1 2 1 2

LEGEND
PB
schedule of loads
PANEL BOARD

3W WARM WHITE
SPOT LIGHT
O C P D WIRE USED CONDUIT
CKT LOAD DESCRIPTION OUTLET VA VOLTS POLE AMPERE
MM2 THW
GROUNDING USED
SIZE
11W DAYLIGHT PIN AT AF KAIC
A A LIGHT

1 lighting outlet 12 300 230 2P 1.30 15 60 10 TW NO. 14 AWG 1-2.0MM2 1/2 01


M
KILOWATT HOUR
METER
2 lighiting outlet 13 325 230 2P 0.70 15 60 10 TW NO. 14 AWG 1-2.0MM2 1/2 01
b b
emergy 2 GANG CONV outlt
lamp
3 convenience outlet 7 1,265 230 2P 6.00 15 60 10 TW NO. 12 AWG 1-2.0MM2 1/2 01
3 GANG
CONVENIENCE

5 w
OUTLET
4 convenience outlet 9 1,620 230 2P 5.50 15 60 10 TW NO. 12 AWG 1-2.0MM2 1/2 01
REFRIGERATOR
REF

RANGE
5 air con 1 1,380 230 2P 6.60 20 60 10 TW NO. 12 AWG 1-2.0MM2 1/2 01
R
c7
range EL
EMERGENCY LIGHT 6 refrigerator 1 1,380 230 2P 6.60 20 60 10 TW NO. 12 AWG 1-2.0MM2 1/2 01
SINGLE POLE
S1
SWITCH
7 range 1 1,380 230 2P 6.60 20 60 10 TW NO. 12 AWG 1-2.0MM2 1/2 01
S2 2 GANG SWITCH

c6 S3 3 GANG SWITCH
ref 8 spare 230 2P 20 60 10
c c S3W 3-WAY SWITCH

SWITCH LINE
main 44 7,650 230 2P 33.30 100 60 10 TW NO. 8 AWG 1-8.0MM2 3/4 1
CIRCUIT LINE
UP
C CIRCUIT HOMERUN

COMPUTATION FOR MAIN BREAKER USE: COMPUTATION FOR MAIN CONDUCTOR:

VA + (150% OF THE LARGEST MOTOR) (80% DF) VA + (25% OF THE LARGEST MOTOR) (80% DF)
1B = 1B =
230 VOLTS 230 VOLTS
acu
emergy
c5 emergy
lamp lamp 7,650 VA + (1.50 OF THE 1380 VA) (80% DF) 7,650 VA + (0.25 OF THE 1380 VA) (80% DF)
d d 1B = 1B =
230 VOLTS 230 VOLTS

1B = 73.02 A : BREAKER USE @ MAIN: 1B = 39.76 A : CONDUCTOR USE @ MAIN:


100 AT,2P, 230V, 60 HZ 2 - 8.0MM2 THW CU WIRE STRANDED
e e CENTER MAIN, BOLT-ON TYPE 1 - 8.0MM2 TW CU WIRE (GROUNDING)

c3 c4

convenience outlet layout plan


b Scale: 1:80 M
ELECTRICAL SPECIFICATIONS
ALL ELCTRICAL INSTALLATION SHAL COMPLY WITH THE
PROVISIONS OF THE ELECTRICAL CODE AND
TO SOURCE
1 1 REGULATIONS OF LOCAL POWER COMPANY AND EXISTING
2 2
AUTHORITIES AND CONCERNED INT THE ENFORCEMENT OF
SUCH LAWS AND ORDINANCE.

MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE NO. 35MM


CONDUIT RESPECTYVELY.
c1
ALL WIRING SHALL BE DONE IN PVC EXCEPT IN SERVICE
A A ENTRANCE WHERE RIGID STEEL CONDUIT SHALL BE USED.
2-8.00mm sq. TW wire in
25mm∅ PVC CONDUIT
10 w
10 w
MOUNTING HIEGHTS:
A. CIRCUIT BREAKER1.70MTS 100 AT
b b B. WALL SWITCH 1.40MTS
S1 S3 C. CONVINIENCE OUTLET 0.30MTS
5 w

10 w
5 w
10 AT 10 AT
S2

10 w
10 w

LIGHTING OUTLET
c1 c2 lighting outlet METER
5w
15 AT 15 AT
10 w

convenience outlet
c3 C4 convenience outlet
10 w
15 AT 15 AT

air con
c5 c6 refrigerator
c c
10 w S2 10 w 20 AT

range
c7 C4 spare
UP

solid brass

10 w 10 w
10 w
5 w
PANEL BOARD
S2 S2
d d GROUND

c2
5 w 5 w 5 w 5 w
GROUND FLOOR
e e
10 w 10 w 2-8.00mm sq. TW wire in 20mm∅ PVC CONDUIT

lighting outlet layout plan riser diagram


A Scale: 1:80 M c Scale: nts

S E A L APPROVED BY: NOTICE: PROJECT TITLE: APPROVED / ACKNOWLEDGED: SHEET CONTENTS: REVISIONS DRAWN SHEET NO.
THESE DRAWINGS as instru ments of
service, are the intellectual A LIGHTING LAYOUT
pro p er ty an d d o c u m en t s o f t he
architect, whether the object for
which they are made is executed or
B CONVENIENCE OUTLET LAYOUT PLAN
EL 1-1
PRC REG NO. PTR NO.
no t. It s hall be u nlawfu l for an y
pers o n t o du pl ic ate o r t o ma ke
copies of said documents for use in
proposed residential jennifer silagon
t he re p e ti t i o n o f a n d f o r o t he r C riser diagram
4 6
DATE REG'D DATE ISSUED
projects o r buildings, whether
executed partly or in whole, without
the written consent of the architect
renovation O W N E R
D schedule of loads
or author of said documents

T I N PLACE ISSUED REPUBLIC ACT 9266, SEC. 33 LOCATION: poblacion ibabao, loay, bohol address: poblacion ibabao, loay, bohol E ELECTRICAL