Customer:
Engineer:
Pump Manufacturer:
Technical Data
Submittal Document
GPx Series
Full Service
Electric Fire Pump Controller
Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
MEMBER
2019 -2020 MEMBER
2019 -2020
June 2022
Technical Data
GPx Series Full Service Electric Fire Pump Controller
*
3L2 T2
M
3L2 T2
*
3L1 T1
3L1 T1 CR4
1M 2M T9
M
CR4 CR5 T8
2M
1M T7
3L1
* M
3L2 T2
3L2
* 3L1
T2
T1
M CR4 CR5 2S
3L1 T1
1S 100%
1M
0% ATR
CR5 1M CR5
1M 2S
3L1 65%
1S
2S
3L1
* *
3L2 T2 3L2 T2
3L1 T1
3L1 T1
M
CR4
M
CR4 1M 2M
1M 2M T5 CR5 1S
T5
T4
CR5 1S T4
2M
2M(LB) CR3A T6
2M
T6 3L1 2S
CR5 2M 2S(LB) 2M(LB) CR3A
3L1
1S
1S 1S
1S
3L2
3L2
2S
RES
RES
RES
MEMBER
2019 -2020 MEMBER
2019 -2020
Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)
Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA
Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)
Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
GPx Series Full Service Electric Fire Pump Controller
Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current
DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
Technical Data
GPx Series Full Service Electric Fire Pump Controller
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 7
Technical Data
GPx Series Full Service Electric Fire Pump Controller
Additional Options:
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Home
2 3
8
5 6 7
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 9
Electric Fire Pump Controller Model:GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard
27 1/4" [694]
26 3/8" [671]
1/2" [12] 17 3/4" [452] 24" [610]
See Notes
48" [1220]
55 1/8" [1400]
54" [1372]
51 7/8" [1318]
27" [685]
21 1/4" [541] 21 5/8" [549]
White
White
White
CR4
Black
Black
Black
17
ST1 1 3L3 64 66 68
65 67 69
SA1 3L2
3L1
4 2 3L1 3L2
To J2-J3-J4 To J76
2
1
NO NO +
C J40 J14 AI4
otor Run C
TB1
NC NC -
2
1
NO NO +
C J42 J15 AI3
Power Availa le C
TB2
NC NC -
2
1
NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1
Red
NO NO
J39
+
White
PT1
Pump Room Alarm C C J17 AI1
TB4 Black
NC NC -
1
2
NO
LS1 **
NO LS1-1
C J41 LS1
otor Trou le C
TB5 J54 LS1-2
NC NC
2
1
UP
NO J20
NO
C J55
Field Programma le C
TB6 DOWN
NC NC J8
V B1
Black - +
J46 Red
AB1
AB
Remote anual Start IN1
SV
SV1-1 Brown SV1
Lockout IN2 J43 SV1-2 Blue
IO
Remote Automatic Start J1* IN3
4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in XTR1
IN6 24V out 3L2
X1 H2
1 24VAC
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
CR4
C
CR4-2
CR4
NO
NC
J38 C
CR5
NO
GF
69
L3 68
J76 67
L2 66 To CT1-CT2-CT3
65 Legend
1 Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay
J3 ST Shunt Trip
L2 3L2 To 3L1-3L2-3L3
SV Solenoid Valve
V B Vi iTouch ain Board
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)
220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)
Bending
12 " (305 mm) 16 " (406 mm)
Space
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------
220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------
380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------
440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)
600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)
Bending
Space 12 " (305 mm) 16 " (406 mm)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- --------
1x (350) **
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500) 3x (350 to 500) 3x (400 to 500) --------
N/A 2x (500) 90°C *
1x (300 to 350)**
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)
Bending
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Space
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.
Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T1 T2 T3
M
Models : GPA,
GPR & GPS
220 to 240 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (3/0)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300) 2x (2/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (400 to 600) -------- -------- -------- -------- -------- --------
220 to 240 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
380 to 416 1x (1/0 to 3/0) 1x (3/0) 1x (250 to 300) 1x (300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (400 to 500) 2x (500 to 600) 2x (600)
440 to 480 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 2x (1/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)
600 1x (3 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (300) 2x (350 to 500)
208 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (1/0 to 2/0) ** 1x (2/0) 90°C * Consult Factory 1x (300)
220 to 240 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (2/0) 1x (3/0) 90°C * Consult Factory
380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to1/0) 1x (1/0)
440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0) 1x (1 to 1/0)
600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300) 90°C * 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (600) -------- -------- -------- -------- -------- --------
220 to 240 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (500) 2x (600) -------- -------- -------- -------- --------
380 to 416 1x (3/0) Consult Factory 1x (300) 90°C * Consult Factory 2x (4/0 to 300) 2x (300) Consult Factory 2x (600) 2x (600) 90°C * 2x (600) 90°C * --------
440 to 480 1x (1/0) 1x (3/0) Consult Factory 1x (300) 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (300) 90°C * 2x (500) 2x (600) 2x (600) 90°C *
600 1x (1 to 1/0) Consult Factory 1x (3/0) 90°C * Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (300) 90°C * Consult Factory
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
** Option V659 required. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
1
Normally open TB1
NO
Normally closed Closes to alarm C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
1
Normally open TB2
NO
Normally closed Closes to alarm
C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm
C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J3
1
Normally open TB4
NO
Normally closed Closes to alarm
C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm
C
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
1
Normally open TB6
NO
Normally closed Closes to alarm C
Opens to alarm NC