Pump Monitor, EL-FI™ PM


Fan Monitor, EL-FI™ FM

MAIN BENEFITS The EL-FI PM and EL-FI FM monitor incorporate Emotron’s


• Stops a pump or fan and/or initiates an own ”phase angle method” to supervise either a centrifugal
alarm when an unacceptable change in pump or belt-driven radial fan system respectively. As no ex-
motor load is detected. ternalsensorisrequired,themonitorisconnecteddirectlyto
the drive motor cable to measure the difference in phase angle
• Can be used with a frequency inverter. between the current and voltage. A change in phase angle in-
• Works with up to 10 A motor current dicates a change in motor load. When the motor load fall below
without requiring an external current the preset alarm level, the motor is stopped and/or a system
transformer. alarmistripped.
A variable alarm level, representing the load at which an
• Separatevoltagesupply. alarm is tripped, can be set on the monitor. An alarm delay
• Alarm can be set to trigger when the time can also be set to suppress relay tripping in the event of
motor current is zero. a momentary or spurious underload. Alternative alarm func-
tions can be set by means of three DIP-switches located on
• Galvanically-isolatedcurrentmeasurement
thecontrolpanel.
increasespersonalsafety.
EL-FI PM/FM monitors suit both large and small asynchro-
• DIN-rail mounting. nous motors. With motors rated at less than l0A current, the
• Monitors and protects simply monitor is wired directly into the motor circuit, at a higher
and economically. currentratingitisconnectedviaastandardcurrenttransformer.

• No external sensor required. APPLICATIONS

• Function delay times can be entered to Pump Monitor EL-FI PM. Stops and/or initiates an alarm
eliminatefalsealarms. when an unacceptable underload is detected on the centrifugal
pump motor. This can result, for example, from dry running, a
• Alternative alarm functions can be set. closedvalveorapumpfailure.
• Easytoinstallforallsizesofinduction
motor. Fan Monitor EL-FI FM. Stops and/or initiates an alarm
when an unacceptable underload is detected on the radial-
• Reliable and maintenance-free. flowfanmotor.Thiscanresult,forexample,fromabeltfailure,
acloseddamperorablockedairfilter.
®

M A X I M I Z I N G U P T I M E

TECHNICAL DATA ALARM FUNCTIONS


The monitor has three different alarm
Main voltage for motor 100-240 VAC or 380-500 VAC +5%, -10% functions which are selected using the
Motor frequency 30-65 Hz DIP-switches on the front panel.
Excitationvoltageformonitor 100-110 VAC, 200-240 VAC; 380-440 VAC • Alarmrelaynormallyenergized(activated)
or 460-500 VAC +5%, -10%
Alarm relay normally de-energized
Supply voltage frequency 45-65 Hz (un-activated)
Currentinput 0.1-10A • No latched alarm
Currenttolerance 60 A in 5 sec Latched alarm
Power consumption 2.5 VA • No alarm at no motor current
Response delay time 1-40 s for PM and 1-90 s for FM Alarm at no motor current
Relaycontact 5A, 250 VAC1 (1.5 A AC11)
EL-FI PM/FM
Fuse Max. 20 A
Reliable and maintenance-free
Terminalwiresize 0.2-4.0 mm2 single core 0.2-2.5 mm2
flexibel core. Stripped length 8 mm. No external sensor
Accuracy ±10% FS
Asynchronous motor is the sensor
Simpletoinstall
Repeatability ±1%, 24h, 20°C
Suits all asynchronous motors
Ambient temperature -20°C till +50°C
Highly accurate
Temp. tolerance < ± 0,1%/°C
Measures cos ϕ
EMC-immunity EN50081-1, EN50082-2

Electricalsafety IEC 947-5-1 STOP/ALARM ON


Protectionclass,case IP20 Dry running (PM)
Dimensions (WxHxD) 45 x 90 x 115 mm Closed valve (PM)
Weight 0.30 kg Drive belt breakage (FM)
Data for current transformer 5 A, 1 VA or more, class optional
Closed damper (FM)
Blocked filter (FM)
Emotron AB reserves the right to alter product specifications
withoutpriornotification.

TYPICAL CONNECTION OF EL-FI PM/FM

L1 L2 L3 N
L1 L2 L3 N

M M
P1 P2

S1 S2 S1 S2

9 10 11 12 13 1 2 9 10 11 12 13 1 2
TYPE ELFI
TYPE ELFI
PM/FM
PM/FM

EL-FI PM/FM, 3x380-500/220-240V EL-FI PM/FM, 3x380-500/380-400V


01-0032-01 Pyramid Communication AB, Helsingborg, 1997

(Withoutcurrenttransformer<10A) (Withcurrenttransformer>10A)

Emotron AB
Mörsaregatan 12
Box 222 25
S-250 24 Helsingborg, Sweden