You are on page 1of 23

Engineer Data ED-FUW-201401A

DAIKIN FUW Air Handling Units


Horizontal Unit
Model: FUW020H-FUW150H
Air Flow: 2000m3/h-15000m3/h

Vertical Unit
Model: FUW040V-FUW250V
Air Flow: 4000m3/h-25000m3/h
Single Skin Air Handling Unit FUW

Literature No.: ED-FUW-201401A


Supersedes: ED-FUW-201311A

Contents
Nomenclature....................................................................................................................... 2
Features................................................................................................................................ 3
Specifications....................................................................................................................... 4
Wet Film Humidifer (Optional)............................................................................................. 6
Dimensions........................................................................................................................... 7
Selection Software............................................................................................................. 13
Special Notes...................................................................................................................... 14
Motor Power-Max ETP........................................................................................................ 15
Wiring Diagram................................................................................................................... 16
Installation........................................................................................................................... 16
Service and Maintenance.................................................................................................. 18
Common Failures............................................................................................................... 20

Note: Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.

Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning: Moving machinery and electrical power hazard may cause severe personal injury or
death. Disconnect and lock off power before servicing equipment.

1
FUW Single Skin Air Handling Unit

Nomenclature

F U W 080 H R 08 -4 L -F F D E
Export
Design ID
Discharge Type
F - Horizontal Discharge Type
T - Top Discharge Type
Power Supply:
F - 380V/3N~/50Hz
R - 380V/3N~/60Hz
P - 208-230V/3N~/60Hz
Q - 460V/3N~/60Hz
Pipe Connection:
R - Left Hand
L - Right Hand
(Facing Air Discharge)
Coil Rows:
4 - 4 Rows
6 - 6 Rows
External Total Pressure
08 - 80Pa; 15 - 150Pa
22 - 220Pa; 30 - 300Pa
Air Conditioning
R - Return Air
F - Fresh Air
Structure Type
H - Horizontal
V - Vertical
Air Flow
080 - 8000m3/h
FUW - Single-Skin AHU

2
Single Skin Air Handling Unit FUW

Features
General Information
Packed in a high-intensity chassis with professional coils, efficient and low-noise fans and filters, the DAIKIN
FUW series air handling units best suit customer demand for horizontal and vertical air handling units. This
series saves customers indoor space but brings them more benefits. These products can be widely used for
the central air-conditioning systems in hotels, supermarkets,airports, hospitals, factories, research institutes,
enterprises and office buildings. They are tailored to installation in the case of limited space, no noise or
housing renovation, where no equipment room is available.

Structure
The high-strength galvanized steel sheets, cured with static spraying, are highly corrosion-proof. Made of a
new type of PU material, the heat insulator features ideal thermal insulation, sound absorption and no water
absorption. The insulator is also proof against cold bridge.

Heat Exchanger
Made on the OAK manufacturing facility we imported, the heat exchanger uses thin-walled copper tubes
mechanically expanded into new-type fins, to ensure close contact between the cooper tubes and fins. This
enables the coils to provide best heat exchange and the units to run reliably and efficiently. The coils are
available in various specifications and loop types, allowing users to derive the optimal operation model from
the different parameters to serve diversified needs.
Fan
With efficient tilted multi-blade centrifugal fans, this unit features large air flow, low noise and high reliability.
As the fan bearing requires no oiling, the unit saves customers maintenance costs.

Motor
V-belt driving, No less than IP54 class F ,provide different amounts of air fow and ETP to meet different needs.

Filter
The air inlet is equipped with a primary nylon filter. A panel filter can also be selected at request of customers.

Coil Selection Software


All the computing results and the products built on these results have passed strict test. This ensures their
safe, reliable and efficient operation.

Performance
The FUW product series features a high ETP and a large cooling capacity. Slim in size and simple in structure,
this series makes it easy for installation and maintenance.

3
FUW Single Skin Air Handling Unit

Specifications
FUW-H (Horizontal)
Model FUW020H FUW030H FUW040H FUW050H FUW060H FUW080H FUW100H FUW120H FUW150H
Nominal air flow (m³/h) 2000 3000 4000 5000 6000 8000 10000 12000 15000
I 80 80 80 80 80 80 - - -
External
total II 150 150 150 150 150 150 150 150 150
pressure III 220 220 220 220 220 220 220 220 220
(Pa)
IV 300 300 300 300 300 300 300 300 300
4 rows (Return air) 12 17 24 28 35 49 58 71 89
Nominal
cooling 4 rows (Fresh air) 24 38 53 64 76 108 128 153 194
capacity 6 rows (Return air) 15 22 29 36 44 60 74 88 112
(kW)
6 rows (Fresh air) 33 47 66 83 97 134 170 200 246
4 rows (Return air) 18 28 37 46 55 74 93 113 139
Nominal
heating 4 rows (Fresh air) 28 43 59 74 87 119 150 179 225
capacity 6 rows (Return air) 22 33 44 54 66 88 110 131 165
(kW)
6 rows (Fresh air) 35 51 70 88 106 139 173 208 261
4 rows (Return air) 0.50 0.80 1.10 1.30 1.60 2.20 2.63 3.21 4.00
Nominal
chilled 4 rows (Fresh air) 1.10 1.52 2.42 2.84 3.50 4.64 5.78 6.93 8.78
water 6 rows (Return air) 0.68 1.00 1.34 1.64 2.10 2.72 3.33 3.99 5.05
flow (I/s)
6 rows (Fresh air) 1.52 2.28 3.01 3.63 4.26 6.09 7.00 7.83 8.70
4 rows (Return air) 0.42 0.66 0.88 1.09 1.30 1.77 2.22 2.68 3.31
Nominal 4 rows (Fresh air) 0.66 1.02 1.40 1.76 2.07 2.82 3.57 4.27 5.37
hot water
flow (I/s) 6 rows (Return air) 0.52 0.79 1.05 1.28 1.57 2.10 2.61 3.13 3.92
6 rows (Fresh air) 0.83 1.21 1.66 2.09 2.52 3.31 4.13 4.95 6.21
Type Corrugated aluminum fin mechanically bonded with copper tube
FPI 12
Work pressure (MPa) 1.6
Coil
Inlet/outlet pipe R1-1/2 R1-1/2 R1-1/2 R2 R2 R2 R2 R2-1/2 R2-1/2
Condensing water pipe R1-1/4
Copper pipe diameter (mm) 9.52 12.7
Type/Material Efficient centrifugal tilted multi-blade fans and galvanized steel
Fan Drive type V-belt
Air discharge Lower horizontal discharge
Power supply 380V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz
Motor type 3-phase asynchronous motor, No less than IP54 protection, class-F insulation
I 0.37(0.37) 0.55(0.55) 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.5) - - -
Motor
Motor output II 0.37(0.37) 0.55(0.55) 0.75(1.1) 1.1(1.1) 1.5(1.5) 1.5(1.5) 2.2(2.2) 2.2(2.2) 3.0(3.0)
power (kW) III 0.55(0.55) 0.75(0.75) 1.1(1.1) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(3.0) 3.0(4.0)
IV 0.55(0.55) 0.75(1.1) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0) 4.0(4.0)
Material Primary nylon filter
Filter
Thickness (mm) 21
Galvanized steel sheet cured with static spraying, and internally glued with advanced sound/heat insulators
Structure Type PU.
Height (mm) 468 468 468 468 468 606 606 697 723
Unit dimension Width (mm) 800 1040 1300 1550 1800 1800 2180 2270 2490
Length (mm) 950 950 950 950 950 1000 1000 1050 1050
Heigth (mm) 628 628 628 628 628 766 762 857 883
Packing Width (mm) 990 1230 1490 1740 1990 1990 2370 2460 2680
dimension
Length (mm) 1120 1120 1120 1120 1120 1170 1170 1220 1220
Unit weight 4 rows 81 96 122 152 161 224 269 294 366
(kg) 6 rows 92 109 133 159 165 244 294 338 404
NOTES:
1. THE ABOVE PARAMETERS ARE FOR STANDARD MODELS ONLY;
2. STANDARD RETURN AIR COOLING CONDITIONS: 27ºC(DB) /19.5ºC(WB);
STANDARD FRESH AIR COOLING CONDITIONS: 34ºC (DB) / 28ºC (WB);
ENTERING/LEAVING CHILLED WATER TEMPERATURE FOR STANDARD UNIT: 7ºC / 12ºC;
ENTERING/LEAVING HOT WATER TEMPERATURE FOR STANDARD UNIT: 60ºC / 50ºC;
3. STANDARD RETURN AIR HEATING CONDITIONS: 21ºC (DB);
STANDARD FRESH AIR HEATING CONDITIONS: 0ºC (DB);
4. THE UNIT WEIGHT IN THE TABLE ABOVE IS NET WEIGHT; OPERATING WEIGHT INCREASES BY APPROXIMATELY 20%;
5. THESE PARAMETERS ARE BASED ON 0M ABOVE SEA LEVEL, AND MAY VARY WITH ALTITUDE CHANGING;
6. THE DATAS IN ( ) ARE FOR 6 ROWS COIL;
7. THE UNIT CAN BE APPLIED UNDER HIGHER ETP AS REQUIRED BY THE CUSTOMER. FOR DESIRED CONFIGURATIONS, PLEASE USE
DAIKIN FUW SELECTION SOFTWARE.
8. NPT WATER INLET/OUTLET CONNECTION IS FOR OPTION.

4
Single Skin Air Handling Unit FUW

FUW-V (Vertical)

FUW FUW FUW FUW FUW FUW FUW FUW FUW FUW
Model 040V 050V 060V 080V 100V 120V 150V 180V 200V 250V
Nominal air flow (m³/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000
I - 80 - - - - - - - -
External
total II 150 150 150 150 150 150 - 150 150 150
pressure III 220 220 220 220 220 220 220 220 220 220
(Pa)
IV 300 300 300 300 300 300 300 300 300 300
4 rows (Return air) 23 31 35 51 59 79 90 116 125 150
Nominal
cooling 4 rows (Fresh air) 50 68 76 111 128 177 205 256 273 325
capacity 6 rows (Return air) 28 39 44 63 75 100 117 144 156 185
(kW)
6 rows (Fresh air) 64 86 96 142 167 219 252 319 343 420
4 rows (Return air) 36 48 55 82 97 126 149 185 201 245
Nominal
heating 4 rows (Fresh air) 58 76 87 129 153 199 237 294 319 398
capacity 6 rows (Return air) 44 57 66 95 115 145 176 214 234 289
(kW)
6 rows (Fresh air) 69 90 105 150 182 229 279 338 369 461
4 rows (Return air) 1.00 1.40 1.58 2.31 2.67 3.54 4.06 5.24 5.66 6.77
Nominal
chilled 4 rows (Fresh air) 1.96 3.05 3.41 5.02 5.77 8.03 9.28 10.44 10.44 10.44
water 6 rows (Return air) 1.25 1.74 1.98 2.86 3.36 4.50 5.29 6.50 7.06 8.36
flow (I/s)
6 rows (Fresh air) 2.88 3.63 3.63 6.42 7.54 9.28 9.28 14.45 15.55 15.66
4 rows (Return air) 0.83 1.11 1.27 1.89 2.24 2.90 3.44 4.26 4.64 5.67
Nominal
hot 4 rows (Fresh air) 1.33 1.74 2.00 2.98 3.53 4.60 5.47 6.80 7.36 9.20
water 6 rows (Return air) 1.00 1.31 1.53 2.20 2.64 3.36 4.06 4.94 5.42 6.68
flow (I/s)
6 rows (Fresh air) 1.60 2.08 2.42 3.47 4.20 5.30 6.45 7.81 8.53 10.66
Type Corrugated aluminum fin mechanically bonded with copper tube
FPI 12
Work pressure (MPa) 1.6
Coil Inlet/Outlet pipe R1-1/2 R1-1/2 R1-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2
Condensing water pipe R1-1/4
Copper pipe 9.52 12.7
diameter (mm)
Type/Material Efficient centrifugal tilted multi-blade fans and galvanized steel
Fan Drive type V-belt
Air discharge Top discharge
Power supply 380V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz
Motor type 3-phase asynchronous motor, No less than IP54 protection, class-F insulation
I - 0.75(1.1) - - - - - - - -
Motor
Motor output II 1.1(1.1) 1.1(1.1) 1.5(2.2) 1.5(1.5) 2.2(3.0) 2.2(2.2) - 4.0(4.0) 4.0(5.5) 5.5(5.5)
power (kW) III 1.1(1.5) 1.1(1.5) 1.5(2.2) 1.5(2.2) 3.0(3.0) 2.2(3.0) 4.0(4.0) 4.0(4.0) 5.5(5.5) 5.5(7.5)
IV 1.5(1.5) 1.5(1.5) 2.2(2.2) 2.2(2.2) 3.0(3.0) 3.0(3.0) 4.0(5.5) 5.5(5.5) 5.5(7.5) 7.5(7.5)
Material Primary nylon filter
Filter
Thickness (mm) 21
Galvanized steel sheet cured with static spraying, and internally glued with advanced sound/heat
Structure Type insulators PU.
Height (mm) 1082 1320 1320 1676 1676 2036 2036 2070 2070 2191
Unit
dimensions Width (mm) 935 1135 1135 1350 1350 1774 1774 2124 2124 2476
Length (mm) 585 655 655 736 736 956 956 955 955 955
Unit weight 4 rows 135 185 188 265 269 440 450 556 571 665
(kg) 6 rows 146 199 202 285 289 473 483 598 613 716

NOTES:
1. THE ABOVE PARAMETERS ARE FOR STANDARD MODELS ONLY;
2. STANDARD RETURN AIR COOLING CONDITIONS: 27ºC(DB) /19.5ºC(WB);
STANDARD FRESH AIR COOLING CONDITIONS: 34ºC (DB) / 28ºC (WB);
ENTERING/LEAVING CHILLED WATER TEMPERATURE FOR STANDARD UNIT: 7ºC / 12ºC;
ENTERING/LEAVING HOT WATER TEMPERATURE FOR STANDARD UNIT: 60ºC / 50ºC;
3. STANDARD RETURN AIR HEATING CONDITIONS: 21ºC (DB);
STANDARD FRESH AIR HEATING CONDITIONS: 0ºC (DB);
4. THE UNIT WEIGHT IN THE TABLE ABOVE IS NET WEIGHT; OPERATING WEIGHT INCREASES BY APPROXIMATELY 20%;
5. THESE PARAMETERS ARE BASED ON 0M ABOVE SEA LEVEL, AND MAY VARY WITH ALTITUDE CHANGING;
6. THE DATAS IN ( ) ARE FOR 6 ROWS COIL;
7. THE UNIT CAN BE APPLIED UNDER HIGHER ETP AS REQUIRED BY THE CUSTOMER. FOR DESIRED CONFIGURATIONS, PLEASE USE
DAIKIN FUW SELECTION SOFTWARE.
8. NPT WATER INLET/OUTLET CONNECTION IS FOR OPTION.

5
FUW Single Skin Air Handling Unit

Altitude Correction Factor


Altitude (m) 300 600 900 1200 1500 1800
Total heating capacity 0.99 0.98 0.97 0.96 0.94 0.93
Sensible heating capacity 0.96 0.93 0.90 0.86 0.83 0.80

Wet Film Humidifer (Optional)


FUW air handing unit

Humidifying volume (kg/h)


Model Air flow (m3/h) Coil rows Fresh air Return air
50mm 100mm 150mm 50mm 100mm 150mm
4 4 8 10 3 6 8
FUW020H 2000
6 4 8 - 3 6 -
4 6 11 14 5 9 12
FUW030H 3000
6 6 11 - 5 9 -
4 8 15 19 6 12 16
FUW040H 4000
6 8 15 - 6 12 -
4 10 19 24 8 15 20
FUW050H 5000
6 10 19 - 8 15 -
4 12 23 29 10 18 24
FUW060H 6000
6 12 23 - 10 18 -
4 15 30 - 13 24 -
FUW080H 8000
6 15 30 - 13 24 -
4 19 37 - 16 30 -
FUW100H 10000
6 19 37 - 16 30 -
4 23 44 - 19 36 -
FUW120H 12000
6 23 44 - 19 36 -
4 29 55 - 24 45 -
FUW150H 15000
6 29 55 - 24 45 -
4 9 17 - 7 14 -
FUW040V 4000
6 9 17 - 7 14 -
4 11 21 - 9 17 -
FUW050V 5000
6 11 21 - 9 17 -
4 14 26 - 11 22 -
FUW060V 6000
6 14 26 - 11 22 -
4 18 35 - 15 29 -
FUW080V 8000
6 18 35 - 15 29 -
4 24 45 - 19 37 -
FUW100V 10000
6 24 45 - 19 37 -
4 25 48 - 20 39 -
FUW120V 12000
6 25 48 - 20 39 -
4 32 61 - 26 50 -
FUW150V 15000
6 32 61 - 26 50 -
4 41 78 - 33 64 -
FUW180V 18000
6 41 78 - 33 64 -
4 43 83 - 35 68 -
FUW200V 20000
6 43 83 - 35 68 -
4 54 103 - 44 84 -
FUW250V 25000
6 54 103 - 44 84 -

NOTES:
1. WHEN THE FUW UNIT IS EQUIPPED WITH A WET FILM HUMIDIFIER, THE EXTERNAL TOTAL PRESSURE (ETP)
OF THE UNIT WILL DECREASE ACCORDINGLY:
50mm-15Pa, 100mm-25Pa, 150mm-35Pa, 200mm-45Pa
2. THE HUMIDIFYING VOLUME OF THE WET FILM HUMIDIFIER IS MEASURED IN THE FOLLOWING CONDITIONS:
FRESH AIR: 28OC DB, 10% RH; RETURN AIR: 28OC DB, RH 25%.
3. THE ABOVE TABLE SHOWS THE STANDARD HUMIDIFYING VOLUME. FOR ANY SPECIAL REQUIREMENT,
PLEASE USE DAIKIN FUW SOFTWARE FOR MODEL SELECTION.

6
Single Skin Air Handling Unit FUW

Dimensions
FUW-H (Horizontal)

45 J

55
L
R

Lifting hole 4-12x32


N

F D
B
M-50 Cooling water Cooling water
M inlet pipe outlet pipe
Manual air vent Terminal box
H

K
E
G
I

Condensation water
25
35

30 outlet pipe R1-1/4 90


A

Unit: mm

Dimension Length Width Heigth Air supply Connection pipe Return air Hanging holes
inlet
Model A B C D E F G H I L L
(4Rows) (6Rows) T J K R M N
FUW020H 950 800 468 238 265 170 326 294 118 66 110 266 680 395 198 940 554
FUW030H 950 1040 468 302 265 313 326 294 118 66 110 266 920 395 198 1180 554

7
FUW Single Skin Air Handling Unit

FUW-H (Horizontal)

44 J

55
R

T
Lifting hole 4-12x32
N

F S D S
B
M-50
M Cooling water Cooling water
Terminal box inlet pipe outlet pipe
Manual air vent
H

K
E
G
I

Condensation water
25
35

outlet pipe R1-1/4


30 90
A

Unit: mm

Dimension Length Width Heigth Air supply Connection pipe Return air Hanging holes
inlet
Model A B C D S E F G H I L L
(4Rows) (6Rows) T J K R M N
FUW040H 950 1300 468 180 235 265 230 326 294 118 66 110 266 1180 395 198 1440 554
FUW050H 950 1550 468 238 301 265 230 326 294 118 66 110 266 1430 395 198 1690 554
FUW060H 950 1800 468 238 301 265 352 326 294 118 66 110 266 1680 395 198 1940 554

8
Single Skin Air Handling Unit FUW

FUW-H (Horizontal)

44 J

55
R

T
Lifting hole 4-Ø12
N

F S D S
B
M-50
M Cooling water Cooling water
Terminal box inlet pipe outlet pipe
Manual air vent
H

K
E
G
I

Condensation water
35
35

outlet pipe R1-1/4


30 90
A

Unit: mm

Dimension Length Width Heigth Air supply Connection pipe Return air Hanging holes
inlet
Model A B C D S E F G H I L L
(4Rows) (6Rows) T J K R M N
FUW080H 1000 1800 606 242 311 343 334 407 392 118 138 138 303 1696 535 132 1940 755
FUW100H 1000 2180 606 242 311 343 658 407 392 118 138 138 303 2076 535 132 2320 755
FUW120H 1050 2270 697 291 376 407 614 469 456 118 138 138 303 2164 618 132 2410 848
FUW150H 1050 2490 723 381 474 407 580 470 519 118 138 138 303 2386 684 132 2630 848

9
FUW Single Skin Air Handling Unit

FUW-V (Vertical)

Cooling water
outlet pipe
Terminal box

Cooling water
inlet pipe

Condensation drain pipe R1-1/4

Unit: mm

Dimension Length Width Heigth Air supply Return Connection pipe Clearance Base hole
air inlet length location
Model A B C D E H P F G I I K K L M N
(4Rows) (6Rows) (4Rows) (6Rows)
FUW040V 585 935 1082 335 293 200 622 446 182 66 110 236 192 1055 968 520
FUW050V 655 1135 1320 395 341 254 724 546 152 66 110 326 282 1255 1168 590
FUW060V 655 1135 1320 395 341 254 724 546 152 66 110 326 282 1255 1168 590

10
Single Skin Air Handling Unit FUW

FUW-V (Vertical)

Cooling water
outlet pipe
Terminal box

Cooling water
inlet pipe

Condensation drain pipe R1-1/4

Unit: mm

Forklift Clearance Base hole


Dimension Length Width Heigth Air supply Connection pipe hole length location
location
Model A B C D E H F G I I K K Q L M N P
(4Rows) (6Rows) (4Rows) (6Rows)
FUW080V 736 1350 1676 471 404 281 720 182 83 137 343 288 500 1493 1400 675 197
FUW100V 736 1350 1676 471 404 281 720 182 83 137 343 288 500 1493 1400 675 197
FUW120V 956 1774 2036 561 482 483 950 480 83 137 228 184 655 1902 1826 907 334
FUW150V 956 1774 2036 561 482 483 950 480 83 137 228 184 655 1902 1826 907 334

11
FUW Single Skin Air Handling Unit

FUW-V (Vertical)

Cooling water
outlet pipe
Terminal box

Cooling water
inlet pipe

Condensation
drain pipe R1-1/4

Unit: mm

Dimension Length Width Heigth Air supply Connection pipe Forklift hole Clearance Base hole
location length location
Model A B C D H I
E F I K K Q L M N P
(4Rows) (6Rows) (4Rows) (6Rows)
FUW180V 955 2124 2070 476 382 406 1077 83 137 224 180 1003 2247 2175 907 334
FUW200V 955 2124 2070 476 382 406 1077 83 137 224 180 1003 2247 2175 907 334
FUW250V 955 2476 2191 561 454 478 1077 83 137 224 180 701 2597 2525 907 660

12
Single Skin Air Handling Unit FUW

Selection Software
DAIKIN selection software provide customers with more convenient and reliable services
„„ Professional model selection software for air handing units
„„ Convenient graphical user interface
„„ Providing most economic and reasonable combination solutions
„„ Provide different configuration options according to the requirements of the customer
„„ Output the performance table of the unit according to the customer’s requirements
„„ Figuring out the component list and automatically calculate the price of the entire unit
„„ Output units arrangement drawing, development drawing and technical specifications

13
FUW Single Skin Air Handling Unit

Special Notes
„„ Facing air discharge, if the chilled water inlet/outlet is on your left, the unit is L connection. Otherwise,
the unit is R connection.
For vertical type unit,refer to the below chart to judge the connection.
„„ Please provide unit model, quantity and operating condition when purchasing. Please contact us if any
other specifications required.

Left connection

Leaving air Entering air

Right connection

Horizontal
Figure 1

Left connection

Entering air

Right connection

Vertical
Figure 2

14
Single Skin Air Handling Unit FUW

Motor Power-Max ETP


FUW-H (Horizontal)

Unit model FUW020H FUW030H FUW040H FUW050H FUW060H FUW080H FUW100H FUW120H FUW150H
3
Air flow (m /h) 2000 3000 4000 5000 6000 8000 10000 12000 15000

Rows Motor output


power (kW) ETP (Pa)

0.37 190
0.55 370 190 65
0.75 510 330 170 110
1.1 550 330 260 170 130
4Rows 1.5 480 390 320 250
2.2 590 520 420 320 230
3 600 500 400 250
4 600 550 380
5.5 520
0.37 160
0.55 320 160
0.75 480 270 120 90
1.1 500 270 230 120
6Rows 1.5 420 350 250 180
2.2 550 460 350 230 160
3 550 440 330 180
4 550 500 320
5.5 460

FUW-V (Vertical)

Unit model FUW040V FUW050V FUW060V FUW080V FUW100V FUW120V FUW150V FUW180V FUW200V FUW250V
Air flow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000

Rows Motor output


power (kW) ETP (Pa)

0.75 90
1.1 270 240 90
1.5 470 390 230 230
2.2 460 420 200 230
4Rows
3 430 420 160
4 360 270 160
5.5 450 350 240
7.5 430
0.75
1.1 190 170
1.5 370 330 150 180
2.2 370 370 130 180
6Rows
3 350 370
4 270 230
5.5 550 400 270 170
7.5 500 360

15
FUW Single Skin Air Handling Unit

Wiring Diagram
Wiring chart for the power of Wiring chart for the power of the motor
the motor less than & equal to 3kW more than 3kW while less than 11kW

380V/3N~/50Hz 380V/3N~/50Hz

U V W U V W

Yellow/Green Yellow/Green

Wiring chart of type Y Wiring chart of type Ƹ

Note: the electric control equipments will be wired and the over-current, short-circuit and overheat
protectors will be set by the client himself.

Installation
Important Notice
Installation and maintenance are to be performed only by technicians who are familiar with local rules and
regulations, and experienced with this type of equipment.
Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate.
Cut off all power supplies before mounting or maintaining the unit.
Electric connections must conform to local laws and regulations.
The voltage should fluctuate within the range of ± 10% of the rated voltage.
The unit must be well earthed to prevent insulation failures.
All the wires must be securely connected.
The design of water pipes and ducts must conform to the Specifications of Heating, Ventilation and Air
Conditioning (GBJ19-87).

FUW Mounting Location


Make sure it is convenient to connect wires and pipes in the selected mounting location. The minimum space.
reserved around FUW horizontal units is shown in Figure 3; FUW vertical units are shown in Figure 4

Base
4-Anchor bolt

Figure 3 Figure 4

16
Single Skin Air Handling Unit FUW

Suspending Installation
During the installation, please handle the unit or packing case with care, to avoid damage to any part. Before
leaving the factory, the unit or its packing case already has forklift handling holes or hoisting holes. During
the hoisting, the lifting poles should be strong enough to bear the unit weight. Please handle the FUW unit
as shown in Figure 5.

Figure 5

Storage
When a unit is placed outdoors before it is installed in an equipment room, please protect it from dirt, rain,
snow and even animals. Be sure not to damage the protective film on its surface.

Base Setup
Adjust the base levelness
The base, if not put on a level surface, may result in water leakage or break the dynamic balance of the fan
due to poor drainage of condensing water or cause the bearing to fail or vibrate.
The base height should match the U-shaped pipe blend. The drain pipe should be connected with the U-
shaped water seal, as shown in Figure 3.
Need suitable water seal when installing in order to condensation water drain smoothly.

Drain pipe
H

Not more than 1/2h

Drain plug

H is more than the negative pressure of unit + 20mm


1mm H2O = 9.8Pa

Figure 6

17
FUW Single Skin Air Handling Unit

Service and Maintenance

Notices
Responsibilities and Obligations
This product comes to you with the DAIKIN service warranty. Only DAIKIN technicians or experienced
technicians authorized by DAIKIN are allowed to install, test or maintain these products.

Using The Unit


After installing the piping system, please first wash the pipes. To do so, be sure to shut off the valve connected
to the unit, to prevent unwanted things in the pipes from entering the coils or blocking the loop.
After the installation, please check there is anything unwanted inside the fan. Turn the blades by hand. If no
unusual noise is heard, turn on the fan, to see if it is running properly.
Before turning on the water flow, please open the exhaust valve to let the air out of the pipe till water flows
out from the pipe.
When the unit stops running, fill the coil with water or otherwise keep the pipe from erosion.
When the environment temperature falls below 0°C in the winter, drain the pipe to prevent it from freezing.
Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every
2 or 3 years. If possible, use soft water to supply hot/cold water to the coils.
Check the unit filter for dust regularly; if possible, please use a pressure difference detector. Once the
resistance reaches the limit, wash or replace the filter media in time.
After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.

Servicing And Maintenance


A sound maintenance schedule helps reduce operational failures.
A dirty filter may worsen the performance and air flow of the unit. Thus, replace or wash the filter in time. Be
sure to check the filter every month to see if it is clean enough.
Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum
cleaner to clean the dust.
Do the following on a regular basis:
- Clean up the fans every 6 months, to keep them in good balance..
- Check and clean the water coils. Check the drain pipe in case dust or unwanted things block the pipes.
- Check if the bearing comes loose. If so, fix the fastening screw tightly to the bearing.
- Clean the dirt in the coils at regular intervals.
- Check that the side front of the fan V-belt is flush with the side front of the motor V-belt, to make sure the
pulleys are placed on a flat plane. Usually, check using the four-point method (see Figure 7).
- Use V-belts of the same brand and model. Never mix old V-belts with new ones. Make sure that the V-
belts match the pulley grooves.
- Use a tensiometer to check the V-belts, and tighten them properly (see Figure 8).

18
Single Skin Air Handling Unit FUW

Tension of The V-shaped Belt


Check and adjust the levelness of the v-belt using the four-point method, as shown in Figure 7.
Ruler

Figure 7

Check the tightness of the V-belt, as shown in Figure 8.


Ce
sp nter
ac
ing to ce
nter
The belt tension indicator acts on the
midpoint of center-to-center spacing

Torture 16mm
every meter

Figure 8

19
FUW Single Skin Air Handling Unit

Common Failures
FUW Units

Common
Locations Possible Causes Solutions
failures

Blower out off center Contact the seller


Loose bearings due to large gap Contact the seller
Blower is loose Contact the seller
1. Blower Loose connection between bearings Contact the seller
Blower is damaged Contact the seller
The fan fastening screw is loose Fasten the screw
There are unwanted things inside fans. Remove unwanted things
Belt pulley is not fastened on the axis. Fasten the V-shaped belt
V-shaped belt is loose.Adjust after it runs for 48 hours for
Fasten the V-shaped belt
the first time.
V-shaped belt it too tight Fasten the V-shaped belt
The V-shaped belt model is not right Replace the V-shaped belt
2. Drive Replace V-shaped belts with those of
V belts are of different length
the same length
The V-shaped belt pulley of the fan does not align with that
Align the belt pulleys
of the motor
V-shaped belt is damaged Replace the V-shaped belt
The screw fixing the motor to the motor base is loose Fasten the screw
Bearing failure Replace bearings
Lack of lubricant oil Add lubricant oil
The bearing housing is loose Fasten the bearing housing
3. Bearing The bearing is not mounted flush Re-mount the bearing
There are unwanted things inside bearings Remove unwanted things
Bearings are damaged Replace bearings
sound
Abnormal Bearings are rusty De-rust or replace bearings
There are unwanted things inside houses Remove the unwanted things
4. Fan house House is loose Contact the seller
Air intake house is damaged Contact the seller
Incoming line is loose Fasten the incoming line
5. Electric
Motor gives AC hum Contact the seller.
appliances
Phase lack Supply 3-phase power
Bent or distorted Replace axis
6. Axis Balance weight is loose Fasten the balance weight
Axis is loose Fasten axis
Duct is too small Re-design the duct
7. Air speed is too
high Static pressure has not reached the set static pressure Change the V-shaped belt pulley to
value reduce the fan speed
The duct is too small Re-design the duct
8. Periodical
System is unstable Adjust the system
vibration
Duct vibrates as the fan pulsates Adjust the fan speed
9. Noise caused
by hi-speed
Duct leaks Seal it with glue
wind passing the
aperture & holes
Duct turns too sharply Re-design the duct
10. When Duct expands sharply Re-design the duct
blocked,the high-
Duct shrinks sharply Re-design the duct
speed air rattles or
howls Air speed is too high inside the duct Re-design the duct
Damping connector is too tight Re-adjust the damping connector

20
Single Skin Air Handling Unit FUW

Common Locations Possible causes Solutions


failures
Blower is mounted incorrectly Contact the seller
1. Fan
Fan rotates in the opposite direction Regulate the power phase sequence
Actual resistance in the duct exceeds set resistance. Re-design the system
2. Duct system Duct is poorly sealed Seal with glue
Fireproof valve is shut off Shut on the fireproof valve
3. Filter Too dirty or even blocked Clean or replace filter
4. Coil Too dirty or even blocked Clean coil
The fan is The air inlet and the air outlet are not properly isolated.
functioning 5. Blocked air supply Thus, the air runs directly to the air inlet through the Add air deflector
but the air separator
supply is Elbow at the return air inlet and fan outlet are too close Move the fan
insufficient 6. F
 an air inlet is to the unit wallboard
blocked
The fan outlet is blocked Remove the obstructions
A length of straight tube is mounted at the fan outlet
during fan testing. Without straight tube, the fan
7.No collimator tube performance might be worsened. Thus, the fan may Mount collimator tube
at the fan outlet run faster to offset the resistance. (Check the fan
speed)
8. There’re unwanted The fan outlet is blocked Remove the obstructions
things inside fan
system There is an elbow at the fan outlet Re-design duct
Improper duct size Remove the obstructions
The access door is open Close the access door
The fan is
functioning 1.System The system is not well balanced and the actual Re-design the system
but the air resistance is lower than the set resistance
supply is No air valve or air valve blade Mount wind valve or wind valve blower
too large
Filter falls off Re-mount the filter
2. Duct Return duct leaks Seal it with glue

21
Warning ● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in
a particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable
for use, in the region where the product will be used. This statement does not purport to exclude,
restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

The air conditioners manufactured The airconditioning factories of


by Daikin Industries have received Daikin Industries have received
ISO 9001 series certification for environmental management system
quality assurance. standard ISO 14001 certification.
Certificate Number. 9601019 Certificate Number. EMS80362

Cautions on product corrosion


1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the
unit close to the sea shore, contact your local distributor.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/

© All rights reserved

Printed with soy ink.

Literature No.: ED-FUW-201401A


Supersedes: ED-FUW-201311A