You are on page 1of 25

-

IEEE Guide for the


Interconnection of User-Owned
Substations to Electric Utilities

Energy and Power


Sponsored by the
Substations Committee of the
IEEE Power Engineering Society

Publishedby the Institute of Electrical and Electronics Engineers, Inc., 345East 47th Street, New York, NY lWlZ USA.

July 17, 1990 SH13409

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE Guide for the Interconnectionof
User-Owned Substations to Electric Utilities

Sponsor
substationscommittee
ofthe
lEEE Power Engineemg Society

Approved May 31, 1990


TEn4:StandardsBoard

Abstract: IEEE Std 1109-1990,ZEEE Guide for the Interconnection of User-Owned Substations to
Electric Utilities, provides a checklist and selected guidance, for persons not normally practicing
in this specialized field, of major technical design areas that should be considered when intercon-
necting user-owned and utility-owned facilities at substations. Only medium- and high-voltage
purchased-power interconnections are addressed. This guide does not discuss the considerable
implications of interactive power systems design and operation, nor does it present criteria or
directions for the design of substations.

Keywords: high-voltage purchased-power interconnections, interconnections, medium-voltage


purchased-power interconnections, non-utility generation, substations, user-owned
and utility-owned facilities at substations

ISBN 1-55937441-6

Copyright 0 1990 by

The Institute of Electrical and Electronics Engineers, Inc.


345 East 47th Street, New York, NY 10017-2394,USA
No part of this publication may be reproduced in any form,
in an electronic retrieval system or otherwise,
without the prior written permission of the publisher.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE Standards documents are developed within the Technical
Committees of the IEEE Societies and the Standards Coordinating
Committees of the IEEE Standards Board. Members of the committees
serve voluntarily and without compensation. They are not necessar-
ily members of the Institute. The standards developed within IEEE
represent a consensus of the broad expertise on the subject within the
Institute as well as those activities outside of IEEE that have
expressed an interest in participating in the development of the
standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to produce,
test, measure, purchase, market, or provide other goods and services
related to the sco,pe of the IEEE Standard. Furthermore, the viewpoint
expressed at the time a standard is approved and issued is subject to
change brought about through developments in the state of the art and
comments received from users of the standard. Every IEEE Standard
is subjected to review a t least every five years for revision or reafir-
mation. w e n a document is more than five years old and has not
been reaffirmed, it is reasonable t o conclude that its contents, al-
though still of some value, do not wholly reflect the present state of the
art. Users are cautioned to check to determine that they have the latest
edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE.
Suggestions for changes in documents should be in the form of a pro-
posed change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the
meaning of portions of standards as they relate t o specific applica-
tions. When the need for interpretations is brought to the attention of
IEEE, the Institute will initiate action to prepare appropriate re-
sponses. Since IEEE Standards represent a consensus of all con-
cerned interests, it is important to ensure that any interpretation has
also received the concurrence of a balance of interests. For this reason
IEEE and the members of its technical committees are not able to pro-
vide an instant response t o interpretation requests except in those
cases where the matter has previously received formal consideration.
Comments on standards and requests for interpretations should be
addressed to:
Secretary, IEEE Standards Board
445 Hoes Lane
P.O. Box 1331
Piscataway, NJ 08855-1331
USA

IEEE Standards documents are adopted by the Institute of Electrical


and Electronics Engineers without regard to whether their adoption
may involve patents on articles, materials, or processes. Such adop-
tion does not assume any liability to any patent owner, nor does it
assume any obligation whatever to parties adopting the standards
documents.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
(This Foreword is not a part of IEEE Std 1109-1990,IEEE Guide for the Interconnection of User-Owned Substations to
Electric Utilities.)

This guide provides a "checklist" and selected guidance, for persons not normally practicing in
this specialized field, on topics that should be considered when developing the interconnection of
user-owned and electric-utility-owned electric power facilities, particularly substations. This
guide is concerned with large substations for purchased-power-only service and also with substa-
tions of all sizes associated with the interconnection of user-owned generating (interactive power,
dispersed power, cogeneration, or small-power-producer) facilities.
This guide is concerned with generation (interactive electrical system) interconnections of all
magnitudes to the degree that the substation facilities are affected. However, it is not within the
scope of this guide to discuss in detail the considerable implications of interactive power systems
design and operations, since these are covered in other documents.
A listing of code and standard agencies relevant t o substation design is included in the
Appendix.
This guide was prepared by Working Group D-6 of the Distribution Substations Subcommittee of
the IEEE Power Engineering Society Substations Committee. The following persons were mem-
beis of Working Group D-6:

Theodore J.Kolenda, Chairman


Mark Carpenter David L. Harris Raymond J. Perina
David L. Garrett Irving H. Koponen Donald R. Schafer
Philip R. Nannery

Acknowledgment: Angela T. Taylor

The following persons were on the balloting committee that approved this document for submis-
sion to the IEEE Standards Board:
W. Ackerman N. G. Hingorani S . P. Meliopoulis
B. Y. Afshar J. E. Holladay P. R. Nannery
S . J. h o t M. L. Holm J. O'Hara
N. Barbeito D.C. Johnson J. T. Orrell
J. D. Betz G. Karady J. Oswald
K. L. Black J. J. Keane J. Paolozzi
C. J. Blattner R. P. Keil S . G. Patel
W. R. Block F. F. Kluge R. J. Perina
R. J. Bower D. F. Koenig T. A. Pinkham, 111
S . D. Brown T. J. Kolenda J. Quinata
D. E.Buettner A. E.Kollar D. G. Rishworth
J. B. Cannon I. R. Koponen B. D. Russell
s.club L. W. Kurtz, Jr. J. Sabath
E.F. Counsel K. C. Labbe D. R. Schafer
P. Danfors D. N. Laird R. C. St. Clair
F. A. Denbrock L. M. Laskowski J. G. Sverak
W. K. Dick A. F. Leibold W. K. Switzer
C. C. Diemond K. E. Lewis E. R. Taylor
P. R. Dolan C. T. Lindenberg H. M. Tucker
L. N.Ferguson P. H. Lips L. F. Volf, Jr.
D. L. Garrett W. F. Long R. J. Wehling
H. R. Gilden R. Matulic W. M. Werner
J. Grzan T. S.McLenahan R. W. Wray
A. Habin R. M. Youngs

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
When the IEEE Standards Board approved this standard on May 31, 1990, it had the following
membership:

Marc0 W.Migliaro, Chairman James M. Daly, Vice Chairman


Andrew G. Salem, Secretary
Dennis Bodson Kenneth D. Hendrk Lawrence V. McCall
Paul L. Bomll John W. Horch L. Bruce McClung
Fletcher J. Buckley Joseph L. KoepfingeP Donald T. Michael*
Allen L. Clapp Irving Kolodny Stig Nilsson
Stephen R. Dillon Michael A. Lawler Roy T. Oishi
Donald C. Fleckenstein Donald J. Loughry Gary S. Robinson
Jay ForsteP John E.May, Jr. Terrance R. Whittemore
Thomas L. Hannan Donald W. Zipse

*Member Emeritus

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
SECTION PAGE

1. Introduction and Scope ................................................................................ 6


2 . Definitions and References .......................................................................... 6
3. System Interconnection Considerations ............................................................ 8
4 . Substation Configuration ............................................................................ 10
5 . Interactive Power (User-Owned Generation) Considerations .................................. 15
6 . Substation Facilities Design ....................................................................... 16
7. Protective R e l a y i n g .................................................................................. 18
8. Metering a n d Instrumentation .................................................................... 19
9. Control and Communications ....................................................................... 20
10. Maintenance a n d Operation ....................................................................... 21
11. Administrative Items ................................................................................ 21
12. Contractual Documents .............................................................................. 22

Appendix Related Code and Standard Agencies ...................................................... 23

FIGURES

Fig 1 Radial Service (or Dedicated Service) ........................................................... 9


Fig 2 Loop Service ........................................................................................ 10
Fig 3 Radial A r r a n g e m e n t ............................................................................. 11
Fig 4 Loop Service Arrangement ...................................................................... 11
Fig 5 H-Tie Arrangement .............................................................................. 11
Fig 6 Ring Bus Arrangement ........................................................................... 12
Fig 7 Main and Transfer Bus Arrangement ......................................................... 12
Fig 8 Breaker a n d One-Half A r r a n g e m e n t ........................................................ 13
Fig 9 Double.Breaker, Double-Bus Arrangement .................................................... 14

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE Guide for the Interconnection of
User-Owned Substations to Electric Utilities

ciated with connecting to and interacting with


1.Introduction and Scope a large electric system by means of a dedi-
cated substation facility, such a s is addressed
This guide presents a "checklist" of major by this document. Therefore, this guide does
technical design areas that should be consid- address in general the interconnection of in-
ered when interconnecting user-owned and teractive (dispersed generation, cogeneration,
utility-owned facilities at substations. and small-power producer) facilities of all
Guidance is presented in selected areas of sizes with electric utilities, to the degree that
particular importance. the interconnection substation design is af-
This guide principally provides guidance fected. However, the subject of interactive
for the interconnection of user-owned substa- power systems is addressed in greater detail
tions. In this regard only medium- and high- in the publications of other agencies or
voltage purchased-power interconnections are committees.
addressed, since low-voltage (and some It is not the intent of this guide t o present de-
medium-voltage) interconnections for typical tailed design criteria or directions. And it is
residential, commercial, and small indus- beyond the scope of this document t o discuss
trial energy purchase are adequately covered commercial or contractual issues, which are
by existing electric utility practices and covered by other existing industry codes, stan-
standards. dards, and practices. Also, detailed discus-
Historically, most utilities with a signifi- sions of the design and operation of interactive
cant industrial base load have established power systems (cogeneration, dispersed power,
technical guidelines for large purchasers of small power producers; and user-owned gen-
electric energy when the user's demand man- eration) are not included, since it would be be-
dates the construction of a medium- or high- yond the scope of this document and since these
voltage substation having a capacity greater topics are covered by other existing or forth-
than 500 kVA and connected to a three-phase coming documents.
power interconnection with a voltage greater A listing of related code and standard agen-
than 15 kV. These substation and interconnec- cies is included as an appendix t o aid the users
tion facilities were usually for the user pur- of this guide in finding other codes and stan-
chase of electric power only. The presence of a dards applicable to the design, operation, and
user's own in-house generation facility was equipment selection of proposed interconnec-
uncommon enough to be handled on a case-by- tion substations.
case basis.
The advent of the Public Utilities Regulatory
Policies Act (PURPA) of 1978, as well as other 2. Definitions and References
public laws, has precipitated the development
of numerous new electric power generating
facilities that are necessarily interconnected 2.1 Definitions
to established electric utilities. It is common
for these "dispersed" facilities to be fostered by cogeneration. The generation of electric en-
entrepreneurial organizations that may or ergy and commercial or industrial quality
may not be cognizant of the complexities asso- heat or steam from a single facility.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
EEE
std1109-1990

dispersed power. An electric power generation [21 ANSI C84.1-1989, Voltage Ratings for
source (or sources) not directly under estab- Electric Power Systems and Equipment
lished electric utility ownership and control. (60 Hz).

electrical system. The existing utility net- 131 IEEE Std C37.1-1987, IEEE Standard
work consisting of interconnected and syn- Definition, Specification, and Analysis of
chronized generation, transmission, and Systems Systems Used for Supervisory
distribution facilities. Control, Data Acquisition, and Automatic
Control (ANSI).2
generation. The production or storage, or both,
of electric energy with the intent of enabling [41 IEEE Std C37.2-1987, IEEE Standard
practical use of commercial sale of the avail- Electrical Power System Device Function
able energy. This includes photovoltaic, wind- Numbers (ANSI).
farm, hydro, etc., as well as normal
commercial and industrial thermal sources. 151 IEEE Std C37.122-1983, IEEE Standard Gas-
Insulated Substations (ANSI).
interactive electrical systems. Two or more
interconnected and compatible electrical sys- [SI IEEE Std 80-1986, IEEE Guide for Safety in
tems with appropriate protection and.measur- AC Substation Grounding (ANSI).
ing provisions a t their interconnection
pointb). [71 IEEE Std 81-1983, IEEE Guide for
Measuring Earth Resistivity, Ground Impe-
interconnection. The physical plant and dance, and Earth Surface Potentials of a
equipment required t o facilitate the transfer of Ground System (ANSI).
electric energy between two or more entities. It
can consist of a substation and an associated [81 IEEE Std 525-1987, IEEE Guide for the
transmission line and communications fa- Design and Installation of Cable Systems in
cilities or only a simple electric power feeder. Substations (ANSI).

small-power producer. A non-utility genera- [91 IEEE Std 605-1987, IEEE Guide for Design of
tion source that is a qualifying small-power Substation Rigid-Bus Structures (ANSI).
production facility under PURPA and the Fed-
eral Energy Regulatory Commission (FERC). [lo] IEEE Std 979-1984, IEEE Guide for
Substation Fire Protection (ANSI).
user (or customer). The independent party that
may be a purchaser of utility electric power or Cl11 IEEE Std 980-1987, IEEE Guide for
a producer of electric energy for sale t o an Containment and Control of Oil Spills in
electric utility or both. Substations (ANSI).

[121 IEEE P998 (Draft), Guide for Direct Light-


2.2 References. This guide shall be used in ing Stroke Shielding of substation^.^
conjunction with the following publications.
When the following standards are superseded 1131 IEEE Std 1001-1988, IEEE Guide for
by an approved revision, the revision shall Interfacing Dispersed Storage and Generation
apply. Facilities With Electric Utility Systems
(ANSI).
E11 ANSI C2-1990, National Electrical Safety
Code.'

%EE publications are available from the Institute of


Electrical and Electronics Engineers, Service Center, 445
Hoes Lane, Rscataway, NJ 08856-1331,USA.
'ANSI publications are available from the Sales *his draft document is currently in production; when
Department, American National Standards Institute, 1430 it is completed, approved, and published, it will become a
Broadway, New York,NY 10018,USA. part of the references of this guide.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
std1109-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED
[141 IEEE Std 1119-1988,IEEE Guide for Fence 60.030 Hz. For interconnected utility opera-
Safety Clearances in Electric-Supply Stations tion, frequency is usually discussed, mea-
(ANSI). sured, and displayed with a resolution of
0.001 Hz. In other parts of the world, other
E51 IEEE P1127 (Draft), Guide for the Design, nominal operating frequencies (for example,
Construction, and Operation of Safe and 50 Hz) and other ranges of instantaneous
Reliable Substations for Environmental operating frequency may be used.
Acceptance .
3.2 Phase Rotation and Phase Position. The
[l6] NFPA 70-1990, National Electrical Code phase designation (A, B, C; 1, 2, 3;etc.) should
(ANSI).5 be consistent and the phase sequence should be
coordinated, particularly for user-owned gen-
erating facilities, as discussed elsewhere. The
3. System Interconnection considerations phase position must be known if the user facil-
ity has interconnections t o different utility
Whether a proposed interconnection is for voltage levels or different utility locations that
an interactive (i.e., including user-owned may have a relative phase shift by virtue of
generation) or purchased-energy-only facil- geography or differing system transformer
ity, the following significant design factors configurations. Accommodating different
should be considered for the high-voltage phase positions is usually accomplished with
electric power interface. Care should be taken appropriate transformer connections or by
to ensure that each party of the interconnection maintaining isolation of out-of-phase user fa-
uses a comparable basis for ratings (i.e., tem- cilities, either administratively or by perma-
perature rise) and the same formulas for cal- nent lack of interconnection.
culations (e.g., transformer loss-of-life or
no-loss-of-life for overloading) to avoid waste- 3.3 Fault Interrupting and Momentary
ful overbuilding on the one hand or potentially Ratings. Power generation and distribution
destructive overloading on the other. equipment directly connected t o an electric
utility can be subjected to fault levels that are
3.1 Voltage, Voltage Range, Frequency, and largely a product of the utility system’s char-
Frequency Range. Interconnection facility acteristics a n d t h e interconnection
ratings should be selected to operate satisfacto- impedance. Therefore, the user-owned facili-
rily with the utility’s nominal and normal op- ties must possess sufficient fault interrupting
erating voltage and frequency. Further, the and momentary withstand ratings to meet the
design of the interconnection facility should maximum expected utility system require-
consider the anticipated minimum and max- ments, with appropriate margin for future
imum voltage ranges below and above nomi- system growth. Large user-owned generators
nal, respectively. Typical permissible voltage and synchronous motors can also be another
ranges are up to f5% of nominal voltage and source of fault current contributions to a utility
can be higher. I t is particularly important to system. Conversely, for planned user-owned
determine the impact of starting large motors generation systems, it is necessary t o confirm
and other major equipment under low-voltage the utility system’s ability to accommodate the
conditions. Standard nominal system volt- additional fault interrupting and momentary
ages and voltage ranges can be found in ANSI withstand requirements.
C84.1-1987 [216. The nominal operating fre-
quency in the United States is 60 Hz. Under
normal conditions, the instantaneous oper- 3.4 Continuous Ratings. The continuous rat-
ating frequency may range from 59.970 to ings of electrical power apparatus associated
with the interconnection should be sufficient to
4See footnote 3. accommodate the user’s maximum load (or
6NFPA publications are available from Publications generation) as well as contributions resulting
Sales, National Fire Protection Association, Battery- from system exchanges, such as power from
march Park, Quincy, MA 02269, USA.
6The numbers in brackets correspond t o those of the the system being transferred
references in 2.2. (“wheeled”) through the user’s facilities, as

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
lEEE
SUBSTATIONS TO ELECTRIC UTILITIES std 1109-1990

TO UTILITY

I ' IN OR OUT (USER FLOW ONLY)

I f INTERCONNECTDN
FACILITY

Fig 1
Radial Service (OrDedicated Service)

NOTE: The user-utility interface points indicated on the figures are shown only to compare alternate substations configu-
rations and do not necessarily indicate the specific interface point(s) that may be negotiated between a user and the local
utility.
can be the case if there is more than one point Both radial and loop service substations can
of interconnection with the utility. The deter- be arranged in numerous (and similar) con-
mination of whether or not there will be system figurations, as is discussed elsewhere in this
electric-energy exchanges depends on the type guide.
of service and the configuration of the inter-
connection facility (i.e., substation), as is dis-
cussed in other sections. If a system energy 3.6 Load and Power-Factor Considerations.
exchange can be expected to be superimposed The magnitude, integrity, duration (load fac-
on the specific user facility loads (or genera- tor), and time-of-day availability of the user's
tion), the utility is the source of information load (or generation) will normally be of great
regarding the magnitude and conditions of commercial interest to both parties. In addi-
this occurrence. tion to the impact that the magnitude of real
power that is to be accommodated can have on
3.5 Types of Service. The overall interconnec- ratings and configuration of facilities, the
tion of a user-owned facility can be generally demand for (or generation of) reactive power
classified a s either radial (or dedicated) o r may also warrant equivalent attention. Any
loop service. large, purchased-power user may be expected
Radial service consists of one or more lines to maintain the overall facility power factor at
configured in a manner such that only the or above a level agreed between the local utility
user's load (or generation) constitutes the total and the user.
loading of the interconnection line or lines. In A penalty charge may be incurred by the
effect, it is a branch of the utility system, with user for even a momentary deviation from the
no power flow other than the user's load or specified power factor. It is not uncommon for
generation passing through the interconnec- large industrial power users to include shunt
tion facility (see Fig 1). capacitors or synchronous motors or both in
Loop service, however, consists of two (or their plants to offset the reactive power de-
more) lines configured in a manner that per- mands resulting from the induction motor
mits utility system exchange power t o flow load of the facility. Where capacitors are pre-
through the interconnection facility in addi- sent, however, consideration should be given
tion to the user's load (or generation) contribu- to the potential problems of electrical system
tions (see Fig 2). self-excitation of induction machines, reso-

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
std1109-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

TO UTILITY

A A
SYSTEM
I

Fig 2
IAupservioe

nance, and waveform distortions in rectify- generation, and interrupting fault current.
ing equipment. The use of bypass switches, particularly on
Conversely, user-owned generating facili- main service breakers, is normally discour-
ties may well be expected to produce reactive aged because of the loss of fault-protection co-
power inherent within equipment capabilities ordination during the period the bypass switch
and make it available to the system, as is dis- is in service. (Using a transfer breaker and
cussed further in 5.5. This is a capability that transfer bus can avoid this concern).
cannot be achieved with induction generators. The simplest breaker arrangement is a sin-
gle-series breaker in a simple radial ar-
rangement (see Fig 3). However, any scheme
4. substationConfiguration requiring more than one connection element
each (i.e., line or load) for the utility or cus-
Normally, some type of substation facility tomer, or requiring loop service, will necessi-
will be necessary to provide for the termina- tate a more complex breaker arrangement.
tion of the utility interconnection line(s). This Several of the most common alternatives are:
substation usually contains the necessary loop service (Fig 41, ""'-tie (Fig 5 ) , ring bus
switching and protective devices as needed to (Fig 61,main and transfer bus (Fig 7), breaker
isolate and mitigate the effects of faults, t o and one half (Fig 81, and double breaker, dou-
synchronize system elements, and to permit ble bus (Fig 9).
routine maintenance and switching. The The final selection of one particular breaker
substation can also be the location for any re- arrangement (or a hybrid arrangement) de-
quired power transformers to match voltages. pends on an engineering analysis of reliabil-
Aesthetics should be considered where local ity and cost, both of which are functions of the
conditions require special attention (see IEEE number of breakers per line and the number of
P1127 [151). load or generation source(s). The arrange-
ment should be acceptable to both the user and
4.1 Breaker Arrangement. Power circuit the utility.
breakers and their associated bypass and dis- Utilities may recommend a scheme that has
connecting switches, where present, usually been demonstrated by past performance to be
constitute the most significant active compo- appropriate for their service area. Figs 4,5, 6,
nents of a substation. Breakers are used for and 7 would include most typical user-owned
load switching, synchronizing, disconnecting installations. Fuses and circuit interrupters

10

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
SUBSTATIONS TO ELECTRIC UTILITIES std1109-1990

UTILITY
-----
CUSTOMER
-I-- UTILITY
----
CUSTOMER

4
Fig3 Fig4
Radial Arrangement LoopServiceArrangement

Fig5
%"-TieArrangement

11

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
std1109-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

CUSTOMER

Fig6
Ring Bus Arrangement

Fig 7
Main and Transfer Bus Arrangement

12

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
SUBSTATIONS TO ELECTRIC UTILITIES Stdllce-1990

UTILITY

CUSTOMER

Fig8
Breaker and One-HalfArrangement

can sometimes be used in lieu of circuit break- wye-grounded; and low-voltage systems are
ers for protection and switching of circuits. also solidly wye-grounded. There are excep-
These devices are usually used only for low- tions to all of these.
voltage o r lower-medium-voltage (i.e., 15 kV When choosing transformer connections,
voltage class or less) applications. Further, the phase shifts should be considered to ensure
user-owned generation may include its own proper synchronization of any interactive
dedicated generator breaker. Relaying of the power systems. Transformer design selection
generator breaker should be coordinated with will require analysis of the utility system and
the substation protective relaying. local generator characteristics (see Section 5).

4.2 Power Transformer Connections. Both 4.3 Switch and Bus Construction. Substation
user and utility should agree on the connection switch and bus facilities can be open-air insu-
scheme for power and metering (instrument) lated, or metal-enclosed SF6 (sulfur hexafluo-
transformers (wye-delta, delta-wye, wye-wye, ride) gas-insulated, or another type of
zig-zig, autotransformer, etc.), a s well a s construction. The conventional outdoor air-
transformer capacity and voltage ratings. insulated substation normally uses alu-
The selection (or absence) of wye-connected minum cable or tubing for bus conductors be-
system grounding sources can have signifi- cause of economic advantages. (See IEEE Std
cant implications on reliability, protective 605-1987 [91J Copper is sometimes encountered
relay selection, metering, fault levels, over- in older stations or where corrosive environ-
voltage conditions, and equipment cost. mental conditions preclude the use of alu-
In typical present-day practice, high-voltage minum. Energized parts are supported by
utility connections are solidly wye-grounded; porcelain, glass, polymer, or epoxy insulators
plant medium-voltage systems are resistance and are maintained at safe vertical and hori-

13

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
std1109-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

Fig9
Double-Breaker,Double-BusArrangement

zontal clearances, which are dictated by occasionally for voltages greater than 15 kV,
industry or utility standards and code re- up to 38 kV.
quirements, such as ANSI C2-1990 111 and Particular attention should be paid to access
IEEE SM 1119-19881141.Compact sF6 gas-insu- and removal of equipment, particularly trans-
lated substations (GIS) are generally installed formers. Also, transformers may require
where space is at a premium or contamination consideration of sound attenuation, oil-fire
is a factor. All energized parts are concentri- prevention, and oil-spill mitigation mea-
cally placed in metallic enclosures that are at sures, particularly in residential or wetland
ground potential. The spaces between the live areas. IEEE Std 979-1984[lo1 and IEEE S M
parts and the enclosures are filled with SF6 980-1987Clll provide further guidance on fire
gas at an appropriate pressure to achieve the prevention a n d oil-spill containment,
desired dielectric strength. See IEEE Std respectively.
C37.122-1983 [51 for further information on
GIS. 4.4 Interconnecting Lines Location and
Supporting structures for electrical equip- Orientation. The location and orientation of
ment are most commonly constructed of gal- the substation facility should consider the di-
vanized steel. Other materials that can be used rection and ultimate destination of the over-
are aluminum, concrete pedestals, weathered head o r underground transmission lines
steel, metalized steel, painted steel, and wood. connecting t o either the utility or the user's
Metalclad switchgear is typically used for facilities.
medium-voltage outdoor distribution substa- Provision should be made for appropriate
tion facilities operating a t 15 kV o r less and right-of-way widths, avoidance of structures

14

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEX
SUBSTATIONS TO ELECTRIC UTILITIES std1109-1990

and other existing facilities, turning-tower generator is a unit-connected arrangement


positioning, and conductor-phase transposi- (i.e., normal auxiliary loads provided from
tions. The use of underground power cables is the generator bus), an additional power source
a technically feasible but usually more expen- is needed to supply the auxiliary loads when
sive alternative t o overhead lines, particu- the generator is off-line or not synchronized.
larly for voltages above 38 kV. Further, an appropriate transfer scheme
should be provided to permit the transfer of
4.5 Control Building. A substation usually in- auxiliary load from startup t o normal source
cludes a building or enclosed area t o provide a and vice versa.
clean, dry indoor environment for needed re- The phase relationship of these two sources
laying, metering, control, and communica- must be coordinated, especially if they origi-
tion equipment. nate at different voltage levels or if they in-
clude different voltage transformation
4.6 Future Expansion Consideration. sequences. Voltage regulation will be a con-
Provision should be included in any substa- sideration, since the generator(s1 could be sup-
tion for future expansion as needed t o accom- porting the system voltage during operation or
modate additional utility interconnections, the generator auxiliary loads could be acting
additional user interconnections or loads, and as a major load during the startup mode.
additional breaker or switching complexity.
5.3 Generator Grounding. The grounding of a
generator should be fully evaluated with re-
gard to its impact on the following:
5. Interactive Power (User-Owned
Generation) Considerations (1) The maximum fault-current level to
which the generator will be subjected
The presence of user-owned generating fa- (2) The presence of sufficient ground fault
cilities operating in parallel with a large current to permit detection and selective
electric utility entails operational complexi- isolation of the faulted generator without
ties that would not exist in the case of a pur- subjecting other generators to unneces-
chase-power-only user, as follows and as is sary additional ground fault current
further discussed in IEEE Std 1001-1988[131. (3) The grounding of the balance of the aux-
iliary power distribution system or util-
5.1 Synchronizing. A proper synchronizing ity system when the generator is
scheme consisting of necessary relays, indi- disconnected
cators, control facilities, and a properly rated
power circuit breaker should be provided for (2) is of particular importance when multi-
each generator to be connected to an interac- ple generators are connected to a common bus.
tive power system. The ideal grounding scheme for a larger gen-
The synchronizing breakeds) can be lo- erator provides for the generator neutral to be
cated in a user substation facility or in the grounded through a distribution transformer
power generating facility, depending on spe- with a secondary winding resistor. However,
cific site conditions, load current magnitude, this assumes that a wye-delta (or delta-wye)
electrical system configuration, and equip- step-up transformer is provided for each gen-
ment cost. The synchronizing breaker should erator power interconnection, which may not
be relatively close to the generator it serves, always be the case. For multiple generators
since there is a voltage drop limit for direct connected to a single bus, resistance ground-
(hard-wired) equipment control circuits. (See ing is typically used. Effective ground protec-
Section 9 for a discussion of control and com- tion of the faulted generator can be provided
munications options). with low resistance grounding. However, re-
sistance grounding usually subjects equip-
5.2 Startup/Auxiliary Power. Any generating ment to higher fault levels than distribution
facility should provide for its normal plant (or transformer grounding.
station) auxiliary power requirements. These
loads can be supplied from the user's own load 5.4 Generator Characteristics. While it is un-
buses or from the substation facility. If the derstood that the gross output capability of the

15

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
std11c8-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

generator(s) is probably the most important tion of the generator-capacitor network in the
rating of interest to the owner, as well as to the event of sectionalization a n d isolation
utility, the specific generator electrical and ("islanding") of the interactive systems. If ca-
dynamic characteristics will also be of equal pacitors are present, switching devices that are
importance to both parties and should not be transfer-tripped by the utility may be neces-
overlooked. sary. This particularly applies to induction
The generator owner will need t o obtain spe- generators. Any application of capacitors
cific generator electrical characteristics in should be done with a full understanding of
order to design the plant electrical distribution capacitor effects.
system. Furthermore, the utility will usually A fbndamental premise is that the utility is
require significant dynamic data as well, in responsible for providing reliable service in
order to ascertain the generator's overall im- accordance with applicable regulatory re-
pact on system fault levels and stability. The quirements that should not be compromised by
latter i s particularly true for a large syn- user-owned operations. Conversely, user-
chronous generator. owned generation should not be subject to ex-
Harmonic voltage generation between reac- traordinary requirements.
tive components within an operating system
can cause severe damage to equipment. The 5.6 Isolating Switch. The user and utility
design effort should address the matter as a should agree on the necessity of providing a
potential problem. manually operated isolation switch(es1 with a
Any generator connected to an operating visible break to isolate the generator(s) from
electrical system becomes, during its syn- the interconnection. Switch location, accessi-
chronous operation, functionally a part of that bility, and capability of being locked or tagged
system. open should also be established.

5.5 Reactive Capability. As a corollary to the


usual understanding that a large power user is 6.substationFacilitiesDesign
expected t o maintain the facility reactive
power demands (power factor) within certain The prudent design of a user-owned substa-
agreed limits, a utility may require each gen- tion should include the following significant
erator to be capable of providing reactive power areas for consideration in the design criteria.
t o the utility system in proportion to the unit
size and capability and within specified volt- 6.1 Grounding. A buried grounding grid of
age limits for both generatorb) and system. bare cable, possibly including electrodes
This is a point that should be established early, (ground rods), is necessary for personnel
since the reactive power contribution from a safety and to provide ground connecting points
facility, whether expressed as a gross power for equipment. Normally, the substation
factor at the generator, a net power factor at the grounding grid design should conform t o the
utility, or a desired voltage to be maintained at requirements of IEEE Std 80-1986 [SI. A
the utility bus, may ultimately be reflected in ground-resistance test should be required and
changes in the capability of the generator conducted in accordance with IEEE Std 81-1983
(rotor, stator, or excitation system) or in the [7]. The grounding design criteria should be
increased heating of these components. coordinated with adjacent utilities, plants, o r
Additional reactive capability does not en- other facilities to ensure that transfer poten-
tail any additional turbine (power) capability, tials will not present personnel hazards in
but is reflected in generator and excitation areas remote from an electrical event or will
system thermal capacity. not damage communications circuits between
If a generator (or generators) is not capable the user-owned facilities and any remote
of meeting some reactive power (var) re- facilities.
quirement, shunt capacitors or static var com- The effect of a generation facility or substa-
pensators o r both may be required t o tion grounding system on adjacent existing or
supplement the generator contribution. The 10- future cathodic protection systems (e.g.,
cation of shunt capacitors on the utility or user pipelines) needs careful study and, probably,
system should be reviewed to avoid self-excita- field testing.

16

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
SUBSTATIONS TO ELECTRIC UTILITIES std1109-1990

6.2 Insulation Levels (BILL For any given 6.6 Transmission (or Distribution) Line
electric power interconnection, the basic im- Termination. High-voltage transmission
pulse insulation level (BIL) (or switching in- lines or medium-voltage distribution lines,
sulation level [SILI for EHV voltage levels) whether overhead or underground cable, will
should be coordinated for power distribution usually constitute the most significant physi-
and transmission lines and equipment. cal interface between a user-owned substation
Industry references or the local utility are the and the electric utility. Because of this, partic-
appropriate sources for existing insulation ular attention is needed to coordinate the inter-
levels, which are frequently different for facing span between the last utility tower and
overhead line, insulated cable, and trans- the substation terminal structure for overhead
former insulation systems at the same voltage lines. For underground lines, the presence of
level in the same region. existing underground utilities in the substa-
tion vicinity should be identified, which may
6.3 Clearances and Access. Appropriate nor- impact a new underground cable location or
mal and minimal electrical clearances from rating. For both overhead and underground
energized parts above walkways, roads, and lines, orientation of the substation in relation
railroads and in other special circumstances to the utility and the user's lines should be ar-
are specified in ANSI C2-1990 [ll and IEEE Std ranged t o minimize line angles, turning tow-
1119-1988 1143, local utility requirements, and ers, crossings, etc., all of which will impact on
state a n d local codes and ordinances. the complexity and cost of the interconnection
Overhead high-voltage lines can require sig- transmission facilities.
nificant right-of-way area. The presence of
energized overhead conductors can affect 6.7 Switching Equipment. The final selection
some potential uses of property located under and arrangement of particular substation
or adjacent t o the conductors. The local utility switching devices is closely related to the sub-
should be consulted to provide access require- station arrangement, discussed in Section 4.
ments for maintenance, operation, and meter- For interactive interconnections, either
ing facilities. power circuit breakers o r circuit interrupters
are required for power circuit switching and
6.4 Lighting. Appropriate minimum lighting fault interruption. The choice between these
levels for various circumstances of indoor, switching devices will depend on required
outdoor, and roadway areas are given in fault interruption capability, clearing and re-
NFPA 70-1990 [161 and ANSI C2-1990 [ll, in closing requirements, etc. For purchase-
ANSI and IES standards, and in other indus- power-only interconnections, the switching
try sources. Emergency lighting should be equipment may be power circuit breakers, cir-
provided in attended areas, in accordance cuit interrupters, or fuses. The choice between
with local codes and regulations. these switching devices will depend on re-
quired fault interruption capability and on
6.5 Lightning (Surge) Protection. Lightning clearing and reclosing requirements. In ad-
(surge) protection for substation facilities dition, the application of fuses should address
should be designed for the isokeraunic level reduced reliability, increased outage time,
(thunderstorm days per year) for the particu- single-phasing, ferroresonance, etc.
lar site location. The local utility may be the Disconnect switches are capable of inter-
best source of information on local lightning rupting line charging currents for short lines
frequency, outage records, and application of and switching low-level transformer magne-
particular lightning protection methods tizing currents, particularly when arcing
(shield wires, masts, arrays, arresters, higher horns o r quick-break (high-speed) interrupt-
BIL levels, reclosing, etc.) to the local system. ing devices are added to the switch. However,
See IEEE P998 1121 for further background on they are normally used only to isolate power
direct stroke lightning protection. For high- switching apparatus, lines, and buses and are
voltage facilities, switching surges are an ad- not suitable for application as a principal
ditional design consideration. The need for switching device.
surge protection at generator, transformer, Any further discussion of the numerous va-
and cable terminals should be considered. rieties and applications of switching devices

17

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std1109-1990 IEEE GUIDE FOR "€E ~ R C O N N E C T I O N
OF USER-OWNED

mentioned above is beyond the scope of this Relay and other devices usually are desig-
guide. nated as outlined in IEEE Std C37.2-1987[41or
as specified by the local utility.
6.8 I n s t r u m e n t Transformers. In strum ent The following categories of protective relay-
transformers are devices that are needed to ing application are typical.
produce a low-voltage reference potential or
current source a s required for protective relay- 7.1 Line Protection. Line protection relays
ing, synchronizing, metering, control, and monitor the condition of a transmission line
indication functions. and initiate isolation of the line if a fault is
Potential sources can be oil-filled or dry- detected. Lightning is frequently the principal
type (epoxy or rubber insulated) wound voltage source of transmission and distribution line
transformers, capacitor voltage transformers faults. Trees, animals, and accidents are
(CVTs), coupling capacitor potential devices, other sources of faults.
(CCPDs) or bushing potential devices. Voltage
transformers are the most accurate sources of 7.2 Transformer Protection. Transformer
potential and are usually needed for revenue protection relays monitor the condition of a
metering. Bushing potential devices, trans- power transformer and initiate its isolation in
former or breaker mounted, are usually suit- the event abnormal conditions are detected
able only for indicating the presence of voltage that can indicate overloading o r an internal
and are inadequate for critical relaying or fault.
metering functions.
Current sources can be separately mounted 7.3 Bus Protection. Bus protection relays
oil-filled or dry-type (epoxy or rubber insu- monitor the integrity of a power bus to which
lated) current transformers or bushing cur- several lines, generators, etc. are connected.
rent transformers (BCTs). Again, separately Detection of a bus fault will initiate isolation
mounted current transformers are the most of the bus from all connected elements.
accurate and are usually needed for revenue
metering. Bushing current transformers, both 7.4 Synchronizing/Synchronism Check.
transformer- and breaker-mounted, are suit- Synchronizing and synchronism check
able for the majority of relaying, control, relays are necessary to verify the phase rela-
indication, a n d nonrevenue metering tionship of interactive power systems or gen-
functions. erators before permitting the interconnection
of two energized (interactive) systems. An
6.9 Cable Systems. Cable systems required to automatic synchronizing device may be used
interconnect protective relaying, metering, to control the speed and voltage of a generator
instrumentation, control, communications, and initiate connection to the system.
and low-voltage power equipment systems
should be in conformance with IEEE Std 525- 7.5 Reclosing and T r a n s f e r Tripping.
1987 [81 or local utility practice. Reclosing relays are employed with power cir-
cuit breakers to permit the rapid restoration of
service to a transmission line that has been
7.proteCtiveRelaying isolated due to the detection of a transient fault
condition. Automatic reclosing is appropriate
Protective relaying is necessary to detect to support continuity of service and to main-
system disturbances and to initiate proper re- tain stability of the interconnected system.
sponse from power switching equipment. The concept of rapid reclosing is based on the
Protective relaying also is necessary to moni- transient nature of most line faults, particu-
tor synchronizing, load transfers, and out-of- larly those caused by lightning. Particular
step operating conditions. care should be used in applying reclosing to
Protective relay application is probably the generator interconnections. An automatic re-
most complex aspect of power systems design. closing scheme should be approved by and
Successful design and operation needs inti- coordinated with the electric utility. Automatic
mate coordination of utility and owner protec- reclosing is generally not applied t o under-
tive relaying facilities and philosophies. ground (cable) lines. Transfer-trip relaying

18

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
SUBSTATIONS TO ELECTRIC UTILITIES std1109-1990

is frequently employed t o isolate a generator 8. Metering and Instrumentation


from a faulted line so as to prevent damage
due to reclosing out of synchronism. The following types of metering could be ex-
pected to be provided as part of any user-owned
7.6 Load Shedding and "Islanding". Load facility interconnected to an electric utility.
shedding is necessary when available gener-
ation in a defined system, such as a large in- 8.1 Revenue Metering. This is a very signifi-
dustrial o r cogeneration plant, should cant interconnection parameter for user-pur-
suddenly become insufficient to meet the con- chased power and for sale of user-generated
nected load with the system. Such action would electric energy. The revenue parameteds) to
serve to preserve essential loads in operation. be metered will depend on the specific inter-
Such a condition could be brought about by loss connection agreement and could include
of in-plant generation or loss of a user-utility kwh, kvarh, kW, kvar, kVA, and power fac-
interconnection tie line that is importing tor, in almost any combination. Since bidirec-
power at the time of failure. The decay of on- tional real and reactive power flow may be
line generatorb) frequency can be measured possible, detented (in and out) metering is fre-
to initiate the sequential removal of selected, quently necessary. Also, time-of-day pricing
low-priority plant loads with the ultimate pur- may be included in the specific rate structure,
pose of maintaining service to essential loads tariff, or contract.
that in-plant generation is capable of supply- Revenue metering requires the most accu-
ing. The complete isolation of independent rate metering equipment available. This
generating systems results in Kislandsnof includes calibrated and certified metering ac-
load and generation, which are individually curacy current and voltage transformers,
less reliable and more sensitive to disturbance transducers, recording devices, and instru-
than the interconnected interactive system. ments. Most utilities usually have well-de-
This islanding condition also raises safety fined requirements for the configuration, type,
concerns and may necessitate transfer-trip- and location of revenue metering equipment.
ping of additional switching devices to com- Revenue metering is normally located in ar-
pletely isolate the systems. Reconnection of the eas that are accessible to the utility representa-
isolated systems to a larger, stable system can tives, although it is not unreasonable to request
also be difficult. a cumulative reading t o be duplicated at a
user-maintained area in order to be monitored
7.7 Generator Protection. Specifically de- by the customer or owner. A communications
signed relaying is required t o monitor the line is needed if remote access of the metering
condition of the numerous mechanical and data is necessary (i.e., for dispatching or load
electrical functions of a turbine generator or research).
any other type of generating machine.
Because of the significant capital investment 8.2 Indicating Instruments and Status.
inherent in any generating unit, sensitivity Indicating instruments are provided t o dis-
and speed of response are necessary to detect play the presence and magnitude of parame-
abnormal conditions. This permits isolating ters on specific lines, buses, and equipment.
and repair before a catastrophic failure can Parameters that could be expected to be mea-
occur, with its consequent financial and sured are voltage, current, kW, kvar, kwh,
safety implications. power factor, kVA, and kvarh. The normal lo-
cation for such an indication would be a t a
7.8 Relaying Interfaces and Interlocks. substation control house, generator control
Protective relaying systems can be intercon- room, or other accessible area.
nected with other electrical control and meter- The choice of indicating instruments is
ing systems and may be interconnected with very site-, user-, and utility-specific in that
mechanical process systems. Interlocks estab- instruments are used to support operations and
lish permissive or restrained systems of op- maintenance functions. Indicating instru-
eration that are necessary to ensure the safety ments as implied here would be located in the
of operation and the protection of the geographic vicinity of the user-owned facility.
investment. Indicating instruments also include the dis-

19

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std1109-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

Crete (open-closed-trip) status display of tions, which is the usual case for substations,
equipment such as power circuit breakers, switchyards, or switching stations.
electrically-operated load interrupters, and
disconnecting switches. 9.2 Supervisory Control. Supervisory control,
also generically referred t o a s SCADA
8.3 Telemetering. Telemetering is the trans- (Supervisory Control and Data Acquisition)
mission of analog or digital parameters to a systems, represents the long-distance control
remote location. Telemetering is closely asso- and data transmission methodology for dis-
ciated with supervisory control, which is dis- tances much greater than that capable with di-
cussed further in 9.2. The parameters that can rect local or remote control. As opposed t o
be telemetered to a remote location are the hard-wired direct local or remote control,
same as those for local metering, status, and which utilizes a dedicated wire pair or similar
indication. dedicated communication medium for each
The remote location that would likely be the control or data signal, supervisory control
destination for telemetered data would be a usually utilizes multiplex technology t o super-
utility dispatch center or a user’s remote con- impose multiple signals on a single commu-
troVmonitoring facility. Telemetering of data nication channel. This system uses an RTU
can be accomplished over wire circuits for (Remote Terminal Unit) at each terminal to
short distances. For long-distance telemeter- collect, process, and transmit the appropriate
ing, dedicated communications lines, carrier multiple input and output signals. Supervisory
equipment, radio transmission, microwave control is generally needed for a utility inter-
facilities, or fiber optics circuitry is needed. connection that includes remote utility control
of selected customer-owned equipment, such
as high-voltage power circuit breakers.
9. Control and Communications Additional information is given in IEEE Std
C37.1-1987 [31.

Control facilities are needed to provide the 9.3 Remote Dispatch. Remote dispatch is
human interface for the operation of installed merely local control of equipment in accor-
equipment. Communications media of vari- dance with the verbal instructions received
ous types are used t o permit the transmission from a remote central control location, such as
and reception of control initiation signals, as a utility central power dispatch center. Remote
well as for data transmission (see 8.3). Utility dispatch can reasonably be expected to be con-
companies may need remote metering, moni- sidered as part of the operations functions of
toring, and control capabilities of large, dis- any generator connected to an operating util-
persed user-owned generating facilities in ity system. A voice communication channel,
order t o satisfy overall system safety and op- either dial-up or dedicated, is the normal dis-
eration needs. patch coordination medium.

9.1 Local Control. Local control is usually ac- 9.4 Communications. Various communica-
complished by a direct electrical, mechanical, tions media may be considered for the differ-
pneumatic, or hydraulic device and is initi- ent control functions, as follows.
ated immediately at the equipment or at some
control facility within sight or walking dis- (1) Metallic Hardwire-Suitable only for
tance of the equipment. It is the least sophisti- relatively short distances (up t o several
cated (and most reliable) control mode. hundred feet) for control/relaying/
“Remote Control” is an extension of local metering functions.
control, which implies a greater distance be- (2) Telephone-For voice, SCADA and se-
tween the controlled device and the initiating lected relaying functions (not guaran-
signal, but this control can utilize the same teed for continuous integrity if a normal
communication medium as for local control line).
and, in fact, can differ only by degree of prox- (3) Power Line Carrier-For voice o r
imity to the controlled device. Remote control SCADA functions (also suitable for re-
is particularly applicable to unattended loca- laying functions). Maintaining con-

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
lEEE
SUBSTATIONS TO ELECTRIC UTILITIES std1109-1990

tinuous integrity during line faults can 10.1 Coordination of Switching. For personnel
be a problem. safety and in order to avoid disruption of user
Leased Telephone Channel-For voice and utility service or equipment damage o r
o r SCADA functions (also for relaying both.
functions). May be more reliable than a
normal telephone line). 10.2 Tagging, Lockout, and Grounding.
Microwave-For voice, SCADA, and re- Clearly defined procedures for isolating and
laying functions (expensive except for grounding of equipment and circuits as
handling many signals at great dis- needed for utility, user, and contractor main-
tances; political and environmental tenance functions.
considerations may also be necessary).
Fiber Optics-For voice, SCADA, and 10.3 Personnel Safety and Training.
relaying functions (option to a leased Minimum level of training needed for opera-
telephone line). tions, maintenance, a n d construction
Radio-For voice communications personnel.
(backup to other systems and for limited
switching operations). 10.4 Access. Provision for both user and utility
ingress and egress in all weather conditions
Redundant communications links should at any time of day.
be considered for any essential function or for
installations with significant customer- 10.5 Testing. From time t o time, customer or
owned generation. Reliable voice communi- utility equipment may have to be removed
cation is essential between generator operators from service. Such equipment may have
and the utility, particularly during system failed, may have to be maintained, or may
emergencies. have to be tested. Circuit breakers require pe-
riodic preventive maintenance. Oil-filled de-
9.5 Communication Circuit Protection. The vices are often DobleTMtested for their power
reliability of the communication circuit factor or dissipation factor. Instrument trans-
should be considered to ensure the integrity of formers used for metering may have to be
the circuit under adverse conditions or to min- tested for accuracy. Therefore, current trans-
imize the likelihood of circuit interruption. formers may have to have bypasses and dis-
Communication circuits should be supervised connects installed.
continuously and checked periodically t o en- The station owner should be aware of these
sure their continued integrity. temporary and scheduled equipment outages
Events that could cause circuit interruption and should factor them into the planned opera-
can be: digging of buried cables, lightning, tion of the station and the generator(s).
insulation failure of conductors or devices due
t o transient potential rise, circulating 10.6 Emergency Conditions. The user and
currents, vandalism, a n d equipment utility should agree on any special control re-
maintenance. quirements for the generating facility during
periods of defined utility system emergency
condition operation. Administrative instruc-
10. Maintenance and Operation tions should be made available to the user's op-
erating personnel.
In addition to the design coordination nec-
essary to realize the physical and electrical
interfaces between the user's facilities and the
utility, it is necessary to coordinate normal U Administrative Items
life-of-plant maintenance and operation
functions. The details of such coordination
are usually outlined in an operational agree- The following administrative items, among
ment t o which all parties are obligated. others, should be considered for equipment
Particular items that are likely to be covered and facilities that interface with both the user
by an operational agreement are as follows. and utility facilities.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std1108-1990 IEEE GUIDE FOR THE INTERCONNECTION OF USER-OWNED

(1) Drawings and Data-A schedule should ( 6 ) Local Building Codes Complknce
be prepared for submission and review ( 7 ) Access of Utility Employees to the User's
of appropriate drawings and data by all Substation
parties during the user-facility inter- ( 8 ) Insurance and Liability
connection design phase and utility or
user system modification activities. l!2.cOntractualDocuments
( 2 ) Color Codes-For cable, wiring, race-
way, signs, etc. This guide is only a basis for specific dis-
(3) Nameplates-For major equipment. cussions and agreements. It is understood that
(4) Equipment Numbers-For operations specific user-utility financial, operating, de-
and maintenance coordination. sign, and other issues would be outlined in
( 5 ) Signs-To indicate ownership limits formal contracts, operating agreements, and
and for safety. other documents.

22

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
SUBSTATIONS TO ELECTRIC UTILITIES std11c9-1990

Appendix
(This Appendix is not a part of IEEE Std 1109-1990, IEEE Guide for the Interconnection of User-Owned Substations to
Electric Utilities, but ie included for information only.)

Related Code and Standard Agencies


(and area of applicability)

American Concrete Institute (ACI) St. Louis, MO 63132


P.O. Box 19150,Redford Station Electrical Testing and Maintenance
Detroit, MI 48219
Concrete Design Edison Electric Institute (EEI)
1111 19th Street, N.W.
Association of Edison Illuminating Washington, D.C. 20036
Companies (AEIC) Handbook for Electricity Metering
51 East 42nd Street
New York, NY 10017 Factory Mutual System Engineering and
H V Cable Systems Research Association(FMER0)
1151 Boston-Providence Turnpike
American Institute of Steel Construction Norwood, MA 02062
(AISC) Insurance Requirements
Three Gateway Center Suite 2350
Pittsburgh, PA 15222 Insulated Cable Engineers Association
Steel Application (ICEA)
P.O. Box P
American National Standards Institute South Yarmouth, MA 02664
(ANSI) Cable Application
1430 Broadway
New York, NY 10018 Institute of Electrical a n d Electronics
Application and Design Standards Engineers (IEEE)
445 Hoes Lane
American Society of Mechanical Engineers Piscataway, NJ 08855
(ASME) Electrical S y s t e m s a n d Equipment
345 East 47th street Application, National Electrical Safety Code
New York, NY 10017
Mechanical Equipment Illuminating Engineering Society of North
American (IESNA)
American Society of Testing and Materials 345 East 47th street
(ASTM) New York, NY 10017
1916 Race Street Lighting
Philadelphia, PA 19103
Components Instrument Society of America (ISA)
67 Alexander Drive
Building Officials and Code Administrators P.O. Box 12277
International (BOCA) Research Triangle Park, NC 27709
4051 W. Flossmoor Road Instruments
Country Club Hills, IL 60477
Building Codes
National Electrical Manufacturers
Association (NEMA)
Electrical Apparatus Service Association 2102 L Street, N.W.
(EASA) Washington, D.C. 20037
1331 Baur Boulevard Electrical Equipment Design

23

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.
IEEE
Std1109-1990

National Fire Protection Association (NFPA) Southern Building Code Congress,


Batterymarch Park International (SBCCI)
Quincy,MA 02269 900 Montclair Road
Fire Protection Requirements, National Birmingham, AL 35213
Electrical Code Building Codes

Prestressed Concrete Institute (PCI) Steel Structures Painting Council (SSPC)


201 North Wells Street 4400 Fifth Avenue
Chicago, IL 60606 Pittsburgh, PA 15213
Concrete Structures Surface Protection and Coatings

24

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on December 14,2011 at 17:23:06 UTC from IEEE Xplore. Restrictions apply.

You might also like