After process 26 / PLC_1 [CPU 1215C DC/DC/DC] / Program blocks


Main [OB1]
Main Properties
General
Name Main Number 1 Type OB Language LAD
Numbering Automatic
Information
Title "Main Program Sweep (Cy‐ Author Comment Family
cle)"
Version 0.1 User-defined ID

Main
Name Data type Default value Comment
Input
Initial_Call Bool Initial call of this OB
Remanence Bool =True, if remanent data are available
Temp
Constant

Network 1:

%I1.2 %I1.1 %I1.0


"Conveyor 2431 "Belt control "Dryer 2420 trip %I0.1 %I0.0 %M0.0
trip sts" 2431" sts" "off switch" "Start switch" "main memory"

%M0.0
"main memory"

Network 2:

%M0.0 NORM_X SCALE_X


"main memory" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD500 4.0 MIN %MD510
OUT "Tag_1" %MD500 OUT "Tag_2"
%IW64
"Temperature "Tag_1" VALUE
sensor 2418" VALUE 20.0 MAX
27648 MAX

Network 3:
range 0 to 800 (SRTH600-400A-2708
Infrared Temperature Sensor)

%MD510
%M0.0 %Q100.0 %Q0.0
"main memory" "Conveyor 2411" "Tag_2" "Dryer 2420"
>
Real
12.0
%Q0.1
"mixing chamber
valve 2418"

Network 4: 2423

%Q0.2
%Q0.0 "Lock feeder
"Timer 0".Q "Dryer 2420" motor"

%Q0.3
"Bucket conveyor
"timer 1".Q motor"

Network 5:
Totally Integrated
Automation Portal

%DB1
"Timer 0"
%I0.2
"Bucket conveyor TON %Q0.4
motor trip sts" Time "Blower fan 2424"
IN Q
T#10m PT ET T#0ms

%I0.3
"Lock feeder
motor trip sts"

%I0.4
"Spark detection
sensor"

%I0.5
"Belt sensor
2423"

%I0.6
"Overload sensor
2423"

Network 6: 2431

%I2.1 %I2.0 %I1.7


%I3.1 %I3.0 %I2.6 %I2.5 %I2.4 %I2.3 %I2.2 "Vibrator "Vibrator "Vibrator %I1.6
"Spark detection "Conveyor 2671 "Spark detection "Conveyor 2681 "Spark detection ( "Spark detection ( "Spark detection ( screening 2653 screening 2652 screening 2651 "Screw conveyor
sts 2671" trip sts" sts" trip sts" 3) 2853" 2) 2652" 1) 2651" trip sts" trip sts" trip sts" 2633 trip sts"
1

%I1.5 %I1.4 %Q0.3 %M100.1


"Screw conveyor "Screw conveyor %M0.0 "Bucket conveyor %Q0.4 "70+ by level %Q0.5
2632 trip sts" 2631 trip sts" "main memory" motor" "Blower fan 2424" sensor2601" "Conveyor 2431"
1

Network 7:

NORM_X SCALE_X
Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD530 4.0 MIN %MD540
%MD520 OUT "Tag_4" %MD530 OUT "Tag_5"
"Tag_3" VALUE "Tag_4" VALUE
27648 MAX 20.0 MAX

Network 8:

CONV
Real to Int
EN ENO
%MD540 %QW64
"Tag_5" IN "Motor Speed
OUT Control"

Network 9:

%M100.0
%I0.7 "2431 spark
"Spark detection detection sensor
sensor 2431" memory"

%DB2
"timer 1"
%M100.0
"2431 spark TON
detection sensor Time
memory" IN Q
T#10s PT ET T#0ms

Network 10:
Totally Integrated
Automation Portal

%M100.0
"2431 spark
detection sensor %Q0.4
memory" "timer 1".Q "Blower fan 2424"

Network 11: DRY FLAKES 2601

NORM_X SCALE_X
Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD560 0.0 MIN %MD560
%MD550 OUT "Tag_7" %MD550 OUT "Tag_7"
"Tag_6" VALUE "Tag_6" VALUE
27648 MAX 100.0 MAX

Network 12:

%Q1.0
%MD560 "Screw conveyor (
"Tag_7" 2) 2601"
>
Real
25.0
%Q0.7
"Screw conveyor (
1) 2601"

%Q1.1
"Screw conveyor (
2) 2601(1)"

Network 13:

%Q0.6
%I1.3 "Pressure
"Spark Detection Release Motor
Sensor2601 STS" 2601"

Network 14:

%M100.1
%MD560 "70+ by level
"Tag_7" sensor2601"
>
Real
70.0

Network 15: Screw conveyor (2631,2632, 2633)

%DB3
"Timer 2"
%Q0.7 %Q1.0 %Q1.2
"Screw conveyor ( "Screw conveyor ( TON "Screw conveyor
1) 2601" 2) 2601" Time 2631"
IN Q
T#10s PT ET T#0ms

%Q1.3
"Screw conveyor
2632"

%Q1.3
"Screw conveyor
2632"

Network 16: Vibrator screening (2651,2652, 2853)

%Q1.2 %Q1.5
"Screw conveyor "Vibrator
2631" screening 2651"
Totally Integrated
Automation Portal

Network 17:

%Q1.3 %Q1.6
"Screw conveyor "Vibrator
2632" screening 2652"

Network 18:

%Q1.4 %Q1.7
"Screw conveyor "Vibrator
2633" screening 2653"

Network 19: Conveyor 2681

%M100.2
%Q1.5 %Q1.6 %Q1.7 "Spark detection
"Vibrator "Vibrator "Vibrator sensor 2730 %Q2.0
screening 2651" screening 2652" screening 2653" memory" "Conveyor 2681"

Network 20: AIR Shifter 2730

NORM_X SCALE_X
Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD570 4.0 MIN %MD580
OUT "Tag_9" %MD570 OUT "Tag_10"
%IW70
"Temperature "Tag_9" VALUE
sensor 2730" VALUE 20.0 MAX
27648 MAX

Network 21:
Range 0-500

%Q2.1
%MD580 "Lock feeder
"Tag_10" 2730"
>=
Real
13.6
%Q2.2
"Dryer 2730"

Network 22:

%M100.2
%I2.7 "Spark detection
"Spark detection sensor 2730
sensor 2730" memory"

%Q2.3
"Timer 3".Q "Blower fan 2730"

%DB4
"Timer 3"
TON
Time
IN Q
T#5m PT ET T#0ms

Network 23: Conveyor 2671

%Q1.5 %Q1.6 %Q1.7 %I3.6 %I3.7


"Vibrator "Vibrator "Vibrator "Conveyor 2672 "Spark detection %Q2.4
screening 2651" screening 2652" screening 2653" trip sts" sts 2672" "Conveyor 2671"
Totally Integrated
Automation Portal

Network 24: Conveyor 2672

%M100.3
%Q2.4 "70%+ Flek in %Q3.0
"Conveyor 2671" 3101" "Conveyor 2672"

Network 25: Conveyor 2673

%I3.3
"Spark detection %Q2.5
sts 2673" "Blower fan 2673"

Network 26: Dry Flake storage 3101

NORM_X SCALE_X
Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD580 0.0 MIN %MD590
OUT "Tag_10" %MD580 OUT "Tag_8"
%IW72
"FLAKES Level "Tag_10" VALUE
Sensor 3101" VALUE 100.0 MAX
27648 MAX

Network 27:

%Q2.7
%MD590 "Screw conveyor (
"Tag_8" 1) 3101"
>=
Real
25.0

Network 28:

%Q2.6
%I3.4 "Pressure
"Spark Detection Release Motor
Sensor 3101 STS" 3101"

Network 29:

%M100.3
%MD590 "70%+ Flek in
"Tag_8" 3101"
>=
Real
70.0