KIDDE® Catalog u Intelligent Input-Output

Compatible with VS & VM control systems

Technology that saves lives

Isolator Module
GSA-IM2 S3424

7300-1483:
0115

Overview Automatic Device Mapping - The Signature loop controller


learns keeps a map where each device’s serial number address
The GSA-IM2 Isolator Module is part of Kidde’s Signature Series is installed relative to other devices on the data circuit.
system. This intelligent device enables part of the Signature data
loop to continue operating should a short circuit occur. The Fast Stable Communication - Built-in intelligence means less
module can be wired into a Class A data loop at any point. information needs to be sent between the module and the loop
controller. Other than regular supervisory polling response, the
If a fault occurs, the isolator cuts power to all devices beyond the module only needs to communicate with the loop controller
isolator on the loop as follows: when it has something new to report.
• a short on the line causes all isolators to open within 23 msec.
• at 10 msec intervals, beginning on one side of the Class A
circuit nearest the loop controller, the isolators close to provide Standard Features
the next isolator down the line with power. • Automatic device mapping
• when the isolator next to the short closes, it reopens within 10 msec. Each module transmits wiring information to the loop
controller regarding its location with respect to other
Once activated, the line fault isolator continuously checks the devices on the circuit.
faulted side of the loop to determine if the short still exists. When
• Electronic addressing
the fault is corrected and system reset, the module automatically
Addresses are downloaded and permanently stored
restores the entire data loop to the normal condition.
from a PC, or the KI-HDT Signature Program / Service
The microprocessor in every Signature module provides at least Tool. There are no switches or dials to set.
three important benefits — Self-diagnostics and History Log,
• Ground fault detection by address
Automatic Device Mapping, and Fast, Stable Communication.
Detects ground faults right down to the device level.
Self-diagnostics and History Log - Each Signature Series • 2-gang mounting
module constantly runs self-checks to provide important
maintenance information. This information is automatically
updated and permanently stored in the module’s non-volatile
memory and is accessible for review any time using the
KI-HDT Signature Program / Service Tool.

Page 1 of 4 DATA SHEET K85001-0272


Not to be used for installation purposes. Issue 1.0
Testing & Maintenance Typical Wiring
The module’s automatic self-diagnosis identifies when it is defective IM IM
and causes a trouble message. The user-friendly maintenance
program shows the current state of each module and other SHORT
CIRCUIT
pertinent messages. Single modules may be turned off (deactivated)
temporarily, from the control panel. Availability of maintenance This part is removed
from circuit
features is dependent on the fire alarm system used. Scheduled
maintenance (Regular or Selected) for proper system operation
should be planned to meet the requirements of the Authority
Typical Class A Configuration
Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ ULC 536 standards. Data Out Data Return
Signature Loop Controller
Warnings & Cautions
This module will not operate without electrical power. As fires frequently cause IM IM
power interruption, we suggest you discuss further safeguardwith your fire
protection specialist.
SHORT
CIRCUIT
This part is removed
from the circuit
Typical Wiring and Installation
The GSA-IM2 module mounts to North American 2-1/2 inch (64
mm) deep 2-gang boxes and 1-1/2 inch (38 mm) deep 4 inch
square boxes with 2 gang covers and GSA-MP mounting plates.
Typical Class A Configuration
The module will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 Data Out Data Return with Class B T-Taps
AWG (1.50mm2), and #12 AWG (2.50mm2) wire sizes. Note: Sizes Signature Loop Controller
#16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for
ease of installation. See Signature Loop Controller catalog sheet
for detailed wiring requirement specifications.
Kidde recommends that this module be installed according to
latest recognized edition of national and local fire alarm codes.

Application
This module should only be used on Class A circuits. The
operation of the GSA-IM2 is determined by its hardware type code
and is assigned at the factory. No user configuration is required.

Compatibility
These modules are part of Kidde’s Signature Series intelligent
processing and control platform. They are compatible with Green LED
VM, and VS Series control panels. (normal - flashing)
TB1

From Signature Loop To Next Device or EOL


Controller or Previous Resistor supplied with
Device UL/ULC Listed Control Panel
DATA IN (+) DATA OUT (+)
DATA IN (-) DATA OUT (-)

4 3 5

1
For maximum wire resistance, refer to the appropriate
manufacturer’s documentation.
2 Max. #12 AWG (2.5mm²)wire.

3
Refer to Signature Loop Controller Installation Sheet for
wiring specifications.
4 This module should be used only with Class A wiring.
5 Maximum circuit resistance between isolators is 6 ohms.
6 All wiring is power-limited and supervised.

Page 2 of 4 D ATA S H E E T K85001-0272


Not to be used for installation purposes. Issue 1.0
Specifications Ordering Information
Isolator Module - factory set hardware type Catalog Description Ship Wt.
Description
code Number lb (kg)
Address Requirements Uses One Detector Address GSA-IM2 Fault Isolator Module - UL/ULC Listed .5 (.23)
Circuit Resistance Six ohms maximum between isolators
Operating Current Standby = 45µA; Activated = 45µA Accessories
Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) 27193-21 Surface Mount Box - 2-gang RED 1 (.4)
High Impact Engineering Polymer 2-gang 27193-26 Surface Mount Box - 2-gang WHITE
Construction & Finish
front plate - White Finish Multifunction Fire Cabinet - Red, supports
MFC-A 7.0 (3.1)
Storage Environment Temperature: -4°F to 140°F (-20°C to 60°C) Signature Module Mounting Plates
Temperature: 32°F to 120°F (0°C to 49°C); GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
Operating Environment
Humidity: 0 to 93% RH GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
On-board Green LED - Flashes when polled GSA- Signature Module Mounting Plate, 1/2 ex- 1.02
LED Operation
(normal) MP2L tended footprint (0.46)
Use with: Signature Loop Controller with KI
Compatibility
series detectors and GSA series modules.
Agency Listings UL, ULC, CSFM, FM

Page 3 of 4 D ATA S H E E T K85001-0272


Not to be used for installation purposes. Issue 1.0
Technology that saves lives

Contact us
Phone: 888.244.9979 (Option 4)
Email: kidde.fire@carrier.com
Website: kidde-esfire.com

Kidde is a Carrier brand.


8985 Town Center Pkwy,
Bradenton, FL 34202

© 2020 Carrier
All rights reserved.

07-31-20

Page 4 of 4 D ATA S H E E T K85001-0272


Not to be used for installation purposes. Issue 1.0