Thermostats are typically mounted at 1500 mm height (above light switches) at a distance of 100mm from the door frames

as per the
sketch below. Also refer to IFC drawing A-06701 for location guidelines.

All thermostats which are mounted within ceiling cove or on the wall at ceiling level, shall be interfaced with the BMS so that thermostat
functions are available at BMS control room. The key pad of these thermostats shall be deactivated.

Thermostats located at 1.5 m height, shall be controlled directly in the room where they are located and need not be interfaced with the
BMS.

L24 Banquet Showroom - Thermostats shall be in white colour. For the plan locations refer markups at page 5.
L25 Whisky Bar - Thermostats shall be in black colour. For the plan locations refer markups at page 6.
L09 Spa - Thermostats to be located as per plan on page 7.
L09 Gym - Thermostats to be located as per plan on page 8.
L23 Bistro - Thermostats to be located as per plan on page 9.
L23 Butcherie - Thermostats to be located as per plan on page 10.
L23 Indian - Thermostats to be located as per plan on page 11.
L23 Wine Cellar - Thermostats to be located as per plan on page 12.

The location of any other thermostats that are required to be mounted in public spaces, shall be agreed in SPD submission.
2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13

SECTION_DESIGNATION
SECTION_DESIGNATION
SHEETNUMBER_A SHEETNUMBER_A

TH

2.J

2 2

CONSULTATION ROOM 1

To be place above light switches shown


CONSULTATION ROOM 2
SECTION_DESIGNATION 2.24
on HKN-SPD-EL-LT-21124A1
2.24 SECTION_DESIGNATION
SHEETNUMBER_A 532 533 SHEETNUMBER_A

24.532 24.533 24.507


A A A
TH TH

TH

SECTION_DESIGNATION 24.507 SECTION_DESIGNATION


SHEETNUMBER_A B SHEETNUMBER_A

TH

A
2.K 24.509

Fx

2
SECTION_DESIGNATION
SECTION_DESIGNATION
SECTION_DESIGNATION CONSULTATION ROOM 3

SHEETNUMBER_A SHEETNUMBER_A
SHEETNUMBER_A 2.24
509
To be place above light switches shown
on HKN-SPD-EL-LT-21124A1
TH

To be place above light switches shown


on HKN-SPD-EL-LT-21124BOH1
SECTION_DESIGNATION SECTION_DESIGNATION
FB-EAF
2.24.2
SHEETNUMBER_A SHEETNUMBER_A
To be place above light switches shown
on HKN-SPD-EL-LT-21124BOH1

SECTION_DESIGNATION
TH
TH
COOKING STATION

2.24
SHEETNUMBER_A B
504
Fx Fx Fx
24.504 TH

FB-EAF A
2.24.1
24.504 Fx
A
24.503

2
FOOD TASTING
C
2.24 STARTING POINT
24.507

SECTION_DESIGNATION
SECTION_DESIGNATION 503
SECTION_DESIGNATION
SECTION_DESIGNATION
CONSULTANT/SALES LOUNGE
SHEETNUMBER_A
SHEETNUMBER_A 2.24
SHEETNUMBER_A
SHEETNUMBER_A
Fx 507

A
Fx Fx Fx Fx Fx 24.507

TH TH

2.L Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx

SECTION_DESIGNATION SECTION_DESIGNATION SECTION_DESIGNATION


SHEETNUMBER_A SHEETNUMBER_A SHEETNUMBER_A
2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20

F 212 F 516
Proposed location accepted THREE ENGINEERED WOOD FLOORING CARPET - MEETING ROOMS (UNDER
Y3 Y5 OAK ROYAL COUNTRY GREEN TEA ,BKB LAYER - ENVIVOLAY 42)
225509-11 225509-11 PARQUET - SMART CUT
Y7 C1
225509-11 225525-12

2.H
Fx Fx Fx Fx

TH TH
TH
Fx Fx

2.25
515

BOU: +4220
Y1 Y2
225509-11 BOU: +4220 225509-11 BOU: +4270 BOU: +4220

BOU: +4220
SMOKING 2.25
ROOM 511

BOU: +4270 2.25


507
2.25
Fx Fx Fx B5 VIP LOUNGE PRIVATE ROOM VIP LOUNGE MEETING ROOM 1

2.25 517 2.25


2.25 514
225525-11
N 512 525
WHISKEY BAR 2.25
516 25.517
225503-17 2.25
2.25 514 A
Fx Fx
509

P D1
Y4 Y6 VIP LOUNGE EASTERN CORRIDOR Y8 225525-12 R
T1 T 225509-11 225509-11 225509-11 225503-17
25.508 2.25 225532-11
225503-20 225503-20 25.508 B 508
A

2.J 22

S2 Fx
225532-11
25.513 25.513
A B

25.501
A Fx

P1
VIP LOUNGE MAIN 225503-18

Right

Left
Rear Rear

2.25 Fx
LIFT LOBBY
505 VIP LOUNGE 2.25.513
G 2.25.510 VIP LOUNGE
225503-16 BUSINESS
25.502
A
CENTER
L Z1 Z3 2.25
225525-11 225525-11 532
225503-17
2.K E
T2
225503-16 Fx Fx Fx
25.504 225532-11 VIP LOUNGE SOUTHERN LIFT LOBBY

A H I Z
2.25 2.25 2.25
25
225503-16 225503-16 024 025 026
F 225503-19
B6 A6
225503-16
225527-11 225527-11
Fx Fx
B O
25.503 225503-17 Q
M
225503-17 Fx 225532-11
Fx Fx
TV ROOM TV ROOM BUFFET AREA
F 120 F 509
2.25.527 2.25.528
C D
Buffet Area

PORCELAIN TILE -TRAVERTINO CARPET - CIRCULATIONS


D C AND LOUNGE (UNDER
LAYER - ENVIVOLAY 42)
25.503
A
K Z2 Z4
225503-16 225525-11 225525-11
VIP LOUNGE

VIP LOUNGE
2.25.503 F 120
PORCELAIN TILE ON -TRAVERTINO F 120
PORCELAIN TILE ON -TRAVERTINO
Fx

B4 B3 B2 B1
225503-14 225503-14 225503-13 225503-13
Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx Fx

2.L

J F 120
F 509
225503-16 Fx PORCELAIN TILE ON -TRAVERTINO Fx
CARPET - CIRCULATIONS AND
LOUNGE
(UNDER LAYER - ENVIVOLAY 42) F 509
1 2 3 4 5 6 7 8

PROJECT
Thermostat to be Thermostat to be
mounted on the wall at mounted on the wall at
1.50 m height vertically 1.50 m height WATERFRONT
aligned with light
switches INTEGRATED
A 2.27 2.28 2.29 2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 2.38
RESORT
CLIENT

04
2.09.651 209560-04 John
2.H
PS4 PS4 PS4
GYM PS2 PS2 PS2 PS2 PS2 PS2 PS2 PS4 PS4 PS4 PS4 PS4 PS4 Keells
2.09.570 2.09.575 2.09.577 AP
L9A L9A MULTI
TREATMENT 1
MULTI
TREATMENT 2
MULTI
TREATMENT 3
2.09.582 Group
MALE
DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A PS4 LOUNGE
2.09 2.09 2.09
AP AP AP 585 586 587

L9A L9A 2.09 2.09 2.09

Thermostat to be 576 578


L9A L9A
571
DESIGN CONSULTANT
DL9B DL9B DL9B DL9B DL9B mounted on the wall at
DL9B DL9B

B L9A
1.50 m height vertically T T PS4
T PS4 T PS4

aligned with light


L9A
PS4 PS4
2.09.581

switches
T
CORRIDOR 2.09
L9A
L9A 589
www.balmondstudio.com
DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A
PS4 PS4 PS4 PS4
Registered in England & Wales No. 7225351
PS2 PS2 PS2 PS2 PS2 PS2 PS2
L9A Thermostat to be L9A
2.09.572
CORRIDOOR
AP AP

mounted on the wall at


PS4 PS4
AP 2.09

Thermostat to be KEY PLAN


T T
588

T
PS4
1.50 m height vertically
PS4
L9A PS4 PS4 PS4
L9A

DL9B DL9B DL9B DL9B DL9B


aligned with light
DL9B DL9B 2.09
590
mounted on the wall at
1.50 m height
PS4

L9A
switches L9A 2.09 2.09
2.09
583
2.09
584

02
574 580

L9A L9A 6
Thermostat to be placed
MALE
209560-02DL9A
AP
PS4 CHANGING
DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A

within ceiling cove


DL9A DL9A DL9A
2.09.573
MULTI
2.09.579
MULTI
TREATMENT 5
4 5
TREATMENT 4
L9A L9A
Thermostat to be PS4 PS4 2
PS2 PS2 PS2 mounted on the wall at
PS2 PS2 PS2 PS2 PS4
PS4 PS4 PS4 PS4
2.09.591 PS4 PS4
SAUNA
1.50 m height vertically
2.09.592

T
PS4

1
STEAM

2.J aligned with light 3

C
switches T PS4

PS4 N
2.09.536
FEMALE TOILET T 2.09.560
DRY
2.09.561
ROOM 2
DRY
ROOM 1 KEY ELEVATION
PS4

2.09.569
CORRIDOR

PS4

PS4

PS4

Thermostat to be placed
within ceiling cove T
PS4 PS4

Thermostat to be
2.09.537
Thermostat to be
FEMALE CHANGING PS4 mounted on the wall at REFERENCE NUMBERS STATUS
mounted on the wall at
ROOM & SHOWER

1.50 m height vertically


2.09.566
WC 02
T 1.50 m height vertically
aligned with light 01 DGD-DWG-IH-I-229201_A
2.09.562
DRY

aligned with light


ROOM 3

D 2.K 2.09.539
MALE CHANGING
ROOM & SHOWER
switches
PS4
switches DGD-DWG-IH-I-229409_A
02 DGD-DWG-IH-I-229410_A
AP

DGD-DWG-IH-I-229411_A
AP
AP 03 DGD-DWG-IH-I-229412_A

T 04 E-210124_P / E-210125_P / E-210424_K


AP

T 2.09.567
WC 01 E-210425_K / E-210224_I / E-210225_I
Thermostat to be placed 05 E-210724_H / E-210725_H
PS4
PS4 PS4 PS4 2.09.601 PS4 PS4 PS4 PS4 PS4
AP
CORRIDOR
Thermostat to be placed
within ceiling cove
T within ceiling cove 06 P-21319_H / P-21320_G
AP
Thermostat to be
mounted on the wall at
PS4 T AP
2.09.606
07
AP 2.09
1.50 m height vertically PS4 PS4 PS4
605 PS4 PS4
PS4
2.09
611
2.09
612
08
AP
2.09.538
MALE TOILET
aligned with light PS4 PS4

switches PS4 PS4 09


2.09.602
UNISEX LOUNGE

Thermostat to be placed
2.09.609
PS4 FEMALE CHANGING
2.09.609 2.09
within ceiling cove FEMALE
LOUNGE
PS4
610

2.09.607
PS4

T T
PS4 PS4

T T
2.09
E
PS4
613
AP PS4
PS4 PS4 PS4 PS4

2.09.560
RECEPTION T PS4 PS4 PS4 PS4
AP
2.09
617

AP

COUPLES ROOM
PS4 PS4 2.09
2.09 614
PS4 PS4 PS4 PS4 603 UNISEX LOUNGE

PS4 PS4 PS4 PS4 A1 17-02-20 FOR APPROVAL


T DATE ISSUE
REV.
2.09
T
MANICURE BAR
AP

2.L
2.09.618 2.09.619
PS4 PS4 608 2.09 SAUNA STEAM
2.09.604
615
ISSUE STATUS
T PEDICURE BAR
PS4 PS4

H=2160 mm
H=2160 mm PS4 PS4
PS4
AP
PS4
2.09
616 FOR APPROVAL
B A

3.A DRAWING TITLE

Thermostat to be placed
BUILDING 2 - L09
F
within ceiling cove SPA

Thermostat to be Thermostat to be Thermostat to be Thermostat to be REFLECTED CEILING PLAN


mounted on the wall at mounted on the wall at mounted on the wall at mounted on the wall at
1.50 m height vertically 1.50 m height vertically 1.50 m height 1.50 m height
03
01 aligned with light aligned with light 1:100 17-02-2020
2.09 - SPA-REFLECTED CEILING PLAN switches switches
209560-03 SCALE DATE

Scale 1:100 DRAWN BY DON


Thermostat to be CHECKED BY KHALIL
mounted on the wall at
1.50 m height vertically DRAWING NO. REVISION
aligned with light
switches HKN-SPD-ID-CL-209560-01 A1

G NOTES:
SUB CONTRACTOR

CI-219
1. ALL CCTV, WIFI, ACMV, PLUMBING EQUIPMENT (INCLUDING ACCESS
C
N
IA
TE
N
R
IO
-IO
T
R
F
-IU
S
TDN
BHD
PANEL) NOT FOR REVIEW. TO BE UPDATED ONCE MEP DRAWINGS ARE m
a,a
U
tg
ni laPte,3/1S P
Jn alaJ ,1N O .

FINALIZED. aisyaM
la,n
7
aE
sh luD
8038
730
6
raro
+ : xF
gn
aS
a 7
le,ayaJg
855 8
ni laP
73 0
6
te0
+ : lT
5
1
6
4
e

JOB NO.
2. THIS SHOP DRAWING IS INTENDED FOR CEILING AND SPRINKLER SETTING mocy.. i@
s-n
actcejorp : lE
mia

OUT ONLY. ALL OTHER MEP SERVICES EQUIPMENT AND LOCATIONS TO


BE UPDATED ONCE COORDINATED MEP DRAWINGS ARE FINALIZED. MAIN CONTRACTOR
REFLECTED CEILING PLAN LEGEND

SYMBOL DESCRIPTION

LIGHT ON WALL
SYMBOL DESCRIPTION
EMERGENCY LIGHT
SYMBOL DESCRIPTION

TERMOVELOCIMETRIC DETECTOR
SYMBOL

SW1 / SW2
DESCRIPTION

SPRINKLER - SIDE WALL


SYMBOL DESCRIPTION

HVAC EQUIPMENT
REMARKS:
HYUNDAI
ENGINEERING & CONSTRUCTION CO. LTD.
WITH PICTOGRAM
a. ALL DIMENSION ARE SUBJECT TO FINAL SITE SETTING OUT & SITE 75, YULGOK-RO, JONGNO-GU, SEOUL, KOREA
WWW.HDEC.CO.KR
EMERGENCY PICTOGRAM GAS/MONOXIDE DETECTOR
DOWN LIGHT ON CEILING CEILING TRAPDOOR / REMOVABLE BUFFEL HVAC WC LOUVRE
CONDITION.
LED PROFILE ON CEILING PULL ALARM FOR DISABLED TOILET OPTICAL SMOKE DETECTOR CCTV MONITORING HVAC-FAN COIL UNIT b. FOR MATERIAL SPECIFICATIONS, PLEASE REFER TO MATERIAL
KNIFE EDGE TRIM
PRESENCE / MOTION
FIRE / SMOKE CURTAIN SPEAKER AC GRILLE / LINEAR DIFFUSER FOR SCHEDULE, SPECIFICATIONS, SAMPLE & CATALOGUE.
SENSOR (WALL MOUNTED) SUPPLY & RETURN
PRESENCE / MOTION SENSOR 360 °
c. ALL MEP SERVICES & INSTALLATION BY MAIN CONTRACTOR.
AC SUPPLY & RETURN GRILLE (SIDE THROW)
CEILING FINISHES LEGEND
LIGHTING ON CEILING
(CEILING MOUNTED) PS1
SPRINKLER - PENDENT HEAT / WATER / STEAM RESISTANT SPEAKER
d. SANITARY WARE & FITTINGS BY MAIN CONTRACTOR.
H LIGHTING ON CEILING
PASSIVE CEILING MOUNTED
SPRINKLER - RECESSED WIFI DEVICE RAIN SHOWER HEAD
530-17 Dapsimni 5-dong, Dongdaemoongu, Seoul, Korea
www.kne.co.kr
MOTION SENSOR PS2 / PS3
CODE DESCRIPTION IFC REF. SPEC
LIGHTING ON CEILING SMOKE DETECTOR PS4 / PS5 / PS6 SPRINKLER - CONCEALED DATA SOCKET SPOT LIGHT ON CEILING
SPA-PT-01 KNAUF 12.5mm THK. PLASTER BOARD CEILING IN NIPPON PAINT HUSH WHITE M60_ID02/2120
VINILEX 5000 LOW ODOUR FINISH LIGHTING ON CEILING SMOKE DETECTOR WITH /
[CEILING FRAME SYSTEM: KCI 001] WITH BATTERY FIRE ALARM UP1 / UP2 UP3 / UP4
SPRINKLER - UPRIGHT LPG VENTILATION
HATCHED AREA NOT FOR REVIEW NAWALOKA CONSTRUCTION
CO. (PVT) LTD
CH0000 COVE HEIGHT INDICATION EMERGENCY LIGHT FIRE ALARM WS1
SPRINKLER - FOR WINDOW HVAC EQUIPMENT NO: 115, SIR JAMES PEIRIS MAWATHA,COLOMBO 02, SRILANKA.
WEB : www.nawaloka.lk
1 2 3 4 5 6 7 8

PROJECT

WATERFRONT
INTEGRATED
A
RESORT
CLIENT

John
Keells
Group
Thermostat to be placed Thermostat to be placed Thermostat to be placed
2.27
within ceiling cove 2.28
within ceiling cove 2.29
within ceiling cove 2.30 2.31
DESIGN CONSULTANT

www.balmondstudio.com
A2 Registered in England & Wales No. 7225351
A2
PT-01 PT-01 SUSPENDED DOWNHANG PT-01 LINEAR A/C SUPPLY &
PT-01
TV SCREEN (BY AV
DUMMY DIFFUSER IN
CH 4100 PT-01 CH 4100 SPECIALIST) CH 4100 CONTINUOUS ROW
CH 4100 KEY PLAN

6
T T T
4 5
AFF 3850
2
2.09.651 AP AP

2.H GYM PS2


S1
PS2 PS2
S1
PS2
S1
PS2 PS2
S1
PS2 3 1
A2 A2 A2 A2
L9A L9A
C A2 A2 A2
DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A N
AFF 4250

KEY ELEVATION
L9A L9A
PT-01 L9A PT-01 AFF 3900-4050 (WAVE CEILING) L9A

PT-01 PT-01
DL9B DL9B DL9B DL9B DL9B DL9B DL9B

AFF 3850 AFF 4250


L9A L9A
AFF 3850
PT-01 AFF 3900-4050 (WAVE CEILING)
PT-01
L9A
L9A
REFERENCE NUMBERS STATUS

DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A 01 DGD-DWG-IH-I-242403_A
D S1
PS2 PS2 PS2 PS2 PS2 PS2 PS2 E-210124_P / E-210125_P / E-210424_K
S1 02 E-210425_K / E-210224_I / E-210225_I
L9A AFF 4250 E-210724_H / E-210725_H
L9A 03 P-21319_H / P-21320_G
A2
PT-01
04 HKN-SPD-FR-FD-21109D1-1
PT-01 AFF 3900-4050 (WAVE CEILING)
PT-01 HKN-SPD-EL-LT-21109D1
PT-01 L9A L9A 05
HKN-SPD-EL-EM-21109D1
HKN-SPD-EL-SA-21109D1
DL9B DL9B DL9B DL9B DL9B DL9B DL9B CH 4100 06 HKN-SPD-EL-TN-21109D1
SMV-AV-I-229201
07 HKN-RFI-EL-00364
AFF 4250
DGD-SCH-IH-I-242601
L9A L9A 08 DGD-SCH-IH-I-229623
PT-01 09 BSC-EI-HKN-DC-2020-124_Rev. A A2
L9A AFF 3900-4050 (WAVE CEILING) L9A
PT-01
DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A DL9A
AFF 4250
E A2 L9A L9A

S1 S1 AP S1
AP DL9A AP
S1
PS2 PS2 PS2 PS2 PS2 PS2 PS2
DL9A

A2 AFF 3850 A2 20-07-21 FOR APPROVAL


A2 A2 A2
2.J T T T A1 31-01-20 FOR APPROVAL
REV. DATE ISSUE

ISSUE STATUS
A2
PT-01 PT-01 PT-01 PT-01 FOR APPROVAL
01 01a LINEAR A/C SUPPLY &
FN-209651-50 C1 CEILING
CH 4100 FN-209651-50 CH 4100 A2 DUMMY DIFFUSER IN CH 4100
209651-40 DETAILS
CONTINUOUS ROW DRAWING TITLE
A2 A2 BUILDING 2 - L09
F
A2
Thermostat to be placed Thermostat to be placed Thermostat to be placed
GYM
within ceiling cove within ceiling cove within ceiling cove
01 2.09 - GYM-REFLECTED CEILING PLAN REFLECTED CEILING PLAN
Scale 1:50
SCALE 1:50 DATE 20-07-2021
(ROOM / AREA: 2.09.651)
DRAWN BY DON

CHECKED BY NANA

DRAWING NO. REVISION

HKN-SPD-ID-CL-209651-01 A2
A1

CI-219
SUB CONTRACTOR
C
N
IA
TE
N
R
IO
-IO
T
R
F
-IU
S
TDN
BHD
m
a,a
U
tg
ni laPte,3/1S P
Jn alaJ ,1N O .
aisyaM
la,n
aE
sh luDraro
g
naS le,ayaJg ni laP
te05
1
6
4
7
8038
730
6
+ : xFa 7 855 8
73 0
6
+ : lTe

JOB NO.
mocy.. i@
s-n
actcejorp : lE
mia

REFLECTED CEILING PLAN LEGEND MAIN CONTRACTOR

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

LIGHT ON WALL
EMERGENCY LIGHT
WITH PICTOGRAM
TERMOVELOCIMETRIC DETECTOR SW1 / SW2 SPRINKLER - SIDE WALL HVAC WC LOUVRE
REMARKS: HYUNDAI
ENGINEERING & CONSTRUCTION CO. LTD.
DOWN LIGHT ON CEILING
a. ALL DIMENSION TO BE VERIFIED VIA SITE SETTING OUT, SURVEY & EXISTING SITE 75, YULGOK-RO, JONGNO-GU, SEOUL, KOREA
EMERGENCY PICTOGRAM GAS/MONOXIDE DETECTOR CEILING TRAPDOOR / REMOVABLE BUFFEL HVAC-FAN COIL UNIT
(DL9A/DL9B/DL9C) CONDITION. WWW.HDEC.CO.KR

LED PROFILE ON CEILING


(L9A)
PULL ALARM FOR DISABLED TOILET OPTICAL SMOKE DETECTOR CCTV MONITORING AC GRILLE / LINEAR DIFFUSER FOR
SUPPLY & RETURN
b. FOR MATERIAL SPECIFICATIONS, PLEASE REFER TO MATERIAL SCHEDULE,
KNIFE EDGE TRIM
PRESENCE / MOTION
SMOKE CURTAIN SPEAKER AC SUPPLY & RETURN GRILLE (SIDE THROW)
SPECIFICATIONS, SAMPLE & CATALOGUE, DATA SHEET AND MSB SUBMISSION.
A2 SENSOR (WALL MOUNTED)
c. ALL MEP SERVICES & INSTALLATION BY MAIN CONTRACTOR.
PRESENCE / MOTION SENSOR 360 °
LIGHTING ON CEILING SPRINKLER - PENDENT WIFI DEVICE AV SPEAKER (BY AV SPECIALIST)
CEILING FINISHES LEGEND (CEILING MOUNTED) PS1
S1 S5
S3a
d. SANITARY WARE & FITTINGS BY MAIN CONTRACTOR.
PASSIVE CEILING MOUNTED
LIGHTING ON CEILING SPRINKLER - RECESSED DATA SOCKET AV DOWNHANG TV (BY AV SPECIALIST) 530-17 Dapsimni 5-dong, Dongdaemoongu, Seoul, Korea
H CODE DESCRIPTION REF. SPEC MSB. REF STATUS
MOTION SENSOR PS2 / PS3
www.kne.co.kr
LIGHTING ON CEILING SMOKE DETECTOR PS4 / PS5 / PS6 SPRINKLER - CONCEALED LPG VENTILATION
KNAUF 12.5mm THK. PLASTER BOARD CEILING IN NIPPON PAINT HUSH WHITE
GYM-PT-01
VINILEX 5000 LOW ODOUR FINISH M60_ID02/2120 HKN-MSB-ID-0168 A
LIGHTING ON CEILING SMOKE DETECTOR WITH
A2
/ SPRINKLER - UPRIGHT
[CEILING FRAME SYSTEM: KCI 001] WITH BATTERY FIRE ALARM UP1 / UP2 UP3 / UP4 HVAC EQUIPMENT
HATCHED AREA NOT FOR REVIEW
NAWALOKA CONSTRUCTION
CH0000 COVE HEIGHT INDICATION EMERGENCY LIGHT FIRE ALARM SPRINKLER - FOR WINDOW HVAC EQUIPMENT CO. (PVT) LTD
A2 WS1
NO: 115, SIR JAMES PEIRIS MAWATHA,COLOMBO 02, SRILANKA.
WEB : www.nawaloka.lk
Thermostat to be placed Thermostat to be placed
within ceiling cove - VAV 04 within ceiling cove - VAV 03

T T

Thermostat to be
mounted on the wall at
ceiling level - VAV 02

VAV
04 VAV
T 03

VAV
02

VAV
01

Thermostat to be
mounted on the wall at
ceiling level - VAV 01
Thermostat to be
mounted on the wall at
ceiling level - VAV 1

VAV
01 T

VAV
03

VAV VAV VAV VAV VAV


02 04 05 06 07

T T T T T T

Thermostat to be Thermostat to be Thermostat to be Thermostat to be Thermostat to be Thermostat to be


mounted on the wall at mounted on the wall at mounted on the wall at mounted on the wall at mounted on the wall at mounted on the wall at
ceiling level - VAV 3 ceiling level - VAV 2 ceiling level - VAV 4 ceiling level - VAV 5 ceiling level - VAV 6 ceiling level - VAV 7
Thermostat to be mounted
within the ceiling cove - VAV 12

VAV VAV
11 12
VAV
07
T T T

VAV
10
VAV VAV
09 08

T Thermostat to be mounted on
T
the wall at ceiling level - VAV 06
VAV
06

Thermostat to be mounted on
T the wall at ceiling level - VAV 07
Thermostat to be mounted on Thermostat to be mounted Thermostat to be mounted Thermostat to be mounted on
the wall at ceiling level - VAV 11 within the ceiling cove - VAV 09 T the wall at ceiling level - VAV 05
within the ceiling cove - VAV 08

VAV
Thermostat to be mounted 05
within the ceiling cove - VAV 10
Thermostat to be mounted on
T the wall at ceiling level - VAV 01

T T

VAV
01

VAV VAV
04 03

Thermostat to be mounted on Thermostat to be mounted on


the wall at 1.50 m height the wall at 1.50 m height
vertically aligned with light vertically aligned with light
switches - VAV 04 switches - VAV 03
Thermostat to be placed Thermostat to be placed Thermostat to be placed
within ceiling cove - VAV 03 within ceiling cove - VAV 04 within ceiling cove - VAV 05 Thermostat to be placed
within ceiling cove - VAV 06

T T T T

VAV
03

VAV
06

VAV
05

VAV
01

VAV
04

VAV
02
FCU
T 01 Thermostat to be
mounted on the wall at
1.50 m height - FCU 01

Thermostat to be
mounted on the wall at
ceiling level - VAV 01

Thermostat to be
mounted on the wall at
1.50 m height - VAV 02