions on Inside and Back.
■ Stainless steel debossed anti-clogging wash
arms
■ Removable integrated pump intake screen
■ Stainless steel self-draining pump and impeller
■ Single, sloping scrap screen and deep basket
■ Stainless panels enclose perimeter and bottom

CL44eN-BAS DISHWASHER
■ Door actuated drain closure
■ Single point electrical connection (three phase
only), does not include the booster heater
■ Convertible hot water or low temp final rinse
■ Vent fan and booster heater control

DIRECTION OF OPERATION
❑ Right to Left
❑ Left to Right

VOLTAGE
❑ 208/60/1 ❑ 240/60/1 ❑ 380/60/3
❑ 208/60/3 ❑ 240/60/3 ❑ 480/60/3
❑ 600/60/3

F40453 – CL44eN-BAS Dishwasher Page 1 of 12


CL44eN-BAS
DISHWASHER 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

THE CLeN WAREWASHER IS NOW STANDARD WITH MORE EFFICIENT FEATURES THAN EVER . . .
Inside and out the CLeN warewashers by Hobart are packed with standard components and patented design
­innovations that make them the biggest value in the dishwasher industry.

The insulated hinged inspection doors provide easy


access in the chamber. Exterior wash pipes and
­reduced interior baffles reduce clean-up time. Wash Manifolds. Computational Fluid Dynamic
The Rapid Return drive allows for a wide separation designed wash manifolds are self-aligning and come
between the wash and the rinse zone. with Hobart’s signature debossed anti-clogging
nozzles for superior result.

Opti-RinSe™. Hobart’s exclusive Opti-RinSe™ signifi-


cantly reduces operating cost by reducing rinse water
New, Improved Control Module. The Hobart exclu- and the energy required to heat the water. The unique
sive microprocessor control ­module offers a choice spray pattern uses large d
­ roplets to more efficiently
of many features, such as an ­exclusive Energy Saver sanitize the ware.
Mode, NSF rated configurable Pot and Pan dwell
mode, Low Temperature Alerts and Dirty Water Indi- OTHER STANDARD FEATURES . . .
cator. It also displays pertinent ­machine status and
has a configurable “intelligent” delime notification. • Thermal Layer Curtains help keep the heat inside
The controls have built-in Service Diagnostics and are the machine.
NAFEM Data Protocol Compliant. • Ball Detent Clutch Conveyor Drive for maximum
­protection against conveyor jams
• Integrated Removable Pump Intake Screen to
offer the ultimate guard of keeping debris from
­entering the pump.
• Hinged Door Seals and stainless steel labyrinth seal
for drip-free operation
• Low-Temp Convertibility In Field. All machines
shipped hot. Change software in field at set up to
low temperature if desired – then, if requirements
change, convert from one mode to the other in the
field. An exclusive feature – standard from Hobart.
Soil Management System. Screen design sheds soil • Door Actuated Drain Closure. Closing the door
more easily than flat screens, reduces frequency of automatically actuates drain closure, eliminates
cleaning — easy to empty large soil particles . . . Just extra manual steps, ensures that closure is in the
lift out the scrap basket. correct position.

Page 2 of 12 F40453 – CL44eN-BAS Dishwasher


CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
DISHWASHER

AVAILABLE OPTIONS AND ACCESSORIES . . . CL44eN


Flexibility is synonymous with Hobart CLe ­dishwash­- Machine Ratings (Mechanical)
ers. If your operation demands a dishwasher with a Racks per hour (193⁄4" x 193⁄4") 202
vent hood, an extended hood . . . a power scrapper, Conveyor Speed - feet per minute 5.6 max.
just specify the combination of options that suit your
needs. Dishes per Hour (Average 25 per rack) 5,025
Glasses per Hour (Average 45 per rack) 9,045
Floor Space – Table to Table (Inches) 44
Overall Dimensions – H x W x D (Inches) 68 ⁄2 x 443⁄4 x 311⁄4
1

Motor H.P. 2
Conveyor Drive H.P. 1
⁄6
Number of Tanks 1
Tank Capacity – Gallons 23
Pump Capacity –
Gallons per Minute - Weir Test 165
Heating Equipment –
(For keeping power wash hot)
Gas Burners (with Natural Gas) 78,000 BTU per hr.
Built-in Pressureless Stainless Steel Booster Heater. Electric Heating Unit – Size Used 15 KW
Interwired and interplumbed. Saves on installation and
Optional Booster Heater / Final Rinse 15 KW / 30 KW
saves floor space. Simplifies operation with just one
switch to power dishmachine and booster. Rinse – Minutes operated during hour of
maximum operation 60
Final Rinse Flow – Gals. per min.
At 15 PSI Flow Pressure 1.8
At 20 PSI Flow Pressure 2.1
Final Rinse Flow – Gals. per hr. – MAXIMUM
At 15 PSI Flow Pressure 108
At 20 PSI Flow Pressure 126
Hot Water Sanitizing -
Rinse 20 PSI Flow Pressure Chemical Sanitizing
Gal./Rack .62 - 180°F – .62 - 120°F
Steam Consumption –
Pounds per hr. - MAXIMUM
Approx. 30 lbs. per hr. = 1 boiler H.P. (BHP)
Dishwasher, based on 20 PSI steam and
on customer supplying final rinse water
at 180°F maximum 65
Steam Booster, if used on 20 PSI steam -
Side Loader. Save up to 20 square feet in the dishroom 20 PSI water flowing - 130°F entering
water raised to 180°F min. 60
layout with an optional C-Line Side Loader. Racks are
indexed 90° into the dishwasher automatically – a Exhaust Requirements –
feature that cuts space and reduces labor dramatically. Cubic Feet per minute
Your dishroom team will ­appreciate this feature. Entrance End 200
Discharge End 400
OTHER AVAILABLE ACCESSORIES . . . Peak Rate of Drain Flow – Gallons per minute.
Blower-dryer, steam booster heater, and a single- (Initial rate with full tank) 38
point electrical ­connection to include electric booster
Shipping Weight Crated – Approximate lbs. 613
heater.

F40453 – CL44eN-BAS Dishwasher Page 3 of 12


CL44eN-BAS
DISHWASHER 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

10" 43 1/2" 10"


OPTIONAL VENT HOODS 26 3/4" 26 3/4"
W/DAMPER
OPTIONAL EXTENDED
VENT HOODS W/DAMPER

4 3/4"
11 1/4"
68 1/2"
20 1/2"

65 9/16"

L-R OPER
34"
8 7/8"

CL

MAY BE DRAINED TO
EITHER SIDE OF VALVE,
PLUG OPPOSITE SIDE.

31 1/16"
BOOSTER HEAT 15 KW 22"
MINIMUM
BOTH ENDS CL
ELEC. RATED SUPPLY MAXIMUM
CIRCUIT PROTECTIVE 15 7/16"
SPECS. AMPS
CONDUCTOR DEVICE
AMPACITY 1 5/16" 1 5/16"
200-240/50/3 40.1 50 50
380-415/50/3 26.6 30 30
200/50/3 43.3 60 60
208-240/60/3 40.1 50 50
208/60/3 45.0 60 60
240/60/3 40.1 50 50
380/60/3 21.3 30 30
380-415/60/3 23.2 30 30
19 11/16"
480/60/3 20.0 25 25
600/60/3 13.5 20 20

BOOSTER HEAT 30 KW 65 1/2"


MINIMUM
ELEC. RATED SUPPLY MAXIMUM FLUE FOR
CIRCUIT PROTECTIVE 58 1/2" GAS HEAT
SPECS. AMPS
CONDUCTOR DEVICE
AMPACITY
200-240/50/3 80.2 90 90 WALL
380-415/50/3 53.2 60 60
200/50/3 80.8 90 90
208-240/60/3 80.2 90 90
208/60/3 83.9 90 90
240/60/3 80.2 90 90
380/60/3 42.5 60 60 14 1/2"
380-415/60/3 46.4 60 60
480/60/3 40.1 50 50
18 5/8"
600/60/3 33.7 40 40
3" MIN. FLUE
CLEARANCE

Page 4 of 12 F40453 – CL44eN-BAS Dishwasher


CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
DISHWASHER

10" OPTIONAL VENT HOODS


10" 43 1/2" W/DAMPER
26 3/4" 26 3/4" OPTIONAL EXTENDED
VENT HOODS W/DAMPER

4 3/4"

11 1/4"

20 1/2"

68 1/2" 65 9/16"

R-L OPER
34"

CL

MAY BE DRAINED TO
EITHER SIDE OF VALVE, 8 7/8"
PLUG OPPOSITE SIDE.

ATTN: PLUMBING CONNECTIONS MUST COMPLY WITH APPLICABLE


SANITARY, SAFETY, AND PLUMBING CODES.
ELECTRICAL AND GROUNDING CONNECTIONS MUST
COMPLY WITH THE APPLICABLE PORTIONS OF THE
NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL
ELECTRICAL CODES.
WIDTH OF
MACHINE 27"
20" AVG INSIDE
CAUTION: CERTAIN MATERIALS INCLUDING SILVER,
27"
WIDTH OF
CL TABLE WIDTH
ALUMINUM, AND PEWTER ARE ATTACKED BY
SODIUM HYPOCHLORITE (LIQUID BLEACH). TRACKS

14 1/2" 11"

SUGGESTED TRACK AND TABLE LAYOUT

FRONT OF
MACHINE
2 HOLES FOR
CL MACHINE BOLTING TABLE
TO TANK
1 1/4" 1 1/4"
8" AVG
3/8"

TRACK HEIGHT
3/8" 3" ABOVE TANK LIP 7/8"
3"
1/4" - 5/16" USE SILICONE SEALER BETWEEN
22" TABLE AND LIP OF TANK TO
INSIDE TANK PREVENT LEAKAGE

SECTIONAL VIEW SHOWING


VIEW SHOWING HOLE LOCATIONS IN TABLE CONNECTIONS
TURNED DOWN PORTION OF TABLE

F40453 – CL44eN-BAS Dishwasher Page 5 of 12


CL44eN-BAS
ELECTRIC L-R 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

CL
MODEL:
11 1/2" CL44eN BASE
L-R OPERATION
11 7/16" D-974801
9 1/16" 19 7/16" REV B
6 7/8" 18 7/16"
6 3/16" 18 1/8"
3 9/16" 4"
BOOSTER
3 7/16"
4 1/4" 3/8" P2
EXHAUST
DWT 4" X 16"
E1 E4
P3
5/8" 11 1/2"
CHEMICAL PORTS

2 1/4"
10 1/2" 1/2"
CL
2"
5 1/2"

E5 E2 P1 E3 P7
FLOOR SINK
23" P12 P6 P5 (BY OTHERS)
OPEN DOOR P1 P4
CLEARANCE 12"
MIN

20" PLUMBING NOTES:


SERVICE
CLEARANCE ELECTRIC, STEAM, AND GAS HEATS
(BOTH SIDES) WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD
OR EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN
COMMON WATER SUPPLY LINE AT SERVICE CONNECTION.
MISCELLANEOUS NOTES: RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS
OPTIONAL VENT HOODS OR EXTENDED HOODS EXHAUST FOR BEST RESULTS.
REQUIREMENTS: 200 CFM ENTRANCE END FOR NON-BOOSTER MACHINE (P6 CONN): RECOMMENDED BUILDING
400 CFM EXIT END. FLOWING WATER PRESSURE TO THE DISHWASHER IS 20 PSI,
ALL DIMENSIONS TAKEN FROM FLOOR LINE MAY BE (15 PSI MIN - 25 PSI MAX). IF PRESSURES HIGHER THAN 25 PSI
INCREASED APPROXIMATELY 3/4" OR DECREASED 1/2". ARE PRESENT, A PRESSURE REGULATING VALVE WITH INTERNAL
THERMAL EXPANSION BY-PASS MUST BE SUPPLIED (BY OTHERS)
44" INSIDE TANK (AT TABLE CONNECTION) IN THE WATER LINE TO THE DISHWASHER.
43-25/32" TABLE TO TABLE.
FOR CONVENIENCE WHEN CLEANING, WATER TAP SHOULD BE
NET WEIGHT OF MACHINE: 501 LBS (STD HEIGHT), INSTALLED NEAR MACHINE WITH HEAVY DUTY HOSE AND
DOMESTIC SHIPPING WEIGHT: 576 LBS (STD HEIGHT). SQUEEZE VALVE.
CLeN LATENT AND SENSIBLE HEAT DISSIPATION WHEN USED, CHEMICAL SANITIZING FEEDER MUST BE CERTIFIED
INFORMATION ON F40459. TO NSF STANDARD 29.

SEPARATE SERVICE SEPARATE SERVICE CONNECTION


SINGLE POINT ELECTRICAL CONNECTION FOR ELEC. HEAT FOR MOTORS ON ELEC. HEAT
CONNECTION (3 PH ONLY) MOTORS MINIMUM MINIMUM
AND ELECTRIC TANK HEAT RATED SUPPLY MAXIMUM RATED SUPPLY MAXIMUM
VOLTAGE AMPS CIRCUIT PROTECTIVE VOLTAGE AMPS CIRCUIT PROTECTIVE
MINIMUM CONDUCTOR DEVICE CONDUCTOR DEVICE
RATED SUPPLY MAXIMUM AMPACITY AMPACITY
VOLTAGE AMPS CIRCUIT PROTECTIVE
CONDUCTOR DEVICE 208/60/3 45 60 60 208/60/3 10 15 15
AMPACITY 240/60/3 43 60 60 240/60/3 9.7 15 15
208/60/3 55 70 70 480/60/3 22 30 30 480/60/3 6.4 15 15
240/60/3 52.6 70 70 200/50/3 43 60 60 200/50/3 10.6 15 15
480/60/3 27.9 40 40 380/60/3 23 30 30 380/60/3 7.3 15 15
200/50/3 53.9 70 70 380-415/50/3 29 40 40 380-415/50/3 7 15 15
380/60/3 30.1 40 40 600/60/3 14.4 20 20 600/60/3 5.9 15 15
380-415/50/3 31.8 40 40 208/60/1 78 100 100 208/60/1 15.9 20 20
600/60/3 20.3 25 25 240/60/1 74.4 100 100 240/60/1 15.7 20 20

Page 6 of 12 F40453 – CL44eN-BAS Dishwasher


CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
ELECTRIC R-L

CL MODEL:
CL44eN BASE
19 7/16" 14 9/16" R-L OPERATION
D-974800
18 7/16" 12" REV B
18 1/8" 9 1/16"
11 7/16" 4"
6 3/16" 3 7/16"
3 9/16"
BOOSTER
EXHAUST 1/8"
4" X 16"

11 1/2"
CHEMICAL 4 1/4" DWT
PORTS
5/8"

10 1/2" P3 5 1/2"
CL
2" P2
2 1/4"
1/2"
FLOOR SINK
P7 P6 E1 E4 E5 E2 P1 P1 P5 (BY OTHERS)
P4
23" E3
OPEN DOOR P12
CLEARANCE 12"
MIN

20"
SERVICE
CLEARANCE
(BOTH SIDES)

PLUMBING CONNECTIONS
CONNECTION INFORMATION
(AFF = ABOVE FINISHED FLOOR)
ELECTRICAL CONNECTIONS LEGEND
CONNECTION INFORMATION
(AFF = ABOVE FINISHED FLOOR) ELECTRIC, STEAM, AND GAS HEATS
P1 DRAIN: 2" FPT, 7-3/8" AFF TWO POSSIBLE CONNECTIONS;
LEGEND MAY BE DRAINED TO EITHER SIDE OF VALVE, PLUG OPPOSITE SIDE.
P2 SANITIZER FEEDER: REMOVE 1/8" NPT PIPE PLUG TO ACCESS TAPPED HOLE.
ELECTRIC, STEAM, AND GAS HEATS 1/8" NPT 59-1/2" AFF (LOW TEMP ONLY)
E1 ELECTRIC CONNECTION: SINGLE POINT, ELEC, GAS, P3 RINSE FEEDER: REMOVE 1/8" NPT PIPE PLUG TO
& STEAM, 1-1/4" CONDUIT HOLE OR 2" CONDUIT, ACCESS TAPPED HOLE. 1/8" NPT 59-9/16" AFF.
63-3/4" AFF
P4 DETERGENT PROBE SENSOR: REMOVE CAP AND STUD ASSEMBLY TO ACCESS
E2 ELECTRIC CONNECTION: BOOSTER. 15KW/30KW, 7/8" DIA HOLE (WASH TANK ONLY). 14-5/8" AFF.
1-1/4" CONDUIT HOLE OR 2" CONDUIT HOLE,
63-3/4" AFF P5 INDIRECT DRAIN-FLOOR SINK: BY OTHERS, 0" AFF. WHEN REQUIRED,
INSTALL FLOOR SINK OUTSIDE THE PERIMETER OF THE DISHWASHER.
E3 ELECTRIC CONNECTION: DETERGENT, SANITIZER
(LOW TEMP ONLY) AND RINSE FEEDERS. P6 COMMON WATER CONNECTION: 1/2" FPT,
1/2" CONDUIT. 64-1/4" AFF 11-3/16" AFF.
HIGH TEMP. W/O BOOSTER 180°F MIN.
194°F MAX.
ELECTRIC HEAT ONLY LOW TEMP. 120°F MIN.
P7 COMMON WATER CONNECTION: 1/2" FPT,
SINGLE PHASE OR FIELD CONFIGURED 11-3/16" AFF
3 PHASE SEPARATE ELECTRIC CONNECTION HIGH TEMP. W/15K BOOSTER 140°F MIN.
E4 ELECTRIC CONNECTION: MOTORS AND CONTROLS HIGH TEMP. W/30K BOOSTER 110°F MIN.
1-1/4" CONDUIT. 63-3/4" AFF.
E5 ELECTRIC HEAT: 15,000 WATTS, OPTIONAL DRAIN WATER TEMPERING
WASH TANK. 1" CONDUIT HOLE, 63-3/4" AFF. P12 COLD WATER CONNECTION: 1/2" FPT, COLD TEMP 80°F MAX 7-3/8" AFF.

F40453 – CL44eN-BAS Dishwasher Page 7 of 12


CL44eN-BAS
GAS L-R 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

CL
11 1/2"
11 7/16" 19 7/16"
9 1/16" 18 7/16"
6 7/8" 18 1/8"
3 9/16"
BOOSTER 4"

3 7/16"
4 1/4" P2
DWT 3/8" EXHAUST
1/4" 4" X 16"
E1
5/8" P3
11 1/2"
5 1/2" CHEMICAL PORTS

2 1/4"
10 1/2"
CL

2"

1/2"
2 7/16"
E2 P1 P11 E3 P7
23" P12 P5 FLOOR SINK
P1 P4 P6 (BY OTHERS)
OPEN DOOR
CLEARANCE P10 12"
MIN

20"
SERVICE
CLEARANCE
(BOTH SIDES)

PLUMBING NOTES:
MISCELLANEOUS NOTES: ELECTRIC, STEAM, AND GAS HEATS
OPTIONAL VENT HOODS OR EXTENDED HOODS EXHAUST WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD
REQUIREMENTS: 200 CFM ENTRANCE END OR EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN
400 CFM EXIT END. COMMON WATER SUPPLY LINE AT SERVICE CONNECTION.
ALL DIMENSIONS TAKEN FROM FLOOR LINE MAY BE RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS
INCREASED APPROXIMATELY 3/4" OR DECREASED 1/2". FOR BEST RESULTS.
44" INSIDE TANK (AT TABLE CONNECTION) FOR NON-BOOSTER MACHINE (P6 CONN):
43-25/32" TABLE TO TABLE. RECOMMENDED BUILDING FLOWING WATER PRESSURE TO THE
DISHWASHER IS 20 PSI, (15 PSI MIN - 25 PSI MAX).
NET WEIGHT OF MACHINE: 501 LBS (STD HEIGHT), IF PRESSURES HIGHER THAN 25 PSI ARE PRESENT, A PRESSURE
DOMESTIC SHIPPING WEIGHT: 576 LBS (STD HEIGHT). REGULATING VALVE WITH INTERNAL THERMAL EXPANSION BY-PASS
CLeN LATENT AND SENSIBLE HEAT DISSIPATION MUST BE SUPPLIED (BY OTHERS) IN THE WATER LINE TO THE
INFORMATION ON F40459. DISHWASHER.
FOR CONVENIENCE WHEN CLEANING, WATER TAP SHOULD BE
INSTALLED NEAR MACHINE WITH HEAVY DUTY HOSE AND
SQUEEZE VALVE.
SERVICE CONNECTION WHEN USED, CHEMICAL SANITIZING FEEDER MUST BE CERTIFIED
FOR MOTORS AND CONTROLS TO NSF STANDARD 29.
MOTORS: 1/6 HP CONVEYOR
2 HP WASH GAS HEAT ONLY
MINIMUM FOR NATURAL GAS, PRESSURE TO THE BURNER (CUSTOMER
RATED SUPPLY MAXIMUM CONNECTION) SHOULD BE 3.5" MIN, 7" MAX W.C.
VOLTAGE AMPS CIRCUIT PROTECTIVE FOR LP GAS, PRESSURE TO THE BURNER (CUSTOMER
CONDUCTOR DEVICE CONNECTION) SHOULD BE 8" MIN, 11" MAX. W.C.
AMPACITY
208-240/60/3 10.7 15 15 IF GAS PRESSURE IS HIGHER THAN 7"(NAT) OR 11"(LP) W.C.,
A PRESSURE REGULATING VALVE MUST BE INSTALLED
380/60/3 7.7 15 15 (BY OTHERS) IN THE GAS LINE TO THE DISHWASHER.
480/60/3 6.7 15 15 GAS HEAT (NATURAL OR LP) BTU/HR INPUT - 78,000.
600/60/3 6.1 15 15 GAS EXHAUST VENTING MUST BE INSTALLED ACCORDING
208-240/60/1 16.9 20 20 TO LOCAL CODE. DO NOT CONNECT FLUE TO POWER VENT.
SEE INSTALLATION MANUAL FOR GAS VENTING.

Page 8 of 12 F40453 – CL44eN-BAS Dishwasher


CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
GAS R-L

CL
14 9/16"
19 7/16" 12 1/4"
18 7/16" 12"
18 1/8" 9 1/16"
11 7/16" 4"
3 9/16" 3 7/16"
BOOSTER
EXHAUST 1/8"
4" X 16"

P10
11 1/2" 4 1/4" DWT
CHEMICAL P11
PORTS 5/8"
2 7/16"
P3 5 1/2"
CL
10 1/2" 2"
P2
2 1/4"
1/2"
FLOOR SINK
P7 P6 E1 E2 P1 P1 P5 (BY OTHERS)
P12 P4
23" E3
OPEN DOOR
CLEARANCE 12"
MIN

20"
SERVICE
CLEARANCE
(BOTH SIDES)
PLUMBING CONNECTIONS
CONNECTION INFORMATION
(AFF = ABOVE FINISHED FLOOR)
LEGEND
ELECTRIC, STEAM, AND GAS HEATS
P1 DRAIN: 2" FPT, 7-3/8" AFF TWO POSSIBLE CONNECTIONS;
ELECTRICAL CONNECTIONS MAY BE DRAINED TO EITHER SIDE OF VALVE, PLUG OPPOSITE SIDE.
P2 SANITIZER FEEDER: REMOVE 1/8" NPT PIPE PLUG TO ACCESS TAPPED HOLE.
CONNECTION INFORMATION 1/8" NPT 59-1/2" AFF (LOW TEMP ONLY)
(AFF = ABOVE FINISHED FLOOR) P3 RINSE FEEDER: REMOVE 1/8" NPT PIPE PLUG TO
LEGEND ACCESS TAPPED HOLE. 1/8" NPT 59-9/16" AFF.
P4 DETERGENT PROBE SENSOR: REMOVE CAP AND STUD ASSEMBLY TO ACCESS
ELECTRIC, STEAM, AND GAS HEATS 7/8" DIA HOLE (WASH TANK ONLY). 14-5/8" AFF.
E1 ELECTRIC CONNECTION: SINGLE POINT, ELEC, GAS, P5 INDIRECT DRAIN-FLOOR SINK: BY OTHERS, 0" AFF. WHEN REQUIRED,
& STEAM, 1-1/4" CONDUIT HOLE OR 2" CONDUIT, INSTALL FLOOR SINK OUTSIDE THE PERIMETER OF THE DISHWASHER.
63-3/4" AFF P6 COMMON WATER CONNECTION: 1/2" FPT,
E2 ELECTRIC CONNECTION: BOOSTER. 15KW/30KW, 11-3/16" AFF.
1-1/4" CONDUIT HOLE OR 2" CONDUIT HOLE, HIGH TEMP. W/O BOOSTER 180°F MIN.
63-3/4" AFF 194°F MAX.
LOW TEMP. 120°F MIN.
E3 ELECTRIC CONNECTION: DETERGENT, SANITIZER
(LOW TEMP ONLY) AND RINSE FEEDERS. P7 COMMON WATER CONNECTION: 1/2" FPT,
1/2" CONDUIT. 64-1/4" AFF 11-3/16" AFF
HIGH TEMP. W/15K BOOSTER 140°F MIN.
HIGH TEMP. W/30K BOOSTER 110°F MIN.

GAS HEAT ONLY


OPTIONAL DRAIN WATER TEMPERING P10 GAS CONNECTION - NAT., 1/2" FPT, 10-3/4" AFF;
3.5" MIN, 7" MAX W.C. INCOMING.
P12 COLD WATER CONNECTION: 1/2" FPT, COLD TEMP 80°F MAX 7-3/8" AFF. P11 GAS CONNECTION - L.P., 1/2" FPT, 10-3/4" AFF;
8" MIN, 11" MAX W.C. INCOMING.

F40453 – CL44eN-BAS Dishwasher Page 9 of 12


CL44eN-BAS
STEAM L-R 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

CL

11 1/2" 19 7/16"
11 7/16" 18 7/16"
9 1/16" 18 1/8"
6 7/8" 1 3/4"
3 9/16"
BOOSTER 4"
3 7/16"
1 5/16"
4 1/4" P2
DWT 3/8"
EXHAUST
4" X 16"
5/8" E1
P3
11 1/2"
5 1/2" CHEMICAL PORTS

10 1/2"
CL
7 1/2"
9 7/8"
2"
2 1/4"
P12 1/2"
E2 P1 E3 P7
23" P5 FLOOR SINK
P1 P4 P9 P6 (BY OTHERS)
OPEN DOOR
CLEARANCE P8 12"
MIN

20"
SERVICE
CLEARANCE
(BOTH SIDES)

MISCELLANEOUS NOTES:
PLUMBING NOTES:
OPTIONAL VENT HOODS OR EXTENDED HOODS EXHAUST
REQUIREMENTS: 200 CFM ENTRANCE END ELECTRIC, STEAM, AND GAS HEATS
400 CFM EXIT END. WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD
ALL DIMENSIONS TAKEN FROM FLOOR LINE MAY BE OR EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN
INCREASED APPROXIMATELY 3/4" OR DECREASED 1/2". COMMON WATER SUPPLY LINE AT SERVICE CONNECTION.
44" INSIDE TANK (AT TABLE CONNECTION) RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS
43-25/32" TABLE TO TABLE. FOR BEST RESULTS.
NET WEIGHT OF MACHINE: 501 LBS (STD HEIGHT), FOR NON-BOOSTER MACHINE (P6 CONN):
DOMESTIC SHIPPING WEIGHT: 576 LBS (STD HEIGHT). RECOMMENDED BUILDING FLOWING WATER PRESSURE TO THE
CLeN LATENT AND SENSIBLE HEAT DISSIPATION DISHWASHER IS 20 PSI, (15 PSI MIN - 25 PSI MAX).
INFORMATION ON F40459. IF PRESSURES HIGHER THAN 25 PSI ARE PRESENT, A PRESSURE
REGULATING VALVE WITH INTERNAL THERMAL EXPANSION BY-PASS
MUST BE SUPPLIED (BY OTHERS) IN THE WATER LINE TO THE
DISHWASHER.
SERVICE CONNECTION FOR CONVENIENCE WHEN CLEANING, WATER TAP SHOULD BE
FOR MOTORS AND CONTROLS INSTALLED NEAR MACHINE WITH HEAVY DUTY HOSE AND
MINIMUM SQUEEZE VALVE.
RATED SUPPLY MAXIMUM WHEN USED, CHEMICAL SANITIZING FEEDER MUST BE CERTIFIED
VOLTAGE AMPS CIRCUIT PROTECTIVE TO NSF STANDARD 29.
CONDUCTOR DEVICE
AMPACITY STEAM HEAT ONLY
200-240/50/3 10.6 15 15
FLOWING STEAM PRESSURES ABOVE 50 PSI MUST HAVE A
208-240/60/3 10.7 15 15 PRESSURE REGULATOR (BY OTHERS) INSTALLED IN THE
380-415/50/3 7.0 15 15 STEAM LINE.
380/60/3 7.7 15 15 SHUT OFF VALVE MUST BE SUPPLIED (BY OTHERS) IN THE
STEAM LINE TO THE DISHWASHER.
480/60/3 6.7 15 15
600/60/3 6.1 15 15
208-240/60/1 16.9 20 20

Page 10 of 12 F40453 – CL44eN-BAS Dishwasher


CL44eN-BAS
701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com
STEAM R-L

CL

14 9/16"
13 3/4"
19 7/16" 12"
18 7/16" 10 11/16"
18 1/8" 9 1/16"
11 7/16" 4"
3 9/16" 3 7/16"
BOOSTER
EXHAUST 1/8"
4" X 16"

11 1/2" 4 1/4" DWT


CHEMICAL
PORTS 5/8"
5 1/2"
7 1/2"
P3
9 7/8"
CL
10 1/2"
2" P2
2 1/4"
1/2"
FLOOR SINK
P7 P6 E1 P12 E2 P1 P1 P9 P5 (BY OTHERS)
P4
23" E3 P8
OPEN DOOR
CLEARANCE 12"
MIN

20"
SERVICE
CLEARANCE
(BOTH SIDES)
PLUMBING CONNECTIONS
CONNECTION INFORMATION
(AFF = ABOVE FINISHED FLOOR)
LEGEND
ELECTRIC, STEAM, AND GAS HEATS
P1 DRAIN: 2" FPT, 7-3/8" AFF TWO POSSIBLE CONNECTIONS;
MAY BE DRAINED TO EITHER SIDE OF VALVE, PLUG OPPOSITE SIDE.
P2 SANITIZER FEEDER: REMOVE 1/8" NPT PIPE PLUG TO ACCESS TAPPED HOLE.
ELECTRICAL CONNECTIONS 1/8" NPT 59-1/2" AFF (LOW TEMP ONLY)
CONNECTION INFORMATION P3 RINSE FEEDER: REMOVE 1/8" NPT PIPE PLUG TO
ACCESS TAPPED HOLE. 1/8" NPT 59-9/16" AFF.
(AFF = ABOVE FINISHED FLOOR)
P4 DETERGENT PROBE SENSOR: REMOVE CAP AND STUD ASSEMBLY TO ACCESS
LEGEND 7/8" DIA HOLE (WASH TANK ONLY). 14-5/8" AFF.
P5 INDIRECT DRAIN-FLOOR SINK: BY OTHERS, 0"AFF. WHEN REQUIRED,
ELECTRIC, STEAM, AND GAS HEATS INSTALL FLOOR SINK OUTSIDE THE PERIMETER OF THE DISHWASHER.
E1 ELECTRIC CONNECTION: SINGLE POINT, ELEC, GAS, P6 COMMON WATER CONNECTION: 1/2" FPT,
& STEAM, 1-1/4" CONDUIT HOLE OR 2" CONDUIT, 11-3/16" AFF.
63-3/4" AFF HIGH TEMP. W/O BOOSTER 180°F MIN.
E2 ELECTRIC CONNECTION: BOOSTER. 15KW/30KW, 194°F MAX.
1-1/4" CONDUIT HOLE OR 2" CONDUIT HOLE, LOW TEMP. 120°F MIN.
63-3/4" AFF P7 COMMON WATER CONNECTION: 1/2" FPT,
E3 ELECTRIC CONNECTION: DETERGENT, SANITIZER 11-3/16" AFF
(LOW TEMP ONLY) AND RINSE FEEDERS. HIGH TEMP. W/15K BOOSTER 140°F MIN.
1/2" CONDUIT. 64-1/4" AFF HIGH TEMP. W/30K BOOSTER 110°F MIN.

STEAM HEAT ONLY


P8 STEAM COILS: 10 TO 50 PSI FLOWING, 3/4" FPT, 11-1/8" AFF.
OPTIONAL DRAIN WATER TEMPERING P9 CONDENSATE RETURN: A 10 PSI MINIMUM DIFFERENTIAL PRESSURE ACROSS
P12 COLD WATER CONNECTION: 1/2" FPT, COLD TEMP 80°F MAX 7-3/8" AFF. THE STEAM TRAP MUST BE MAINTAINED. 3/4" FPT. 11-1/8" AFF ONE
CONNECTION. (ONE BUCKET TYPE TRAP FURNISHED).

F40453 – CL44eN-BAS Dishwasher Page 11 of 12


CL44eN-BAS
DISHWASHER 701 S Ridge Avenue, Troy, OH 45374
1-888-4HOBART • www.hobartcorp.com

SPECIFICATIONS: Meets requirements of ASSE Standard solenoid valve in common piping system. Rinse agent and Low
No. 1004. Temp Final Rinse – Sanitizer agent (5.25% sodium hypochlorite
– bleach) dispenser injection ports provided in final rinse piping
DESIGN: Semi automatic, high or low temperature single-tank,
above chamber. Caution: Certain materials, including silver,
rack-type dishwasher with flexible thermal layer curtains at
aluminum, and pewter are attacked by sodium ­hypochlorite
the ends of chamber and between wash and final rinse zones.
(bleach) in the chemical sanitizing dishwasher mode of
Insulated hinged inspection doors located in front of machine
­operation.
provide easy access to wash arms, rinse arms, strainer, strainer
basket, and pump intake screen. Length of machine inside FILL: Fill water line is equipped with vacuum breaker on down-
tank (at table connection) 44". Machine designed to clean and stream side of electrically operated solenoid valve in common
sanitize with hot water 160°F wash and 180°F (minimum) final piping system, for automatic maintenance of tank level.
rinse, or low temperature 130°F wash and 120°F final rinse and DRAIN AND OVERFLOW: Large bell-type automatic ­overflow
a chemical sanitizer. Water hardness recommended to be 3 gr. and drain valve controlled from inside of machine. Drain
or less for best results. Automatic interlocks shut off pump and automatically seats by closing inspection doors. Drain seal is
conveyor if door is opened when machine is in operation. large diameter, high temperature o-ring. Drain housing can be
CONSTRUCTION: Tank, chamber, frame, legs, control box, plumbed from load or unload end of machine.
doors, and all panels are constructed of stainless steel. STANDARD EQUIPMENT: Digital display of wash and final
PUMP: The 165 gpm recirculating stainless steel pump and rinse temperature. Positive low water protection for tank heat.
impeller with a ceramic seat seal. Easily accessible pump Thermal Layered Curtains throughout machine are keyed to
assembly permits quick inspection. The pump is self-draining. ensure proper placement. Drain is ­automatically closed when
All piping distributing water to the upper and lower wash arms inspection doors are closed. Stainless steel adjustable feet.
is stainless steel tubing. Bolted stainless steel enclosure panels around perimeter
and underneath machine. Automatic tank fill. Door interlock.
PUMP MOTOR: Built for Hobart 2 hp grease-packed ball bear- Auto-timer. Vent fan and booster heater controls. Single point
ings, splash proof, ventilated with manual, resettable inherent electrical connection. Low temperature alerts. Service diag-
overload protection. Available in electrical specifications of nostics. Dirty water indicator. Configurable delime notification.
208-240/60/1, 208-240/60/3, 480/60/3 and 600/60/3. Also NSF rated configurable Pot and Pan dwell mode. Energy Saver
available, but not submitted for UL listing are 200-240/50/3 and Mode. NAFEM Data Protocol compliant.
380-415/50/3.
WASH TANK HEATING SELECTIONS (must choose one):
CONTROLS: A stainless steel control module with power ELECTRIC: One electric Incoloy® sheathed immersion heater
and “start/stop” buttons is mounted on top of the machine. (15 KW) removable from inside tank. Tank water temperature is
Machine control circuitry will be operated from a 120-volt con- controlled by microprocessor controlled thermostat with posi-
trol circuit transformer. Electrical components are completely tive low-water protection and magnetic contactor. (Disconnect
wired with 105°C, 600V thermoplastic insulated wire with switches not furnished.) A high limit device mounted on the
stranded conductors routed through UL listed electrical conduit surface of the tank additionally protects heating element.
or covered wire way.
STEAM: One-inch stainless steel steam coil. Tank water
CONVEYOR: Rapid Return drive, designed for more even temperature controlled by microprocessor controlled ther-
throughput of racks and allows for a 16-inch separation mostat with positive low-water protection. Steam supplied to
between the wash and the rinse zone. Racks conveyed auto- machine through high temperature steam solenoid valve and
matically through wash and rinse zones and onto clean dish line strainer.
table. Ball Detent Clutch drive prevents damage to machine or
racks, should movement of racks be obstructed. Rack tracks, GAS: Regulated infrared immersion tube gas burner system.
conveyor structure, and drive units of stainless steel for 193⁄4" x Microprocessor controlled thermostat and a blower with a
193⁄4" racks as standard. Conveyor speed: 5.6 FPM. pressure switch control tank water temperature. Positive low
water protection is provided. A high limit device mounted on
DRIVE MOTOR: Built for Hobart, 1⁄6 horsepower gear motor, the surface of the tube additionally protects immersion tube.
­ventilated with manual, resettable inherent overload protec- A solid-state igniter board controls the gas valve and provides
tion. Available in electrical specifications of 208-240/60/1, flame ignition. A transformer steps the control circuit voltage
208-240/60/3, 480/60/3 and 600/60/3. Also available, but not down from 120 volts to 24 volts to power the igniter board and
submitted for UL Listing are 200-240/50/3 and 380-415/50/3. gas valve. For natural gas, gas pressure to burner (customer
POWER WASH: Wash tank is equipped with upper and lower connection) not to exceed 7" W.C. For LP gas, gas pressure
stainless steel CFD Wash Arms which effectively direct water to burner (customer connection) not to exceed 11" W.C. If gas
jets to all ware surfaces. Both upper and lower wash arms are pressure is higher than 7" W.C. natural or 11" W.C. LP pressure
self-aligning and have easily r­ emovable end caps for cleaning regulating valve must be supplied (by others) in the gas line to
without use of tools. A removable ­perforated ­stainless steel the dishwasher.
strainer pan supports a deep perforated stainless steel basket. OPTIONAL EQUIPMENT AT EXTRA COST:
FINAL RINSE: Final rinse flow rate: 2.1 gpm, .62 gpr, 126-gph. Stainless steel pressureless booster heater. Stainless steel vent
Stainless steel upper and lower Auto Position Rinse Arms™ hoods with vent stack and locking-type damper. Higher than
have single rows of nozzles. Racks entering the rinse zone standard chamber. Side loaders and unloaders. Floor mount-
automatically trigger rinse. Final rinse water line is equipped ed steam booster. 193⁄4" x 193⁄4" peg, combination and miscel-
with a vacuum breaker downstream of an electrically ­operated laneous racks. Table limit switch. Drain water tempering kit.
As continued product improvement is a policy of Hobart, specifications are subject to change without notice.

Page 12 of 12 F40453 – CL44eN-BAS Dishwasher