THERMOBREAK ™

Ther mal I nsulat ion

Technical Information Bulletin

Controlling Surface Temperature

At steady state, the heat flow through the insulation to the outside surface equals the
heat flow from the surface to the ambient air. In equation form:

qins = qsurf

Or

(k/X)·A·(Thot–Tsurf) = ro·A·(Tsurf–Tamb)

Rearranging, this equation yields:

X = (k/ro)·[(Thot–Tsurf)/(Tsurf–Tamb)]

Since the ratio of temperature differences is known, the required thickness can be
calculated by multiplying by the ratio of the insulation material conductivity to the
surface coefficient.

X = Insulation thickness (m)


ro =external Surface coefficient

External Surface coefficient is affected by the type of surface of insulation as well as


ventilation of the surface:

For Thermobreak (foil faced)


Still air conditions 5.7 W/m2K
Moderate ventilation (2.2 m/s): 22.7 W/m2K
High Ventilation ( 3.3m/s) : 33.3 W/m2K

This information on Sekisui Pilon foams is presented to the best of our knowledge. All product data is based on
average values and is for guidance only.

Recommendations as to methods of post fabrication, application and use of Sekisui Pilon foams are based on our
experience and knowledge of the characteristics of our products and are given in good faith. As producer of the
material, we have no control over the application of Sekisui Pilon foams and no legal responsibility is accepted for
such recommendations. In particular, no responsibility is accepted by us for any system in which Sekisui Pilon foams
are utilised nor for any application. Thermobreak - Registered trademark of Sekisui Pilon