You are on page 1of 50

ANSI/IEEE C37.20.

2-1987

metal-clad and
station-type cubicle switchgear

July 6, 1987 SHI0850

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE C37.20.2-1987

An American National Standard


IEEE Standard for Metal-Clad and
Station-Type Cubicle Switchgear

Sponsor
Switchgear Committee of the
IEEE Power Engineering Society

Secretariat
Institute of Electrical and Electronics Engineers
National Electrical Manufacturers Association

Approved September 22, 1983


IEEE Standards Board

Approved August 7, 1986


American National Standards Institute

@ Copyright 1987 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA
No part of this publication m a y be reproduced in a n y form,
in a n electronic retrieval system or otherwise,
without the prior written permission of the publisher.

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
IEEE Standards documents are developed within the Technical Com-
mittees of the IEEE Societies and the Standards Coordinating Committees
of the IEEE Standards Board. Members of the committees serve volun-
tarily and without compensation. They are not necessarily members of the
Institute. The standards developed within IEEE represent a consensus of
the broad expertise on the subject within the Institute as well as those
activities outside of IEEE which have expressed an interest in participating
in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE
Standard does not imply that there are no other ways to produce, test,
measure, purchase, market, or provide other goods and services related
to the scope of the IEEE Standard. Furthermore, the viewpoint expressed
a t the time a standard is approved and issued is subject to change brought
about through developments in the state of the art and comments received
from users of the standard. Every IEEE Standard is subjected to review
a t least once every five years for revision or reaffirmation. When a doc-
ument is more than five years old, and has not been reaffirmed, it is
reasonable to conclude that its contents, although still of some value, do
not wholly reflect the present state of the art. Users are cautioned to
check to determine that they have the latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any in-
terested party, regardless of membership affiliation with IEEE. Sugges-
tions for changes in documents should be in the form of a proposed change
of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean-
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since IEEE
Standards represent a consensus of all concerned interests, it is important
to ensure that any interpretation has also received the concurrence of a
balance of interests. For this reason IEEE and the members of its technical
committees are not able to provide an instant response to interpretation
requests except in those cases where the matter has previously received
formal consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA

Corrected Edition
July, 1987

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Foreword

(This Foreword is not a part of ANSI/IEEE C37.20.2-1987, IEEE Standard for Metalclad and Station-Type Cubicle
Switchgear.)

This standard includes only the requirements for metal-clad and station-type cubicle switchgear.
These requirements were previously a part of ANSI/IEEE C37.20-1969 (R 1981), IEEE Standard for
Switchgear Assemblies including Metal-Enclosed Bus (1974 Consolidated Edition). Other types of
equipment previously included in ANSI / IEEE C37.20-1969 (R 1981) will now be incorporated in
separate publications.
ANSI / IEEE C37.20 has for many years covered all switchgear assemblies including metal-enclosed
bus. Standards committees of IEEE Switchgear Assemblies Subcommittee and NEMA Power Switch-
gear Assemblies Technical Committee recommended that the document be further developed and,
where appropriate, the various sections be identified with their own standards. This approach also
identifies with the Conformance Test Procedure Standards.
This edition was prepared by the Power Switchgear Assemblies Technical Committee, National
Electrical Manufacturers Association (NEMA). NEMA is responsible for Section 4, Ratings and Section
6, Construction.
The Switchgear Assemblies Subcommittee of the IEEE Switchgear Committee is responsible for
Section 2, Definitions; Section 3, Service Conditions; Section 5, Tests; Section 7, General Application
Conditions; and Section 8, Handling, Storage, and Installation.
A Working Group of the NEMA Power Switchgear Assemblies Technical Committee revised ANSI /
IEEE C37.23-1970, IEEE Guide for Calculating Losses in Isolated-Phase Bus, to include ANSI / IEEE
C37.20 Section 8. The document updates the material for metal-enclosed conductors including cable
bus. The IEEE Switchgear Assemblies Subcommittee refined and expanded the document.
The following documents were developed for each product type based on ANSI/IEEE C37.20 (see
Fig A).

C37.20.1 Metal-Enclosed Low-Voltage Power Circuit-Breaker Switchgear (1000 V and Below)


C37.20.2 Metal-Clad and Station-Type Cubicle Switchgear (Above 1000 V)
C37.20.3 Metal-Enclosed Interrupter Switchgear (Above 1000 V)
C37.21 Control Switchboards
C37.23 Metal-Enclosed Bus and Guide for Calculating Losses in Isolated Phase Bus.

Through this joint effort over the many years, the switchgear assemblies standards have been of
extreme value to the industry and further suggestions for improvement gained in the use of this
standard will be welcomed.
The Standards Committee on Power Switchgear, C37, which reviewed and approved this standard,
had the following personnel at the time of approval:

W.E. Laubach, Chairman Charles H. White, Secretary

W.N. Rothenbuhler, Executive Vice-chairman of High- Voltage Switchgear Standards


S. H. Telender, Executive Vice-Chairman of Low-Voltage Switchgear Standards
D. L. Swindler, Executive Vice-chairman of IEC Activities
Organization Represented Name of Representative
Association of American Railroads. .................................................... Vacant
Association of Iron and Steel Engineers ................................................ J. M. Tillman
Electric Light and Power Group ....................................................... D. 0. Craghead
R. L. Capra (AZt)
D. A. Ditzler (AZO
K. D. Hendrix
David E. Soffrin (Alt)
T. D. Weston
J. H. Provanzana (AZt)

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Organization Represented Name of Representative
Institute of Electrical and Electronics Engineers.. ...................................... H. W. Mikulecky
M. J. Beachy (Alt)
G. R. Hanks
R. P. Jackson (Alt)
E. W. Schmunk
C. A. Schwalbe
C. E. Zanzie
National Electrical Manufacturers Association.. ........................................ G. A. Wilson
R. 0. D. Whitt
T. L. Fromm
R. A. McMaster
Tennessee Valley Authority.. ......................................................... Robert C. St. Clair
Testing Laboratory Group ............................................................. L. Frier
W. T. O’Grady
R. W. Seelbach (AW
US Department of the Army .......................................................... H. K. Snyder
US Department of the Interior, Bureau of Reclamation ................................. R. H. Auerbach
US Department of Defense, Defense Communications Agency.. .......................... Vacant
US Department of the Navy, Naval Construction Battalion Center.. ..................... R. L. Clark
Western Area Power Authority.. ...................................................... G. D. Birney

The Switchgear Assemblies Subcommittee of the IEEE Switchgear Committee that prepared and
approved this standard had the following personnel:

S.C. Atkinson, Chairman


A. Alsaker H. G. Frus J. Rule
C. Burland J. Joannou J. C. Scott
A. P. Colaiaco A. J. Kalvaitis J. F. Sellers
J. J. Dravis W. E. Lauach S. D. Smith
R. P. Ehas J. J. Mikos E. M. Spencer
F. C. Farrell M. Olender S. H. Telender
G. 0. Perkins

The Power Switchgear Assemblies Technical Committee of the NEMA Switchgear Section that
prepared and approved this standard had the following personnel:

S. H. Telender, Chairman C. White, Secretary


M. Boyle J. Laughlin
E. Dvorak R. K. Leidy
K. Hanke M. Shepnew
H. Hornhorst D. Swindler
W. E. Laubach C. L. Welter

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
The following persons were on the balloting committee that approved this document for submission
to the IEEE Standards Board.
A. K. Alsaker G. R. Hanks D. C. Mills
J. G. Angelis W. E. Harper G. 0. Perkins
R. E. Arndt K. D. Hendrix C. A. Popeck
J. E. Atkinson E. J. Huber J. C. W. Ransom
J . E. Beehler W. C. Huening A. B. Rishworth
F. L. Cameron W. B. Kelly H. C. Ross
L. V. Chabala P. L. Kolarik W. N. Rothenbuhler
A. P. Colaiaco S. R. Lambert G. G. Schockelt
J. J. Dravis D. M. Larson C. A. Schwalbe
J. L. Drown W. E. Laubach J . C. Scott
C. J . Dvorak T. S.Lauber E. M. Spencer
R. P. Ehas G. N. Lester H. Swanson
F. C. Farrell E. L. Luehring G. H. Taylor
J . D. Finley P. C. Lyons S. H. Telender
R. F. Friedrich M. J. Maier F. C. Teufel
G. B. Fritz J. A. Maneatis J. R. Truitt
H. G. Frus J . R. Marek C. L. Wagner
G. Genest L. V. McCall G. A. Wilson
W. F. Giles W. C. McKay W. R. Wilson
G. P. Gill R. A. McMaster B. F. Wirtz
R. D. Hambrick H. W. Mikulecky C. E. Zanzie

When the IEEE Standards Board approved this standard on September 22,1983, it had the following
membership:

James H. Beall, Chairman Edward Chelotti, Vice Chairman


Sava I. Sherr, Secretary
J. J . Archambault Donald N. Heirman John P. Riganati
John T. Boettger Irvin N. Howell Frank L. Rose
J. V. Bonucchi Joseph L. Koepfinger' Robert W. Seelbach
Rene Castenschiold Irving Kolodny Jay A. Stewart
Edward J. Cohen George Konomos Clifford 0. Swanson
Len S. Corey t R. F. Lawrence Robert E. Weiler
Donald C. Fleckenstein John E. May W. B. Wilkens
Jay Forster Donald T. Michael* Charles J. Wylie

'Member emeritus
?Deceased

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
I
+ SWITCHGEAR ASSEMBLIES
w
I -1
1
CONTROL
METAL-ENCLOSED M ETAL-ENC LOS ED SWITCH BOARDS
POWER SWITCHGEAR BUS C37.21
C37.23

I
LOW-VOLTAGE POWER
CIRCUIT BREAKER (LV)
C37.20.1

METAL-CLAD (MC)
C37.20.2
NONSEGREGATED
PHASE

SEGREGATED
PHASE
C
l
1
I

VERTICAL

ENCLOSED)
I
ISOLATED PHASE
REQUIREMENTS AND
STATION-TYPE CUBICLE (SC) GUIDE FOR
C37.20 2 CALC U LATl NG LOS S E S DUPLEX

CONTROL
METAL-ENCLOSED DESK
INTERRUPTER (ME i)
C37.20.3
BENCHBOARD

DUAL
BENCHBOARD

DUPLEX
BENCHBOARD

FIXED RACK
CABINET

SWING RACK
CAB IN ET

Fig A
Types of Switchgear Assemblies

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Contents

SECTION PAGE

1. Scope and References ................................................................................ 11


1.1 Scope ........................................................................................... 11
1.2 References ..................................................................................... 11
2. Definitions ............................................................................................ 12
2.1 Switchgear .................................................................................... 12
2.2 Qualifying Terms ............................................................................. 14
2.3 Common or Related Terms .................................................................. 14
2.4 Ambient Air Temperature .................................................................. 14
2.5 Design Tests................................................................................... 14
2.6 Production Tests .............................................................................. 14
2.7 Conformance Tests ........................................................................... 14
2.8 Field Tests .................................................................................... 14
2.9 Circuit-Breaker Compartment .............................................................. 15
2.10 Auxiliary Compartment ..................................................................... 15
2.11 Vertical Section .............................................................................. 15
3. Service Conditions ................................................................................... 15
4. Ratings ................................................................................................ 15
4.1 General ........................................................................................ 15
4.2 Voltage and Insulation Levels .............................................................. 15
4.3 Rated Frequency ............................................................................. 15
4.4 Rated Current ................................................................................ 15
4.5 Temperature Limitations .................................................................... 16
4.6 Current Transformer Ratings ............................................................... 18
4.7 Current Transformer Accuracies ........................................................... 18
5. Tests ................................................................................................... 19
5.1 General ........................................................................................ 19
5.2 Design Tests................................................................................... 19
5.2.1 Dielectric Tests ........................................................................ 19
5.2.2 Rated Continuous Current Tests .................................................... 20
5.2.3 Short-Time Current Withstand Test ................................................ 21
5.2.4 Momentary Current Tests ........................................................... 22
5.2.5 Mechanical Endurance Tests ........................................................ 22
5.2.6 Sheet, Molded or Cast Insulating Materials for Support of Primary Buses
and Connections....................................................................... 22
5.2.7 Flame-Resistance Tests for Applied Insulation .................................... 23
5.2.8 Paint Qualification Test.............................................................. 24
5.2.9 Rain Test for Outdoor ME Switchgear ............................................. 25
5.3 Production Tests .............................................................................. 25
5.3.1 Dielectric Tests ........................................................................ 25
5.3.2 Mechanical Operation Tests ......................................................... 25
5.3.3 Grounding of Instrument Transformer Cases Test ............................... 25
5.3.4 Electrical Operation and Control Wiring Tests ................................... 25
5.4 Conformance Tests ........................................................................... 26
5.5 Field Dielectric Tests ........................................................................ 26
6. Construction .......................................................................................... 26
6.1 General Requirements ....................................................................... 26
6.1.1 Buses and Primary Connections .................................................... 26
6.1.2 Grounding ............................................................................. 26

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
SECTION PAGE

6.1.3 Control and Secondary Circuits and Devices ...................................... 27


6.1.4 Miscellaneous ......................................................................... 28
6.1.5 Materials, Finishes. and Color ...................................................... 29
6.1.6 Precautionary Labels ................................................................. 29
6.2 MC Switchgear ............................................................................... 29
6.2.1 Barriers ................................................................................ 29
6.2.2 Shutters ................................................................................ 29
6.2.3 Insulating Materials for Covering Buses and Connections ...................... 29
6.2.4 Interlocks .............................................................................. 30
6.2.5 Interchangeability of Removable Switching and Interrupting Devices ......... 30
6.2.6 Primary Fuses and Voltage Transformers ......................................... 30
6.2.7 Secondary Disconnect Devices ....................................................... 30
6.2.8 Control Wiring ........................................................................ 30
6.2.9 Handling Device ...................................................................... 30
6.2.10 Test Cabinet ........................................................................... 30
6.2.11 Outdoor MC Switchgear, Access, and Ventilation ................................ 31
6.2.12 Outdoor MC Switchgear, Access, and Ventilation ................................ 31
6.3 SC Switchgear ................................................................................ 31
6.3.2 Barriers ................................................................................ 31
6.3.3 Buses and Connections ............................................................... 31
6.3.4 Interlocks .............................................................................. 31
6.3.5 Control Wiring ........................................................................ 31
6.3.6 Indoor Station-Type Cubicles, Access, and Ventilation ........................... 31
6.3.7 Outdoor Station-Type Cubicles, Access, and Ventilation ......................... 31
6.3.8 Secondary and Control Devices ..................................................... 32
7. Application Guide for ME Switchgear ............................................................ 32
7.1 Unusual Service Conditions ................................................................. 32
7.1.1 Ambient Air Temperature Above 40 "C ............................................ 32
7.1.2 Ambient Air Temperatures Below - 30 "C......................................... 32
7.1.3 Application at Unusual Altitudes ................................................... 32
7.1.4 Modification of Equipment for Unusual Environment ........................... 32
7.2 System Characteristics-Voltage and Frequency ........................................ 34
7.3 Overvoltage Considerations-Insulation Levels .......................................... 34
7.4 Continuous Current Rating and Overload Capability .................................... 34
7.5 Short-circuit Considerations ................................................................ 38
7.6 Nuclear Power Plant Application .......................................................... 38
7.7 Associated Devices Often Used in ME Switchgear ....................................... 38
7.8 Protection and Isolation of Switchgear Connected to Other
Circuit Protective Equipment ............................................................... 38
8. Guide for Handling. Storage. and Installation ................................................... 38
8.1 General ........................................................................................ 38
8.2 Handling ...................................................................................... 38
8.3 Preoperation Check .......................................................................... 40
8.4 Removable Elements ......................................................................... 40
8.5 Interlocks ...................................................................................... 40
8.6 Energization .................................................................................. 40

FIGURES
Fig 1 Test Apparatus ................................................................................. 23
Fig 2 Current-Time Relationship to Determine Short-Time Load-Current-Carrying Capa-
bility of Metal-Clad Switchgear Assemblies ................................................ 36

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
TABLES PAGE

Table 1 Voltage and Insulation Levels-MC and SC Switchgear .............................. 16


Table 2 MC and SC Switchgear Continuous Current Ratings of Main Bus ................... 16
Table 3 Temperature Limits for Insulating Materials As Used
in Switchgear Assemblies .................................................................. 17
Table 4 Temperature Limits for Buses and Connections as Used in
Switchgear Assemblies ..................................................................... 17
Table 5 Standard Accuracy Class Ratings-Current Transformers in MC Switchgear ...... 18
Table 6 Standard Accuracy Class Ratings-Current Transformers in SC Switchgear ....... 19
Table 7 Copper Conductors for Use in Continuous Current Tests .............................. 21
Table 8 Copper Conductors for Use in Continuous Current Tests .............................. 21
Table 9 Altitude Correction Factors ............................................................... 32
Table 10 Summary of Temperature Limitations ................................................... 35
Table 11 Ratios of ( I , / I . ) for Various Ambient Temperatures .................................. 35
Table 12 Typical Thermal Constants for MC Switchgear ......................................... 37
APPENDIX
Appendix A Guide for Enclosure Categories and Related Requirements ...................... 41
APPENDIX TABLES
Table A1 Requirements for Enclosure Categories .................................................. 42
Table A2 Minimum Thickness of Sheet Metal for Enclosures Carbon
Steel or Stainless Steel ..................................................................... 42
Table A3 Clearance to Ventilation Openings ....................................................... 43

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
An American National Standard
IEEE Standard for Metal-Clad and
Station-Type Cubicle Switchgear
Corrections are indicated by vertical bars in the margins opposite the areas of change. I
1. Scope and References [5] ANSIIIEEE C37.04-1979 (R 1982), IEEE
Standard Rating Structure for AC High-Voltage
1.1 Scope. This standard covers metal-clad and Circuit Breakers Rated on a Symmetrical Cur-
station-type cubicle switchgear containing but rent Basis.3
not limited to such devices as power circuit
breakers, other interrupting devices, switches, [6] ANSI I IEEE (337.010-1979, IEEE Standard
control, instrumentation and metering, and pro- Application Guide for AC High-Voltage Circuit
tective and regulating equipment. It includes, Breakers Rated on a Symmetrical Current Basis.
but is not specifically limited to, equipment for [7] ANSI I IEEE C37.2-1979, IEEE Standard
the control and protection of apparatus used for Electrical Power System Device Function Num-
power generation, conversion, and transmission bers.
and distribution.
This standard is concerned with enclosed, [8] ANSIIIEEE C37.24-1971 (R 1984), IEEE
rather than open, switchgear assemblies rated Guide for Evaluating the Effect of Solar Radia-
above 1OOOV. It includes equipments that are tion on outdoor Metal-Clad Switchgear.
part of primary and secondary unit substations.
It does not include gas insulated substation [9] ANSI IIEEE C37.100-1981, IEEE Standard
equipments. Definitions for Power Switchgear.
In this standard metalclad switchgear shall [lo] ANSI I IEEE C57.13-1978 (R 1986), IEEE
be called MC switchgear and station type cubicle Standard Requirements for Instrument Trans-
switchgear shall be called SC switchgear. When- formers.
ever the data covers both types of equipments,
then they shall be called ME switchgear. [ l l ] ANSIIIEEE Std 1-1986, IEEE Standard
General Principles for Temperature Limits in
1.2 References the Rating of Electric Equipment and for the
Evaluation of Electrical Insulation.
[l] ANSI (22-1987, National Electrical Safety
Code.' [12] ANSIIIEEE Std 4-1978, IEEE Standard
Techniques for High-Voltage Testing.
[2] ANSI C37.11-1979,American National Stan-
dard Requirements for Electrical Control for AC [13] ANSI/IEEE Std 100-1984, IEEE Standard
High-Voltage Circuit Breakers Rated on a Sym- Dictionary of Electrical and Electronics Terms.
metrical Current Basis and a Total Current Ba- [14] ANSIIIEEE Std 141-1986, IEEE Recom-
sis.' mended Practice for Electric Power Distribution
[3] ANSI 235.1-1972, American National Stan- for Industrial Plants.
dard Specification for Accident Prevention [15] ANSI/IEEE Std 241-1983, IEEE Recom-
Signs. mended Practice for Electric Power Systems in
Commercial Buildings.
[4] ANSI 255.1-1967 (R 1973), American Na-
tional Standard Gray Finishes for Industrial A p [16] ANSIIIEEE Std 242-1986, IEEE Recom-
paratus and Equipment. mended Practice for Protection and Coordina-
tion of Industrial and Commercial Power
This document is published by the Institute of Electrical Systems.
and Electronics Engineers, Inc. Copies are also available
from the Sales Department, American National Standards ANSI / IEEE publications are available from the Institute
Institute, 1430 Broadway, New York, NY 10018. of Electrical and Electronics Engineers, Service Center, 445
Hoes Lane, PO Box 1331, Piscataway, NJ 088541331. Copies
ANSI publications are available from the Sales Depart- are also available from the Sales Department, American
ment, American National Standards Institute, 1430 Broad- National Standards Institute, 1430 Broadway, New York,
way, New York, NY 10018. NY 10018.

11

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAL-CLAD AND

[17] ANSIIIEEE Std 344-1975 (R 1980), IEEE [29] NEMA LI1-1983, Industrial Laminated
Recommended Practices for Seismic Qualifica- Thermosetting Products.
tion of Class 1E Equipment for Nuclear Power
Generating Stations. [30] NEMA WC5-1973 (R 1985), Thermoplastic-
Insulated Wire and Cable for the Transmission
[18] ANSI/IEEE Std 446-1987, IEEE Recom- and Distribution of Electrical Energy. (ICEA
mended Practice for Emergency and Standby S61-402 3rd Ed).
Power Systems for Industrial and Commercial
Applications. [311 NEMA WC7-1982, Cross-Linked-Thermo-
setting-Polyethylene-Insulated Wire and Cable
[19] ANSI / NFPA 70-1987, National Electrical for the Transmission and Distribution of Elec-
Code.4 trical Energy (ICEA S66-524).
[20] ANSI/UL 486A-1982, Lugs for Use with [32] NEMA 260-1982, Safety Labels for Pad-
Copper Conductors Wire Connectors and Sol- mounted Switchgear and Transformers Sited in
dering.5 Public Areas.
[21] ASTM B117-85, Standard Method of Salt [33] NEMA Bulletin No 77-1973 (R 1975), Guide
Spray (FOG) Testing.' Lines for Warning Labels.
[22] ASTM D229-82, Standard Method of Test- [34] Federal Specification UU-T-111.'
ing Rigid Sheet and Plate Materials Used for
Electrical Insulation.
[23] ASTM D1535-80, Standard Method by 2. Definitions
Specifying Color by The Munsell System.
The definitions of terms contained in this stan-
[24] ASTM D714-80, Standard Method of Eval- dard, or in other standards referred to in this
uating Degree of Blistering of Paints. standard are not intended to embrace all legit-
[25] ASTM D1654-79a, Standard Evaluation of imate meanings of the terms. They are appli-
Painted or Coated Specimens Subjected to Cor- cable only to the subject treated in this standard.
rosive Environments. If a term is not defined in this standard, the
definition in ANSI/IEEE C37.100-1981 [919 ap-
[26] ASTM D2303-85, Standard Test Method for plies. An asterisk (*) following a definition in-
Liquid-Contaminant, Inclined-Plane Tracking of dicates that the definition in this standard is not
Erosion of Insulating Materials. contained in ANSIIIEEE C37.100-1981 [9];
while a dagger (j-) indicates the definition differs
[27] ASTM G21-70 (R 1980), Standard Practice from that in ANSIIIEEE C37.100-1981 [9].
for Determining Resistance of Synthetic Poly-
meric Materials to Fungi. 2.1 switchgear. A general term covering
switching and interrupting devices and their
[28] NEMA CC1-1984, Electrical Power Connec- combination with associated control, instru-
tors for substation^.^ ments, metering, protective and regulating de-
vices, also assemblies of these devices with
'The National Electrical Code is published by the Na- associated interconnections, accessories, and
tional Fire Protection Association, Batterymarch Park, supporting structures used primarily in connec-
Quincy, MA 02269. Copies are also available from the Sales
Department, American National Standards Institute, 1430 tion with the generation, transmission, distri-
Broadway, New York, NY 10018. bution, and conversion of electric power.
ANSI/ UL publications are available from the Under-
writers Laboratories Inc, Publication Stock, 333 Pfingsten Electrical Manufacturers Association, 2101 L Street, NW,
Road, Northbrook, IL 60062. Copies are also available from Washington, DC 20037.
the Sales Department, American National Standards Insti-
tute, 1430 Broadway, New York, NY 10018. "This publication is available from the Federal Specifi-
cations Director, US Navy Publications and Printing Ser-
ASTM publications are available from the American S e vice, Eastern Division, 700 Robbins Avenue, Philadelphia,
ciety for Testing and Materials, 1916 Race St, Philadelphia, PA 19111.
PA 19103. 'The numbers in brackets correspond with those of the
'NEMA publications are available from the National references in 1.2.

12

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

2.1.1 switchgear assembly (see Fig A). An of wire such as at instrument transformer ter-
assembled equipment (indoor or outdoor) in- minals.
cluding, but not limited to, one or more of the (8) The door through which the circuit inter-
following: switching, interrupting, control, in- rupting device is inserted into the housing may
strumentation, metering, protective and regu- serve as a n instrument or relay panel and may
lating devices, together with their supporting also provide access to a secondary or control
structures, enclosures, conductors, electrical in- compartment within the housing.
terconnections, and accessories.
2.1.2 metalenclosed power switchgear. A NOTES: (1)Auxiliary vertical sections may be required for
mounting devices or for use as bus transition.
switchgear assembly completely enclosed on all (2) The term metul-clad (as applied to switchgear assem-
sides and top with sheet metal (except for ven- blies) is correctly used only in connection with switchgear
tilating openings and inspection windows) con- conforming fully to the definition for metalclad switchgear
taining primary power circuit switching or given in 2.1.2.1. Metalclad switchgear is metalenclosed but
not all metalenclosed switchgear can be correctly desig-
interrupting devices, or both, with buses and nated as metalclad.
connections. The assembly may include control
and auxiliary devices. Access to the interior of 2.1.2.2 station-type cubicle switchgear.
the enclosure is provided by doors or removable Metalenclosed power switchgear characterized
covers, or both. by the following required features:
2.1.2.1 metal-clad switchgear. Metal-en- (1) The main switching and interrupting de-
closed power switchgear characterized by the vice is of the stationary mounted type, composed
following necessary features: of a primary circuit compartment and a second-
(1)The main switching and interrupting de- ary or mechanism compartment; arranged with
vice is of the removable (drawout) type arranged gang-operated isolating switches that are me-
with a mechanism for moving it physically be- chanically interlocked with the main switching
tween connected and disconnected positions and and interrupting device.
equipped with self-aligning and self-coupling (2) Each phase for the major parts of the pri-
primary disconnecting devices and disconnect- mary circuit switching or interrupting devices,
able control wiring connections. buses, and line-to-ground potential transformers
(2) Major parts of the primary circuit, that is, are completely enclosed (or segregated) by
the circuit switching or interrupting devices, grounded metal barriers that have no inten-
buses, voltage transformers, and control power tional openings between compartments. Specif-
transformers, are completely enclosed by ically included are mechanically interlocked
grounded metal barriers, that have no inten- doors in front of or a part of the primary circuit
tional openings between compartments. Specif- compartment of the circuit switching and inter-
ically included is a metal barrier in front of or rupting device so that when the group operated
a part of the circuit interrupting device to ensure isolating switches are closed no primary parts
that, when in the connected position, no primary can be exposed by the attempted opening of the
circuit components are exposed by the opening interlocked doors.
of a door.? (3)All live parts are enclosed within grounded
(3) All live parts are enclosed within grounded metal compartments.
metal compartments. (4) Primary bus conductors and connections
(4) Automatic shutters that cover primary cir- are bare.
cuit elements when the removable element is in (5) Mechanical interlocks are provided for
the disconnected, test, or removed position. proper operating sequence under normal oper-
(5) Primary bus conductors and connections ating conditions.
are covered with insulating material through- (6) Secondary control devices and their wiring
out. are isolated by grounded metal barriers from all
(6) Mechanical interlocks are provided for primary circuit elements with the exception of
proper operating sequence under normal oper- short lengths of wire such as at instrument
ating conditions. transformer terminals.
(7) Instruments, meters, relays, secondary (7) The doors to the secondary or mechanism
control devices and their wiring are isolated by compartment of the primary switching or inter-
grounded metal barriers from all primary cir- rupting device are to provide access to the sec-
cuit elements with the exception of short lengths ondary or control equipment within the housing

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAL-CLAD AND

without danger to exposure to the primary cir- terminal


cuit parts. terminal block
test position
NOTE: Auxiliary vertical sections may be required for
mounting devices or for use as bus transition.
2.4 ambient air temperature. The tempera-
2.2 qualifying terms. (Relating to types of en- ture of the surrounding air that comes in contact
closures, ventilation methods, etc) (1)The fol- with equipment.*
lowing qualifying terms are defined in ANSI/ NOTE: Ambient air temperature, as applied to enclosed
IEEE Std 100-1984 [13] and the user is referred switchgear assemblies, is the average temperature of the
surrounding air that comes in contact with the enclosure
to the definitions given therein: (see 5.2.2.3 for method of measurement).
accessible
alive (live) 2.5 design tests. Tests made by the manufac-
automatic turer to determine the adequacy of the design
enclosed of a particular type, style, or model of equipment
insulating or its component parts to meet its assigned rat-
isolated ings and to operate satisfactorily under normal
ventilated service conditions or under special conditions if
(2) The following qualifying terms are defined specified, and may be used to demonstrate com-
in ANSIIIEEE C37.100-1981 [9] and the user is pliance with applicable standards of the indus-
referred to the definitions given therein: try.?
electrical NOTES: (1) Design tests are made on representative appa-
enclosure ratus or prototypes to verify the validity of design analysis
flame-resistant (retardant) and calculation methods and to substantiate the ratings as-
signed to all other apparatus of basically the same design.
indoor These tests are not intended to be made on every design
metal-enclosed variation or to be used as part of normal production. The
outdoor applicable portion of these design tests may also be used to
evaluate modifications of a previous design and to ensure
resistant (suffix) that performance has not been adversely affected. These
secondary data from previous similar designs may also be used for
ventilated enclosure current designs, where appropriate. Once made, the tests
need not be repeated unless the design is changed so as to
modify performance.
2.3 common or related terms. The following (2) Design tests are sometimes called type tests.
common or related terms are defined in ANSI/
IEEE C37.100-1981 [9] and the user is referred 2.6 production tests. Tests made for quality
to the definitions given therein: control by the manufacturer on every device or
asymmetrical representative samples, or on parts, or materials
auxiliary switch required to verify during production that the
barrier product meets the design specifications and a p
bus plicable standards.t
connected position NOTES: (1) Certain quality assurance tests on identified
continuous current tests critical parts of repetitive high-production devices may be
current limiting fuse tested on a planned statistical sampling basis.
(2) Production Tests are sometimes called routine tests.
disconnected position
drawout-mounted device 2.7 conformance tests. Conformance tests
ground bus demonstrate compliance with the applicable
live parts standards. The test specimen is normally sub-
main (primary switchgear connections) jected to all planned production tests prior to
primary disconnecting devices initiation of the conformance test program.?
removable element
NOTE: The conformance tests may, or may not, be similar
secondary and control wiring to certain design tests. Demonstration of margin (capabili-
secondary disconnecting contact ties) beyond the standards is not required.
shutter
silver surfaced 2.8 field tests (for switchgear). Tests made after
stationary mounted device the assembly has been installed at its place of
symmetrical utilization.?

14

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

2.9 circuit-breaker compartment. That por- (1) Rated maximum voltage


tion of the switchgear assembly that contains (2) Rated frequency
one circuit breaker or other removable primary (3) Rated insulation levels
interrupting device and the associated primary (4) Rated continuous current
conductors.* (5) Rated short-time current
(6) Rated momentary current
2.10 auxiliary compartment. That portion of The designated ratings in this standard are
the switchgear assembly that is assigned to the preferred but are not considered to be restric-
housing of auxiliary equipment, such as poten- tive.
tial transformers, control power transformers, In addition to these ratings, a switchgear as-
or other miscellaneous devices.* sembly may have interrupting or switching ca-
pabilities, which are determined by the rating
2.11 vertical section. That portion of the of the particular interrupting and switching de-
switchgear assembly between two successive vices that are integral parts of the switchgear
vertical delineations and may contain one or assembly. Refer to specific American National
more circuit breakers, auxiliary compartments, Standards for the ratings of these devices.
and associated primary conductors.
4.2 Voltage and Insulation Levels. See
Table 1.
4.2.1 Rated Maximum Voltage. The rated
3. Service Conditions maximum voltage of ME switchgear is the high-
est rms voltage for which the equipment is de-
American National Standards for the design signed, and is the upper limit for operation.
and performance of ME switchgear are based on 4.2.2 Rated Insulation Levels. The rated in-
usual service conditions as described below. The sulation levels of ME switchgear shall consist of
selection of equipment for a particular appli- two items
cation can be based on the construction and rat- (1) Low frequency 1 min withstand voltage
ings as defined in this standard provided that (2) Impulse withstand voltage
these usual service conditions exist. 4.2.3 Voltages and Insulation Levels. The
(1) The temperature of the cooling air (am- rated maximum voltages, and corresponding in-
bient air temperature) surrounding the enclo- sulation levels for ME switchgear are listed in
sure of the ME switchgear is within the limits Table 1.
of - 30 "C and +40 "C.
(2) The altitude of the installation does not
exceed 3300 ft (1000 m). 4.3 Rated Frequency. The rated frequency of
(3) The effect of solar radiation is not signif- a device, or an assembly, is the frequency of the
icant. (The principles stated in ANSI/IEEE circuit for which it is designed (Ratings are based
C37.24-1971 (R 1984) [8] may be used for guid- on a frequency of 60 Hz).
ance.)
(4) Unusual service conditions such as out- 4.4 Rated Current
lined in 7.1 do not prevail. 4.4.1 Rated Continuous Current. The rated
continuous current of ME switchgear is the max-
imum current in rms amperes at rated fre-
quency, which can be carried continuously by
4. Ratings the primary circuit components, including buses
and connections, without causing temperatures
4.1 General. The ratings of a switchgear assem- in excess of specified limits for
bly are designations of operating limits under (1) Any primary or secondary circuit compo-
specified conditions of ambient temperature, nent
temperature rise, etc. Where the switchgear as- (2) Any insulating medium, or structural or
sembly comprises a combination of primary and enclosing member
secondary circuits, each may be given ratings. The specified temperature limits applicable to
ME switchgear shall have the following rat- switchgear assemblies are given in 4.5.1 through
ings: 4.5.6.

15

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

Table 1
Voltage and Insulation Levels
MC and SC Switchgear
Insulation Levels (kV)
Rated Low Frequency Reference;
Maximum Voltage Withstand Impulse DC
(rms) (kV) (rms) Withstand Withstand
MC switchgear 4.76 19 60 27
8.25 36 95 50
15.0 36 95 50
38.0 80 150 t
SC switchgear 15.5 50 110 t
38.0 80 150 t
72.5 160 350 t
* The column headed DC Withstand is given as a reference only for those using dc tests to
verify the integrity of connected cable installations without disconnecting the cables from the
switchgear. It represents values believed to be appropriate and approximately equivalent to the
corresponding power frequency withstand test values specified for each voltage rating of switch-
gear. The presence of this column in no way implies any requirement for a dc withstand test on
ac equipment or that a dc withstand test represents an acceptable alternative to the low-frequency
withstand tests specified in this standard, either for design tests, production tests, conformance
tests, or field tests. When making dc tests, the voltage should be raised to the test value in
discrete steps and held for a period of 1 min.
t Because of the variable voltage distribution encountered when making dc withstand tests,
the manufacturer should be contacted for recommendations before applying dc withstand tests
to the switchgear. Voltage transformers above 34.5 kV should be disconnected when testing with
dc. See ANSI/IEEE C57.13-1978 (R 1986)[lo],Section 8 and in particular 8.8.2(the last paragraph)
which reads “Periodic kenotron tests should not be applied to transformers of higher than 34.5
kV voltage rating.”

Table 2 unless limited to a shorter time by the protective


MC and SC Switchgear device.
Continuous Current Ratings of Main Bus 4.4.4 Momentary Current Ratings. The mo-
Rated Continuous mentary current ratings of the individual cir-
Current of Buses cuit-breaker compartments of ME switchgear
Tvpe of Assembly (A) shall be equal to: The circuit breaker close and
MC switchgear 1200,2000,3000 latch, switch fault close, or asymmetrical mo-
SC switchgear 2000,3000,4000,5000 mentary current ratings of the switching devices
used.
4.4.5 Rated Short-Time Current. The rated
4.4.2 Continuous Current Ratings. The con- short-time current of the ME switchgear is the
tinuous current ratings of the main bus in ME average rms current that it can carry for a pe-
switchgear are listed in Table 2. riod of 2 s unless limited to a shorter time by
The continuous current rating of the individ- the protective device or current transformer rat-
ual circuit-breaker compartment shall be equal ings.
to the ratings of the switching and interrupting 4.4.6 Short-Time Current Rating. The
devices used, except as may be modified by lower short-time current ratings of the individual cir-
continuous current ratings for current trans- cuit-breaker compartments of the ME switch-
formers, power fuses etc. gear shall be equal to the short-time ratings of
4.4.3 Rated Momentary Current. The rated the switching and protective devices used or the
momentary current of ME switchgear is the short time rating of the current transformers
maximum rms total current that it shall be re- (see ANSI/IEEE C57.13-1978(R 1986)[lo]).
quired to withstand. The current shall be the
rms value, including the direct-current compo- 4.5 Temperature Limitations
nent, at the major peak of the maximum cycle 4.5.1 Limiting Temperature. “he limiting
as determined from the envelope of the current temperature for ME switchgear is the maximum
wave during a test period of at least 10 cycles temperature permitted

16

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

Table 3
Temperature Limits for Insulating Materials
As Used in Switchgear Assemblies
Class of Limit of Hottest-Spot Limit of Hottest-Spot
Insulating Temperature Rise Total Temperature
Material ('C) ('C)
Class 90 50 90
Class 105 65 105
Class 130 90 130
Class 155 115 155
Class 180 140 180
Class 220 180 220
NOTE: For additional information on temperature limits see ANSIIIEEE Std 1-1986[ll].

Table 4
Temperature Limits for Buses and Connections
As Used in Switchgear Assemblies
Limit of
Hottest-Spot Limit of Hottest-Spot
Type of Bus or Temperature Rise Total Temperature
Connection ('C) ('C)
Bus connections with unplated copper to
copper connection joints 30 70
Buses and bus connections silver surfaced, tin
surfaced or equivalent connection joints 65 105
Connections to insulated cables (unplated
copper to copper) 30 70

Connections to insulated cables silver surfaced,


tin surfaced or equivalent 45 85
NOTE All aluminum bus shall have silver surfaced, tin surfaced, or equivalent connecting joints.
Welded bus connections are not considered connecting joints.

(1) For any component, such as insulation, bly, considered in conjunction with their rating
buses, instrument transformers, and switching and loading as used, shall not cause these devices
and interrupting devices to operate outside their rated temperature range
(2) For air in cable termination compartments when the enclosure of the assembly is sur-
(3) For any noncurrent-carrying structural rounded by air within a n ambient temperature
parts range of -30 "C to +40 "C.
(4) For air surrounding devices 4.5.5 Temperature Limitations for Air
4.5.2 Temperature Limits for Insulating Surrounding Insulated Power Cables. The
Materials. The total temperature to which in- temperature of the air surrounding insulated
sulating materials are subjected shall not exceed cables within any compartment of a n enclosed
the values listed in Table 3 for the various assembly shall not exceed 65 "C when the assem-
classes of insulating materials. bly is
(1) Equipped with devices having maximum
4.5.3 Temperature Limits for Buses and current rating for which the assembly is de-
Connections. The total temperature of buses signed
and connections shall not exceed the value listed (2) Carrying rated continuous current at
in Table 4. rated voltage and at rated frequency
4.5.4 Temperature Limitations for Air (3) In a n ambient air temperature of 40 "C
Surrounding Devices Within an Enclosed
NOTE: This temperature limitation is based on the use of
Assembly. The temperature of the air sur- 90 "C insulated power cables. Use of lower temperature rated
rounding all devices within an enclosed assem- cables requires special consideration.

17

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAGCLAD AND

4.5.6 Temperature Limitations for Parts plied. When the primary circuit is protected by
Subject to Contact by Personnel. (1) Parts fuses, the current transformers shall success-
handled by the operator in the normal course of fully withstand the maximum 1't of the fuses.
his duties shall have no higher total tempera- Unless specifically limited to a shorter time by
ture than 50°C. the associated protective equipment, the dura-
(2)External surfaces accessible to a n operator tion of the short circuit shall be considered as
in the normal course of his duties shall have no 1 s.
higher total temperature than 70 "C.
4.6.3 Current Transformer Ambient Tem-
(3) External surfaces not accessible to an o p
perature. Current transformers for use in
erator in the normal course of his duties shall
switchgear assemblies shall be rated on the basis
have no higher total temperature than 110 "C.
of at least 55 "C ambient temperature in accord-
ance with ANSI / IEEE C57.13-1978 (R 1986)[lo],
4.6 Current Transformer Ratings 4.1.1.2.
4.6.1 Current Transformer Mechanical
Ratings. The mechanical ratings of current
transformers shall be such that they will suc- 4.7 Current Transformer Accuracies. Accur-
acies tabulated hereafter are the minimum that
cessfully withstand the momentary current for
which the associated circuit interrupting devices shall be supplied. The manufacturer should be
are applied. When the primary circuit is pro- consulted if higher accuracies are required by
tected by current-limiting fuses, the current the purchaser. It should be recognized that cur-
rent transformers with higher accuracies may
transformers shall successfully withstand the
maximum let-through current of the fuses. Un- not meet the requirements of 4.6.1 and 4.6.2.
less specifically limited to a shorter time by the 4.7.1 Current Transformer Accuracies for
associated protective equipment, the duration of MC Switchgear. For installation in MC switch-
the short-circuit shall be considered as being 10 gear, the standard current transformer accur-
cycles. acies for metering and relaying are listed in
4.6.2 Current Transformer Thermal Rat- Table 5. When multiratio current transform-
ings. The thermal ratings of current trans- ers are supplied, the metering and relaying
formers shall be such that they will successfully accuracies listed in Table 5 apply only to the
withstand the short-circuit current for whieh the full winding in accordance with ANSI / IEEE
associated circuit interrupting devices are a p (37.13-1978 (R 1986) [lo], 6.3.2.

Table 5
Standard Accuracy Class Ratings*
Current Transformers in MC Switchgear
Metering Accuracy
60 Hz Standard Burdens Relaying
Ratio BO.l B0.2 B0.5 B1.O B2.0 Accuracy
50:5t 1.2 2.4 $ - - - C o r T 10
75:5t 1.2 2.4 $ - - - C o r T 10
100:5 1.2 2.4 $ - - - C o r T 10
150:5 0.6 1.2 2.4 $ - - C o r T 20
200:5 0.6 1.2 2.4 $ - - C o r T 20
300:5 0.6 1.2 2.4 $ 2.4 $ - C o r T 20
400:5 0.3 0.6 1.2 1.2 2.4 $ C o r T 50
600:5 0.3 0.3 0.3 1.2 2.4 $ C o r T 50
800:5 0.3 0.3 0.3 0.6 1.2 C o r T 50
1200 : 5 0.3 0.3 0.3 0.3 0.3 c 100
1500 : 5 0.3 0.3 0.3 0.3 0.3 c 100
2OOO:5 0.3 0.3 0.3 0.3 0.3 c 100
3OOO:5 0.3 0.3 0.3 0.3 0.3 c 100
4OOO:5 0.3 0.3 0.3 0.3 0.3 c 100
* See ANSI/IEEE C57.13-1978 (R 1986) [lo].
t These ratios and transformer accuracies do not apply for metalclad switchgear assemblies having rated momentary
current above 60 OOO A rms. Where such assemblies have a rated momentary current above 60 OOO A rms, the minimum
current transformer ratio shall be 100:5.
$This metering accuracy is not in ANSIIIEEE C57.13-1978 (R 1986) [lo].

18

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPECUBICLE SWITCHGEAR C37.20.2-1987

Table 6
Standard Accuracy Class Ratings*
Current Transformers in SC Switchgear
Metering Accuracy
60 Hz Standard Burdens Relaying
Ratio BO.l B0.5 B2.0 Accuracy
300:5t
400:5t
600:5t
0.6
0.6
0.3
1.2
1.2
0.6
2.4
2.4
**
2.4 $ C or T 100
CorT100
Cor T200
800:5 0.3 0.3 1.2 C o r T200
1200 : 5 0.3 0.3 0.6 c 200
1500 : 5 0.3 0.3 0.3 c 400
2000:5 0.3 0.3 0.3 C400
3000:5 0.3 0.3 0.3 C 400
4000:5 0.3 0.3 0.3 c 400
5000:5 0.3 0.3 0.3 c 400
m : 5 0.3 0.3 0.3 c 400
* See ANSI/IEEE C57.13-1978(R 1986) [lo].
t These ratios and transformer accuracies do not apply for station-type cubicle switchgear having momentary current above
115 kA. Where such assemblies have a rated momentary current above 115 kA, the minimum current transformer ratio shall
be 800:5.
I:Not in ANSI/IEEE C57.13-1978 (R 1986) [lo].

4.7.2 Current Transformer Accuracies for ance with Table 1. In addition, dielectric tests
SC Switchgear. For installation in SC switch- shall be made on the bus-bar insulation as spec-
gear, the standard current transformer accur- ified in 5.2.1.3.
acies for metering and relaying are listed in The tests on the insulation system shall be
Table 6. made under the temperature and humidity con-
ditions normally obtained under conditions of
commercial testing with appropriate correction
5. Tests
factors for relative air density and humidity ap-
plied as outlined in ANSI / IEEE Std 4-1978[12].
5.1 General. This section establishes physical
Humidity correction factors shall be based on
and electrical conditions for tests and methods
curves for rod gaps as stated in ANSI / IEEE Std
of determining temperatures and test values. All
4-1978[12], Fig 1.3.The equipment shall be clean
apparatus and devices in the power circuit shall
and in good condition.
be mounted in their normal locations during
Test voltages shall be applied between the pri-
tests. No statement in this section is to be con-
mary circuits and ground in the following man-
strued as modifying the test requirements for
ner:
devices included in switchgear assemblies.
(1) For equipment with stationary mounted
Tests are classified as design tests, production
devices and for equipment with drawout devices
tests, conformance tests, and field tests. These
are defined in Section 2. with the removable elements in the connected
position.
NOTE: Except for the main switching or interrupting device, (a) With the switching device contacts
other devices, such as voltage transformers that are mounted closed; between each phase of the switchgear
in the switchgear assemblies, may be disconnected during
the dielectric test. Such devices are individually tested in assembly with the frame and all other phases
accordance with standards applying to them. grounded.
(b) With the switching device contacts open;
5.2 Design Tests. Design tests as applicable between each terminal of the switchgear assem-
shall be made in accordance with 5.2.1 through bly with the frame and other terminals
5.2.9. grounded.
5.2.1 Dielectric Tests. Low-frequency with- (2) For equipment with drawout devices with
stand tests (5.2.1.1),and impulse withstand tests the removable elements in the test position and
(5.2.1.2)shall be performed on switchgear assem- the main switching devices in the closed posi-
blies to demonstrate the ability of the insulation tion, apply the test voltage to primary circuits.
system to withstand rated voltages in accord- (a) Simultaneously to all the incoming ter-

19

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAGCLAD AND

minals of the switchgear assembly with the materials, the use of appropriate methods, such as the a p
plication of impulses of the reverse polarity at lower voltage
frame and outgoing terminals grounded. Repeat before the tests, is recommended.
tests by applying test voltage to the outgoing
terminals with the frame and incoming termi- 5.2.1.3 Test for Bus-Bar Insulation. The
nals grounded. insulated bus-bar sample shall have a low-fre-
(b) Simultaneously between all incoming quency voltage applied from the conductor to an
and outgoing terminals of the switchgear assem- electrode effectively covering the outer surface
bly. The test shall be made with a value of volt- of the insulation. The alternating-current test
age 10% higher than that specified in Table 1. voltage shall have a value not less than the ap-
propriate rated maximum voltage as shown on
NOTES (1)For the test across the open gap at 10% higher
voltage, a n intermediate point of the voltage source may, if Table 1. The alternating-current test voltage
practicable, be connected to ground and to the frame of the shall have a crest value equal to 1.414 times the
assembly so that the voltage between any live part and the rms value and the wave shape shall be essen-
frame will not exceed that specified in Table 1. If this is not
practicable the frame may be insulated from ground. tially sinusoidal. The test voltage shall be ap-
(2) Successful completion of these tests does not neces- plied for 1 min. The bus-bar sample shall have
sarily provide assurance that with the circuit breaker in the construction that is typical of bus bars, elbows,
test position, it will always flashover to ground instead of
across the gap between line and load terminals. Switchgear and joints.
insulation does not provide surge protection for the open
gap. Where surge protection of the gap is required, suitable NOTES: (1) Suggested external electrodes are conductive
protective devices must be applied. paint or metallic foil or equivalent.
(2) This test is required on only one insulated bus-bar test
Low-frequency withstand tests, impulse with- sample for each rated voltage.
stand tests, and where applicable, bus-bar in-
sulation tests and wet tests on entrance bushings 5.2.1.4 Wet Tests on Entrance Bushings.
shall be made as follows: To be conducted in accordance with ANSI / IEEE
5.2.1.1 Low-Frequency Withstand Tests. Std 4-1978 [12].
Alternating-current voltage shall have a crest 5.2.2 Rated Continuous Current Tests. To
value equal to 1.414 times the rms value speci- determine compliance with continuous current
fied in Table 1. The wave shape shall be essen- ratings, it is necessary to determine that tem-
tially sinusoidal. The frequency shall be within peratures of the various components of the
-+ 20% of the rated frequency. The test potential switchgear assembly are within the limits set
is to be increased gradually from zero to reach forth in 4.5.1 through 4.5.6. Temperature mea-
the required test value within 30 s to 60 s and surements shall be made in accordance with
shall be held at that value for 1 min. 5.2.2.1 through 5.2.2.6.
5.2.1.2 Impulse Withstand Tests. The 5.2.2.1 Test Area Conditions. Tempera-
standard impulse is a full impulse having a vir- ture tests shall be conducted indoors in a test
tual front time of 1.2ps and a virtual time to area that is reasonably free from drafts.
half value of 50 ps of the value specified in Table 5.2.2.2 Ambient-&-Temperature Lim-
1. It is described as a 1.2/50 ps impulse test its. Tests may be made at any ambient air tem-
wave. In these tests, three positive and three perature between 10 "Cand 40 "C.
negative impulse voltages shall be applied to 5.2.2.3 Measurement of Ambient Air
each point without causing damage or flashover. Temperature. Indoor ambient air temperatures
If flashover occurs on only one test during any shall be determined by taking the average of the
group of three consecutive tests, three more tests readings of three temperature-measuring de-
shall be made. If the equipment successfully vices such as thermometers or thermocouples,
withstands all three of the second group of tests, placed as follows:
the flashover in the first group shall be consid- (1) One level with the top of the structure
ered as a random flashover and the equipment (2) One 12 in (305 mm) above the bottom of
shall be considered as having successfully passed the structure
the tests. The wave shape, used to define the (3) One midway between the two above posi-
limits, is described in ANSI/IEEE Std 4-1978 tions
WI. All temperature-measuring devices shall be
placed 12 in (305 mm) from the structure, not
NOTE: Some insulating materials retain a charge after an
impulse test and for these cases care should be taken when in front of ventilators, and in locations unaf-
reversing the polarity. To allow the discharge of insulating fected by drafts caused by the structure or ap-

20

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPECUBICLE SWITCHGEAR C37.20.2-1987

preciable radiation from the equipment. When that destroy some parts. It is recognized that
the ambient air temperature is subject to vari- thermocouples cannot be located in the actual
ations that might result in errors in measuring contact point of line or point contacts without
the temperature rise, the temperature-measur- destroying the effectiveness of such line or point
ing devices should be immersed in a suitable contacts.
liquid such as oil in a suitable container or re- Measurements shall be made at junction
liably attached to a suitable mass of metal. points of insulation and conducting parts to en-
sure against exceeding temperature limits of the
NOTE: A convenient form for such a container consists of
a metal cylinder with a hole drilled partly through it. This insulation.
is filled with liquid and the temperature-measuring device 5.2.2.5 Duration of Tests. The continuous
is placed therein. A glass bottle may also be used as a con-
tainer. The size of the container shall be at least 1 in current test shall be made for such a period of
(25.4 mm) in diameter and 2 in (50.8 mm) high. time that the temperature rise of any monitored
point in the assembly has not increased by more
5.2.2.4 Method of Measuring Tempera-
than 1.0"C during each of two successive 30 min
ture. Thermocouples shall be used to measure
intervals as indicated by three successive read-
the temperature at the required locations on the
switchgear assembly test arrangement. The ings. If the temperature rise at the end of the
thermocouples when used for measuring the second interval is equal to the established limits
temperature of insulation, shall be located on and if the temperature rise has increased since
the currentcarrying member or other metal the previous reading, the test shall be continued
part. Thermocouples used for measuring the until the temperature rise is constant.
temperature of the circuit-breaker separable pri- 5.2.2.6 Frequency of Test Current. The
mary contacts shall be located approximately frequency of the test current shall not be less
0.5 in (13 mm) from the contacts on the current- than the rated frequency of the assembly tested.
carrying member. For cable terminations, the A sine-wave shape is recommended. The test
thermocouples shall be located at the junction shall be made with alternating current having
of the conductor and its insulation. a crest value equal to 1.41 times the rms test
Thermocouples shall be held in intimate con- current.
tact with the conductor surface by such methods 5.2.2.7 Copper Conductors for Use in
as welding, drilling, and peening or cementing. Continuous Current Tests. Bus bars as speci-
The thermocouples on a design test shall be fied in Table 7 shall be utilized for connection
located in a manner so as to measure the hottest to the main bus. Cables or bus bars as specified
spot, even though it may involve drilling holes in Table 8 should be utilized for connection to

Table 7
Copper Conductors for Use in Continuous Current Tests
Main Bus Bus Per Terminal*
Ratine Quantitv Size, (in) (mm)
1200 1 4 (6.35 * 101.6)
2000 2 .
% 4 (9.52 . 101.6)
3000 3 % 5 (9.52 * 127.0)
Where multiple bus bars are used, they are to be spaced % in (9.52 mm) apart. Vertical or
horizontal configuration shall be at the option of the manufacturer.

Table 8
Copper Conductors for Use in Continuous Current Tests
Circuit Breaker Circularmil Size Bus Per Terminal;
Rating of Copper Conductort Quantity Size, (in) (mm)
1200 4-500MCM
2000 2 % . 4 (9.52 . 101.6)
3000 3 % . 5 (9.52 . 127.0)
* Where multiple bus bars are used, they are to be spaced % in (9.52 mm) apart. Vertical or
horizontal configuration shall be at the option of the manufacturer.
t Tests based on cross-sectional area, not cable insulation classification.

21

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAL-CLAD AND

the circuitibreaker outgoing terminals. If test sition interlocks (every tenth operation to with-
arrangement internal bus sizes or configura- drawn position)
tions are different from Tables 7 and 8, external (d) Stored energy mechanism interlocks, as
bus sizes or configurations equal to internal bus applicable (every tenth operation to withdrawn
bars may be substituted at the option of the position)
manufacturer. The conductors shall have a min- (e) Auxiliary switches mounted on station-
imum external length of 4 f t (1.2 m) and shall ary structure (every tenth operation)
be insulated for proper voltage rating in accord- (f) Housing mounted position switches
ance with the manufacturer’s practice. (g) Shutters
5.2.3 Short-Time Current Withstand Tests. (2) For SC switchgear at least 100 mechanical
Short-time current withstand tests shall be close-open operation tests shall be performed,
made to demonstrate the electrical adequacy of using each frame size and type of circuit switch-
buses and connections in ME switchgear to with- ing and interrupting device to ensure proper
stand the rated short-time current for a 2 s pe- sequential operation and to establish satisfac-
riod without physical damage. tory function of the following elements (All pri-
This test may be a single-phase test at any mary power should be disconnected during these
convenient value of voltage. If the test current mechanical tests).
meets the requirements of 5.2.4, this test may (a) Isolating switch operation
be combined with the momentary current test. (b) Switching and interrupting device in-
5.2.4 Momentary Current Tests. Three- terlocks as coordinated with isolating switch op-
phase momentary current tests shall be made eration
to demonstrate the mechanical adequacy of the (c) Stored energy mechanism interlocks, as
structure, buses, and connections in ME switch- applicable
gear to withstand the rated momentary current (d) Housing mounted position switches
of the assembly with 5.2.6 Sheet, Molded, or Cast Insulating
(1)No permanent deformation of bus bar, or Materials for Support of Primary Buses and
(2) Some deformation that is insufficient to Connections. Sheet, molded, or cast insulating
prevent the dielectric requirements from being materials used for the support of primary con-
met ductors shall be tested for flame resistance and
The current shall be the rms value, including tracking resistance as follows:
the direct-current component, during the max-
imum cycle as determined from the envelope of NOTE While these insulation flame-resistance and track-
the current wave during a test period of at least ing-resistance tests are not design tests applied to assembled
10 cycles. This test may be made at any conve- switchgear, they are included here because of the wide va-
riety of insulating materials used in switchgear assemblies
nient voltage. and because of the relative importance of these properties.
The only intent here is that such insulation materials shall
NOTE The tests conducted in 5.2.3 and in 5.2.4 are to dem- meet the requirements of the specified test procedures.
onstrate the mechanical and thermal capability of the main When the insulation design utilized includes cut edges in
bus and main bus connections. Connections on the outgoing the tracking path, these edges shall not degrade the tracking
terminals of protective devices may be limited to a shorter resistance below that required by this standard.
time and let-through current by the protective devices.

5.2.5 Mechanical Endurance Tests. Me- 5.2.6.1 Flame-Resistance Tests. Sheet,


chanical endurance tests shall be performed as molded, or cast primary insulating materials
follows: used in switchgear assemblies shall have a min-
(1)For MC switchgear at least 100mechanical imum average ignition time of 60 s and a max-
endurance test cycles between test and con- imum average burning time of 100 s when tested
nected positions shall be performed, using each in accordance with ASTM D229-82 [22],
frame size and type of switching and interrupt- Method 11.
ing device to demonstrate proper sequential o p 5.2.6.2 Tracking-Resistance Tests.
eration and to establish satisfactory function of (1) Switchgear assemblies of rated maximum
the following elements (All primary power voltage of 4.76 kV and less.
should be disconnected during mechanical tests): The material shall be tested in accordance
(a) Separable primary contacts with ASTM D2303-85 [26] and under Condition
(b) Separable control contacts A (see NEMA LI 1-1983 [29], 7.03) with speci-
(c) Circuit-breaker removable element po- mens of inch in thickness shall have a mini-

22

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

Fig 1
Test Apparatus

I mum time to track to the 1in mark of 20 min specimen at the upper end and supporting it in
with 2500 V applied. a vertical position.
(2) Switchgear assemblies of rated maximum (2) Means for adjusting the position of the test
voltage of 8.25 kV and greater. specimen.
The material shall be tested in accordance (3) Tirrill burner with an attached pilot light
with ASTM D2303-85 [26] and under Condition and mounted on a 20" angle block. The burner
A (see NEMA LI 1-1983 [29], 7.03) with speci- shall have a nominal bore of in (9.5 mm) and
mens of inch in thickness shall have a mini- a length of approximately 4 in (102 mm) above
mum time to track to the 1 in mark of 300 min the primary air inlets.
with 2500 V applied. (4) An adjustable steel angle (fixture) at-
5.2.7 Flame-Resistance Tests for Applied tached to the bottom of the chamber to ensure
Insulation. Applied insulation, such as fluidized the correct location of the burner with relation
bed systems, tape systems, and shrinkable-type to the test specimen.
tubing shall be tested as follows: (5) A supply of ordinary illuminating gas or
5.2.7.1 Test Apparatus. The test appara- equivalent at normal supply pressure.
tus shall consist of (see Fig 1) (6) T'imer
(1) Test chamber of sheet metal 12 in (7) Flame indicators consisting of strips of
(305 mm) wide, 14 in (356 mm) deep, and 24 in gummed kraft paper having a nominal thickness
(610 mm) high, that is open at the top and that of 1.0 mm (5 mil) and a width of 1/2 inch
is provided with means for clamping the test (13.0 mm).

23

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

NOTE The paper used for the indicators is known to the application of the flame shall be noted, and any
trade as 60 Ib stock and is material substantially the same specimen that continues to burn for more than
as that described in Federal SpecificationUU-T-111 covering
Tape, Paper, Gummed (Kraft) [34]. 1min shall be considered to have failed this test.
5.2.8 Paint Qualification Test. The paint
5.2.7.2 Preparation of Sample. Prepare a qualification test applies to all enclosures incor-
copper rod approximately % in (19.0 mm) in di- porating external ferrous parts. Nonferrous en-
ameter, 22 in (560 mm) in length, with the nec- closures with no external ferrous parts need not
essary covering to be tested to a thickness of be tested.
approximately 60 mil to 125 mil (1.5 mm to 3.0 The paint qualification test shall be performed
mm). to ensure the adequacy of finishes to inhibit the
5.2.7.3 Procedure. The test shall be made buildup of rust on ferrous metal materials used
in a room that is reasonably free from drafts of for enclosures.
air, although a ventilated hood may be used if The methods used are as follows:
air currents do not affect the flame. One end of 5.2.8.1 Test Specimens. Representative
the test specimen approximately 22 in (560 mm) test panels of a 3 in by 6 in minimum size that
in length shall be clamped in position at the can be accommodated by the test chamber shall
upper end of the chamber. A paper indicator be provided. Each specimen shall be uniformly
shall be applied to the specimen so that the lower processed in the standard production paint-fin-
edge is 10 in (250 mm) above the point at which ishing system. At least four panels shall be se-
the inner blue cone of the test flame is to be lected for the test. All the test specimens shall
applied. The indicator shall be wrapped once be of standard gauge ferrous metal equivalent
around the specimen, with the gummed side to- to that used for the enclosure. The specimen
ward the conductor. shall be allowed to age for a minimum of seven
The ends shall be pasted evenly together and days before being tested.
shall project % in (19.0 mm) from the specimen 5.2.8.2 Test Apparatus. The test appara-
on the opposite side of the specimen to that to tus shall consist of a fog chamber, salt solution
which the flame is to be applied. The paper tab reservoir, compressed-air supply, provisions for
shall be moistened only to the extent necessary heating, and means of control. The conditions
to permit proper adhesion. The height of the in the salt spray chamber including the posi-
flame with the burner vertical shall be adjusted tioning of the specimens, content of the salt so-
to 5 in (127 mm), with a n inner blue cone l x in lution, and temperature and pressure to be
(38.0 mm) high. maintained, shall be as defined in ASTM B117-
The burner, with only the pilot lighted, shall 85 [21].
be placed in front of the sample so that the 5.2.8.3 Preparation of Test Specimens.
vertical plane through the stem of the burner Two of the test panels shall be suitably scribed
includes the axis of the specimen. The angle for testing in accordance with ASTM D1654-79a
block shall rest against the jig, which shall be ~51.
adjusted so that there is a distance of 1%in 5.2.8.4 Exposure of Test Specimens. All
(38.0 mm) along the axis of the burner stem test specimens shall be tested in the salt spray
between the tip of the stem and the surface of chamber for a period of 200 h continuously ex-
the specimen. The valve supplying the gas to the cept for the short, daily interruptions necessary
burner proper shall then be opened and the to inspect the test specimen or replenish the
flame automatically applied to the sample. This solution in the reservoir.
valve shall be held open for 15s and then closed 5.2.8.5 Procedure. After completion of the
for 15s. This process shall be repeated four exposure period, the scribed specimens shall be
times. During each application of the flame, the processed in accordance with ASTM D1654-79a
specimen shall be adjusted if necessary, so that [25], either Method A (tape) or Method B
the top of the inner blue cone touches the surface (scraper).
of the specimen. 5.2.8.6 Evaluation. The scribed specimens
5.2.7.4 Analysis. If more than 25% of the shall then be evaluated for creepage from the
extended portion of the indicator is burned after scribe mark in accordance with ASTM D1654-
the five applications of the flame, the specimen 79a [25], Rating Schedule No. 1.The nonscribed
is considered to have conveyed flame. The du- specimen shall be evaluated for degree of blis-
ration of burning of the specimen after the fifth tering in accordance with ASTM D714-80 [24].

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

5.2.8.7 Performance. The scribed speci- isfactorily met the requirements of this test if
mens shall be judged to have met the require- the visible inspection indicates
ments of the test if their rating number is 5 or (1) No water on primary or secondary insu-
higher as determined by ASTM D1654-79a [25]. lation
The nonscribed specimens shall be judged to (2) No water on any electrical components or
have met the requirements of the test if their mechanisms of the assembly
blistering size is No 6 or higher, and their fre- (3) No significant accumulation of water re-
quency designation is F or M as determined by tained by the structure or other noninsulating
ASTM D714-80 [24]. parts (to minimize corrosion)
5.2.9 Rain Test for Outdoor ME Switch-
gear. The enclosure to be tested shall be fully 5.3 Production Tests. Production tests for ME
equipped and complete with all appurtenances switchgear shall be low-frequency dielectric
such as roof bushings, and placed in the area to tests, mechanical tests, grounding of instrument
be supplied with artificial precipitation. For transformer case tests, and electrical operation
multiple-unit construction a minimum of two and control wiring test. For these tests, the re-
units shall be used to test the joints between movable elements need not be tested in the as-
units. A roof joint shall be included. The arti- sembly if they are tested separately.
ficial precipitation shall be supplied by a suffi- 5.3.1 Dielectric Tests. Low-frequency with-
cient number of nozzles to produce a uniform stand tests shall be made on ME switchgear in
spray over the entire surface or surfaces under accordance with the general requirements of
test. The various vertical surfaces of an enclo- 5.2.1, with the exception that tests across the
sure may be tested separately or collectively, open gap are not required. Tests shall be made
provided that a uniform spray is simultaneously between each phase and ground with the other
applied to both (1)and (2). phases grounded.
(I ) roof surface, from nozzle located at a
The 5.3.2 Mechanical Operation Tests. Mechan-
suitable height ical tests shall be performed to ensure the proper
(2) The floor outside the enclosure for distance functioning of shutters, mechanical interlocks,
of approximately 1m (3ft) in front of the surface etc. These tests shall ensure the interchangea-
under test with the enclosure located a t floor bility of removable elements designed to be in-
level. terchangeable.
The nozzle used for this test shall deliver a 5.3.3 Grounding of Instrument Trans-
square-shaped spray pattern with uniform spray former Case Tests. The effectiveness of instru-
distribution and shall have a capacity of at least ment transformer case or frame grounding shall
7.1 gallmin (450 cm3/s) at a pressure of 60 lbfl be checked by a low potential source, such as
in2 (41.4 Nlcm'), and a spray angle of approx- 10 V or less, using bells, buzzers, or lights. This
imately 75". The centerline of the nozzles shall test is required only when instrument trans-
be inclined downward so that the top of the spray formers are of metal case design.
is horizontal as it is directed toward the vertical 5.3.4 Electrical Operation and Control
and roof surfaces being tested. Wiring Tests
The pressure at the nozzles shall be a mini- 5.3.4.1 Control Wiring Continuity. The
mum of 60 lbf/in2 (41.4 N/cm2) under flow con- correctness of the control wiring of a switchgear
ditions. (This is approximately equivalent to, assembly shall be verified by either
rain driven by a 65 m i / h wind (29 mls). The (1) Actual electrical operation of the compo-
quantity of water applied to each surface under nent control devices or
test shall be at least 0.2 in (0.5 cm) per unit (2) Individual circuit continuity checks by
surface per minute, and each surface so tested electrical circuit testers.
shall receive this rate of artificial precipitation 5.3.4.2 Control Wiring Insulation Test. A
for a duration of 5 min. The spray nozzle shall 60 Hz test voltage, 1500V to ground, shall be
not be more than 10 f t (3 m) from the nearest applied for 1 min after all circuit grounds have
vertical surface under test. been disconnected and all circuits wired together
After the test is completed, a n inspection shall with small, bare wire to short-circuit coil wind-
be made promptly to determine if the enclosure ings. The duration of the test may be 1 s if a
meets the requirements of outdoor construction. voltage of 1800 V is applied. At the option of the
More specifically, the equipment shall have sat- manufacturer, switchgear mounted devices that

25

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

have been individually tested may be discon- these cases the phasing shall be suitably indi-
nected during the test. cated.
5.3.4.3 Polarity Verification. Tests shall (2) Panel mounted devices shall be mounted
be made to ensure that connections between in- in the same arrangement as in (1)as viewed from
strument transformers and meters or relays, etc, the front of the panel.
are correctly connected with proper polarities. 6.1.1.2 Phase Sequence. The phase se-
Instruments shall be tested to ensure that point- quence on connection diagrams shall be such
ers move in the proper direction. This does not that, when considering voltages to neutral on a
require tests using primary voltage and current. polyphase system with respect to the element of
5.3.4.4 Sequence Tests. ME switchgear in- time, the voltage of Phase 1 will reach a maxi-
volving the sequential operation of devices shall mum ahead of the voltage of Phase 2, Phase 3,
be tested to ensure that the devices in the se- etc. This sequence shall be designated as phase
quence function properly and in the order in- sequence in the order 1, 2, 3, etc.
tended. 6.1.1.3 Cable Terminations. The ME
This sequence test need not include remote switchgear shall provide space for the devices
equipment controlled by the switchgear assem- used for making electrical and mechanical con-
bly. However, this equipment may be simulated nections to the incoming and outgoing cables.
where necessary. Each cable terminal connection point shall meet
the bolt hole requirements of NEMA CC1-1984
5.4 Conformance Tests." [28], CC1-4.05.
6.1.1.4 Bushings, Potheads, or Other
5.5 Field Dielectric Tests. When low-fre- Terminators. Space for mounting these devices
quency withstand tests are to be made on ME shall be provided in the ME switchgear as re-
switchgear after installation in the field, the quired.
6.1.2 Grounding. A ground bus shall be in-
switchgear shall not be tested a t greater than
75% of the test values given in Table 1. cluded that will electrically connect together the
structure in a switchgear assembly in or on
NOTE Field tests are recommended when new units are which primary equipment or devices are
added to an existing installation or after major field modi- mounted.
fications. The equipment should be put in good condition
prior to the field test. It is not expected that equipment shall At all points of connection between the ground
be subjected to these tests after it has been stored for long bus and the assembly, any nonconductive coat-
periods of time or has accumulated a large amount of dust, ings, such as paint, shall be removed or pene-
dirt, moisture, or other contaminants without first being
restored to good condition. trated to ensure good electrical contact.
The ground bus for each group of vertical sec-
tions shall have facilities for connection to a
station ground bus by suitable conductors.
6. Construction Circuit connections to the ground bus shall be
made so that it is not necessary to open circuit
6.1 General Requirements the ground bus to remove any connection made
6.1.1 Buses and Primary Connections. to the ground bus.
Buses and primary connections shall be of cop- Ground connections shall be provided for all
per or aluminum, or both. For bus ratings see removable elements to ensure that they are
Table 2. grounded until the primary circuit is discon-
6.1.1.1 Phase or Polarity Arrangements. nected and the removable element is moved a
(1) The phase arrangement on three-phase as- safe distance. See ANSI / IEEE C37.100-1981 [9],
sembled switchgear buses and primary connec- test position.
tions shall be 1, 2, 3, from front to back, top to When mounted on metal switchgear struc-
bottom, or left to right, as viewed from the main tures, cases of instruments, instrument trans-
switching device operating mechanism side. Cer- formers, meters, relays, and similar devices shall
tain types of equipment may require other phas- be considered as being adequately grounded
ing arrangements and a neutral conductor. In when secured to these structures by metal
mounting hardware with adequate provision for
Conformance test procedures for MC switchgear will be penetrating the paint film.
available when draft C37.57 is approved and published. The ground bus shall be capable of carrying

26

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPECUBICLE SWITCHGEAR C37.20.2-1987

the rated short-time current of the ME switch- The insulated wire shall meet the require-
gear for 2 s. ments of the following standards publications as
applicable:
6.1.3 Control and Secondary Circuits and (1) Type TBS. NEMA WC 5-1973 (R 1985) [30]
Devices (ICEA S61-402)
6.1.3.1 General. All voltage circuits used (2) Type SIS. NEMA WC 7-1982 [31] (ICEA
for control, relaying, or metering shall be pro- S-66-524).
tected within the ME switchgear as follows: For wiring from supervisory and annunciator
(1) All circuits supplied from external sources devices to terminal blocks, smaller wire may be
(ac or dc) shall have short-circuit protection. This used provided it is adequately supported and will
may be provided by a single set of short-circuit meet the voltage and current requirements of
protective devices within the control source in- the circuit. Smaller wire shall not run in the
coming section. same wire packs with other control and second-
(2) All circuits supplied from internal sources ary wiring.
(ac or dc) circuits shall have short-circuit pro- Bushings, grommets, or other mechanical pro-
tection within the same section as the supply tection shall be provided for the wiring where
source. If these circuits are supplied by a control control or secondary wiring is run through a
power transformer, this protection may be in metal sheet, barrier, or raceway.
the primary circuit only. The internal wiring of component devices or
Overcurrent protection of voltage circuits may parts shall be in accordance with the applicable
be provided in addition to the required short- industry standards.
circuit protection. 6.1.3.4 Secondary-Wiring Terminals.
Other circuits supplying loads, such as heat- Stranded control wire shall have solderless ter-
ers, receptacles, or lights shall have overload minals of the type wherein the body of the ter-
and short-circuit protection. minal is crimped or indented onto the conductor
Overcurrent protection of current trans- or where the wire is formed into a n eye and
former secondary circuits shall not be provided. confined within a crimp and flat-washer assem-
6.1.3.2 Voltage Transformer Fusing. bly. Solderless terminals are not required for
(1) Primary circuits of all voltage trans- connection to devices that have integral pres-
formers shall include current-limiting fuses. sure terminal connections." The wire may be
(2) Secondary circuits of all voltage trans- soldered into terminals or, where desirable, di-
formers shall include fuses or their equivalent. rectly to devices, such as secondary disconnect-
ing contacts, or to soldered terminals on
EXCEPTION Fuses may be omitted from secondary circuits
of voltage transformers if the secondary burden includes supervisory control and annunciator equipment.
voltage regulators, protective relays, or other devices con- 6.1.3.5 Terminal Blocks. Terminal blocks
sidered sufficiently essential to the operation of the instal- incorporating screw or stud-and-nut-type ter-
lation to make it preferable to incur hazards associated with
the possible destruction of the voltage transformer by a sus- minals shall accommodate wire lugs or similar
tained secondary short-circuit rather than to risk interrup devices affixed to stranded wire. Screw or stud-
tion of the voltage supply to such devices as the result of a and-nut-type terminals intended for use with
momentary secondary short-circuit.
stranded wire shall be such that all strands of
Primary and secondary protective devices the conductor are confined. Terminal blocks in-
may be omitted from voltage dividing devices corporating pressure connectors shall not dam-
such as capacitive and resistive voltage dividers. age" the wire and, when terminating stranded
6.1.3.3 Control and Secondary Wiring. conductors, all strands shall be clamped within
Flame-resistant, 600 V insulated copper wire, the connector.
with a cross-sectional area not less than AWG Terminal blocks for external connections
No 14 stranded (4110 nominal cmil) shall be used shall be suitable to accept AWG No 10
on small wiring between component devices or (10 380 nominal cmil) stranded wire. The use of
parts of switchgear assemblies. Where wire is solid wire is not recommended.
connected across a hinge, flexible (41 or more
strands) wire shall be used.
The insulated wire shall be type TBS, or SIS
In the absence within this standard of definitive per-
or equivalent as listed in ANSI/NFPA 70-1987 formance requirements, compliance with this clause can be
~191. assessed by referencing ANSI/ UL 48661982 [20].

27

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAL-CLAD AND

6.1.3.6 Designation of Auxiliary function numbers shall be in accordance with


Switches and Contacts. The operation of aux- ANSI / IEEE C37.2-1979 [7].
iliary switches and contacts for circuit inter- 6.1.3.8 Voltage Limits of Instrument and
rupting and switching devices shall be Control Circuits. Voltage and current trans-
designated as follows: formers shall be used for the instruments, me-
ters, and relays connected to alternating-current
U. Open when the device is in the de-ener- circuits over 240 V so as to reduce the voltage
gized or nonoperated position on instrument wiring that must necessarily be
b. Closed when the device is in the de- closely grouped.
energized or nonoperated position Direct-current instruments, meters, and re-
aa Open when the operating mechanism of lays may be used directly on circuits up to
the main device is in the de-energized or 250 V if their cases are grounded to the switch-
nonoperated position gear structures in accordance with 6.1.2.
bb Closed when the operating mechanism 6.1.3.9 Polarity of Direct-Current Con-
of the main device is in the deenergized nections to Device Coils. Where coils on de-
or nonoperated position vices used in ME switchgear are connected to a
directcurrent supply and when de-energized,

;I
are not disconnected from both the positive and
Special contacts and auxiliary switches
negative supply leads, such coils shall be so con-
h other than U, b, uu, or bb
nected that, when de-energized, they will be left
k
connected to the negative supply lead to mini-
Auxiliary switches mounted on the stationary mize the possibility of corrosion.
housing used to indicate the connected position 6.1.3.10 Isolation. Instruments, meters, re-
of the removable element shall have a suffix lays, secondary control devices and their wiring
TOC (curcuit-breaker truck-operated cell shall be isolated by grounded metal barriers
switch). The position of the removable element from the primary circuit elements with the ex-
in which the contacts are closed or open shall ception of short lengths of wire such as at in-
be designated. As examples: strument transformer terminals and secondary
devices.
52TOC Open when the circuit breaker is
U not in the connected position 6.1.4 Miscellaneous
52TOC Closed when the circuit breaker is 6.1.4.1 Nameplate Marking. The follow-
b not in the connected position ing minimum information shall be given on
switchgear assemblies nameplates:
Auxiliary switches mounted on the stationary (1)Manufacturer’s name and address
housing operated by the circuit breaker to in- (2) Manufacturer’s type designation (optional)
dicate circuit-breaker openclosed position shall (3) Manufacturer’s identification reference
have a suffix MOC (circuit-breaker mechunism- (4) Rated maximum voltage (where applica-
operated cell switch). The openclosed position ble)
of the circuit breaker shall be designated for the (5) Rated frequency (where applicable)
contacts. As examples: 6.1.4.2 Wiring Devices. Lighting fixtures
provided in outdoor switchgear shall be of a type
52MOC and shall be so located that lamps may be safely
Open when circuit breaker is open
U replaced without de-energizing the primary
52MOC Closed when circuit breaker is equipment. Convenience outlets shall be of the
b open two-pole, three-wire grounding type and pro-
tected by a ground-fault interrupter.
If several auxiliary switches and contacts are 6.1.4.3 Inspection Windows. Windows
present on the same device, they shall be des- provided for the inspection of disconnecting
ignated numerically 1,2,3, etc, when necessary. switches or other devices shall be of a material
On diagrams of all types, contacts and suitable for this application.
switches shall be shown in the de-energized po- 6.1.4.4 Covers. For ease in handling, cover
sition of the device. plates that are intended to provide access for
6.1.3.7 Device Function Numbers. Device inspection and maintenance shall not exceed

28

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

12 ft2 (1.12 m2) in area or 60 lb (27 kg) unless (3) For conformance testing a recognized organic coating
system that has been investigated and found suitable for
they are equipped with lifting means or hinges. use as protection against atmospheric corrosion of electrical
6.1.4.5 Ventilation Openings and Vent equipment steel enclosures for outdoor use may be utilized.
Outlets. Openings for pressure relief or venti-
lation shall be so arranged that the gas or vapor 6.1.6 Precautionary Labels. Each LV
escaping during normal operation will not en- switchgear should be provided with appropriate
danger personnel operating the switchgear. precautionary labels to call the user’s attention
6.1.4.6 Service Disconnecting Means. to potential hazards that are inherent to the
Switchgear assemblies designated as the service equipment and which cannot be eliminated by
disconnecting means shall be designed so that design. See ANSI 235.1-1972 [3], NEMA Bulletin
they can be installed in accordance with the NO 77-1973 (R 1975) [33], NEMA 260-1962 [32]
applicable provisions of ANSI / NFPA 70-1987 for recommendations.
[19] Section 230.
6.1.5 Materials, Finishes, and Color 6.2 MC Switchgear
6.1.5.1 Materials. The materials for ME 6.2.1 Barriers. MC switchgear shall be pro-
Switchgear shall be sheet metal suitably sup- vided with metal barriers between primary sec-
ported. Barriers between adjacent vertical sec- tions of adjacent vertical sections and between
tions and between major parts of each primary major primary sections of each circuit. Primary
circuit, shall not be less than MSG No 11 (nom- sections are: the bus compartment; the primary
inal thickness 0.1196 in (3 mm)). All other cov- entrance compartment; the removable element
ers, barriers, panels, and doors shall be not less compartment; the voltage transformer(s1 com-
than MSG No 14 (nominal thickness 0.0747 in partment; and the control transformer(s1 com-
or (1.9 mm)). partment. To minimize the possibility of
The minimum thickness is based on the use communicating faults between primary sec-
of steel. Where other metals are used, the thick- tions, the barriers between primary sections
ness shall be modified to provide equivalent shall have no intentional openings.
strength and deflection.12 NOTES (1) Barriers are provided to segregate the voltage
Doors or panels used to support devices shall transformers for each polyphase circuit but not to segregate
be increased in thickness or otherwise strength- them individually.
(2) Where buses penetrate barriers, suitable bushings or
ened as necessary to support the devices. other insulation shall be provided.
6.1.5.2 Finishes and Color. All steel sur-
faces to be painted shall receive a phosphatizing 6.2.2 Shutters. On MC switchgear, automatic
treatment or equivalent prior to application of shutters shall be provided to prevent incidental
paint. contact with the live parts of the primary circuit
External and internal surfaces shall be coated when the removable element is in the test po-
with at least one coat of corrosion-resisting sition, disconnected position, or has been re-
paint. The finish paint system shall comply with moved.
the requirement of 5.2.8. 6.2.3 Insulating Materials for Covering
The under-surfaces of outdoor assemblies Buses and Connections. The insulation system
shall additionally receive either a corrosion-re- for the primary or powercarrying conductors
sistant undercoating or a n additional thickness and connections shall be rated in accordance
of corrosion-resistant paint. with Table 1 and shall withstand the tests in
The preferred color for the finish on switch- 5.2.1. Each conductor shall have a n insulating
gear assemblies shall be light gray No 61 per covering that by itself will withstand the max-
ASTM D1535-80 [23], (MUNSELL NOTATION imum rated line-to-line voltage between the con-
8.3 G6.10/0.54). ductor and outside surface of the insulating
NOTES: (1) See ANSI 255.1-1967 (R 1973) [4].
covering for a period of 1 min.
(2) Internal detail parts may have metallic plating or This insulating covering is a requirement of
equivalent in lieu of paint finish. metalclad switchgear (see 2.1.3.1) and is pro-
vided to minimize the possibility of communi-
cating faults and to prevent development of bus
l2 For example, if aluminum alloy sheet, having a yield
strength of 20 OOO lbf/in2,is used in the place of sheet steel,
faults that would result if foreign objects mo-
to provide equivalent strength and deflection, it is required mentarily contacted bare bus. This insulating
that the thickness specified above be increased by 50%. covering is usually only a part of the primary

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAGCLAD AND

insulation system and in such cases the outer 6.2.5 Interchangeability of Removable
surface of this insulating covering will not be at Switching and Interrupting Devices. All re-
ground potential. It should not be assumed, movable elements of the same type and rating
therefore, that personnel can contact this in- on a given assembly shall be physically and elec-
sulating covering with complete safety. trically interchangeable. Removable elements
Where possible, bus joints shall be completely not of the same type and rating shall not be
covered by insulating materials at the factory. interchangeable.
For interconnecting bus joints that must be 6.2.6 Primary Fuses and Voltage Trans-
made in the field, insulating material shall be formers. The primary fuses of voltage trans-
supplied for application in accordance with the formers shall be mounted in such a way that
switchgear manufacturer's instructions. Insu- they must be disconnected from the primary cir-
lating material for line and load terminations cuit before access can be obtained. Provisions
may not be furnished as standard. shall be made for disconnecting or automatically
Insulating materials for buses and connec- grounding the secondary circuit of the voltage
tions shall be flame resistant. transformer when the primary circuit is discon-
nected. Provisions shall be made for momentar-
6.2.4 Interlocks. Mechanical interlocks shall ily grounding the primary winding during the
be provided on metal-clad switchgear as follows: disconnecting operation.
(1)To prevent moving the removable element 6.2.7 Secondary Disconnect Devices. Con-
to or from the connected position when the trol wiring connections between stationary
switching device is in the closed position. structure and the removable element shall be
(2) To prevent closing the switching device un- provided with automatic (self coupling) contacts
less the primary disconnecting devices are in full or manual plug and receptacle for disconnection.
contact or are separated by a safe distance. See The manual control connector shall be either
ANSI / IEEE C37.100-1981 [9], test position. interlocked or inaccessible to prevent connection
(3) Means shall be provided for positively or disconnection of the control circuits when the
holding the removable element in place in the removable element is in the connected position
housing when it is in either the connected or and the removable element shall be prevented
test position. When a separate disconnected po- from being installed in the connected position
sition is provided with the door closed, the re- unless the manual control connector is con-
movable element shall be positively held in this nected.
position. With the manual arrangement, all connec-
(4) To prevent the disconnection of and access tions shall be group connectable simultaneously
to fuses on the primary side of control power with the male contacts on the removable ele-
transformers unless the secondary circuit is ment and the female receptacles on the station-
open. ary structure.
(5) Circuit breakers equipped with stored en-
ergy mechanisms shall be designed to prevent NOTE: "he intent of this requirement is to ensure that the
circuit-breaker control connections are always made and
the release of the stored energy unless the mech- maintained when the circuit breaker is in the connected
anism has been fully charged. Operators and position.
service personnel shall be protected from the
effects of accidential discharge of the stored en- One set of test jumpers or their equivalent
ergy by any of the following means: shall be provided for each installation to com-
(a) Interlocks provided in the housing to plete all secondary connections for test in the
prevent the complete withdrawal of the circuit withdrawn position.
breaker from the housing when stored energy 6.2.8 Control Wiring. Power circuit-breaker
mechanism is charged. control wiring shall be in accordance with ANSI
(b) A suitable device provided to prevent the C37.11-1979 [2], Figs 1, 2, 3, or 4.
complete withdrawal of the circuit breaker until 6.2.9 Handling Device. One of each size of
the closing function is blocked. handling device required to remove the remov-
(c) A mechanism is provided to automati- able element from metal-clad switchgear shall
cally discharge the stored energy before or dur- be provided for each installation.
ing the process of withdrawing the circuit 6.2.10 Test Cabinet. When a test cabinet is
breaker from the housing. furnished, it shall provide connection to the sec-

30

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

ondary contacts on a n electrically operated re- ments. To minimize the possibility of commu-
movable element, permitting operation and nicating faults between primary sections the
testing of the removable element when removed barriers between the sections shall have no in-
from the housing. tentional openings.
6.2.11 Indoor MC Switchgear, Access, and 6.3.3 Buses and Connections. The buses and
Ventilation. MC switchgear for indoor appli- connections shall have bare conductors mounted
cations shall be enclosed in general-purpose,ven- on procelain, glass, or organic (Class 105 or
tilated enclosures equipped with front-hinged higher) insulation, suitable for the voltage rat-
panels with hand-operated fasteners and bolted ing (see Table 3).
rear covers. Ducts or grilles for venting exhaust 6.3.4 Interlocks. Interlocks shall be provided
gases shall be so constructed as to prevent for- between the circuit switching or interrupting
eign materials from entering the circuit breaker. device and isolating switches to prevent oper-
6.2.12 Outdoor MC Switchgear, Access, ating the switches if the circuit switching or
and Ventilation. Enclosures (ventilated) for interrupting device is closed.
outdoor applications of MC switchgear shall be Interlocks shall be provided between the iso-
of either of the following types: lating switches and the circuit switching or in-
(1)Outdoor enclosure without operating and terrupting device to prevent opening the
maintenance aisle that provides an enclosure for primary-circuit compartment of the circuit
the switchgear and auxiliaries only. Doors shall switching or interrupting device unless the
be equipped with latches, stops shall be provided switches are in the open position.
to hold the doors in the open position, and pro-
vision shall be made for padlocks. Heaters or 6.3.5 Control Wiring. Power circuit switch-
other effective means shall be provided to min- ing or interrupting control wiring shall be in
imize condensation. accordance with the requirements of ANSI
(2) Outdoor enclosure with operating and C37.11-1979 [2], Figs 5, 6, or 7.
maintenance aisle that provides a n enclosure for 6.3.6 Indoor Station-Type Cubicles, Ac-
the switchgear and auxiliaries and, in addition, cess, and Ventilation. Station-type cubicles for
provides an enclosed aisle for operating and indoor applications shall be enclosed in general-
maintenance. The aisle shall be of sufficient size purpose enclosures (ventilated) with front-
to permit interchanging removable elements. hinged panels and bolted rear covers.
The operating or maintenance aisle shall have Adequate ducts or grilles shall be provided on
access doors equipped with safety latches to per- units with air-blast circuit switching or inter-
mit opening from within under all conditions. rupting devices to remove exhaust gases. Ducts
Stops shall be provided to hold these doors in or grilles for venting exhaust gases shall be so
the open position, and provision shall be made constructed as to inhibit foreign material from
for padlocks. Heaters shall be provided to min- entering the circuit switching or interrupting
imize condensation in compartments containing device.
primary-circuit apparatus and devices. 6.3.7 Outdoor Station-Type Cubicles, Ac-
6.2.13 Position Indication. Indicating lights cess, and Ventilation. Station-type cubicles for
shall be provided to indicate the open and closed outdoor applications shall be enclosed in enclo-
position of the switching devices. Unless other- sures (ventilated) and shall be equipped with
wise specified, the closed position shall be indi- suitable access doors.
cated by a red light and the open position by a Doors shall be equipped with latches, stops
green light. shall be provided to hold doors in the open po-
6.2.14 Enclosure Categories. See Appendix sition, and provision shall be made for padlocks.
A for Description of enclosure categories and Heaters shall be supplied to minimize conden-
related requirements. sation.
Adequate ducts or grilles shall be provided on
6.3 SC Switchgear units with air-blast circuit switching or inter-
6.3.2 Barriers. Metal barriers shall be pro- rupting devices to remove exhaust gases. Ducts
vided to segregate the circuit switching or in- or grilles for venting exhaust gases shall be so
terrupting device compartment, incoming and constructed as to prevent foreign materials from
outgoing circuit and bus compartments, and the entering the circuit switching or interrupting
individual phases in each of these compart- devices.

31

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAGCLAD AND

6.3.8 Secondary and Control Devices. Table 9


Heaters, relays, control switches, and similar Altitude Correction Factors
items, other than circuit switching or inter- Altitude
rupting device control relays, are not mounted (ft) Voltage Current
integral with this type of switchgear. 3300 ft (1000 m) (and below) 1.00 1.00
5000 ft (1500 m) 0.95 0.99
10 000 ft (3000 m) 0.80 0.96

7. Application Guide for ME NOTES (1) Intermediate values may be obtained by inter-
polation.
Switchgear (2) For devices used in switchgear assemblies, standards
covering the specific devices should be used to determine
the specific altitude correction factors.
7.1 Unusual Service Conditions. It is strongly
recommended that the usual service conditions,
as described in 3.1,be provided for ME switch-
gear applications if practical (artificially, if nec-
essary). However, if unusual conditions exist and
cannot be eliminated, the following considera-
tions apply:
rection factors in Table 9 to obtain the modified
NOTE: Any unusual service condition should be specified ratings. For applications above 3300 ft (1000m),
by the user.
use of surge arresters on each circuit, selected
7.1.1 Ambient Air Temperature Above to keep transient voltages below the reduced lev-
40 "C.When ME switchgear is applied where the els, should be considered.
ambient air temperature is higher than 40 "Cits
7.1.4 Modification of Equipment for Unu-
performance may be affected and special con-
sual Environment. Successful performance of
sideration should be given to these applications.
standard ME switchgear may be extended to un-
The total temperature limits for parts and ma-
usual environments by special considerations
terials as listed in 4.4 should not be exceeded.
when developing equipment specifications. Sev-
Therefore, for the higher ambients, the equip-
eral construction modifications that will miti-
ment should be derated to a continuous current
gate the effects of these environments may be
value that maintains the total temperature lim-
made in accordance with 7.1.4.1through 7.1.4.6,
its. In general, the derating may be calculated
but the emphasis should be on eliminating such
in accordance with Table 11.
conditions if at all possible. However, if these
7.1.2 Ambient Air Temperature Below
undesirable conditions cannot be eliminated,
-30 "C. Special consideration is also required more frequent maintenance may be required.
when ME switchgear is applied where the am-
bient air temperature is less than -30 "C for 7.1.4.1 Exposure to Damaging Fumes,
significant periods of time. Space heating and Vapor Steam, Salt Air, and Oil Vapors. In-
thermal insulation to minimize the effects of door and outdoor equipment should be provided
exposure should be considered. If this is not pos- with the following modifications:
sible, the effect of low temperatures on the func- (1)Minimum of two coats of paint, one of
tional performance of such materials as oils, which should be a corrosion- or rust-resisting
plastic insulation on primary and secondary cir- primer, on all structural parts.
cuits, control wire insulation, and lubricants (2)All steel parts that are not painted or
should be considered. plated should be covered with protective grease.
7.1.3 Application at Unusual Altitudes. (3)All current-carrying joints should be cov-
Switchgear assemblies that depend on air for a n ered with a coating of nonoxidizing grease.
insulating and cooling medium will have a Greasing of nonarcing contacts should only be
higher temperature rise and a lower dielectric done on recommendations of the manufacturer.
withstand capability when operated at altitudes (4)All coils should be impregnated with in-
above values specified in 3.1(2).For applications sulating compound and covered with appropri-
at higher altitudes, the rated 1 min power-fre- ate protective coating.
quency withstand voltage, the impulse with- (5) Heaters, in quantity and rating sufficient
stand voltage, and continuous current rating of to minimize condensation in all compartments,
the assemblies should be multiplied by the cor- should be furnished.

32

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

7.1.4.2 Exposure to Excessive Dust, Ab- (4) Paints such as alkyd enamels having a fun-
rasive Dust, Magnetic or Metallic Dust. In- gus- and rust-resistant property should be used.
door or outdoor equipment should be provided Insulation that is not inherently fungus-re-
with the following modifications: Totally en- sistant should have fungus-resistant coating a p
closed nonventilated equipment should be fur- plied. Insulation in switchgear assemblies, that
nished with a current rating of 70% of the is inherently fungus-resistant, should not re-
ventilated rating or as specified by the manu- quire further treatment. Fungus-resistant coat-
facturer. Condensation could be a problem and ings should not be applied where they will
should be evaluated. interfere with proper operation of apparatus. In
Ventilation filters for outdoor assemblies: For such cases, the part should be inherently fungus-
outdoor assemblies ventilated enclosures may be resistant. These coatings should not reduce the
furnished with the ventilating openings flame-resistant properties.
equipped with dust filters. The requirements for The fungus-resistance of materials should be
these filters vary over such a range that stan- determined in accordance with ASTM G21-70
dard specifications for their application are not (R1980)[27]. Materials to be classified as fungus-
practicable. Filters are available in the washable resistant should have a rating not greater
type and the disposable type. Where used, they than 1.
must be cleaned or replaced at intervals, de- Materials that are made fungus-resistant by
pending upon the amount of dust in the air. means of a coating should have the coating r e a p
Filters that are not cleaned or changed when plied at periodic intervals.
required can cause excessive equipment tem- 7.1.4.4 Exposure to Explosive Mixtures
perature or condensation. of Dust or Gases. Application of ME switchgear
The type of filter used should be selected based for explosion-proof requirements is not recom-
on the size of dust particles encountered and the mended.
extent to which dust is to be excluded. Where 7.1.4.5 Exposure to Abnormal Vibration,
very fine dust particles are to be excluded, dis- Shocks, or Tilting. Indoor and outdoor equip
posable filters soaked in oil should be used. ment is designed for mounting on level struc-
These must be changed at frequent intervals. tures free from vibration, shocks, or tilting.
Forced ventilation may be required depending Since these conditions vary so widely, it is
upon the volume of air required for ventilation recommended that the manufacturer be con-
and the severity of the environment. When fur- sulted for each specific application where vibra-
nished due to environment, the blower and filter tion, shocks, or tilting are to be encountered.
should be installed on the intake to minimize It is important that the full nature of the ab-
the possibility of drawing dust or other foreign normal motion be specified. The magnitude and
matter into and throughout the switchgear as- frequency range of the dynamic motion is re-
sembly. quired so that resonances may be investigated.
7.1.4.3 Exposure to Hot and Humid Cli- This is usually specified by means of a n accel-
mate. Indoor and outdoor equipment intended eration response spectrum curve for the mount-
for exposure to hot and humid climates should ing surface on which the ME switchgear is to be
be made fungus-resistant by the following mod- installed. The response spectrum is a plot of the
ifications: maximum response of singledegree-of-freedom
(1)Heaters in quantity and rating sufficient bodies, at a damping value expressed as a per-
to minimize condensation in all compartments cent of critical damping of different natural fre-
should be furnished. quencies, when these bodies are rigidly mounted
(2) Secondary wiring that is not inherently on the surface of interest (that is, on the ground
fungus-resistant should have fungus-resistant for the ground response spectrum or on the floor
coating applied. Secondary wiring that has fun- for the floor response spectrum) when that sur-
gus-resistant insulation should not require fur- face is subjected to a given abnormal motion as
ther treatment. modified by any intervening structures. The re-
(3) All impregnated coils should be given an sponse spectrum is useful in designing a test or
external treatment with fungus-resistant coat- in making a n analysis of the performance of the
ing. Encapsulated coils that are inherently fun- ME switchgear equipment mounted on the same
gus-resistant should not require further surface and subjected to the same motion.
treatment. In the case of tilting, it is also important that

33

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAXLAD AND

the maximum angles of tilt, both transverse and and ANSI / IEEE C37.24-1971(R 1984) [8] should
longitudinal, be specified. The exact perform- be referred to. The rated continuous current is
ance requirements should also be defined. It based on not exceeding the limits of the hottest-
should be recognized that equipment that is spe- spot total temperature of the various parts of
cifically designed for a usual installation on a the switchgear assembly when this value of cur-
substantially level surface free from excessive rent is sustained in an ambient air temperature
vibration, shock, or tilting may be damaged and of 40°C. When the ambient air temperature is
may not be able to function properly when sub- greater than 40°C, the current should be re-
jected to excessive motion and displacement. duced to less than rated continuous current to
Hence, the application should be carefully ana- keep total temperature of these parts within al-
lyzed and the essential performance require- lowable limits. The application of switchgear as-
ments should be precisely defined. semblies should be based on avoiding operation
7.1.4.6 Exposure to Seismic Shock. Be- at current higher than the rated continuous cur-
cause of the importance of adequate perform- rent of the assembly. However, since the crite-
ance of equipment when applied as Class 1E rion is total temperature, the following
equipment in a nuclear power generating sta- considerations are in order:
tion, ANSI/IEEE Std 344-1975 (R 1980) was de- (1) It is permissible to exceed rated current:
veloped for this application. (a) For short periods, such as in the starting
of motors or synchronous condensers, or when
7.2 System Characteristics-Voltage, and energizing cold loads. Generally, the short du-
Frequency. ME switchgear is designed for use ration of this type of current increase does not
on three-phase, 60 Hz, grounded or ungrounded raise temperatures significantly.
ac systems. Application on other types of sys- (b) When operating at an ambient air tem-
tems, such as perature below 40 "C(see 7.4.1).
(1) Three-phase, 4-wire with insulated neutral (c) For short periods following operation at
(2) Two-phase a current less than that permitted by the exist-
(3) Frequency other than 60 Hz or sinusoidal ing ambient air temperature (see 7.4.1.1).
waveforms should be reviewed with the manu- (2) Since current transformers and outgoing
facturer. cable sizes are frequently less than the contin-
ME switchgear is intended for application on uous current rating of the circuit breaker, any
systems where the maximum operating voltage overloading must be carefully controlled.
of the system does not exceed the maximum 7.4.1 Load Current-Carrying Capabili-
voltage for which the equipment is designed. The ties Under Various Conditions of Ambient
voltages for various types of ME switchgear are Temperature and Load. When ambient air
listed in Table 1. temperature is other than 40 "C, on which con-
7.3 Overvoltage Considerations-Insulation tinuous ratings in Table 2 are based, the con-
Levels. The insulation levels to which ME tinuous current can be calculated by the
switchgear is designed are also listed in following formula
Table 1.
The information on the application of surge
arresters and surge capacitors for protection
against overvoltages is given in 7.7.2. where
7.4 Continuous Current Rating and Over- Ia = allowable continuous load current, A,
load Capability. ME switchgear assemblies are a t the actual ambient temperature 8,
designed for normal application where the sus- (I,is not to exceed two times I,)
tained load current does not exceed the rated I, = rated continuous current, A, on basis
continuous current, the altitude above sea level of 40 "C ambient
is 3300 ft (1000 m) or less, the ambient air tem- ,,e, = allowable hottest-spot total temper-
perature does not exceed 40"C, and the effects ature
of solar radiation can be neglected. For unusual 8, = actual ambient temperature expected
altitudes, derating factors should be applied in (between -30 "C and 60 "C), "C
accordance with 7.1.3. If solar radiation is sig- 8, = allowable hottest-spot temperature
nificant, continuous current capability is limited rise at rated current, "C

34

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

Table 10 specified limit of total temperature should be


S u m m a r y of Temperature Limitations selected.
Switchgear Component (2) If the actual ambient air temperature is
Circuit Breaker ANSI / IEEE C37.04 - 1979 greater than 40 "C,the component with the Zow-
(R 1982) [5] est specified limit of total temperature should
Current Transformers ANSI / IEEE C57.13 - 1978
(R 1986) [lo] be selected. The use of this value in the calcu-
Insulating Material in ANSI/IEEE C37.20.2 - 1987 lation will result in a n allowable, continuous
Switchgear Assemblies current that will not cause the temperature of
Temperature Limits for ANSI / IEEE C37.20.2 - 1987
Buses and Connections any part of the assembly to exceed the specified
Temperature Limits for Air ANSI! IEEE C37.20.2 - 1987 limit.
Surrounding Insulated
Power Cables NOTE: Information on the load currentcarrying capability
Temperature Limits for ANSI! IEEE C37.20.2 - 1987 of power circuit breakers for applications other than ME
Parts Subject to Contact switchgear is given in ANSI/IEEE C37.010-1979 [6], 4.4.3.
bv Personnel When the power circuit breaker is used in MC switchgear
all considerations of ANSI /IEEE C37.010-1979 [6], 4.4.3.2
apply in this standard, except it should be noted that the
NOTE The temperature rise of a currentcarrying part is exponent X is used in the formula for determining load
proportional to an exponential value of the current flowing current capability rather than 1/ 1.8.
through it. The exponent value of X in the formula observed
has been found to be generally valid for overload capability Table 11lists the calculated values of Ia/Ir
for
of ME switchgear and is therefore used in this standard.
each specified temperature limit for the various
The construction features of ME switchgear components of ME switchgear over a range of
dictate the appropriate values of 8, and Om,,. The typicai ambient air temperatures. The alhvdde
major components have several different tem- current in any given situation can be estimated
perature limits specified in the American Na- from Table 11or may be calculated directly from
tional Standards or sections of this standard the stated formula.
listed in Table 10.
In order that none of the limitations specified 7.4.1.1 Short-Time Load Current Capa-
in the standards or sections of Table 10 be ex- bility. The considerations of ambient air tem-
ceeded, the permissible load current based on peratures in 7.4.1 are based on steady-state
the actual ambient air temperature is deter- conditions. When the switchgear assembly has
mined by using the values for 8, and,,,e selected been operating at current levels below the al-
as follows: lowable continuous current I,, it is possible to
(1) If the actual ambient air temperature is increase the load current for a short period to
less than 40 "C, the component with the highest a value greater than the allowable I, without

Table 11
Ratios of ( I , / I,) for Various Ambient Temperatures
Limiting Temperatures of Different Switchgear Components
Maximum
Ambient omax 50 55 70 80 85 90 95 105 110
"C 0, (rise) 10 15 30 40 45 50 55 65 70

60 * - - 0.58 0.71 0.75 0.77 0.80 0.83 0.85


50 * - 0.58 0.82 0.87 0.88 0.89 0.80 0.92 0.93
40 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
30 t 1.41 1.29 1.15 1.12 1.11 1.10 1.09 1.07 1.07
25 t 1.58 1.41 1.22 1.17 1.15 1.14 1.13 1.11 1.10
20 t 1.73 1.53 1.29 1.22 1.20 1.18 1.17 1.14 1.13
10 t 2.0 $ 1.73 1.41 1.32 1.29 1.26 1.24 1.21 1.20
07 2.0 $ 1.91 1.53 1.41 1.37 1.34 1.31 1.27 1.25
-10 t 2.0 $ 2.0 I: 1.63 1.50 1.45 1.41 1.38 1.33 1.31
-20 t 2.0 $ 2.0 $ 1.73 1.58 1.53 1.48 1.45 1.39 1.36
-30t 2.0 $ 2.0 $ 1.83 1.66 1.60 1.55 1.51 1.44 1.41
* For limiting current, use lowest 0, and Om,,
t For limiting current, use highest 0, and Omax
$ Designated limit-not calculated

35

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METAMLAD AND

time, t , or t, (time constant units)

I IIII I l l 1 I l l 1 I l l 1 1 1 I I I I I I I l l 1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 .o

current, I / l , or la/ls, (per unit)

muired Initial Data NOTE: This procedure and the design of this figure are based
on the following assumptions:
Ii= initial steady-state current (1)At constant current, the temperature approaches its
I. = allowable continuous load current based on actual steady-state value at an exponential rate. During any time
ambient temperature (from 7.4.1) interval equal to the thermal time constant of the main bus,
I . = desired short-time load current circuit breaker, or interrupter switch, or both, the temper-
Calculation Procedure ature rise will be equal to 63.2% of the remaining increment
(1)Determine Ii/I,, per unit initial current of possible increase existing at the start of the period. This
(2) From the f g u r e determine corresponding time, t i is represented by the time scale at the top of the chart.
(3) Determine I a / I Bper
, unit allowable continuous cur- (2) The temperature of the main bus, circuit breaker, or
rent interrupter switch, or both, increases as the 2.0 power of
(4) From the figure determine corresponding time t , the current increases. This is represented by the current
(5) Calculate t , - t i = time (in time constant units) that scale at the bottom of the figure. Here, the current in per
main bus, circuit breaker or interrupter switch, or unit value is plotted to a scale representing the temperature
both, can carry I., starting from initial continuous produced by that current.
current of Ii,with ambient air temperature permitting
continuous operation at I,.

Fig 2
Current-Time Relationship to Determine Short-Time
Load-Current-CarryingCapability of
Metal-Clad Switchgear Assemblies

exceeding the permissable temperature limits. (b) The value used for the initial current Ii
The length of time that the short-time load cur- is the maximum current carried by the main
rent I, can be carried depends on the following bus or circuit breaker, during the 4 h period
factors: immediately preceding the application of short-
(1) The magnitude of I, to be carried time load I,.
(2) The magnitude of initial current Iicarried (c) At the end of the time period, the current
prior to application of I.. I, is reduced to a value that is no greater than
(3) The thermal-time characteristics of the the allowable continuous load current I,.
switchgear assembly (d) The value of the current I. is limited to
The duration of the short-time current may a maximum value of two times rated continuous
be calculated directly or may be obtained by current I,.
simply using Fig 2. The time duration of the
current Is determined in this manner will not
cause the total temperature limits of any com-
ponent of the switchgear assembly to be ex- 7.4.1.2 Determination of Allowable Time
ceeded provided that the following requirements for Overload Value I,. One method of deter-
are fulfilled: mining the allowable duration of current I, is
(a) all main and feeder bus joints and power shown in Fig 2. The values of time obtained from
terminal connections are checked periodically in the figure are given in time-constant units. The
accordance with the manufacturer’s instruc- actual time is determined by multiplying the
tions. Bolted connections should be torqued to time-constant units by the proper thermal time
recommended foot-pound values. constant listed in Table 12.

36

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

Table 12 NOTE These equations are derived in the following man-


ner:
Typical Thermal Time Constants for MC
Switchgear let

Circuit Breakers 0. = total temperature, 'C, that would be reached if cur-


and Bus Rating Heating rent Z. were applied continuously at ambient 0.
0, = total temperature, "C,due to continuous current Z,at
1200 A 0.5 h ambient 8.
2000 A 0.5 h 0, = total temperature, "C,at some time t after current is
3000 A 0.5 h raised from Z,to Z.
then
e, = (e, - e,) (1 - e -T+ e,
let
0, =, 8 solve for t
then
7.4.1.3 Determination of Allowable Time t. = - r In [I -
for Z. by Direct Calculation. The allowable du- (e, - e,)
ration of current I, may be calculated directly. where
4 = e,( +
- ~ o ~ c ) ( z , / I , e,) ~
While the chart method is quicker and simpler e. =e
,( - ~O~C)(ZJZ,)~e. +
than hand calculation of these equations, the
increasing availability of digital computers For the special case where the initial current
makes it desirable to provide the details of these is zero, the equations in this form are useful. By
calculations. These equations may be written in substitution the equations given above in terms
a computer language such as FORTRAN so that of Y a r e obtained; these are convenient to use
many sets of conditions may be analyzed quickly. in the more unusual case where the initial cur-
The program also should then be immediately rent is not zero.
available for use. These are the equations used 7.4.2 Special Continuous Current Ratings.
to calculate the time duration t. for a short-time If a n unusual situation requires consideration
load current I, of a rating not included in the preferred rating
structure, nor possible utilizing ambient com-
pensation, consideration should be given to
(1) Design modifications for increased current
capacity of the primary circuit by means of
larger conductor sizes or the use of higher con-
ductivity materials.
(2) Forced-air cooling utilizing automatic con-
trols so that the forced cooling for increased rat-
ing is operational only when actually required.
where The air supply for forced cooling should be clean
and dry.
Om, = allowable hottest-spot total tempera- 7.4.3 Conductor Temperature. Cables con-
ture from Table 1, "C nected to ME switchgear should be capable of
8, = actual ambient expected (between withstanding the 65 "C ambient temperature to
-30 "C and 60 "C), which they may be subjected.
Ii = initial current carried prior to appli-
7.4.4 Conductor Terminations. Considera-
cation of I., A (the maximum current
tion should be given to the use of suitable con-
carried by the breaker during the 4 h
nectors that are designed for use with the
period immediately preceding the ap-
outgoing conductor and terminals in the switch-
plication of current I,)
gear units.
I, = short-time load current, A
I, = rated current, A 7.4.5 Control Supply Terminations. Where
T = thermal time constant of the circuit long connections to the control battery are nec-
breaker from Table 3, h essary, the cable should be large enough to pre-
t, = permissible time for carrying current vent excessive voltage drop.
I. at ambient 8, after initial current Ii NOTE: Larger terminal blocks than specified in 6.1.3.5may
time is in same units of hours as T be required for this termination.

37

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

7.5 Short-circuit Considerations. ME switch- equipment. Special consideration should be


gear should have short-circuit capability equal given to the use of coordinated surge arresters
to or greater than the short-circuit capability of for ME switchgear installed at high altitudes.
the system on which it is applied. The short-
circuit capability (monetary or short-time, or 7.8 Protection and Isolation of Switchgear
both) of a unit of a switchgear assembly is equal Connected to Other Circuit Protective
to that of the included circuit breaker. Equipment. When ME switchgear is electri-
cally connected to other power switching and
circuit protective equipment, the circuit protec-
7.6 Nuclear Power Plant Application. When
tive equipment should be provided in the con-
ME switchgear is applied in nuclear power gen-
nection between the two so that a fault in one
erating stations and particularly when it is ap-
assembly will not result in the loss of the other
plied as Class 1E equipment it should meet the
assembly.
requirements of pertinent standards that have
been developed for such applications. NOTE Where both assemblies supply power to an entire
integral unit process, so that the shutdown of one part ne-
cessitates the shutdown of the entire process, tie circuit
7.7 Associated Devices Often Used In ME protection equipment is not required. For additional infor-
mation and further study of switching arrangements, see
Switchgear ANSI/IEEE Std 141-1986 [14], ANSI/IEEE Std 241-1983
7.7.1 Current Transformers. The current [15], ANSI/IEEE Std 242-1986 [16], and ANSI/IEEE Std
transformers included in ME switchgear are in 446-1987 [le].
accordance with 4.5 and 4.6. The accuracies
listed in 4.6 are the minimum supplied in the
usual design of these equipments, and are ade-
quate for most applications. If a n application
requires higher accuracies, it should be specified 8. Guide for Handling, Storage, and
by the user. It should be recognized that current Installation
transformers with higher accuracies than listed
in 4.6 may not meet the requirements of 4.5. The 8.1 General. This section is a guide for the han-
manufacturer should be consulted for possible dling, storage, and installation of ME switchgear
solutions to the problem of obtaining required and emphasizes safety aspects and other consid-
accuracy without compromising on other re- erations when working with this type of equip-
quirements. ment. It supplements, but does not replace, the
7.7.2 Surge Protective Devices manufacturer’s detail instructions on these sub-
7.7.2.1 Rotating Equipment. Capacitors jects. The objective is to furnish additional guide-
or surge arresters, or both, used to protect the lines to promote and enhance a reliable
insulation of rotating machines, should be installation.
housed in a suitable enclosure adjacent to the The manufacturers of ME switchgear include
machine and connected without fuses or discon- instruction books and drawings with their equip-
necting devices. Cable connections to these de- ment, containing detailed recommendations for
vices should be able to withstand possible short- storage, handling, installation, operation, and
circuit current, both thermally and mechani- maintenance.
cally. Personnel responsible for these functions
7.7.2.2 Exposed Circuits. Protection should review these recommendations before
against lightning surges should be considered for handling the equipment. Particular attention
all switchgear assemblies having exposed cir- should be given to recommendations for prepa-
cuits. Exposed circuits are those outside of build- ration of foundation and forms on which the
ings or those that do not have adequate surge switchgear is to be mounted. One set of manu-
protection connected to limit voltages to less facturer’s instruction books should remain with
than the withstand level of the switchgear. the ME switchgear when in storage or at the
7.7.2.3 Surge Arresters in Switchgear installation site.
Assemblies. Surge arresters used in switchgear
assemblies should have adequate discharge ca- 8.2 Handling
pability and be voltage limiting to keep voltage 8.2.1 Receiving. ME switchgear should be
surges below the insulation level of the protected carefully inspected and packed before leaving

38

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

the factory. Immediately upon receipt, the (1) Protect workers adequately from live parts
equipment should be examined for damage that with barriers, screens, etc.
may have been sustained during transit. If dam- (2) Observe ANSI C2-1987 [l], Rule 124 for
age is evident or indications of rough handling guarding live parts.
are visible, the carrier (transportation company)
8.2.5 Removal of Shipping Members. Be-
and the manufacturer should be notified
fore installation of ME switchgear a careful
promptly.
check should be made to ensure that all mem-
Only authorized personnel should be permit-
bers included for shipping purposes, have been
ted to handle the equipment. Care should be
removed.
exercised in handling each piece of equipment
(even if crated) because parts may be damaged. 8.2.6 Connections
8.2.2 Rigging. Instructions for lifting and 8.2.6.1 Bus Connections. When the ME
handling of the equipment are contained in the switchgear consists of several shipping sections,
manufacturer’s instruction books and drawings. the main bus is necessarily disconnected before
The rigging should be adequate for the size and shipping. The main bus should be reconnected
weight of the equipment. with particular attention to the cleanliness of
8.2.3 Storage. Indoor switchgear that cannot and pressure between the contact surfaces. It is
be installed immediately should be stored in a essential that the connections be securely bolted
dry, clean location and should remain in crates because the conductivity of the joints is depen-
during the storage period. The longer the period dent on the applied pressure. Refer to manufac-
of storage, the greater the care required for pro- turer’s torque instructions and any other special
tection of the equipment. During storage, the instructions.
ME switchgear should be placed on a level sur- 8.2.6.2 Cable Connections. Before making
face to prevent unnecessary strain and possible up the cable connections, the phasing of each
distortion. During the construction period, pro- cable should be determined in accordance with
tection should be provided against dust, dirt, fall- the connection diagram, and the cables tagged
ing objects, dripping water, excessive water, accordingly. The cable manufacturer’s instruc-
excessive moisture, and other possible causes of tions should be followed when forming cable ter-
damage to the equipment. Any temporary cov- minations and during the installation of the
ering should not restrict ventilation and should cable. It is essential that the connections be
not be removed until the equipment is ready for clean and securely bolted, since the conductivity
installation. It is preferable to store indoor of the joints is proportional to the applied pres-
equipment within a heated building. If this is sure. The terminating devices (where required)
not possible, special precaution should be taken should be installed pursuant to the terminator
to keep the equipment sufficiently warm with manufacturer’s instructions.
adequate ventilation to prevent condensation 8.2.6.3 Control Connections. Control
during the storage period. If necessary, tempo- wires between shipping sections should be re-
rary heating should be installed in the equip- connected as marked by the manufacturer. Con-
ment. nections that are to be connected to terminals
If outdoor switchgear cannot be installed and in apparatus remote from the switchgear should
energized, temporary power must be provided be carefully checked against the connection dia-
for the operation of the space heaters provided gram. When making connections to terminals,
so as to minimize condensation of moisture care should be exercised to ensure that the con-
within the housing. nections are properly made.
8.2.6.4 Grounding. Sections of ground bus
previously disconnected at shipping sections
CAUTION: Ensure that the normal supply must be reconnected when the units are in-
source is open to prevent backfeed. stalled. Make sure that all secondary wiring is
connected to the switchgear ground bus as in-
dicated on the drawings. The ground bus should
Ventilation openings in ME switchgear should be connected to the system ground with as direct
be left open to permit proper circulation of air. a connection as possible and should not be run
8.2.4 Installation. When installing ME in metal conduit unless the conduit is ade-
switchgear quately bonded to the circuit. The grounding

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

conductor should be capable of carrying the 8.4 Removable Elements. All circuit breakers
maximum line-to-ground short-circuit current should be inspected for damaged parts and any
for the duration of a fault. A reliable ground loose connections pursuant to the manufactur-
connection is necessary for every switchgear in- er’s instructions. Check manual operation with
stallation. It should be of sufficient capacity to the manual closing lever or with the mainte-
handle any abnormal condition that might occur nance closing handle on the larger size circuit-
on the system and should be independent of the breaker elements. Trip each circuit breaker by
grounds used for other apparatus. A permanent operating the manual trip device. Operation
low-resistance ground is essential for adequate with maintenance handle and slow closing
protection and safety. should be done outside the circuit-breaker cu-
bicle. The power-operated circuit breakers
8.3 Preoperation Check. Care must be exer- should be checked for proper operation while in
cised to prevent the ME switchgear from being the switchgear cubicle test position, for both clos-
energized from the power system while prelim- ing and tripping at the normal control voltage.
inary tests are being conducted. If disconnecting
means is not available, line leads should be dis- 8.5 Interlocks. Interlocks should be checked for
connected. All internal connections should be proper operation before power is applied to the
examined to ensure that they have not been switchgear.
loosened or damaged during shipment or in- 8.5.1 Metal-Clad Switchgear. Check inter-
stallation and all bolted connections and joints locks between removable element and housing
should be tightened to ensure good contact. If to see that
spring washers are used under bolt head and (1)The element cannot be moved to or from
nuts, they should be tightened in accordance the connected position when the breaker is in
with manufacturer’s instructions. All wiring the closed position
connections should be checked for tightness, in- (2) The circuit breaker cannot be closed un-
cluding those at the instrument transformers less it is in the fully connected position or in the
and all terminal blocks. Remove current trans- test position
former shorting devices on all active circuits. Check that the shutters are operable so that
Remove all ties and blocking from the relay the primary disconnecting devices in the hous-
armatures or discs before the control energy is ing are automatically covered when the circuit
applied. breaker is withdrawn.
Protective relays, overcurrent trip devices, 8.5.2 Station-Type Cubicle Switchgear.
and breaker attachments included with the ME Check the interlock between isolating switches
switchgear should be tested for correct connec- and circuit switching or interrupting device to
tions and operation at the factory. However, the be sure that switches can be operated only when
protective device settings for current, voltage, circuit switching or interrupting device is open.
or other quantities must be made by the user in When grounding switches are used, check for
accordance with his operating practices. The proper sequential operation with the interlocks.
manufacturer’s instruction books should be Check the interlock between isolating switches
studied carefully before setting the protective and the primary circuit compartment of the cir-
devices. cuit switching or interrupting device to be sure
It is recommended that the integrity of control that access is only allowed when the switches
buses be checked with an ohmmeter to ensure are open.
against short circuits in the control wiring. Con- To maintain the integrity of key interlock sys-
trol wiring should be given a high-potential test tems, duplicate keys should be destroyed or re-
or be insulation resistance tested and power cir- tained in a place accessible only to authorized
cuits, such as buses and circuit breakers, should personnel.
be given a low-frequency withstand test as de-
scribed in 5.1 and 5.5. After ME switchgear has 8.6 Ehergization. After the removable circuit-
been installed and all interconnections com- breaker elements and interlocks have been
pleted, any control schemes should be opera- tested satisfactorily, the circuit breakers may be
tionally tested and power connections given a moved to the connected position. Each compart-
final check for phase rotation /sequence before ment door should be closed and secured before
the switchgear is finally energized for service. energizing the circuit.

40

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI/ IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

Appendix

(This Appendix is not a part of ANSI/IEEE C37.20.2-1987, IEEE Standard for Metal-Clad and Station-Type Cubicle
Switchgear, but is included for information only.)

Appendix A

Guide for Enclosure Categories


and Related Requirements

Foreword A2. Enclosure Categories


ANSI / IEEE C37.20-1969 (1974 Consolidated Switchgear assemblies are installed in a va-
Edition) (R 1984) IEEE Standard for Switchgear riety of locations that have a different degree of
Assemblies Including Metal-Enclosed Bus, in- exposure to the general public. The enclosure of
cluded Section 7, entitled Tamper-ProofSwitch- the switchgear assembly provides a degree of
gear. However, this terminology created protection to the enclosed conductors or equip
questions of intent as related to public exposure ment and provides a degree of protection to per-
and therefore C37.20.2 eliminated this construc- sonnel against incidentally contacting live parts.
tion feature from the basic standard. Enclosures are categorized as Category A, E,
During the development of othter standards, and C as listed in Table Al.
a n enclosure security section was developed to
provide guidance for varying types of construc- A2.1 Category A Enclosure. Category A en-
tion described as Categories A, B, and C. These closures are intended to provide a degree of pro-
categories will be included in C37 57, Conform- tection against contact with enclosed equipment
ance Testing of Metal-Clad Switchgear Assem- in ground level installations subject to deliber-
blies, (see footnote lo), but basic construction ate unauthorized acts by members of the un-
features are not normally included in a con- supervised general public. The enclosure shall
formance test standard. meet the requirements of Table Al, Category A.
Construction details are normally included in
the basic standards. However, since Category A
covers the prior concept of Tampe,P-Proof;it was A2.2 Category B Enclosures. Category B en-
decided that it would be best contained in this closures are intended for use in installations not
Appendix with the other categories to be utilized subject to deliberate unauthorized acts by mem-
as options. Category C covers metal-clad switch- bers of the unsupervised general public pri-
gear with exposed bushings, bus, or terminals. marily to provide a degree of protection to
Category B, while it represents basic metal- unauthorized and untrained personnel against
clad switchgear construction, reimains in the incidental contact with enclosed equipment. The
Appendix for continuity. enclosures shall meet the requirements of Table
It is noted that C37.57 will contain the test Al, Category B.
requirements for Categories A, B and C.
A2.3 Category C Enclosures. Category C en-
closures are intended to provide a degree of pro-
Al. Scope tection against contact with enclosed equipment
in secured installations intended to be accessible
This guide covers enclosure categories and only to authorized persons. The enclosures shall
related requirements. meet the requirements of Table Al, Category C.

41

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
C37.20.2-1987 IEEE STANDARD FOR METALCLAD AND

Table A1
Requirements for Enclosure Categories
Reference Required for Categories
Feature Paragraphs A B C
All enclosures
Basic requirements
Rigidity (sheet metal) 3.6 Yes Yes Yes
Exposed live parts permissible 3.14 No No Yes
Operating handle protection 3.9 Yes No No
Vent openings (permissible) 3.8 Yes Yes NIA
Doors (if supplied) 3.7 Yes Yes Yes
Doors-handles lockable 3.7 Yes Yes No
Doors-captive fasteners permitted 3.7 N/A Yes Yes
Hinge pins-nonremovable door 3.7 Yes No No
Drain valves, gauges, etc.
Locked cover 3.12 Yes No No
Caution and warning signs 3.15 Yes Yes Yes
Viewing pane-lockable cover 3.11 Yes No No
Outdoor enclosures
Material 3.13 Yes Yes Yes
Hinges 3.13 Yes Yes Yes
Gaskets 3.13 Yes Yes Yes
Doorstop 3.13 Yes Yes Yes
Drainage 3.13 Yes Yes Yes
Design tests 3.13 Yes Yes Yes
N/A = Not applicable

A3. Enclosure Requirements must withstand the applicable paint qualifica-


tion test.
A3.1 Enclosures shall be of metal suitably sup-
ported, constructed and assembled so that the A3.3 The thickness of a sheet-metal enclosure
enclosure will have the strength and rigidity shall not be less than that indicated in Table
necessary to meet the requirements of this stan- A2. If metals other than steel are used, the thick-
dard. ness shall be such that equivalent strength and
deflection are provided.
A3.2 Unless the enclosure is of a material that
will resist corrosion, both inside and outside sur- A3.4 A supporting structure shall be formed of
faces shall be finished in accordance with ANSI/ angles, channels, folded rigid sections of sheet
IEEE C37.20.2-1987,6.1.5.2. The ME1 switchgear metal, or the equivalent, rigidly fastened to-

Table A2
Minimum Thickness of Sheet Metal for Enclosures Carbon Steel or Stainless Steel
With Supporting Frame or Equivalent Minimum Thickness
Without Supporting Frame* Reinforcing' (MSG)
Maximum Width? Maximum Length$ Maximum Width? Maximum Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) Uncoated
33.0 Not limited 51.0 (1295) Not limited 14 MSG
38.0 47.0 (1194) 54.0 (1372) 66.0 (1676) 14 MSG
42.0 Not limited 64.0 (1626) Not limited 13 MSG
47.0 59.0 (1499) 68.0 (1727) 84.0 (2134) 13 MSG
52.0 Not limited 80.0 (2032) Not limited 12 MSG
60.0 74.0 (1880) 84.0 (2134) 103.0 (2616) 12 MSG
63.0 Not limited 97.0 (2464) Not limited 11 MSG
73.0 90.0 (2286) 103.0 (2616) 127.0 (3226) 11 MSG
See 5.2.7.1.
The width is the smaller dimension of a rectangular sheet metal piece that is part of an enclosure. Adjacent surfaces of
a n enclosure may have supports in common and be made from a single sheet.
$ For panels that are not supported along one side (for example, side panels of boxes) the length of the unsupported side
shall be limited to the dimensions specified.

42

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

gether and having essentially the same outside cover more than 48 in (1.22m) long on the hinged
dimensions as the enclosure surfaces. side shall have at least a two-point latch, or have
at least two captive fasteners.
A3.5 With reference to A3.4 and Table A2, a The opening handles for doors on equipment
construction is not considered to have a sup- for Category A shall be lockable. Captive fas-
porting frame if it is: teners are permitted on Category B equipment.
(1) A single sheet with single formed flanges Exposed hinge pins shall be nonremovable on
(formed edges) doors of Category A or, as an alternative, the
(2) A single sheet that is die formed (corru- door shall be removable in the closed position.
gated or ribbed)
(3) An enclosure surface loosely attached to a A3.8 Enclosure and Ventilation Openings
frame that is with spring clips A3.8.1 Enclosure Openings. When the en-
closure is completely and properly installed,
openings in the enclosure, other than ventilation
A3.6 Equivalent Construction
openings, shall prevent the entrance of a rod
A3.6.1 The unsupported area of an enclosure
having a diameter of 0.125 in (0.32 cm), except
may be greater than shown in Table A2 if the
that if the distance between the opening and the
enclosure is reinforced so that it meets the re-
nearest not fully insulated live part is greater
quirements of A3.6.2 and A3.6.3.
than indicated in Table A3 the opening may
A3.6.2 Deflection Test. The following test is
permit the entry of a rod having a diameter
to be applied to the front, end, side, and rear
greater than 0.125 in (0.32 cm), but not greater
walls of each enclosure.
than 0.500 in (1.27 cm).
The inward deflection when a force of 100 lbf
A barrier or equivalent shall be located so that
(444.8 N) is applied perpendicular to the surface
it intercepts all live parts from line-of-sight
of any point on the enclosure through a rod hav-
through the opening protected.
ing a in by '/2 in (12.7 mm by 12.7 mm) ft2face
will not impair the dielectric criteria of 4.2.1 or
affect mechanical performance. For the test, the Table A3
enclosure may be laid on its back on a smooth, Clearance to Ventilation ODenines
solid, horizontal surface with the door closed and Clearance
the front panel or cover secured as intended.
Rated Maximum Voltage (in)
~- (mm)
The test force shall be applied at various points
on the enclosure likely to cause deflection. The 4.76
8.25
same sample may be used for more than one test 15.0
provided there is no permanent deflection due 38.0
to a previous test.
A3.6.3 Torsion Test. With each enclosure in
a vertical position, the base is to be secured to A3.8.2 Ventilation Openings. Ventilation
a rigid surface. The top corners are then to be openings shall prevent the entrance of a rod
twisted around the vertical axis of the enclosure having a diameter of 0.500 in (1.27 cm), except
by application of 200 lbf (889.6 N) force to the that if the distance from the opening and the
corner that results in the greatest torsional de- nearest not fully insulated live part is greater
flection. With this torsional force applied the than indicated in Table A3 the opening may
dielectric capability shall not be impaired, nor permit entry of a rod having a diameter greater
shall mechanical performance be adversely than 0.500 in (1.27 cm) but not greater than
affected. 0.750 in (1.9 cm).
A barrier or equivalent shall be located so that
A3.7 Access Doors and Covers. A part of the it intercepts all live parts from line-of-sight
enclosure such as a door, cover, or tank shall be through the opening protected.
provided with a means (such as latches, locks, EXCEPTION A larger opening above the upper edge of the
interlocks, or captive fasteners) for firmly se- enclosure, but under the overhang of the top, is acceptable,
curing it in place. Such fasteners shall be located if by means of its size,baffling, etc, it will prevent a straight
rod 0.500 in (1.27 cm) in diameter from approaching any
or used in multiple so as to hold the door or uninsulated live parts inside the enclosure by a distance not
cover closed over its entire length. A hinged less than indicated by Table A3.

43

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI / IEEE
(37.20.2-1987 IEEE STANDARD FOR METAL-CLAD AND

The diameter of the wires of a screen shall If the viewing pane has an area less than 16 in2
not be less than 0.51 in (1.30mm) if the screen (0.010m2), the force shall be evenly distributed
openings are in2 (322 mm2) or less in area, over the entire viewing area. The 100 lbf
and shall not be less than 0.081 in (2.06mm) for (444.8N) force shall be sustained for a period of
larger screen openings. 1 min.
Perforated sheet steel and sheet steel em- (3)The viewing pane shall be subjected to a n
ployed for expanded-metal mesh shall not be less impact of 2.5 ft-lbf (3.4J) using a steel ball
than 0.042in (1.07mm) thick for mesh openings weighing approximately 1.18 lb (0.535kg) and
or perforated '/z in2 (322 mm2) or less in area, approximately 2 in (50 mm) in diameter.
and shall not be less than 0.080in (2.3mm) thick (4)Separate samples may be used for each of
for larger openings. the tests described in (11, (2),and (3).
A ventilating opening in the top of the enclo- (5) If a viewing pane is intended to be exposed
sure shall prevent the entry of falling dirt. to insulating oil in a tank or compartment it
A3.8.3 Rod Entry Tests. These tests shall be shall be of a material that is resistant to the
made by attempting to insert the end portion of corrosive effects of the insulating oil.
straight rods of diameters specified in A3.8.1and (6) Category A equipment shall have lockable
A3.8.2 into the equivalent cavities of the enclo- covers over viewing panes if viewing panes are
sure. furnished.
A3.8.4 Evaluation. The enclosure is consid-
A3.12 Accessories. Drain valves, gauges, etc
ered to have met the requirement of these tests
shall have a lockable cover on enclosures des-
if the rod either has not entered the enclosure
ignated as Category A.
or is restricted by a barrier from intrusion into
the enclosure interior. A3.13 Outdoor Enclosure Requirements
A3.13.1 General. These enclosures are in-
A3.9 Operating Handle Protection. Device- tended for outdoor use primarily to provide a
operating handles on the external surface of degree of protection against rain and sleet. They
metal-clad switchgear enclosures shall be lock- shall meet rain test and paint qualification
able or provided with lockable covers for Cate- design tests.
gory A equipment. Hinges and other attachments shall be resist-
ant to corrosion. Metals shall be used in com-
A3.10 Operating Handles. If the mechanism binations that result in galvanic action that
of a switching device is such that operation of a adversely affects any part of the device.
remote or automatic tripping device will result If a n outdoor enclosure has any opening for
in sudden movement of a n operating handle, the passage of a wire or bus bar to a switchboard
motion of the handle shall be restricted or the section or to a wireway, auxiliary gutter or bus-
handle shall be guarded to prevent injury to way, a suitable gasket or other means shall be
persons in the vicinity of the handle. provided that will prevent the entrance of water
at such opening. If the opening is for attachment
A3.11 Viewing Panes. A transparent material of a busway, the outdoor enclosure and the bus-
covering a n observation opening and forming a way are to be investigated together to determine
part of the enclosure shall be reliably secured that water does not enter along the bus bars.
in such a manner that it cannot be readily dis- A3.13.2 Test Requirements. Outdoor enclo-
placed in service, and shall meet the following sures shall be tested and evaluated by
requirements: (1)Rain test per ANSI/IEEE C37.20.2-1987,
(1)Viewing panes shall not shatter, crack, or 5.2.10.
become dislodged when both sides of the viewing (2)Paint qualification per ANSI / IEEE
panes in turn are subjected to the tests described C37.20.2-1987, 5.2.8.
below. A3.13.3 Gasketing. An outdoor construction
(2)A force of 100 lbf (444.8N) shall be exerted requiring a gasketed joint shall meet the follow-
perpendicular to the surface in which the view- ing requirements:
ing pane is mounted. This force shall be evenly (1)A gasket of rubber or neoprene, or a com-
distributed over an area of 16 in2 (0.010 m2) (as position thereof, is to be exposed for 96 h to
nearly square as possible and as near the geo- oxygen at a pressure of 300 lbf / in2(2068.0kPa)
metric center of the viewing pane as possible). and a temperature of 70 "C. The gasket is con-

44

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
ANSI/ IEEE
STATION-TYPE CUBICLE SWITCHGEAR C37.20.2-1987

sidered adequately resistant to aging if there is A3.14 Exposed Live Parts. ME1 switchgear
no visible evidence of deterioration such as soft- shall have no exposed live conductors (such as
ening, hardening, or cracking after flexing. entrance bushing studs, terminal connections,
(2) A gasket of thermoplastic material, or a or bus bars) unless it is designated as a Category
composition thereof, may be accepted after con- C equipment.
sideration of the effects of heat aging, distortion
under conditions of use, and the means of se- A3.15 External Marking. An assembly shall
curing the gasket to the cover or enclosure. be marked with its exposure category.

45

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.
c37
Complete 1987 Edition

The documents in the C37 series include definitions, applications guides, test methods and proce-
dures, requirements, and specifications for circuit breakers, switchgear, fuses, relays, and substations.

Purchased separately, the standards in this book of more than two thousand pages would cost
nearly $550. At $75 this is probably the most remarkable standards bargain you can ever expect to
encounter.

This collection includes 62 standards, 15 supplements and 17 draft documents. Users of C37 will
experience a degree of convenience in utilizing this valuable collection that will save weeks, possibly
months, of waiting time each and every time it is consulted.

Draft documents have been included in the format in which they are currently under consideration.
They are unedited and may contain errors in spelling and inaccuracies regarding the other documents they
reference. Because these draft documents are still under review and subject to change prior to publication,
both the draft and the current ANSI-approved standards are included in this collection. Users should be
cautioned that both editorial and substantive changes may occur in the draft documents prior to final
approval and publication.

Available from
American National Standards Institute, 1430 Broadway, New York, New York 10018
Wiley-Interscience, A Division of John Wiley and Sons, Inc. 605 Third Avenue, New York,
New York 10158
Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, P.O. Box 1331,
Piscataway, New Jersey 08855-1331

Authorized licensed use limited to: Universidad de Concepcion. Downloaded on September 11,2012 at 12:19:11 UTC from IEEE Xplore. Restrictions apply.

You might also like