You are on page 1of 17

1994

STANDARD for
METHOD OF
MEASURING
MACHINERY
SOUND
WITHIN AN
EQUIPMENT
SPACE

Standard 575

4301 NORTH FAIRFAX DRIVE ! ARLINGTON, VIRGINIA 22203


IMPORTANT

SAFETY RECOMMENDATIONS

It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements appropriate for products covered by this standard.

ARI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-art and
accepted industry practices. However, ARI does not certify or guarantee safety of any products, components or
systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted
under its standards will be non-hazardous or free from risk.

FOREWORD

This document establishes a uniform method of measuring the sound levels produced by air-conditioning and
refrigerating machinery installed in mechanical equipment spaces. However, it should be emphasized that this
standard was developed for use where the test conditions usually cannot be controlled, e.g., ambient temperature;
equipment loading; physical attributes of the space; background sound sources, etc. Since the results obtained may
vary substantially, a tolerance on these results cannot be specified.

Uniform practices in making sound level measurements are necessary for effective communication between the owner,
the architect, the acoustician, the consulting engineer, the contractor and the equipment manufacturer.

Specification for sound levels produced by machinery may be written, both for the purpose of supplying information
in order to evaluate compliance with noise exposure limits and for the purpose of providing information for adequate
building design to meet the acoustical design goals of adjacent occupied spaces. In view of the geometrical and
acoustical properties of large equipment, both purposes can best be served by sound data expressed in terms of sound
pressure level measured close to the equipment. Sound pressure measurements close to the equipment are least affected
by the environment in which the machines are installed.

This standard is based upon the procedures established in American National Standard S1.13-1971 (R1986).

Note:

This standard supersedes ARI Standard 575-87.

Price $15.00 (M) $30.00 (NM) ©Copyright 1994, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A. Registered United States Patent and Trademark Office
TABLE OF CONTENTS

SECTION PAGE

Section 1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 3. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 4. Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 5. Sound Measurements and Calculation Procedures . . . . . . . . . . . . . . . . . . . . 2

Section 6. Machinery Sound Spedifications and Data Presentation . . . . . . . . . . . . . . . . 4

Section 7. System Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Section 8. Voluntary Conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

FIGURES

Figure 1. Test Unit Measurement Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

APPENDICES

Appendix A. Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Appendix B. Sound Level Recording Format Per ARI Standard 575 . . . . . . . . . . . . . . . . . 9

Appendix C. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ARI STANDARD 575-94

METHOD OF MEASURING MACHINERY SOUND


WITHIN AN EQUIPMENT SPACE
Section 1. Purpose 3.5 Sound Pressure Level. The sound pressure level (Lp),
in decibels (dB), of a sound is 20 times the logarithm to the
1.1 Purpose. The purpose of this standard is to establish base 10 of the ratio of a given pressure to a reference
a uniform method of measuring and recording the sound pressure. The reference pressure (Po) used in this standard
pressure level of machinery installed in a mechanical is 20 micropascals.
equipment space. It is not the intent of this standard to be
used for the sound rating of equipment. Lp = 20 log10 (p/Po)

where p is the measured RMS (root mean square) sound


Section 2. Scope pressure, in Pa.

2.1 Scope. This standard applies to water chilling 3.6 Uncertain and Valid Measurements.
systems, pumps and similar operating machines and parts
thereof, which for reasons of size or operating characteristics 3.6.1 An uncertain measurement is at a point where
are more practically evaluated in situ. sound energy of other sources causes the observed value
to be above its true value.

Section 3. Definitions 3.6.2 A valid measurement is at a point where other


equipment or adjacent surfaces do not significantly
3.1 "A" -Weighted Sound Pressure Level. The measured affect the value observed.
value obtained with a sound level meter using its "A"
weighting network.
Section 4. Instruments
3.2 Octave Band. An octave band is a band of sound
covering a range of frequencies such that the highest is twice 4.1 Sound Level Meter. A meter meeting the requirements
the lowest. The octave bands used in this standard are those of the Type 1 meter described in American National
defined in American National Standard Institute Standard Standards Institute Standard S1.4-1983 is to be used.
S1.11-1986.
4.2 Frequency Analyzer. An octave or third-octave band
3.3 Operating Conditions. Operating conditions are those filter set meeting the requirements for Class II or III filters
conditions specified for the particular installation. In respectively, of American National Standards Institute
general, they are those parameters listed in the job Standard S1.11-1986 is to be used.
specification sheets for the particular equipment. Examples
of parameters to be recorded are found on data sheets in 4.3 Calibration. During each series of measurements, an
Appendix A. acoustical calibrator with an accuracy of ±0.5 dB shall be
applied to the microphone for checking the calibration of the
3.4 "Shall," "Should," "Recommended" or "It Is entire measuring system at one or more frequencies over the
Recommended." "Shall," "should," "recommended" or "it is frequency range of interest. The calibrator shall be checked
recommended" shall be interpreted as follows: at the manufacturer's recommended intervals or at least once
every year to verify that its output has not changed. In
3.4.1 Shall. Where "shall" or "shall not" is used for addition, an electrical calibration of the instrumentation
a provision specified, that provision is mandatory if system over the entire frequency range of interest shall be
compliance with the standard is claimed. performed periodically as recommended by the
manufacturer, but at intervals of not more than two years.
3.4.2 Should, Recommended or It Is Recommended.
"Should," "recommended" or "it is recommended" is
used to indicate provisions which are not mandatory but
which are desirable as good practice.
Section 5. Sound Measurements and

1
ARI STANDARD 575-94

Calculation Procedures the measured values. If the "A" weighted sound


pressure level or any octave band sound pressure level
5.1 Measurements. varies 6 dB or more within an area of 0.5 meter radius
of the measuring point and on the surface of the
5.1.1 Measurement Points. The points where measurement parallelopiped, the highest and lowest
measurements are to be taken are determined relative to values observed within this area shall be recorded. If
a reference parallelopiped, which is the smallest variations are less than 6 dB the value obtained at the
imaginary rectangular parallelopiped that will enclose specified measurement point shall be recorded.
the machine (see Figure 1). Minor projections from the
machine are disregarded in determining the size of the 5.2 Calculation Procedures.
reference parallelopiped.
5.2.1 Uncertain Measurements Due to Background
The measurement points shall be positioned on the Noise. Any "A"-weighted or octave band sound
surface of a measurement parallelopiped whose planes pressure level taken with test unit operating must be at
are 1 meter out from the vertical sides of the reference least 6 dB above the corresponding level with the test
parallelopiped. Key measurement points are located at unit off and other equipment operating. Any level
the center of each vertical plane of the measurement which does not meet this criterion shall be marked
parallelopiped. The remaining measurement points are uncertain by the use of an asterisk (*). The number of
at 1 meter intervals on the measurement planes starting uncertain measurement points is NU.
from the key points. All measurement points are at a
height of 1.5 meters from the floor. If the shortest 5.2.2 Pure Tones. Where the highest and lowest
distance between two measurement points at a corner of values were recorded for a measurement point as
the measurement parallelopiped is less than 1 meter, the specified in 5.1.5 the value used in the calculations for
point nearest to the corner shall be eliminated. The this point shall be the highest value minus 3 dB.
total number of points on the measurement
parallelopiped is N. 5.2.3 Representative "A"-Weighted Sound Pressure
Level. If half or more of the measurement points
5.1.2 Operation of Sound Level Meter. The sound remain (that is, if N - NU - N1 $ N/2) after applying the
level meter shall be used in the slow response position. limitations of 5.1.4 and 5.2.1, the representative "A"-
The instrument manufacturer's recommendations shall Weighted Sound Pressure Level (AR) shall be calculated
be followed in using the meter and in determining the using Equation 1. However, if less than half remain,
correct microphone orientation for the flattest frequency the Representative High Limit Sound Pressure level
response. shall be calculated per 5.2.5.

5.1.3 Data to be Taken. "A" weighted sound 5.2.4 Representative Octave Band Sound Pressure
pressure level measurements shall be taken at all Levels. If two or more key measuring points remain
measurement points. Octave band measurements (63 after applying the limitations of 5.1.4 and 5.2.1, the
through 8000 Hz octave bands) shall be made at the Representative Octave Band Sound Pressure Levels
four key measurement points. (OBR) shall be calculated using Equation 1. However,
if less than two remain the Representative High Limit
A full set of measurements shall be taken with the test Octave Band Sound Pressure Level shall be calculated
unit operating. A second full set of data shall be per 5.2.6.
obtained with the test unit off and all other equipment
in the area operating as before to establish the
background sound levels.

5.1.4 Valid Measurement Points. A valid


measurement point cannot be closer than 1 meter to a
wall or other plane surface larger than 1 square meter.
A measurement shall not be recorded at any
measurement point that does not meet this criterion.
The number of invalid measurement points is N1.

5.1.5 Pure Tones. When pure tones are generated by


the operating machine, interference patterns may affect

2
Figure 1. Test Unit Measurement Points

3
ARI STANDARD 575-94
ARI STANDARD 575-94

5.2.5 Representative High Limit "A"-Weighted Sound 6.2 Data Presentation. When a sound test is conducted in
Pressure Levels. If half or more of the measurement accordance with this standard, a report shall be supplied and
points can be obtained by adding the uncertain to the it shall include the information in 6.2.1; 6.2.2 and 6.2.3. In
valid measurement points (that is, if N - N1 $ N/2), then addition, the data defined in 6.2.4 should be provided when
a Representative High Limit "A"-Weighted Sound specified by the user.
Pressure Level (AH) can be calculated using Equation 1
with NU = O. If this criteria cannot be met neither a 6.2.1 Statement that the test was conducted in
Representative or Representative High Limit "A"- accordance with ARI Standard 575.
Weighted Sound Pressure Level can be obtained.
6.2.2 Description of the machine, the operating
5.2.6 Representative High Limit Octave Band Level. conditions and a sketch showing the test layout and
If two or more key measurement points can be obtained microphone locations (see Appendix B for Form and
by adding the uncertain points to the valid measurement sample calculation).
points a Representative High Limit Octave Band Sound
Pressure Level (OBH) can be calculated using 6.2.3 Representative "A"-Weighted Sound Pressure
Equation 1. If this criteria cannot be met neither Level (AR) or Representative High Limit Sound
Representative nor Representative High Limit Octave Pressure Level (AH) as calculated per 5.2. AH will be
Band Sound Pressure Levels can be obtained. reported only if the data for computing AR cannot be
obtained. If the latter course is followed, the reasons
5.2.7 Sound Pressure Level Averaging Equation. that the AR cannot be obtained shall be submitted to the
user.

L = 10 log10 j
n
L i 10
10 - 10 log10 n (1) 6.2.4 Representative Octave Band Sound Pressure
i ' 1
Levels at (OBR) or Representative High Limit Octave
Band Sound Pressure Levels (OBH), in the 63 Hz
through 8000 Hz bands, inclusive, as calculated high
Where: L = Representative or High Limit Sound limit. OBH levels, calculated per 5.2, shall only be
Pressure Level Logarithmic average reported in the case that OBR levels cannot be obtained.
rounded off to the nearest 0.5 dB) If the latter course is followed, the reasons that the
Ln = Sound pressure level at the measured lower value OBR cannot be obtained shall be submitted
points to the user.
n = Number of points to be averaged =
(N - NU - N1)
Section 7. System Operating Conditions

Section 6. Machinery Sound Specifications 7.1 Operating Conditions for Test. Sound tests shall be
and Data Presentation made with the machine operating at design operating
conditions. If this operating point cannot be obtained, the
6.1 Sound Level Specifications. Information required for sound test may be made at some other steady state condition
specifying machinery sound levels should include the mutually agreed upon by the parties concerned. This
following: condition shall clearly be described in the test report. See
Appendix A for examples of typical report forms.
a. Machine description.

b. Desired Representative "A"-Weighted Sound Section 8. Voluntary Conformance


Pressure Level (AR).
8.1 Conformance. While conformance with this standard
c. If desired, optional Representative Octave Band is voluntary, conformance shall not be claimed or implied
Sound Pressure Level (OBR). for products or equipment within its Purpose (Section 1) and
Scope (Section 2) unless such claims meet all of the
d. Operating conditions at which (AR) and (OBR) are requirements of the standard.
specified (see Section 7).

4
ARI STANDARD 575-94

APPENDIX A
Operating Conditions

The following data forms shown in this appendix are intended as a guide to ensure that adequate data are recorded. Because
of the wide range of machinery which can be expected to be installed in building machinery spaces, a universal data form is not
practical. If the attached forms are not adequate, one should be tailored to meet individual requirements.

CENTRIFUGAL CHILLER OPERATIONAL DATA RECORDING FORM


PER ARI STANDARD 575

MACHINE SPECIFICATIONS:
Model: Manufacturer: Serial:
Rated Compressor Speed: Capacity:
Rated Load Amperage: Volts:
Type of Driver: Refrigerant:
Auxiliaries, such as Gears:
Comments:

TEST CONDITIONS:
Suction Temperature/Pressure EF [EC]/ psig [kPa]
Chilled Water Temperature In/Out EF [EC]/ EF [EC]
Chilled Water Pressure In/Out psig [kPa]/ psig [kPa]
Discharge Temperature/Pressure EF [EC]/ psig [kPa]
Condenser Water Temperature In/Out EF [EC]/ EF [EC]
Condenser Water Pressure In/Out psig [kPa]/ psig [kPa]
Interstage(s) Temperature/Pressure EF [EC]/ psig [kPa]
EF [EC]/ psig [kPa]
Compressor Speed rpm
Compressor Capacity Control Position
Driver Speed rpm
Electric Motor amps volts
Steam Turbine Pressures:
Before Control Valve psig [kPa]
Steam Chest psig [kPa]
Condenser psig [kPa]

5
ARI STANDARD 575-94

RECIPROCATING CHILLER OPERATIONAL DATA RECORDING FORM


PER ARI STANDARD 575

MACHINE SPECIFICATIONS:
Model: Manufacturer: Serial:
Rated Compressor Speed: Capacity:
Rated Load Amperage: Volts:
Type of Driver: Refrigerant:
Auxiliaries, such as Gears:
Comments:

TEST CONDITIONS:
Suction Temperature/Pressure EF [EC]/ psig [kPa]
Chilled Water Temperature In/Out EF [EC]/ EF [EC]
Chilled Water Pressure In/Out psig [kPa]/ psig [kPa]
Discharge Temperature/Pressure EF [EC]/ psig [kPa]
Condenser Water Temperature In/Out EF [EC]/ EF [EC]
Condenser Water Pressure In/Out psig [kPa]/ psig [kPa]
Number of Compressors
Number of Compressors Running
Compressor Speed rpm
Electric Motor—Compressor 1 amps volts
2 amps volts
3 amps volts
4 amps volts

6
ARI STANDARD 575-94

ABSORPTION CHILLER OPERATIONAL DATA RECORDING FORM


PER ARI STANDARD 575

MACHINE SPECIFICATIONS:
Model: Manufacturer: Serial:
Capacity: Pump Speed:
Heat Source: Steam: Hot Water:
Rated Steam Pressure: Rated Hot Water Temperature:
Type and Location of Steam (Hot Water) Control Valve:
Comments:

TEST CONDITIONS:
Chilled Water Temperature In/Out EF [EC]/ EF [EC]
Chilled Water Pressure In/Out psig [kPa]/ psig [kPa]
Condenser Water Temperature—Absorber In/Out EF [EC]/ EF [EC]
Condenser Water Pressure—Absorber In/Out psig [kPa]/ psig [kPa]
Condenser Water Temperature—Condenser In/Out EF [EC]/ EF [EC]
Condenser Water Pressure—Condenser In/Out psig [kPa]/ psig [kPa]
Capacity Control Valve Position
Steam (Hot Water) Pressure at Control Valve
Upstream/Downstream psig [kPa]/ psig [kPa]
Steam (Hot Water) Temperature at Control Valve
Upstream/Downstream EF [EC]/ EF [EC]

7
ARI STANDARD 575-94

PUMP OPERATIONAL DATA RECORDING FORM


PER ARI STANDARD 575

MACHINE SPECIFICATIONS:
Model: Manufacturer: Serial:
Rated Pump Speed: Capacity:
Rated Load Amperage: Voltage:
Type of Driver: Type of Pump:
Auxiliaries, such as Gears:
Comments:

TEST CONDITIONS:
Fluid Being Pumped
Suction Temperature/Pressure EF [EC]/ psig [kPa]
Discharge Temperature/Pressure EF [EC]/ psig [kPa]
Pump Speed rpm
Driver Speed rpm
Electric Motor amps volts

8
ARI STANDARD 575-94

APPENDIX B. SOUND LEVEL RECORDING FORMAT


PER ARI STANDARD 575
Unit Type

Model Number

Serial Number

Measurement 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
Position

db(A) Test
Unit ON

db(A) Test
Unit Off

A-Weighted Sound Pressure Level dbA AR ______________ or AH ____________

Octave Band Sound Pressure Levels at Key Measurement Points

Key Location ( ) Key Location ( ) Key Location ( ) Key Location ( )

Hz Test Test Test Test Test Test Test Test Average


Unit Unit Unit Unit Unit Unit Unit Unit Octave Band
ON Off ON OFF ON OFF ON OFF Level

63

125

250

500

1000

2000

4000

8000

*Indicates uncertain measurements (See 5.2.1 of standard)

Sketch Showing Microphone Locations, Orientation of Test Unit,


Key Measurement Points, and Surroundings

Tested By: Reported By: Date:

9
10
SOUND RECORDING FORMAT PER ARI STANDARD 575

Unit Type
Model Number
Serial Number
ARI STANDARD 575-94
Sketch Showing Microphone Locations, Orientation of Test Unit
Key Measurement Points and Surroundings

Tested By: I.M. Korrect Reported By: R.U. Accurate Date: 1-16-94

11
ARI STANDARD 575-94
ARI STANDARD 575-94

SAMPLE CALCULATIONS
Sample calculation for a water chiller where the measurement procedure is complicated by

1) the close proximity of a wall,


2) the close proximity of a water tank,
3) a pure tone generated in the gear box at 2,000 Hz,
4) a pure tone generated by an adjacent pump at 4,000 Hz,
5) high background level in the 63 Hz band.

To obtain the Representative "A" Weighted Sound Pressure Level

(Note D)

89 88 87 89 91 90
AR = 10 log10 antilog10 % antilog10 % antilog10 % antilog10 % antilog10 % antilog10
10 10 10 10 10 10

90 90 90 88 87 88 87
% antilog10 % antilog10 % antilog10 % antilog10 % antilog10 % antilog10 % antilog10
10 10 10 10 10 10 10

- 10 log10 13

AR = 100.1 - 11.1

= 89.0 dB (Note E)

To obtain the Representative Octave Band Sound Pressure at 1 Meter

For the 63 Hz Band:

(Note C)

77( 81(
OBH = 10 log10 antilog10 % antilog10 - 10 log10 2
10 10

OBH = 79.4 dB; use 79.5 dB

For the 125 Hz Band:

83 84
OBR = 10 log10 antilog10 % antilog10 - 10 log10 2
10 10

OBR = 83.4 dB; use 83.5 dB

For the 2000 Hz Band:

(Note B)

87 & 3 77(
OBH = 10 log10 antilog10 % antilog10 - 10 log10 2
10 10

OBH = 81.7 dB; use 81.5 dB

12
ARI STANDARD 575-94

NOTE A: No measurements can be taken at these points because they are less than 1 meter from large surfaces (see 5.1.4).

NOTE B: Two values are recorded because of the pure tones present (see 5.1.5). The value used in the calculations shall be
3 dB below the highest value (see 5.2.2).

NOTE C: A valid measurement must be 6 dB above the ambient (see 5.2.1). Final results using these values less than 6 dB
above background result in Representative High Limit Values.

NOTE D: The level of the ambient here is 84 - 3 = 81 dB. This is 7 dB below the measured value and is an acceptable
measurement.

NOTE E: Thirteen valid measurements exist out of a possible 24 measurements. This is greater than half, and a value of AR
can be obtained. See the last statement of 5.2.3.

13
ARI STANDARD 575-94

APPENDIX C. REFERENCES
Listed here are all standards, handbooks, and other
publications essential to the formation and implementation
of the standard. All references in this appendix are
considered as part of this standard.

ASHRAE Terminology of Heating, Ventilation, Air-


Conditioning and Refrigeration, American Society of
Heating, Refrigerating, and Air-Conditioning Engineers,
Inc., 1991.