NOTES:
1. ALL DIMENSION ARE IN MILLIMETER UNLESS
OTHERWISE SPECIFIED.

2. SIZE AND THE NUMBER OF CABLES RUN IN THIS


CABLE TRENCH. ACTUAL CABLE ARRANGEMENT SHALL
BE DECIDED BY CONTRACTOR ACCORDING TO SITE
CONDITION AND EQUIPMENT LOCATION.

OF
3. FOR MINIMUM DEPTH OF BURIAL REQUIREMENTS OF

CONSENT
UNDERGROUND INSTALLATION SEE SAUDI ARAMCO
YELLOW WARNING YELLOW WARNING YELLOW WARNING STANDARD DWG. AD-036874.
TAPE TAPE TAPE
50mm THICK PRE-CAST 50mm THICK PRE-CAST 50mm THICK PRE-CAST 4. CABLE INSTALLATION SHALL COMPLY WITH SAUDI
RED CONCRETE TILE RED CONCRETE TILE RED CONCRETE TILE ARAMCO STANDARD SAES-P-104.
FINISHED GRADE LEVEL FINISHED GRADE LEVEL FINISHED GRADE LEVEL

TTEN
5. REFER TO SAUDI ARAMCO STANDARD DRAWINGS

620
BACKFILL AD-036874, AB-036326 AND AB-036273 FOR

WRI
SOIL UNDERGROUND CABLE INSTALLATION AND MARKERS.

920
6. CONCRETE MINIMUM COMPRESSIVE STRENGTH,
MINIMUM DIRECT BURIED

THE
300
DIRECT BURIED Fc' = 28Mpa AND CEMENT TYPE-V.
DRY SAND CABLE (TYP)
100 100 300 CABLE (TYP)
COVER
7. ALL THE CABLE ROUTING ARRANGEMENT HAVE

THOUT
0F4 BEEN CHANGED FROM FLAT FORMATION TO TREFOIL
FORMATION IN REVISION 0F4.

150
MINIMUM DRY
SAND CUSHION

WI
CIRCUIT CIRCUIT CIRCUIT CIRCUIT

NG
13-44-01 13-44-02 13-40-09 13-40-10

DRAWI
LEGEND

1800
1800
0F4 - DENOTES REVISION

S
THI
150 D1 150 150 D1 150 150 D1 150
- INDICATE AS REVISION

FROM
SECTION A-A & B-B

BE NED
OBTAI
PART,SHALL
YELLOW WARNING
YELLOW WARNING
TAPE

N
TAPE

I
50mm THICK PRE-CAST
50mm THICK PRE-CAST
RED CONCRETE TILE

FULL,OR
RED CONCRETE TILE
FINISHED GRADE LEVEL
FINISHED GRADE LEVEL
620

BACKFILL
SOIL
920

N
I
DIRECT BURIED
MINIMUM DIRECT BURIED
300

CABLE (TYP)

ON
DRY SAND CABLE (TYP)
100

REPRODUCTI
COVER 100
150

MINIMUM DRY
SAND CUSHION

CIRCUIT
CIRCUIT
13-44-01
13-44-01

SAUDIARAMCO.NO
1800

150 D1 150
150 D1 150

REFERENCE DRAWINGS
DWG. CONTROL FOR BI 10-01883 BD-754413

OF
CABLE ROUTING PLAN HA-432157
SECTION C-C
GENERAL NOTES - CONCRETE WORKS HA-431941.001

PROPERTY
SOLE
THE
FINISHED GRADE LEVEL FINISHED GRADE LEVEL FINISHED GRADE LEVEL

ARE
SOIL BACKFILL SOIL BACKFILL STIRRUPS, 2-SETS STIRRUPS, 2-SETS

N
SOIL BACKFILL

HEREI
STIRRUPS, 2-SETS
{12 @ 300MM O.C {12 @ 300MM O.C
{12 @ 300MM O.C
745

745

745
920

920

920
10-{12 BARS 6-{12 BARS
14-{12 BARS
(TOP & BOTTOM) (TOP & BOTTOM)
(TOP & BOTTOM)

NED
SCALE: NONE

CONTAI
175

175

175
REVISION VALIDATION
1 2 3 4
1-{12 1-{12 1-{12
THIS REVISION NO. 0F4 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
SIDE BAR
150

SIDE BAR SIDE BAR


150

150
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
SPARE SPARE EACH FACE SPARE EACH FACE SPARE SPARE EACH FACE
SPARE TWO (2) COATS OF

ON
SPARE SPARE SPARE 10-10041-0002-001
BITUMINOUS PAINT

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
CONFORMING TO
175

175

175
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
TWO (2) COATS OF APCS-10 OF SAES-H-003 ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
TWO (2) COATS OF BITUMINOUS PAINT RCM JRB KI JSA
BITUMINOUS PAINT 07/28/22 07/28/22
01/26/22 07/28/22
01/26/22 07/28/22
01/26/22
CONFORMING TO 50MM THK. LEAN 50MM THK. LEAN
CONFORMING TO APCS-10 OF SAES-H-003 CONCRETE CONCRETE
REV.NO. DATE REVISION DESCRIPTION

I
APCS-10 OF SAES-H-003 0F4 07/28/22
01/26/22 RE-ISSUED FOR CONSTRUCTION

100 150 50 150 50 150 50 150 100 100 150 50 150 50 150 50 150 50 150 50 150 50 150 50 150 100 100 150 50 150 50 150 100

THE
JOB ORDER/EWO NO.
50MM THK. LEAN 1800 THIS REVISION IS NOT TO BE USED FOR
1800
CONCRETE 10-10041-0002 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DB-1 / DB-2
DRAWING TYPE

CABLE ROUTING DETAILS CBL

NG
OVERALL CABLE ROUTING LAYOUT

DRAWI
SUBSTATIONS ELEC.POWER & DIST.SYS.

DHAHRAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
208 P HA-432165 001 0F4
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01