Mini TVR Plus
4TVH0076GE000AA
4TVH0096GE000AA
4TVH0115GE000AA
CONTENTS
1
2
TVR 50/60Hz
Part 1
General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4
3 Nomenclature ....................................................................................... 7
3
TVR 50/60Hz
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
Table 1-1.1: Indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T2 Medium Static Pressure Duct
4.5 15 1.6 45 45 45 45 45 45 — 45 45 45
5.6 19 2 56 56 56 — 56 56 — 56 56 56
7.1 24 2.5 71 71 71 — 71 71 71 71 71 71
8.0 27 3 80 — — — 80 80 80 80 80 80
9.0 30 3.2 90 — — — 90 90 90 90 90 —
10.0 34 3.6 100 — — — 100 — — — — —
11.2 38 4 112 — — — 112 112 112 — 112 —
14.0 48 5 140 — — — 140 140 140 — 140 —
16.0 55 6 160 — — — — — 160 — 160 —
20.0 68 7 200 — — — — — 200 — — —
25.0 85 9 250 — — — — — 250 — — —
28.0 96 10 280 — — — — — 280 — — —
40.0 136 14 400 — — — — — 400 — — —
45.0 154 16 450 — — — — — 450 — — —
56.0 191 20 560 — — — — — 560 — — —
4
TVR 50/60Hz
2 External Appearance
2.1 Indoor Units
Table 1-2.1: Indoor unit appearance
Q1 Q2
Q4C Q4
T2 T1
G DL
Floor Standing
5
TVR 50/60Hz
2.2 Heat Recovery Ventilator
Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator
6
TVR 50/60Hz
3 Nomenclature
3.1 Indoor Units
4 T V E 0 0 0 7 E F 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Legend
No. Code Remarks
1 4 R-410A
2 T Trane
3 V TVR
Indoor Unit Type
E: One - Way Cassette
G: Two - Way Cassette
B: Compact Four - Way Cassette
C: Four - Way Cassette
4 D: Medium Static Pressure Duct
A: High Static Pressure Duct
7
TVR 50/60Hz
3.2 Heat recovery ventilator
AC Series
T E R V 0 1 2 0 A B 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13
Legend
No. Code Remarks
1 T
2 E Energy recovery Fan
3 R Trane TVR
4 V
5 0
6 1
CFM
7 2
8 0
9 A TVR
1: 380V/60Hz/1Ph
10 B
B: 380/50Hz/1Ph
11 0 Currently not used
12 A First design sequence
Engineering Data Book
8
TVR 50/60Hz
4 Combination Ratio
9
TVR 50/60Hz
5 Selection Procedure
5.1 Procedure
Step 1: Establish design conditions
Use the sum of the peak load of each room Use the system peak load
Confirm that the number of indoor units connected to the outdoor unit is within limitation
Correct cooling and heating capacities of the outdoor unit for the following items:
Outdoor air temperature / Indoor air temperature WB / Combination ratio / Piping length, level
difference / Piping heat loss / Frost accumulation (for heating capacity only)
No
Is corrected outdoor unit capacity ≥ Required total heat load on outdoor unit?
Yes
10
TVR 50/60Hz
5.2 Example
The following is a selection example based on total heat load for cooling.
Figure 1-5.1: Room plan
Room D Room E
Room A
Room B Room C
Outdoor
Unit
Indoor unit type for all rooms: Medium Static Pressure Duct (T2).
11
TVR 50/60Hz
Table 1-5.2: Extract from medium static pressure duct (T2) cooling capacity table
Indoor air temperature
Capacity 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB
Model
index 20°C DB 23°C DB 26°C DB 27°C DB 28°C DB 30°C DB 32°C DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
22 1.5 1.4 1.8 1.5 2.1 1.6 2.2 1.6 2.3 1.7 2.4 1.5 2.4 1.5
28 1.9 1.7 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.1 3.1 2.0 3.1 1.9
36 2.5 2.1 2.9 2.3 3.4 2.5 3.6 2.6 3.8 2.7 4.2 2.8 3.9 2.3
45 3.1 2.6 3.7 2.8 4.2 3.1 4.5 3.2 4.8 3.2 4.9 3.1 5.1 2.9
56 3.9 3.0 4.6 3.3 5.3 3.6 5.6 3.7 5.9 3.8 6.2 3.7 6.2 3.4
T2
71 4.9 3.9 5.8 4.3 6.7 4.7 7.1 4.9 7.5 4.8 7.8 4.6 7.8 4.3
80 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 8.8 5.2 8.8 4.8
90 6.2 5.3 7.3 5.8 8.4 6.3 9.0 6.4 9.6 6.5 9.9 6.1 9.9 5.7
112 7.7 6.4 9.1 7.1 10.5 7.7 11.2 7.8 11.9 8.1 12.5 7.8 12.5 7.4
140 9.7 7.8 11.3 8.6 13.2 9.6 14.0 9.8 14.8 9.8 15.7 9.7 15.4 8.8
Abbreviations:
TC: Total capacity (kW); SHC: Sensible heat capacity (kW)
12
TVR 50/60Hz
Table 1-5.5: Combinations of Indoor and outdoor units
Outdoor unit capacity Sum of capacity indexes of Maximum number of
Capacity connected indoor units (standard connected indoor
kW HP
index indoor units only) units
28.0 10 280 140 to 364 140 to 280
33.5 12 335 167.5 to 435.5 167.5 to 335
The number of connected indoor units is 5 and the maximum number of connected indoor units on the 10HP outdoor
unit is 16, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 314 and the CI of the 10HP outdoor unit (4TVH0096GE000AA) is 280, so the
combination ratio is 314 / 280 = 112%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.6 and 1-5.7.
Table 1-5.6: Extract from Table 2-8.1 4TVH0096GE000AA Table 1-5.7: Cooling capacity calculated by
cooling capacity interpolation
Indoor air temp. Indoor air temp.
Outdoor (°C DB / °C WB) Outdoor (°C DB / °C WB)
air 25.8 / 18.0 air 25.8 / 18.0
CR CR
temp. temp.
(°C DB) TC PI (°C DB) TC PI
kW kW kW kW
13
TVR 50/60Hz
c) Find the correction factor for piping length and level difference (“K1”)
Figure 1-5.3: V4+i rate of change in cooling capacity
H(m)
0.90
0.87
0.85
0.84
0.81
0.92
50
40
0.95
30
0.97
20
1.0
10
0
10 20 30 40 50 60 70 80 90 100 110 120
L(m)
0
-10
1.0
-20
0.97
-30
0.95
-40 0.92
0.90
0.87
0.85
0.84
Notes:
1. The horizontal axis shows equivalent length of piping between farthest indoor unit and
first outdoor branch joint; the vertical axis shows the largest level difference between
indoor unit and outdoor unit. For level differences, positive values indicate that the
outdoor unit is above the indoor unit, negative values indicate that the outdoor unit is
below the indoor unit.
The corrected capacity 26.66 kW is lower than required total heat load 27.5kW, so selection is not complete. Step 3
should be repeated from the point where the outdoor unit capacity is provisionally selected.
The number of connected indoor units is 5 and the maximum number of connected indoor units on the 12HP outdoor
unit is 20, so the number of connected indoor units is within the limitation.
14
TVR 50/60Hz
Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 314 and the CI of the 10HP outdoor unit (4TVH0115GE000AA) is 335, so the
combination ratio is 314 / 335 = 94%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.10 and 1-5.11.
Table 1-5.10: Extract from Table 2-8.2 4TVH0115GE000AA Table 1-5.11: Cooling capacity calculated by
cooling capacity interpolation
Indoor air temp. Indoor air temp.
Outdoor (°C DB / °C WB) Outdoor (°C DB / °C WB)
air 25.8 / 18.0 air 25.8 / 18.0
CR CR
temp. temp.
(°C DB) TC PI (°C DB) TC PI
kW kW kW kW
31 32.84 8.47
100% 33 32.84 8.87 100% 33 32.84 8.87
35 32.84 9.05
B = 29.691
31 28.13 6.77
90% 33 28.13 7.10 90% 33 28.13 7.10
35 28.13 7.24
Notes:
1. 28.13 + (32.84 – 28.13) × (100 – 94) / (100 – 90) = 30.96
15
TVR 50/60Hz
c) Find the correction factor for piping length and level difference (“K1”)
Figure 1-5.4: V4+i rate of change in cooling capacity
H(m)
0.90
0.87
0.85
0.84
0.81
0.92
50
40
0.95
30
0.97
20
1.0
10
0
10 20 30 40 50 60 70 80 90 100 110 120
L(m)
0
-10
1.0
-20
0.97
-30
0.95
-40 0.92
0.90
0.87
0.85
0.84
Notes:
2. The horizontal axis shows equivalent length of piping between farthest indoor unit and
first outdoor branch joint; the vertical axis shows the largest level difference between
indoor unit and outdoor unit. For level differences, positive values indicate that the
outdoor unit is above the indoor unit, negative values indicate that the outdoor unit is
below the indoor unit.
The corrected capacity 27.8 kW is larger than required total heat load 27.5kW, so selection is complete.
16
Part 1 - General Information
16
TVR 50/60Hz
TVR 50/60Hz
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 18
17
TVR 50/60Hz
1 Layout of Functional Components
Figure 2-1.1: front view Figure 2-1.2: side view
Tf
6
SV2
8
SV4
9
TL 7
SV7
2
3 10
12
11
4 T5
T3
Service Manual
Legend
No. Parts name No. Parts name
1 Compressor 11 Stop valve (gas side)
2 High pressure switch 12 Stop valve (liquid side)
3 High pressure sensor T3 Heat exchanger temperature outlet sensor
4 Oil separator T4 Outdoor ambient temperature sensor
5 Four-way valve T5 Discharge temperature sensor
6 Heat exchanger Tf Heat sink temperature sensor
7 Electronic expansion valve (EXV) TL Refrigerant cooling pipe temperature sensor
8 Fan SV2 Liquid injection valve
9 Low pressure switch SV4 Oil return valve
10 Accumulator SV7 Refrigerant bypass valve
18
TVR 50/60Hz
2 Piping Diagrams
Figure 2-1.1: 8HP piping diagram
11
SV7
SV2
9 12
2 3
T5 T4 Tf
5
10 1 4
TL
6 7
T3
11
SV7
SV2
9 12
2 3
T5 T4 Tf
5
10 1 4
TL
SV4 6 7
T3
8
Legend
No. Parts name No. Parts name
1 Compressor 11 Stop valve (gas side)
2 High pressure switch 12 Stop valve (liquid side)
3 High pressure sensor T3 Heat exchanger temperature sensor
4 Oil separator T4 Outdoor ambient temperature sensor
5 Four-way valve T5 Discharge temperature sensor
6 Heat exchanger Tf Heat sink temperature sensor
7 Electronic expansion valve (EXV) TL Refrigerant cooling pipe temperature sensor
8 Fan SV2 Liquid injection valve
9 Low pressure switch SV4 Oil return valve
10 Accumulator SV7 Refrigerant bypass valve
19
TVR 50/60Hz
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 98°C, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
below 85°C.
6. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
7. Solenoid valve SV7:
Allows refrigerant return to the compressor directly. Opens when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off.
Service Manual
20
TVR 50/60Hz
3 Refrigerant Flow Diagrams
Cooling operation
Figure 2-3.1: refrigerant flow during cooling operation (8HP outdoor unit doesn’t has SV4)
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Unit on
11 Fan Thermostat on
on
SV7
Filter Filter
SV2
Normal control
9 12
2
T5 3
Fan Unit on
T4 Tf on Thermostat on
5 Filter Filter
8
Unit on
Fan Thermostat off
on
Filter Filter
Closed
Unit on
11 Fan Thermostat on
on
SV7
Filter Filter
SV2
Normal control
9 12
2 T5 3
Fan Unit on
T4 Tf on Thermostat on
5 Filter Filter
8
Unit on
Fan Thermostat off
on
Filter Filter
300 steps
21
TVR 50/60Hz
Heating operation
Figure 2-3.3: refrigerant flow during heating operation (8HP outdoor unit doesn’t has SV4)
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Unit on
11 Fan Thermostat on
on
SV7
Filter Filter
SV2
Normal control
9 12
2 T5 3
Fan Unit on
T4 Tf on Thermostat on
5 Filter Filter
8
Unit on
Fan Thermostat off
on
Filter Filter
96 steps
Unit on
11 Fan Thermostat on
on
SV7
Filter Filter
SV2
Normal control
9 12
2 3
T5
Fan Unit on
T4 Tf on Thermostat on
5 Filter Filter
TL
Fan Unit off
SV4 6 7 off
Filter Filter
T3
480steps
8
Unit on
Fan Thermostat off
on
Filter Filter
480 steps
22
TVR 50/60Hz
Defrosting operation
Figure 2-3.5: refrigerant flow during defrosting operation (8HP outdoor unit doesn’t has SV4)
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Unit on
11 Fan Thermostat on
on
SV7
Filter Filter
SV2
480steps
9 12
2 3
T5
Fan Unit on
T4 Tf on Thermostat on
5 Filter Filter
TL
Fan Unit off
6 7 off
SV4 Filter
Filter
T3
480steps
480 steps
23
Service Manual
24
TVR 50/60Hz
TVR 50/60Hz
Part 3
Control
1 General Control Scheme Flowchart ...................................................... 26
Part 3 - Control
7 Special Control..................................................................................... 34
25
TVR 50/60Hz
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated.
2
Stop operation
Abnormal shutdown
System stop
3
Standby control
Crankcase heater control
Thermo on
4
Startup control
Compressor startup delay control
Startup control for cooling operation
Startup control for heating operation
Series Service Manual
5 7
Normal operation control Special control
Component control during normal operation Conditions met
Compressor output control for oil return Oil return operation
Compressor step control
Conditions met
Electronic expansion valve control
for defrosting
Outdoor fan control Defrosting operation
6
Protection control
High pressure protection control
Low pressure protection control
Discharge temperature protection control
Legend
Compressor and inverter module protection Numbers in the top right-hand
control corners of boxes indicate the
relevant section of text on the
Disable heating control following pages.
26
TVR 50/60Hz
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3 Standby Control
3.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressor is stopped. The
crankcase heater is controlled according to outdoor ambient temperature and the compressor on/off state. When the
outdoor ambient temperature is above 8°C or the compressor is running, the crankcase heater is off; when the outdoor
ambient temperature is at or below 8°C and either the compressor has been stopped for more than 3 hours or the unit has
just been powered-on (either manually or when the power has returned following a power outage), the crankcase heater
turns on.
Part 3 - Control
27
TVR 50/60Hz
4 Startup Control
4.1 Compressor Startup Delay Control
In initial startup control and in restart control (except in oil return operation and defrosting operation), compressor startup
is delayed such that a minimum of 5 minutes has elapsed since the compressor stopped, in order to prevent frequent
compressor on/off and to equalize the pressure within the refrigerant system.
SV2 ● Off
injection)
Solenoid valve (oil balance) SV4 ● Closed for 200 secs, open for 600 secs, then closed
Solenoid valve (indoor units Open for 5 mins, then controlled according to indoor heat exchanger
SV7 ●
bypass) refrigerant outlet temperature (T2B)
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.5 “Outdoor Fan Control”.
28
TVR 50/60Hz
4.3 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode
Wiring diagram
Component 8-12Hp Control functions and states
label
Controlled according to load requirement, operating frequency
Inverter compressor COMP ●
increased by 1 step / sec
Fan speed1 controlled according to ambient temperature (T4) and
Upper DC fan motor FAN_UP ●
discharge pressure (Pc):
T4 ≥ 0oC, start up after the compressor running for 10s.
Lower DC fan motor FAN_DOWN ●
T4 < 0oC, start up after the compressor running for 30s.
Position (steps) from 0 (fully closed) to 480 (fully open), controlled
Electronic expansion valve EEV ●
according to discharge superheat temperature
Four-way valve ST1 ● On
Solenoid valve (liquid refrigerant
SV2 ● Off
injection)
Solenoid valve (oil balance) SV4 ● Closed for 200 secs, open for 600 secs, then closed
Solenoid valve (indoor units When T4 < 3oC and compressor frequency is ≥ 52Hz , open for 10
SV7 ●
bypass) minutes and then closed
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.5 “Outdoor Fan Control”.
Part 3 - Control
29
TVR 50/60Hz
5 Normal Operation Control
5.1 Component Control during Normal Operation
Table 3-5.1: Component control during normal cooling operation
Wiring diagram
Component 8-12Hp Control functions and states
label
Inverter compressor COMP ● Controlled according to load requirement
Upper DC fan motor FAN_UP ●
Fan speed1 controlled according to ambient temperature (T4) and
Lower DC fan motor FAN_DOWN ● discharge pressure (Pc):
Position (steps) from 0 (fully closed) to 480 (fully open), controlled
Electronic expansion valve EEV1 ●
according to discharge temperature
Four-way valve ST1 ● Off
Solenoid valve (liquid refrigerant Open when compressor discharge temperature rises above 98°C,
SV2 ●
injection) closes again once the discharge temperature has fallen below 85°C
Solenoid valve (oil balance) SV4 ● Opens for 3 minutes every 20 minutes
Solenoid valve (indoor units Controlled according to indoor heat exchanger refrigerant outlet
SV7 ●
bypass) temperature (T2B)
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.5 “Outdoor Fan Control”.
30
TVR 50/60Hz
5.2 Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
unit first estimates the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures.
In cooling mode:
When the outdoor unit is in standby:
EXV is at position 352 (steps).
When the outdoor unit is running:
EXV is controlled according to discharge temperature.
Part 3 - Control
In heating mode:
When the outdoor unit is in standby:
EXV is at position 352 (steps).
When the outdoor unit is running:
EXV is controlled according to discharge superheat.
31
TVR 50/60Hz
6 Protection Control
6.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
Figure 3-6.1: High pressure protection control
Normal operation
Notes:
1. Pc: Discharge pressure
When the discharge pressure rises above 4.4MPa the system displays P1 protection and the unit stops running. When the
discharge pressure drops below 3.2MPa, the compressor enters re-start control.
pressure.
Figure 3-6.2: Low pressure protection control
Normal operation
Normal operation
When the discharge temperature rises above 110°C the system displays P4 protection and the unit stops running. When
the discharge temperature drops below 85°C, the compressor enters re-start control.
When P4 protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system
restart is required before the system can resume operation.
32
TVR 50/60Hz
6.4 Compressor and Inverter Module Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally
high temperatures.
Figure 3-6.4: Compressor current protection control
Normal operation
Normal operation
Part 3 - Control
Compressor output reduced Tf < 66oC
Tf ≥ 72oC
Notes:
1. Tf: Heat sink temperature
Heating operation
Units stop
33
TVR 50/60Hz
7 Special Control
7.1 Oil Return Operation
In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby.
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode.
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode
Wiring diagram
Component 10Hp/12Hp Control functions and states
label
Inverter compressor COMP ● Controlled according to load requirement
Upper DC fan motor FAN_UP ●
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode
Component Unit state Control functions and states
Thermo on Remote controller setting
Fan Standby Off
Thermo off Off
Thermo on Normal control
Electronic expansion valve Standby 300 (steps)
Thermo off 300 (steps)
34
TVR 50/60Hz
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode.
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode
Wiring diagram
Component 10Hp/12Hp Control functions and states
label
Inverter compressor COMP ● Controlled according to load requirement
Fan speed controlled according to outdoor ambient
Upper DC fan motor FAN_UP ●
temperature (T4), outdoor unit heat exchanger
refrigerant temperature (T3) and discharge pressure
Lower DC fan motor FAN_DOWN ●
(Pc)
Electronic expansion valve EEV1 ● Position 350 (steps)
Four-way valve ST1 ● Off
Solenoid valve (liquid refrigerant
SV2 ● Normal control
injection)
Solenoid valve (oil balance) SV4 ● Normal control
Solenoid valve (indoor units
SV7 ● Normal control
bypass)
Table 3-7.4: Indoor unit component control during oil return operation in heating mode
Component Unit state Control functions and states
Thermo on Normal control
Fan Standby Off
Thermo off Off
Thermo on Normal control
Part 3 - Control
Electronic expansion valve Standby 480 (steps)
Thermo off 480 (steps)
35
TVR 50/60Hz
7.2 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor
heat exchanger temperature, indoor heat exchanger temperature and outdoor unit running time. When the outdoor unit is
running in defrosting, the digital display on outdoor main PCB will display “df”.
Table 3-7.5: Outdoor unit component control during defrosting operation
Wiring diagram
Component 10Hp/12Hp Control functions and states
label
Inverter compressor COMP ● Controlled according to load requirement
Upper DC fan motor FAN_UP ●
Off
Lower DC fan motor FAN_DOWN ●
Thermo on Off
Fan Standby Off
Thermo off Off
Thermo on 480 (steps)
Electronic expansion valve Standby 480 (steps)
Thermo off 480 (steps)
36
TVR 50/60Hz
Part 4
Field Settings
1 Outdoor Unit Field Settings ................................................................. 38
37
TVR 50/60Hz
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches
PCB switches
ENC1 ENC3 S9
S1 S2
Service Manual
38
TVR 50/60Hz
Table 4-1.1: Outdoor unit main PCB switch settings
Switch Setting Switch positions1 Description
The number of indoor units is in the range 0-15
ENC1 S9-3 0-9 on ENC1 indicate 0-9 indoor units; A-F on ENC1 indicate 10-15 indoor units
Number of
indoor units
The number of indoor units is in the range 16-31
0-9 on ENC1 indicate 16-25 indoor units; A-F on ENC1 indicate 26-31 indoor units
ENC3
Network
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0)
address
No action (default)
Clear indoor
unit
S1-2 addresses
Clear indoor unit addresses
Reserved Reserved
S1-3
Cooling priority
First on priority
Priority
S2 mode3
Heating only
Cooling only
Heating priority3
8HP
Outdoor unit
10Hp
S9-1 capacity5
12Hp
Reserved Reserved
S9-3
Notes:
1. Black denotes the switch position.
2. When the system connected to both 2nd generation IDU and AC or 1st generation IDU, SW1-1 should be positioned to 1. The VRF-AHU control kit should
be treated as AC IDU.
3. Refer to Part 4, 1.2.1 “Priority mode setting”.
4. When S2 in other switch positions not mentioned above indicates heating priority mode.
5. Switch S9 is factory-set and its setting should not be changed.
39
TVR 50/60Hz
1.2 Modes Set on Main PCB
1.2.1 Priority mode setting
Priority mode can only be set on the outdoor unit. When an indoor unit is in mode conflict with the outdoor units the unit
displays the mode conflict error. The digital display on indoor main PCB will display error code E0.
Figure 4-1.2: Indoor unit digital displays
13oC
Heating priority
41
Service Manual
42
TVR 50/60Hz
TVR 50/60Hz
Part 5
Electrical Components and
Wiring Diagrams
1 Outdoor Unit Electric Control Box Layout .............................................. 44
43
TVR 50/60Hz
1 Outdoor Unit Electric Control Box Layout
Figure 5-1.1: front view of electric control box
Main PCB
Communication
terminals block
Reactor
Inverter module
44
TVR 50/60Hz
2 Outdoor Unit Main PCB
2.1 Ports
Figure 5-2.1: Outdoor unit main PCB ports1
① ② ③
④
⑤
⑥
⑦
⑩
19
18 11
17
16
12
15
14 13
Notes:
1. Label descriptions are given in Table 5-2.1.
45
TVR 50/60Hz
Table 5-2.1: Main PCB ports
Label in
Port code Content Port voltage
Figure 5-2.1
220V AC between A/B/C and N;
1 CN30 Power input of main board
380V AC between A,B and C
2 CN36 Inverter module connection 0V or 5V DC
3 CN4 Control port of filter board 0V or 12V DC
4 CN14 Heat sink temperature sensor (Tf) connection 0-5V DC (varying)
5 CN24 Refrigerant cooling pipe temperature sensor (TL) connection 0-5V DC (varying)
6 CN5 Discharge pipe temperature sensor (T5) connection 0-5V DC (varying)
Heat exchanger temperature sensor (T3A) connection
7 CN8 0-5V DC (varying)
(Reserved)
8 CN12 High pressure sensor and low pressure sensor connections 0-5V DC (varying)
9 CN6 High pressure switch connection 0V or 5V DC
Heat exchanger temperature sensor outlet (T3) and ambient
10 CN9 0-5V DC (varying)
temperature sensor (T4) connections
11 CN22 EEV drive port 0V or 12V DC
12 CN20 Communication port 0-5V DC (varying)
13 CN53 DC fan motor power supply connection 310V DC
CN107
14 DC fan motor control port 0-310V DC (varying)
CN109
Service Manual
46
TVR 50/60Hz
2.2 Components
2.2.1 Layout
Figure 5-2.2: Outdoor unit main PCB components
Display
Dial switches
Button Function
SW3 (UP) In menu mode: previous and next buttons for menu modes.
Not in menu mode: previous and next buttons for system
SW4 (DOWN)
check information.
47
TVR 50/60Hz
2.2.3 Menu mode
1. Long press SW1 “MENU” button for 5 seconds to enter menu mode, and the digital display displays “n1”;
2. Press SW3 / SW4 “UP / DOWN” button to select the first level menu “n1”, “n2”, “n3”, “n4”, “nb” or “nF”;
3. Press SW2 “OK” button to enter specified first level menu, for example, enter “n3” mode;
4. Press SW3 / SW4 “UP / DOWN” button to select the second level menu from “n31” to “n34”;
5. Press SW2 “OK” button to enter specified second level menu, for example, enter “n32” mode;
Start
SW1 “MENU”
Short press
button
button to enter
specified first level
menu “-nX”
Digital display displays “-nX1”
DOWN” button to
Short press
button
48
TVR 50/60Hz
Menu mode function:
Table 5-2.3: Menu mode function
Digital display
Menu mode Remarks
content
n14 Force cooling mode All indoor units running in cooling mode
n16 Maintenance mode The system does not check the indoor units’ number.
It is only used in maintenance process. The digital display displays “R01”, and all solenoid
n27 Vacuum mode
valves are opened and EXVs are positioned to 480 steps.
In the non-menu selection state, long press SW2 “OK” button for 3s, it will automatically exit all test modes.
49
TVR 50/60Hz
2.2.4 UP / DOWN system check button
Before pressing UP or DOWN button, make sure that the system has been operating steadily for more than one hour. On
pressing UP or DOWN button, the parameters listed in Table 5-2.5 will be displayed in sequence.
Table 5-2.5: System check
DSP
Parameters displayed on DSP Remarks
content
0.-- Unit capacity (Hp) Actual value = value displayed
1.-- Setting number of indoor units
2.-- Operating mode Refer to Note 1
3.-- Fan speed index Refer to Note 2
4.-- Total capacity of outdoor unit
5.-- Total capacity requirement of indoor units
6.-- Main heat exchanger pipe (T3) temperature (°C) Actual value = value displayed
7.-- Outdoor ambient (T4) temperature (°C) Actual value = value displayed
8.-- Inverter compressor discharge temperature (°C) Actual value = value displayed
9.-- Invert module (TF) temperature (°C) Actual value = value displayed
10.-- Refrigerant cooling pipe (TL) temperature (°C) Actual value = value displayed
11.-- Compressor discharge pressure (MPa) Actual value = value displayed × 0.1
12.-- Discharge superheat degree (°C) Actual value = value displayed
13.-- EXVA position Actual value = value displayed × 8
Service Manual
Notes:
1. Operating mode:
0: off; 2: cooling; 3: heating; 4: forced cooling.
2. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 9 (fastest).
3. Priority mode:
0: heating priority; 1: cooling priority; 2: first ON priority; 3: heating only; 4: cooling only; 5: test mode 1; 6: test mode 2.
50
TVR 50/60Hz
2.2.5 Digital display output
Table 5-2.6: Digital display output in different operating states
51
TVR 50/60Hz
3 Compressor Inverter Module
3.1 Ports
Figure 5-3.1: Outdoor unit inverter module ports1
⑧
①
LED
3-phase bridge
rectifier power input ⑩
3-phase bridge
rectifier power output
Service Manual
④
⑤
⑥
⑦
Notes:
1. Label descriptions are given in Table 5-3.1.
52
TVR 50/60Hz
Table 5-3.1: Inverter module ports
Label in
Port code Content Port voltage
Figure 5-2.1
1 CN6 Power input L1 of inverter module 380V AC
2 CN7 Power input L2 of inverter module 380V AC
3 CN11 Power input L3 of inverter module 380V AC
Above 156V DC (varying according to
4 CN12 Power output U of inverter module to compressor
frequency)
Above 156V DC (varying according to
5 CN13 Power output V of inverter module to compressor
frequency)
Above 156V DC (varying according to
6 CN14 Power output W of inverter module to compressor
frequency)
7 CN2 DC power supply input 310V DC
8 CN8 Main PCB connection 0-5V DC (varying)
Inverter module operating indicator. Continuously on if the compressor is running normally and
LED 1
flashing if an inverter module error has occurred1.
LED 2 Inverter module error indicator. Continuously on if an inverter module error has occurred1.
Note:
1. If an inverter module error occurs, refer to Part 6, “H4 Troubleshooting”. The error code is displayed on the digital display.
53
TVR 50/60Hz
4 Filter Board
4.1 Ports
Figure 5-4.1: Outdoor unit filter board ports1
⑩ ⑨ ⑧
①
⑦
11
Service Manual
Notes:
1. Label descriptions are given in Table 5-4.1.
③ ④ ⑤ ⑥
54
TVR 50/60Hz
Table 5-4.1: Filter board ports
Label in
Port code Content Port voltage
Figure 5-4.1
1 CN8 Control port of filter board 12V DC
CN211 Power supply to inverter board (CN211) and DC fan motor
2 310V DC
CN212 (CN212) of filter board
220V AC between L1/L2/L3 and N;
3 CN203 Power input N of filter board
380V AC between L1,L2 and L3
220V AC between L1/L2/L3 and N;
4 CN200 Power input L1 of filter board
380V AC between L1,L2 and L3
220V AC between L1/L2/L3 and N;
5 CN201 Power input L2 of filter board
380V AC between L1,L2 and L3
220V AC between L1/L2/L3 and N;
6 CN202 Power input L3 of filter board
380V AC between L1,L2 and L3
55
Service Manual
56
TVR 50/60Hz
5 Wiring Diagrams
CN22
PED-
MD-
Figure 5-5.1: 10Hp/12HP wiring diagram
BOARD
CN23
or shorting stub
CN30(CN11)
(CN10) PE1(GND1)
Part 6
Diagnosis and
Troubleshooting
1 Error Code Table .................................................................................. 58
2 Troubleshooting .................................................................................. 59
57
TVR 50/60Hz
1 Error Code Table
Table 6-1.1: Error code table
P5 Outdoor heat exchanger temperature protection Displayed on the outdoor unit PCB No
PE Indoor heat exchanger temperature protection Displayed on the outdoor unit PCB No
PL Heat sink high temperature protection Displayed on the outdoor unit PCB No
L0 Inverter module protection Displayed on the outdoor unit PCB Yes
L1 DC bus low voltage protection Displayed on the outdoor unit PCB Yes
L2 DC bus high voltage Heat sink temperature sensor protection Displayed on the outdoor unit PCB Yes
L4 MCE error Displayed on the outdoor unit PCB Yes
L5 Zero speed protection Displayed on the outdoor unit PCB Yes
L7 Phase sequence error Displayed on the outdoor unit PCB Yes
Compressor frequency variation greater than 15Hz within one
L8 Displayed on the outdoor unit PCB Yes
second protection
Actual compressor frequency differs from target frequency by
L9 Displayed on the outdoor unit PCB Yes
more than 15Hz protection
Notes:
1. For some error codes, a manual restart is required before the system can resume operation.
58
TVR 50/60Hz
2 Troubleshooting
2.1 Warning
Warning
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
59
TVR 50/60Hz
2.2 E1: Phase sequence error
2.2.1 Digital display output
2.2.2 Description
Phase sequence error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
60
TVR 50/60Hz
2.2.5 Procedure
E1
The phase sequence of the 3-phase Yes Exchange any two of the 3 phase wires
power supply is incrorrect1
No
Notes:
1. The L1, L2, L3 terminals of the 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the
compressor will operate inversely.
2. Loose power supply terminals can cause the compressor to operate abnormally and compressor current to be very large.
61
TVR 50/60Hz
2.3 E2: Communication error between indoor and outdoor unit
2.3.1 Digital display output
2.3.2 Description
Communication error between indoor and outdoor unit.
The system stops running.
Error code is displayed on the outdoor unit PCB.
62
TVR 50/60Hz
2.3.5 Procedure
E2
No
Interference from high voltage (220V or Yes Ensure the communication wires and
higher) wires high voltage wires are separated
No
The length of communication wire is over Yes Reduce the wire length to less than
1200m 1200m or strengthen the signal
No
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.
63
TVR 50/60Hz
2.4 E4: Temperature sensor (T3/T4) error
2.4.1 Digital display output
2.4.2 Description
Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
64
TVR 50/60Hz
2.4.5 Procedure
E4
Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
65
TVR 50/60Hz
2.5 E5: Abnormal power supply voltage
2.5.1 Digital display output
2.5.2 Description
Abnormal power supply voltage.
The system stops running.
Error code is displayed on the outdoor unit PCB.
66
TVR 50/60Hz
2.5.5 Procedure
E5
Notes:
1. The normal voltage between L1and N, L2 and N, and L3 and N is 172-265V.
2. Control port of filter board is CN4 on the main PCB (labeled 3 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
67
TVR 50/60Hz
2.6 E6, Eb: DC fan motor error
2.6.1 Digital display output
2.6.2 Description
DC fan motor error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
Recover condition: Actual fan speed is > 120 rps and the actual fan speed differs from target speed less than 200rps.
Reset method: Resume automatically.
For E6 protection: Resume automatically.
For Eb protection: Manually restart.
68
TVR 50/60Hz
2.6.5 Procedure
E6, Eb
DC fan motor connection on main PCB or Yes Ensure the wires are connected properly
filter board is loose1
No
The voltage of CN53 terminals is 310V Yes Replace the filter board
No
Notes:
1. DC fan motor connections on main PCB are ports CN017, CN109 (labeled 14 in Figure 5-2.1 in Part 5, 2.1 “Ports”) and CN53 (labeled 13 in Figure 5-2.1 in
Part 5, 2.1 “Ports”). DC fan motor connection on filter board is ports CN212 (labeled 2 in Figure 5-4.1 in Part 5, 4.1 “Ports”).
DC fan motor connection ports CN36 on main PCB DC fan motor connection port CN212 on filter board
69
TVR 50/60Hz
2.7 E7: Temperature sensor (T5) error
2.7.1 Digital display output
2.7.2 Description
A compressor discharge pipe temperature sensor (T5) error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
70
TVR 50/60Hz
2.7.5 Procedure
E7
Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
71
TVR 50/60Hz
2.8 EH: Outdoor refrigerant cooling pipe temperature sensor (TL) error
2.8.1 Digital display output
2.8.2 Description
An outdoor refrigerant cooling pipe temperature sensor (TL) error.
The system stops running.
Error code is displayed on the outdoor unit PCB.
72
TVR 50/60Hz
2.8.5 Procedure
EH
Refrigerant cooling pipe temperature Yes Ensure the sensor is connected properly
sensor connection on main PCB is loose1
No
Notes:
1. Outdoor refrigerant cooling pipe temperature sensor connection is port CN24 on the main PCB (labeled 5 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
73
TVR 50/60Hz
2.9 F1: DC bus voltage error
2.9.1 Digital display output
2.9.2 Description
F1 indicates compressor DC bus voltage error.
The system stops running.
Error code is displayed on the unit with the error.
74
TVR 50/60Hz
2.9.5 Procedure
75
TVR 50/60Hz
2.10 H0: Communication error
2.10.1 Digital display output
2.10.2 Description
H0 indicates a communication error between the main control chip and the compressor inverter driver chip.
The system stops running.
Error code is displayed on the outdoor unit PCB.
76
TVR 50/60Hz
2.10.5 Procedure
H0
Communication wire from main PCB Yes Reconnect the communication wire
CN36 to invert module CN8 is loose1
No
Both LED1 and LED2 on the inverter Yes Check the power supply circuit3
module are off when power on2
No
Notes:
1. Communication wire from outdoor main PCB CN36 to inverter module CN8.
Communication port CN36 on main PCB Communication port CN8 on inverter module
3. Check the power supply for the compressor inverter module, port CN211 on filter board, the normal voltage should be DC310V; Check the single phase
bridge and fuse on filter board; check the connection cable from ODU main PCB port CN4 to filter board port CN8 which is 12V DC power control port.
Communication port CN4 on main PCB Communication port CN8 and fuse on filter board
77
TVR 50/60Hz
2.11 H4: Inverter module protection
2.11.1 Digital display output
2.11.2 Description
H4 indicates compressor inverter module protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
78
TVR 50/60Hz
The specific error codes L0, L1, L2 and L4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.
79
TVR 50/60Hz
2.11.6 L0: Inverter module protection
L0 protection
Service Manual
80
TVR 50/60Hz
2.11.7 L1: DC bus low voltage protection
L1 protection
No
Yes
No output from bridge rectifier
No
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
Figure 6-2.3: P and N terminals on Inverter module
81
TVR 50/60Hz
2.11.8 L2: DC bus high voltage protection
L2 protection
No
No
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Figure 6-2.4: P and N terminals on Inverter module
Service Manual
82
Part 6 - Diagnosis and Troubleshooting
83
TVR 50/60Hz
2.11.9 L4: MCE error
TVR 50/60Hz
2.11.10 L5: Zero speed protection
L5 protection
84
TVR 50/60Hz
2.11.11 L7: Phase sequence error
85
TVR 50/60Hz
2.11.12 L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection
Service Manual
86
TVR 50/60Hz
2.11.13 Compressor replacement procedure Figure 6-2.5: Draining oil from a compressor
Step 1: Remove faulty compressor and remove oil
Remove the faulty compressor from the outdoor unit.
Before removing the oil, shake the compressor so as to not allow
impurities to remain settled at the bottom.
Drain the oil out of the compressor and retain it for inspection.
Normally the oil can be drained out from the compressor discharge
pipe.
Step 6: Replace the faulty compressor and re-fit the other compressors Figure 6-2.6: Compressor piping
88
TVR 50/60Hz
2.12 H7: Unmatched total number of indoor units
2.12.1 Digital display output
2.12.2 Description
Number of indoor units detected by the outdoor unit not same as number set on main PCB.
The system stops running.
Error code is displayed on the outdoor unit PCB.
89
TVR 50/60Hz
2.12.5 Procedure
H7
Number of indoor units set on main PCB Change the setting on the PCB to be the
not same as actual number of indoor Yes same as the actual number of indoor
units1 units
No
Some indoor units are powered off Yes Power on all indoor units
No
After re-starting the ODUs and IDUs and Refer to indoor unit troubleshooting
then waiting 6 minutes, an IDU displays Yes guide. Resolving the indoor unit error
an E1 or FE error2 resolves the outdoor unit error
No
Yes
Notes:
1. The number of indoor units can be set on switches ENC1 and S9-3 on the main PCB.
2. Indoor unit error code E1 indicates a communication error between indoor and outdoor unit. Indoor unit error code FE indicates that an indoor unit has
not been assigned an address.
3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the outdoor unit.
90
TVR 50/60Hz
2.13 H8: High pressure sensor error
2.13.1 Digital display output
2.13.2 Description
High pressure sensor error.
The system stops running.
Error code is displayed on the unit with the error.
91
TVR 50/60Hz
2.13.5 Procedure
H8
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
Insufficient refrigerant caused by Yes Add refrigerant and inspect system for
refrigerant leakage3 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, closed EXV or Yes filter is blocked by ice, the piping should
dirty filter4 be cleaned
No
Service Manual
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Notes:
1. High pressure sensor connection is port CN12 on the main PCB (labeled 8 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
92
TVR 50/60Hz
2.14 P1: Discharge pipe high pressure protection
2.14.1 Digital display output
2.14.2 Description
Discharge pipe high pressure protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.14.5 Procedure
P1
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
93
TVR 50/60Hz
… flowchart continued from previous page
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV5
No
The condenser heat exchange is poor6 Yes Inspect the system and fix the error
No
Notes:
1. The high pressure sensor connection is port CN12 on the main PCB (labeled 8 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
94
TVR 50/60Hz
2.15 P2, H5: Suction pipe low pressure protection
2.15.1 Digital display output
2.15.2 Description
Suction pipe low pressure protection.
The system stops running.
Error code is displayed on outdoor unit PCB.
95
TVR 50/60Hz
2.15.5 Procedure
P2 / H5
ODU stop valves are closed Yes Open the stop valves
No
Insufficient refrigerant caused by Yes Add refrigerant or inspect the system for
refrigerant leakage1 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, blocked EXV, or Yes filter is blocked by ice, the piping should
dirty filter2 be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Service Manual
Notes:
1. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
3. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
96
TVR 50/60Hz
2.16 P3: Compressor current protection
2.16.1 Digital display output
2.16.2 Description
P3 indicates current protection on compressor.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.16.5 Procedure
P3
ODU stop valves are closed Yes Open the stop valves
No
The power supply is abnormal Yes Check the power supply equipment
No
Sudden interruption of power to IDUs Yes Inspect the system and fix the error
No
Flowchart continued on next page …
97
TVR 50/60Hz
… flowchart continued from previous page
The condenser heat exchange is poor4 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV5
No
No
No
Notes:
1. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
2. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
3. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
7. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
98
TVR 50/60Hz
2.17 P4: Discharge temperature protection
2.17.1 Digital display output
2.17.2 Description
Discharge temperature protection.
The system stops running.
Error code is displayed on the unit with the error.
2.17.5 Procedure
P4
ODU stop valves are closed Yes Open the stop valves
No
99
TVR 50/60Hz
… flowchart continued from previous page
Insufficient refrigerant caused by Yes Add refrigerant and inspect the system
refrigerant leakage3 for leaks
No
The condenser heat exchange is poor7 Yes Inspect the system and fix the error
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”). The discharge temperature switch connection is port CN18 on the main PCB (labeled 2 in Figure 5-2.1 in
Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
7. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
100
TVR 50/60Hz
2.18 P5: Outdoor heat exchanger temperature protection
2.18.1 Digital display output
2.18.2 Description
Outdoor heat exchanger temperature protection.
The system stops running.
Error code is displayed on the unit with the error.
101
TVR 50/60Hz
2.18.5 Procedure
P5
ODU stop valves are closed Yes Open the stop valves
No
Outdoor heat exchanger temperature Yes Ensure the sensor is connected properly
sensor connection on main PCB is loose1
No
The condenser heat exchange is poor5 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV6
No
Notes:
1. Outdoor heat exchanger temperature sensor connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”
3. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
102
TVR 50/60Hz
2.19 P8: Typhoon protection
2.19.1 Digital display output
2.19.2 Description
P8 indicates strong wind protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
103
TVR 50/60Hz
2.19.5 Procedure
P8
There is strong wind around the outdoor Yes Wait unit the strong wind stops1
unit
No
Notes:
1. P8 protection recovers in 2 minutes when the strong wind stops.
Service Manual
104
TVR 50/60Hz
2.20 PL: Inverter module temperature protection
2.20.1 Digital display output
2.20.2 Description
PL indicates inverter module temperature protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
105
TVR 50/60Hz
2.20.5 Procedure
PL
The inverter module heat sink is blocked Yes Clean or replace the heat sink
or dirty
No
The screws connecting the heat sink to Yes Tighten the screws and make sure the
the inverter module are loose heat sink is well-connected
No
Heat sink temperature sensor connection Yes Ensure the sensor is connected properly
on main PCB is loose1
No
Notes:
2. Heat sink temperature sensor connection is port CN14 on the main PCB (labeled 4 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
3. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.3 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
106
TVR 50/60Hz
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics
Table 6-3.1: Outdoor ambient temperature sensor, outdoor heat exchanger temperature sensor and refrigerant cooling pipe temperature
sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
-20 115.3 20 12.64 60 2.358 100 0.6297
-19 108.1 21 12.06 61 2.272 101 0.6115
-18 101.5 22 11.50 62 2.191 102 0.5939
-17 96.34 23 10.97 63 2.112 103 0.5768
-16 89.59 24 10.47 64 2.037 104 0.5604
-15 84.22 25 10.00 65 1.965 105 0.5445
-14 79.31 26 9.551 66 1.896 106 0.5291
-13 74.54 27 9.124 67 1.830 107 0.5143
-12 70.17 28 8.720 68 1.766 108 0.4999
108
TVR 50/60Hz
Table 6-3.3: Heat sink temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
109
TVR 50/60Hz
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 6-3.4 and 6-3.5 should be observed:
The outdoor unit can detect all the indoor units.
The number of indoor units displayed on DSP is steady and is equal to the actual number of indoor units installed.
All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB.
All the indoor units are currently running.
If the outdoor ambient temperature is high, the system is being run in cooling mode with the following settings:
temperature 17°C; fan speed high.
If the outdoor ambient temperature is low, the system is being run in heating mode with the following settings:
temperature 30°C; fan speed high.
The system has been running normally for more than 30 minutes.
110