Technical Particulars and Guarantees of 2.5 MVA, 11/0.416kV Transformer
Specification
Description Unit
No. Required Proposed
• Hot spot of winding K To be filled in
Impedance voltage at continuous
2.8 % ≥6
rated power
2.9 Winding connection:
• Primary Delta
Star (Neutral
• Secondary
brought out)
3 Rated insulation level for Primary
• Impulse withstand voltage kV
75
(1.2/50µS) peak
• One minute 50Hz withstand
kV rms 28
voltage
4 DESIGN DETAILS
4.1 Off-load tap changer
• Tapping range (±2 x 2.5%)
• Tapping step 2.50%
No load current at rated voltage
4.2 A To be filled in
(11kV)
Type of oil (As per IEC requirement
4.3 SHELL DIALA B
)
4.4 Standards IEC 60296
4.5 Type of corrosion protection
• Inside tank To be filled in
• Outside tank To be filled in
4.6 Type of valves glove or valve gates
5 DIMENSION AND WEIGHT
Dimension of Transformer (L x W x
5.1 mm To be filled in
H)
5.2 Total oil required
• Volume Liter To be filled in
Page 2 of 3
Technical Particulars and Guarantees of 2.5 MVA, 11/0.416kV Transformer
Specification
Description Unit
No. Required Proposed
• Weight Ton To be filled in
Net weight of copper winding and
5.3 kg To be filled in
core
Total weight of complete
5.4 kg To be filled in
transformer including fitting and oil
Page 3 of 3
11 kV XLPE 1 Core 150 mm2
Specification
No. Description Unit
Required Proposed
GENERAL
Manufacturer and country of origin To Be Filled
IEC60502-2 &
Applicable Standards
IEC60228
1 Type To Be Filled
Rated Frequency Hz 50
Conductor details:
Compacted Circular
Compacted
Stranded
Conductor screen:
Page 1 of 5
Minimum thickness mm To Be Filled
Insulation:
Material XLPE
Insulation Screen
5 B. Semi-conducting tape
Material To Be Filled
Width mm To Be Filled
Swelling Yes/No
C. Metallic screen
Material To Be Filled
Page 2 of 5
Electrical cross section mm2 To Be Filled
- Material To Be Filled
- Width and thickness mm
- Lay length mm
Filler
6 Material To Be Filled
Extruded Yes/No
Inner Sheath:
7 Extruded Yes/No
Armour:
Material Yes/No
Type To Be Filled
8
Thickness of tape mm To Be Filled
Waterproof
9
Tape Description To Be Filled
10 Outer sheath:
Page 3 of 5
Material PVC ST2
Color Black
˂5,according to
19 Maximum Partial Discharge at 1.5 Uo pc
IEC60840
Page 4 of 5
23 AC. Withstand voltage for 5 minutes kV rms 42
30°C To be filled in
90 °C To be filled in
Cable Termination:
Slip On or
Type
30 Shrinkable To be filled in
- Straight,
As Required To be filled in
- End Joint.
As Required
Page 5 of 5
11 kV XLPE 1 Core 400 mm2
Specification
No. Description Unit
Required Proposed
GENERAL
Manufacturer and country of origin To Be Filled
IEC60502-2 &
Applicable Standards
IEC60228
1 Type To Be Filled
Rated Frequency Hz 50
Conductor details:
Compacted Circular
Compacted
Stranded
Conductor screen:
Page 1 of 5
Minimum thickness mm To Be Filled
Insulation:
Material XLPE
Insulation Screen
5 B. Semi-conducting tape
Material To Be Filled
Width mm To Be Filled
Swelling Yes/No
C. Metallic screen
Material To Be Filled
Page 2 of 5
Electrical cross section mm2 To Be Filled
- Material To Be Filled
- Width and thickness mm
- Lay length mm
Filler
6 Material To Be Filled
Extruded Yes/No
Inner Sheath:
7 Extruded Yes/No
Armour:
Material Yes/No
Type To Be Filled
8
Thickness of tape mm To Be Filled
Waterproof
9
Tape Description To Be Filled
10 Outer sheath:
Page 3 of 5
Material PVC ST2
Color Black
˂5,according to
19 Maximum Partial Discharge at 1.5 Uo pc
IEC60840
Page 4 of 5
23 AC. Withstand voltage for 5 minutes kV rms 42
30°C To be filled in
90 °C To be filled in
Cable Termination:
Slip On or
Type
30 Shrinkable To be filled in
- Straight,
As Required To be filled in
- End Joint.
As Required
Page 5 of 5
11kV Metal Clad Switchgear
Technical Particulars and Guarantees of 11 kV Metal Clad Switchgear
• Busbar A 2000
• Bus Section/Bus Riser A 1250
• Incoming transformer feeder A 1250
• Outgoing A 630
Page 1 of 1
110V Battery and Battery Charger
Page 1 of 6
110V Battery and Battery Charger
No. Description Unit Specification
Required Proposed
2.12 Type of mounting rack Steel painted trays
with anti-acid
coating
2.13 Anticipated life of electrolyte under Years To be filled in
actual operation condition
3 DIMENSION AND WEIGHT
3.1 Over all dimension of batteries on rack m To be filled in
(W x L x H)
3.2 Weight of cell with electrolyte Kg/ cell To be filled in
3.3 Volume of electrolyte Liter/cell To be filled in
B BATTERY CHARGERS
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type of battery charger Full automatic
constant voltage DC
power source
1.4 Type of rectifier Single phase
Thyristor full wave
bridge
1.5 Type of cooling for rectifier Self air-cooled
1.6 Model To be filled in
1.7 Applicable Standards IEC62040-1, -2, -3
1.8 Degree of protection IP 41
1.9 Number of chargers 2 x 100% for battery
2 ELECTRICAL DATA
2.1 Rated input AC voltage V 230±10%
2.2 Number of phase of AC input 1
2.3 Rated Frequency Hz 50
Page 2 of 6
110V Battery and Battery Charger
No. Description Unit Specification
Required Proposed
2.4 Input Power VA To be filled in
2.5 Regulated voltage range on DC busbar V 110 V ±10%
(Automatic Voltage regulator)
2.6 Means of regulating output voltage on Semi-conductor
DC busbar dropper
2.7 Di-electric strength (50Hz for 1 minute)
• Between AC phases and earth V 2000
• Between AC and DC circuit V 2000
3 DESIGN DETAIL
3.1 Continuous rated output current including
the de rating factor
• On float mode A To be filled in
• On boost mode A To be filled in
3.2 Charger rate output voltage
• Float Charging V To be filled in
• Boost Charging V To be filled in
3.3 Manual voltage regulator (float/boost
charge)
• Voltage setting range V To be filled in
• Boost charging current setting range A To be filled in
• Boost charging voltage limit setting V To be filled in
range
3.4 Voltage ripple % To be filled in
3.5 Setting range of DC under-voltage relay To be filled in
Page 3 of 6
110V Battery and Battery Charger
No. Description Unit Specification
Required Proposed
4 DIMENSION AND WEIGHT
4.1 Overall dimensions of Cubicle (L x W x m To be filled in
H)
4.2 Total weight of battery charger kg To be filled in
C 110 V D.C. SWITCHBOARD
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
1.5 Location of services Indoor
1.6 Degree of protection IP 41
2 ELECTRICAL DATA
2.1 Rated DC voltage V 110
2.2 Rated current of busbars at 55°C ambient A To be filled in
temperature
2.3 Busbar cross section mm2 To be filled in
2.4 Busbar insulation material To be filled in
2.5 Number of circuits To be filled in
2.6 Main isolator rating A To be filled in
2.7 Main fuse rating A To be filled in
3 DESIGN DETAIL
A MCCB (Incomings & Bus Coupler)
3.1 Manufacturer Name To be filled in
3.2 Type Molded Case
3.3 Model To be filled in
Page 4 of 6
110V Battery and Battery Charger
No. Description Unit Specification
Required Proposed
3.4 Applicable Standards IEC 60947-2
3.5 Site current rating (at 55°C) A To be filled in
3.6 Rated short time current (3 s) kA To be filled in
3.7 Maximum operating time
• Opening ms To be filled in
• Closing ms To be filled in
3.8 Voltage / power coil rating V/W To be filled in
3.9 Typical circuit diagram number To be filled in
3.10 Protection Thermal &
Magnetic
B DETAILS OF EARTH FAULT PROTECTION
1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
C DETAILS OF UNDER VOLTAGE PROTECTION
1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
D INSTRUMENTS
1.1 Manufacturer Name To be filled in
1.2 Type of meter
• Voltmeter To be filled in
• Ammeter To be filled in
Page 5 of 6
110V Battery and Battery Charger
No. Description Unit Specification
Required Proposed
1.3 Catalogue Provided Yes
1.4 Single line diagram & Arrangement To be filled in
drawing number
4 DIMENSION AND WEIGHT
4.1 Overall dimensions of Switchboard (L x m To be filled in
W x H)
4.2 Total weight of Switchboard kg To be filled in
Page 6 of 6
160 A Molded Case Circuit Breaker
Page 1 of 1
250 A Molded Case Circuit Breaker
Page 1 of 1
1000 kVA 11/0.416kV Transformer
Page 1 of 3
Technical Particulars and Guarantees of 1000kVA, 11/0.416kV Transformer
Specification
Description Unit
No. Required Proposed
• Hot spot of winding K To be filled in
Impedance voltage at continuous
2.8 % ≥6
rated power
2.9 Winding connection:
• Primary Delta
Star (Neutral
• Secondary
brought out)
3 Rated insulation level for Primary
• Impulse withstand voltage kV
75
(1.2/50µS) peak
• One minute 50Hz withstand
kV rms 28
voltage
4 DESIGN DETAILS
4.1 Off-load tap changer
• Tapping range (±2 x 2.5%)
• Tapping step 2.50%
No load current at rated voltage
4.2 A To be filled in
(11kV)
Type of oil (As per IEC requirement
4.3 SHELL DIALA B
)
4.4 Standards IEC 60296
4.5 Type of corrosion protection
• Inside tank To be filled in
• Outside tank To be filled in
4.6 Type of valves glove or valve gates
5 DIMENSION AND WEIGHT
Dimension of Transformer (L x W x
5.1 mm To be filled in
H)
5.2 Total oil required
• Volume Liter To be filled in
Page 2 of 3
Technical Particulars and Guarantees of 1000 kVA, 11/0.416kV Transformer
Specification
Description Unit
No. Required Proposed
• Weight Ton To be filled in
Net weight of copper winding and
5.3 kg To be filled in
core
Total weight of complete
5.4 kg To be filled in
transformer including fitting and oil
Page 3 of 3
1250A Air Circuit Breakers
Page 1 of 1
1600A Air Circuit Breakers
Page 1 of 1
2000A Air Circuit Breakers
Page 1 of 1
5000A Air Circuit Breakers
Page 1 of 1
DC Distribution Panel
Page 1 of 3
Technical Particulars and Guarantees of LV AC Distribution Panel
Specification
No. Description Unit
Required Proposed
1.6 Protection Thermal & Magnetic
B BUSBAR
Rated current of busbars at 55°C
2.1 A To be filled in
ambient temperature
2.2 Busbar cross section mm2 To be filled in
2.3 Busbar insulation material To be filled in
C DETAILS OF MCBs
1.1 Manufacturer Name To be filled in
1.2 Type Molded Case
1.3 Model To be filled in
1.4 Applicable Standards IEC 60947-2
1.5 Site current rating (at 55°C) A To be filled
1.6 Rated short time current (3 s) kA To be filled
1.7 - Typical circuit diagram number To be filled
1.8 Protection Thermal & Magnetic
D DETAILS OF UNDER VOLTAGE PROTECTION
1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
E INSTRUMENTS
1.1 Manufacturer Name To be filled in
1.2 Type of meter
• Voltmeter To be filled in
• Ammeter To be filled in
Page 2 of 3
Technical Particulars and Guarantees of LV AC Distribution Panel
Specification
No. Description Unit
Required Proposed
1.3 Catalogue Provided Yes
Single line diagram & Arrangement
F To be filled in
drawing number
4 DIMENSION AND WEIGHT
Overall dimensions of Distribution
Panel m To be filled in
(L x W x H)
Total weight of Distribution Panel kg To be filled in
Page 3 of 3
Handling Tool
Handling Tool
Specification
No. Description
Required Proposed
1 GENERAL
1.1 Manufacturer Name SK, Proto or Beta
Page 2 of 2
Laptop/HP ProBook 650 G2 Notebook PC (ENERGY STAR)
Specification
No. Description Unit
Required Proposed
1 GENERAL
Page 1 of 3
1 USB 3.0; 1 USB 3.0
charging; 1 USB Type-C™; 1
DisplayPort; 1 VGA; 1
2.12 Ports
headphone/microphone combo;
1 AC power; 1 RJ-45; 1
docking connector; 1 serial port
Premium Spill-Resistant
2.16 Keyboard
Keyboard/ Arabic Keyboard
45 W Smart AC adapter; 65 W
2.19 Power supply Smart AC adapter; 90 W Smart
adapter
3-cell, 48 Wh Li-ion: up to 10
2.21 Battery life
hours and 15 minutes
Page 2 of 3
2.23 Weight To Be Filled
1- Baggage
2.25 Additional
2- Wireless mouse.
Page 3 of 3
Low Voltage power Cables – 240mm2
Technical Particulars and Guarantees of Low Voltage power Cables – 240mm2
Specification
No. Description Unit
Required Proposed
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
(According to
1.3 Type
MoE specifications)
1.4 Rated voltage (Uo/U) kV 600/1000
IEC 60502, IEC
60183, IEC 60228,
1.5 Applicable Standards IEC 60287, , IEC
60287, IEC 60811,
IEC 60853,
1.6 Type Test Certificate Yes
2 ELECTRICAL DATA
2.1 Rated Frequency Hz 50
2.2 AC. Withstand voltage for 5 minutes kV rms 3
2.3 Max. DC Conductor resistance at 20 °C ohm/km 0.0754
2.4 Temperature range ◦C -15 to +90
3 CABLE DATA
3.1 Number of conductor Core Single
Cross sectional area (Phase)
3.2 mm2 240
Stranded and Compacted
Compacted circular
3.3 Shape of conductor
stranded
3.4 Material of Conductor Cu.
3.5 Weight of Conductor (Approx.) kg/km To be filled in
3.6 Material of insulation XLPE
3.7 Insulation thickness (Nominal) mm 1.7
3.8 Material of sheath PVC
Nominal Thickness of over sheath
3.9 mm To be filled in
(Approx.)
3.10 Capacitance of Cable (Approx.) µF/km 0.621
Insulation resistance between core /
3.11 MOhm To be filled in
screen
Page 1 of 2
3.12 Inductance of cable mH/km To Be Filled
3.13 Color of sheath Black
Type of chemical treatment against
3.14 To be filled in
termite in the outer sheath.
3.15 Rated short-time current for 1 sec. kA 34.3
Minimum Bending Radius of Cable
3.16 mm 160
(during installation)
3.17 Overall diameter of cable (Approx.) mm 25.3
3.18 Net weight (Approx.) kg/km To be filled in
3.19 Voltage Droop at rated current at 30 °C v/km To be filled in
4 DOCUMENTS
Cross section drawing and details of
4.1 cable layers and catalogues, Includes To be Submitted
catalogues for Cable Terminations
4.2 Type test reports To be Submitted
Page 2 of 2
LV AC Distribution Panel
Technical Particulars and Guarantees of LV AC Distribution Panel
No. Description Unit Specification
Required Proposed
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Metal-clad
totally enclosed
1.4 Model To be filled in
1.5 Applicable Standards IEC 60439
1.6 Location of services Indoor
1.7 Degree of protection IP 41
2 ELECTRICAL DATA
2.1 Rated AC voltage V 400/240V,
3pase 4 wires
2.2 Power frequency withstand test voltage KVrms 3