General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4
2 External Appearance.............................................................................. 6
3
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
40VZ One-way Cassette 42VD*1010 High Static Pressure Duct
40VT Two-way Cassette 42VH Wall-mounted
40VX Compact Four-way Cassette 42VF Ceiling & Floor
40VK Four-way Cassette 42VS Floor Standing
42VD*301* Medium Static Pressure Duct 42VC Console
2.2 0.8 22 22 22 22 — 22 — 22 — 22 22
2.8 1 28 28 28 28 28 28 — 28 — 28 28
3.6 1.25 36 36 36 36 36 36 — 36 36 36 36
4.5 1.6 45 45 45 45 45 45 — 45 45 45 45
5.6 2 56 56 56 — 56 56 — 56 56 56 —
7.1 2.5 71 71 71 — 71 71 71 71 71 71 —
8.0 3 80 — — — 80 80 80 80 80 80 —
9.0 3.2 90 — — — 90 90 90 90 90 90 —
4
1.2 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Capacity 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP
Model
008 010 012 014 016 018 020 022
(38VF*H119015)
5
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor units
Table 1-2.1: Standard indoor unit appearance
40VZ 40VT
40VX 40VK
42VC 40VD*301*
40VD*1010 42VH
42VF 42VS
6
2.2 Outdoor Units
2.2.1 Single units
Table 1-2.4: Single outdoor unit appearance
8/10/12HP 14/16/18/20/22HP
7
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations
1
System capacity Number Modules 2
Outdoor branch joint kit
kW HP of units 8 10 12 14 16 18 20 22
25.2 8 1 ●
28.0 10 1 ●
33.5 12 1 ●
40.0 14 1 ●
●
—
45.0 16 1
50.0 18 1 ●
56.0 20 1 ●
61.5 22 1 ●
67.0 24 2 ●●
73.0 26 2 ● ●
78.0 28 2 ● ●
84.0 30 2 ● ●
89.5 32 2 ● ●
95.0 34 2 ● ● BJC-02-CM(i)
100.0 36 2 ●●
106.5 38 2 ● ●
111.5 40 2 ● ●
117.5 42 2 ● ●
123.0 44 2 ●●
128.5 46 3 ●● ●
134.5 48 3 ● ● ●
139.5 50 3 ● ● ●
145.5 52 3 ● ● ●
151.0 54 3 ● ●●
156.5 56 3 ● ●● BJC-03-CM(i)
161.5 58 3 ●● ●
168.0 60 3 ● ●●
173.0 62 3 ● ●●
179.0 64 3 ● ●●
184.5 66 3 ●●●
190.0 68 4 ●● ●●
196.0 70 4 ● ● ●●
201.0 72 4 ● ● ●●
207.0 74 4 ● ● ●●
212.5 76 4 ● ●●●
218.0 78 4 ● ●●● BJC-04-CM(i)
223.0 80 4 ●● ●●
229.5 82 4 ● ●●●
234.5 84 4 ● ●●●
240.5 86 4 ● ●●●
246.0 88 4 ●●●●
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.
8
4 Combination Ratio
Use the sum of the peak load of each room Use the system peak load
Confirm that the number of indoor units connected to the outdoor units is within limitation
Correct cooling and heating capacities of the outdoor units for the following items:
Outdoor air temperature / Indoor air temperature WB / Combination ratio / Piping length, level
difference / Piping heat loss / Frost accumulation (for heating capacity only)
No
Is corrected outdoor unit capacity ≥ Required total heat load on outdoor units?
Yes
VRF system selection is complete
Notes:
1. If the indoor design temperature falls between two temperatures listed in the indoor unit's capacity table, calculate the corrected capacity by interpolation.
If the indoor unit selection is to be based on total heat load and sensible heat load, select indoor units which satisfy not only the total head load
requirements of each room but also the sensible heat load requirements of each room. As with total heat capacity, the sensible heat capacity of indoor
units should be corrected for indoor temperature, interpolating where necessary. For the indoor unit capacity tables, refer to the indoor unit technical
manuals.
5.2 Example
The following is a selection example based on total heat load for cooling.
Figure 1-6.1: Room plan
Room H Room G
Room A Room F
Room B Room E
Room C Room D
The maximum piping lengths and level differences in this example are as given in Figure 1-6.2.
Figure 1-6.2: System diagram
Outdoor
Unit
Indoor unit type for all rooms: medium static pressure duct (T2).
The number of connected indoor units is 8 and the maximum number of connected indoor units on the 20HP outdoor
unit is 33, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor units:
a) The sum of the indoor unit CIs is 706 and the CI of the 20HP outdoor unit (38VF020H119015) is 560, so the
combination ratio is 706 / 560 = 126%.
b) Using the outdoor units’ cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-6.6 and 1-6.7.
Table 1-6.6: Extract from Table 2-8.7 38VF020H119015 Table 1-6.7: Cooling capacity calculated by
cooling capacity interpolation
Indoor air temp. Indoor air temp.
Outdoor (°C DB / °C WB) Outdoor (°C DB / °C WB)
air 25.8 / 18.0 air 25.8 / 18.0
CR CR
temp. temp.
(°C DB) TC PI (°C DB) TC PI
kW kW kW kW
31 60.0 13.69
130% 33 59.2 14.20 130% 33 59.2 14.20
35 58.2 14.73 1
B = 58.8
31 59.0 13.61
120% 33 58.2 14.12 120% 33 58.2 14.12
35 57.2 14.63
Notes:
1. 58.2 + (59.2 – 58.2) × (126 – 120) / (130 – 120) = 58.8.
c) Find the correction factor for piping length and level difference (“K1”)
Figure 1-6.3: 38VF020H119015 rate of change in cooling capacity
0.81
0.80
0.78
0.78
0.77
0.76
0.84
90
0.85
80
0.87
70
0.90
60
0.92
50 K1 = 0.898
40
0.95
30
0.97
20
1.0
10
0
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
0
-10
1.0
-20
0.97
-30
0.95
-40
-50
0.92
-60
0.90
-70
-80
0.87
-90
0.85
-100
0.84
-110
0.81
0.80
0.78
0.78
0.77
Notes:
1. The horizontal axis shows equivalent length of piping between farthest indoor unit and
first outdoor branch joint; the vertical axis shows the largest level difference between
indoor unit and outdoor unit. For level differences, positive values indicate that the
outdoor unit is above the indoor unit, negative values indicate that the outdoor unit is
below the indoor unit.
The corrected capacity 52.8kW is larger than required total heat load 50.7kW, so selection is complete. (In the event
that the corrected capacity is lower than the required total heat load, Step 3 should be repeated from the point
where the outdoor unit capacity is provisionally selected.)