Professional Documents
Culture Documents
& CHAPTER 4
✓ Cooking (kitchen)
✓ Gardening and
✓ fire protection
Types of System
✓ Direct connection from the main to all fixtures
✓ Pumped system
Hand wash
basin
Water closet
Bath tub
Hand wash Basin (HWB)
Water closet (WC)
Laundry (LA)
Urinals (UR)
10
2 Rate of flow
I. Design flow rate and loading units (Table 4.8)
II. Shall satisfy the required simultaneous
discharge
III. Loading units should not be used for outlet
fittings having high peak demands, e.g. those
in industrial installations. In these cases use
the continuous flow.
IV. Table 4.8 for WCs and Urinals does not give
loading units for sink tap DN20 or pressure
flushing valve
11
Table 4.8 Design flow rates and loading units
Outlet fitting4 Design flow rate Minimum Loading units
l/s flow rate l/s
WC flushing cistern single or dual flush – 0.13 0.05 2
to fill in 2 minutes
Source: BS 6700 12
Notes:
(1) Flushing troughs are advisable where likely use
of WCs is more than once per minute.
(2) Mixer fittings use less water than separate taps,
but this can be disregarded in sizing.
(3) Flow rates to shower mixers vary according to
type fitted. Manufacturers should be consulted.
(4) Manufacturers should be consulted for flow rates
to washing machines and dishwashers for other
than a single dwelling.
(5) For cistern fed urinals demand is very low and
can usually be ignored. Alternatively, use the
continuous flow.
13
3. Sizing procedure for supply pipes
i) The procedure below is followed by an
explanation of each step with appropriate
examples.
(1) Assume a pipe diameter.
(2) Determine the flow rate: (Refer fig. 4.4)
(a) By using loading units;
(b) For continuous flows;
(c) Obtain the design flow rate by adding (a) and (b).
(3) Determine the effective pipe length:
(Refer fig. 4.5 to 4.7)
(d) Work out the measured pipe length;
(e) Work out the equivalent pipe length for fittings;
14
(f) Work out the equivalent pipe length for draw-offs;
(g) Obtain the effective pipe length by adding (d), (e)
and (f).
(4) Calculate the permissible loss of head:
(h) Determine the available head:
(i) Determine the head loss per meter run through
pipes (Figure 4.10);
(j) Determine the head loss through fittings;
(k) Calculate the permissible head loss.
(5) Determine the pipe diameter:
(l) Decide whether the assumed pipe size will give the
design flow rate in (c) without exceeding the
permissible head loss in (k).
15
Fig. 4.4 Conversion chart - loading unit to flow
rate
16
Figure 4-10 Determination of pipe diameter
17
Fig. 4.5 Example of use of loading units
18
Fig. 4.6 Example of measured pipe length
19
Fig. 4.7 Examples of equivalent pipe length (using the example from fig. 4.6)
20
4 Distribution system in multi-storey building
1 Direct supply where municipal pressure is adequate
a) Direct supply to fixtures
b) Direct supply to elevated water tank
2 Pumping system, where pressure is not adequate or
storage is required
a) Direct pumping from a water main to
i. Sanitary fixture after water meter
- Where storage is not required
- Where the municipal water supply system
is not affected and approval is obtained
from water supply authority
21
Pumping system…
b) Direct pumping from water
supply line to elevated water
tank
c) Pumping from ground reservoir
to elevated tank
d) Direct pumping from ground
reservoir using Hydro- pneumatic
e) Direct pumping from ground
reservoir using variable speed
drive pumps (VSD)
22
23
d) Direct pumping from ground reservoir using Hydro- pneumatic
system
24
5 Residual pressure, pressure regulators, etc
1 Residual pressure
a) Min. 5 meters at fixture outlets
b) Some fixture or equipment require more
than 5 meter
2 Excessive water pressure
- To be regulated
3 Pressure relief valves
4 Vacuum relief valves
25
Pipe sizing
✓ Prepare layout of pipes & valves for the rooms requiring water supply
installation (from source to each fixtures)
3
5
2
4
For pipe 1-2
12 wash basins x 0.5 =6
10 WCs x 0.5 =5
1
2 urinals x 0.5 =1 Q = 0.25 14 = 0.935 𝑙/𝑠𝑒𝑐
2 sinks x1 =2
Total loading units = 14
wb bath wc
Ground floor
15
Pipe sizing
Pipe sizing
✓ Calculate the available head at the point of concern
Pipe sizing
✓ Select velocity; Maximum water velocities in pipe work are given in
table 3.8 (EBCS 9) for different water temperature
Water temperature Maximum water velocity
(oC) (m/s)
10 3.0
50 3.0
70 2.5
90 2.0
✓ Assume a pipe diameter based on selected velocity
✓ Determine percentage head loss for
the selected velocity from nomograph
and multiply by the effective length
or
1 2 3 4 5 6 7 8 9 10 11 12 13 14
2-3
3-4
4-5
5-6
6-7
7-8
5-9