You are on page 1of 16

FUSES

Introduction:

 A fuse is a device that protects a circuit from an over current condition only. It has a fusible link directly
heated and destroyed by the current passing through it. A fuse contains a current- carrying element
sized so that the heat generated by the flow of normal current through it does not cause it to melt the
element; however, when an over current or short-circuit current flows through the fuse, the fusible link
will melt and open the circuit.
 A device that protects a circuit by fusing opens its current-responsive element when an over-current
passes through it. An over-current is either due to an overload or a short circuit condition.
 The Underwriter Laboratories (UL) classifies fuses by letters e.g. class CC, T, K, G, J, L, R, and so forth.
The class letter may designate interrupting rating, physical dimensions, and degree of current limitation.
 As per NEC and ANSI/IEEE standard 242 [2] – A current limiting fuse is a fuse that will interrupt all
available currents above its threshold current and below its maximum interrupting rating, limit the clearing
time at rated voltage to an interval equal to or less than the first major or symmetrical loop duration, and
limit peak let-through current to a value less than the peak that would be possible with the fuse replaced by
a solid conductor of the same impedance.

Fuse Construction:

 The typical fuse consists of an element which is surrounded by filler and enclosed by the fuse body. The
element is welded or soldered to the fuse contacts (blades or ferrules).
 The element is a calibrated conductor. Its configuration, mass and the materials employed are selected to
achieve the desired electrical and thermal characteristics.
 The element provides the current path through the fuse. It generates heat at a rate dependent on its
resistance and the load current.
 The heat generated by the element is absorbed by the filler and passed through the fuse body to the
surrounding air. The filler material, such as quartz sand, provides effective heat transfer and allows for the
small element cross-section typical in modern fuses.
 The effective heat transfer allows the fuse to carry harmless overloads .The small element cross section
melts quickly under short-circuit conditions. The filler also aids fuse performance by absorbing arc energy
when the fuse clears an overload or short circuit.
 When a sustained overload occurs, the element will generate heat at a faster rate than the heat can be
passed to the filler. If the overload persists, the element will reach its melting point and open. Increasing
the applied current will heat the element faster and cause the fuse to open sooner. Thus, fuses have an
inverse time current characteristic: that is, the greater the over current, the less time required for the fuse
to open the circuit.
 This characteristic is desirable because it parallels the characteristics of conductors, motors, transformers,
and other electrical apparatus. These components can carry low-level overloads for relatively long periods
without damage. However, under high-current conditions, damage can occur quickly. Because of its
inverse time current characteristic, a properly applied fuse can provide effective protection over a broad
current range, from low-level overloads to high-level short circuits.

Commonly used terms for Fuse:

 I2t (Ampere Square second): A measure of the thermal energy associated with current flow.I2t is equal to
(I RMS) 2 X t, where is the duration of current flow in seconds. A measure of thermal energy associated
with current flow. It can be expressed as melting I 2t, arcing I2t or the sum of them as Clearing I2t. Clearing
I2t is the total I2t passed by a fuse as the fuse clears a fault, with t being equal to the time elapsed from the
initiation of the fault to the instant the fault has been cleared. Melting I 2t is the minimum I2t required to melt
the fuse element
 Interrupting Rating (Abbreviated I.R.)Same as breaking capacity or short circuit rating. The maximum
current a fuse can safely interrupt at rated voltage. Some special purpose fuses may also have a
“Minimum Interrupting Rating”. This defines the minimum current that a fuse can safely interrupt. Safe
operation requires that the fuse remain intact. Interrupting ratings may vary with fuse design and range
from 35 amperes AC for some 250V metric size (5 x 20mm) fuses up to 200,000 amperes AC for the 600V
industrial fuses (for example, ATDR series).
 Clearing I2t: The total I2t passed by a fuse as the fuse clears a fault, with being equal to the time elapsed
from the initiation of the fault to the instant the fault has been cleared.
 Melting I2t: The minimum I2t required melting the fuse element.
 Ampere Rating: The continuous current carrying capability of a fuse under defined laboratory conditions.
The ampere rating is marked on each fuse.
 Available Fault Current: The maximum short-circuit current that can flow in an unprotected circuit.
 Coordination: The use of over current protective devices that will isolate only that portion of an electrical
system that has been overloaded or faulted.
 Current limiting Range: currents a fuse will clear in less than ½ cycles, thus limiting the actual magnitude
of current flow.
 Element: A calibrated conductor inside a fuse that melts when subjected to excessive current. The
element is enclosed by the fuse body and may be surrounded by an arc quenching medium such as silica
sand. The element is sometimes referred to as a link.
 Fast acting Fuse: This is a fuse with no intentional time-delay designed into the overload range. It is
sometimes referred to as a “single-element fuse” or “non-delay fuse.”
 Fault Current: Short-circuit current that flows partially or entirely outside the intended normal load current
path of a circuit component. Values may be from hundreds to many thousands of amperes.
 Ferrule: copper mounting terminals of fuses with amp ratings up to 60 amperes. The cylindrical terminals
at each end of a fuse fit into fuse clips.
 Current limiting Fuse: A fuse that meets the following three conditions:
1. interrupts all available over currents within its interrupt rating.
2. Within its current limiting range, limits the clearing time at rated voltage to an interval equal to, or less
than, the first major or symmetrical current loop duration.
3. Limits peak let-through current to a value less than the available peak current. The maximum level of
fault current that the fuse has been tested to safely interrupt.
 Arcing time: The amount of time from the instant the fuse link has melted until the over current is
interrupted, or cleared.
 Clearing time: The total time between the beginning of the over current and the final opening of the circuit
at rated voltage by an over current protective device. Clearing time is the total of the melting time and the
arcing time.
 Fast acting fuse: A fuse which opens on overload and short circuits very quickly. This type of fuse is not
designed to withstand temporary overload currents associated with some electrical loads. UL listed or
recognized fast acting fuses would typically open within 5 seconds maximum when subjected to 200% to
250% of its rated current. IEC has two categories of fast acting fuses:
1. F= quick acting, opens 10x rated current within 0.001 seconds to 0.01 seconds
2. FF = very quick acting, opens 10x rated current in less than 0.001 seconds
 Overload Can be classified as an over current which exceeds the normal full load current of a circuit by 2
to 5 times its magnitude and stays within the normal current path.
 Resistive load: An electrical load which is characterized by not drawing any significant inrush current.
When a resistive load is energized, the current rises instantly to its steady state value, without first rising to
a higher value.
 RMS Current: The R.M.S. (root mean square) value of any periodic current is equal to the value of the
direct current which, flowing through a resistance, produces the same heating effect in the resistance as
the periodic current does.
 Short circuit: An over current that leaves the normal current path and greatly exceeds the normal full load
current of the circuit by a factor of tens, hundreds, or thousands times.
 Time delay fuse: A fuse with a built-in time delay that allows temporary and harmless inrush currents to
pass without operating, but is so designed to open on sustained overloads and short circuits. UL listed or
recognized time delay fuses typically open in 2 minutes maximum when subjected to 200% to 250% of
rated current. IEC has two categories of time delay fuses:
1.T= time lag, opens 10x rated current within 0.01 seconds to 0.1 seconds
2.TT = long time lag, opens 10x rated current within 0.1 seconds to 1 second
 Voltage rating: A maximum open circuit voltage in which a fuse can be used, yet safely interrupt an over
current. Exceeding the Voltage rating of a fuse impairs its ability to clear an overload or short circuit safely.
 Over current: A condition which exists in an electrical circuit when the normal load current is exceeded.
Over currents take on two separate characteristics-overloads and short circuits.
 Threshold Current: The magnitude of symmetrical RMS available current at the threshold of the current-
limiting range, where the fuse becomes current-limiting when tested to the industry standard.
 Threshold ratio: A threshold ratio is a relationship of threshold current to a fuse’s continuous current
rating.

Threshold Ratio = Fuse Threshold Current / Fuse Continuous Current.


Maximum threshold ratio for various types of fuses:
Fuse Class Ratio

CLASS RK5 65

CLASS RK1 30

CLASS J 30

CLASS CC 30

CLASS L 30 (601-1200 Amps)

CLASS L 35(1201-2000 Amps)

CLASS L 40 (2001-4000 Amps)

 A current limiting fuse may be current limiting or may not be current limiting. The current limiting
characteristic depends on the threshold ratio and available fault current.
 Let’s consider an example of 1500 kVA radial service feeding a fusible switchboard with 2000 amps class
L fuses. As per ANSI C 57 [3] standard, a typical impedance value for this size of a transformer is 5.75%;
this value is a key factor in calculating the short circuit current.
 All utility’s network provides a specific fault current at a specific location which depends on various factors,
e.g.; cable lengths, cable size, X/R ratio and etc. If we ignore this limitation and assume that there is an
unlimited fault current available from a utility, then let’s calculate short circuit current from a 1500 kVA
transformer at 480 volts
 The formula to calculate short circuit current (Isc)
 ISC = (KVA X 10,000) / (1.732 X VOLT X %Z).
 ISC = 1500 X 10,000 / 1.732 X 480 X 5.75
 ISC = 31378.65 Amp.

Type of Fuse:

 A fuse unit essentially consists of a metal fuse element or link, a set of contacts between which it is fixed
and a body to support and isolate them. Many types of fuses also have some means for extinguishing the
arc which appears when the fuse element melts. In general, there are two categories of fuses.
1. Low voltage fuses.
2. High voltage fuses.
 Usually isolating switches are provided in series with fuses where it is necessary to permit fuses to be
replaced or rewired with safety.
 In absence of such isolation means, the fuses must be so shielded as to protect the user against
accidental contact with the live metal when the fuse is being inserted or removed.

LOW VOLTAGE FUSES:

 Low voltage fuses can be further divided into two classes namely
1. Semi-enclosed or Rewire able type.
2. Totally enclosed or Cartridge type.

(1) Re Wire able Fuse:

 The most commonly used fuse in ‘house wiring’ and small current circuit is the semi-enclosed or rewire
able fuse. (also sometime known as KIT-KAT type fuse). It consist of a porcelain base carrying the fixed
contacts to which the incoming and outgoing live or phase wires are connected and a porcelain fuse
carrier holding the fuse element, consisting of one or more strands of fuse wire, stretched between its
terminals.
 The fuse carrier is a separate part and can be taken out or inserted in the base without risk, even without
opening the main switch. If fuse holder or carrier gets damaged during use, it may be replaced without
replacing the complete unit.
 The fuse wire may be of lead, tinned copper, aluminum or an alloy of tin lead.
 The actual fusing current will be about twice the rated current. When two or more fuse wire are used, the
wires should be kept apart and a de rating factor of 0.7 to 0.8 should be employed to arrive at the total fuse
rating.
 The specification for re wire able fuses are covered by IS: 2086-1963. Standard ratings are 6, 16, 32, 63,
and 100A.
 A fuse wire of any rating not exceeding the rating of the fuse may be used in it that is a 80 A fuse wire can
be used in a 100 A fuse, but not in the 63 A fuse. On occurrence of a fault, the fuse element blows off and
the circuit is interrupted. The fuse carrier is pulled out, the blown out fuse element is replaced by new one
and the supply can is resorted by re-inserting the fuse carrier in the base.
 Though such fuses have the advantage of easy removal or replacement without any danger of coming into
the contact with a lie part and negligible replacement cost but suffers from following disadvantages:
1. Unreliable Operations.
2. Lack of Discrimination.
3. Small time lag.
4. Low rupturing capacity.
5. No current limiting feature.
6. Slow speed of operations.

(2) Totally Enclosed Or Cartridges Type Fuse:

 The fuse element is enclosed in a totally enclosed container and is provided with metal contacts on both
sides. These fuses are further classified as
1. D-type.
2. Link type.
 Link type cartridges are again of two type’s viz. Knife blade or bolted type.

A) D- Type Cartridges Fuses:


 It is a non-interchangeable fuse comprising s fuse base, adapter ring, cartridge and a fuse cap. The
cartridge is pushed in the fuse cap and the cap is screwed on the fuse base. On complete screwing the
cartridge tip touches the conductor and circuit between the two terminals is completed through the fuse
link. The standard ratings are 6, 16, 32, and 63 amperes.

 The breaking or rupturing capacity is of the order of 4k A for 2 and 4 ampere fuses the 16k A for 63 A
fuses.
 D-type cartridge fuse have none of the drawbacks of the re wire able fuses. Their operation is reliable.
Coordination and discrimination to a reasonable extent and achieved with them.
B) Link type Cartridge or High Rupturing Capacity (HRC):
 Where large numbers of concentrations of powers are concerned, as in the modern distribution system, it
is essential that fuses should have a definite known breaking capacity and also this breaking capacity
should have a high value. High rupturing capacity cartridge fuse, commonly called HRC cartridge fuses,
have been designed and developed after intensive research by manufactures and supply engineers in his
direction.

 The usual fusing factor for the link fuses is 1.45. the fuses for special applications may have as low as a
fusing factor as 1.2.
 The specification for medium voltage HRC link fuses are covered under IS: 2202-1962.

(A) Knife Blade Type HRC Fuse:

 It can be replaced on a live circuit at no load with the help of a special insulated fuse puller.

(B) Bolted Type HRC Link Fuse:

 It has two conducting plates on either ends. These are bolted on the plates of the fuse base. Such a fuse
needs an additional switch so that the fuse can be taken out without getting a shock.
 Preferred ratings of HRC fuses are 2, 4, 6, 10, 16, 25, 30, 50, 63, 80, 100, 125, 160, 200, 250, 320, 400,
500, 630,800, 1000 and 1,250 amperes.

Fuse Selection Guide:

 The fuse must carry the normal load current of the circuit without nuisance openings. However, when an
over current occurs the fuse must interrupt the over current, limit the energy let-through, and withstand the
voltage across the fuse during arcing. To properly select a fuse the followings must be considered:
 Normal operating current (The current rating of a fuse is typically de rated 25% for operation at 25C to
avoid nuisance blowing. For example, a fuse with a current rating of 10A is not usually recommended for
operation at more than 7.5A in a 25C ambient.)
 Overload current and time interval in which the fuse must open.
 Application voltage (AC or DC Voltage).
 Inrush currents, surge currents, pulses, start-up currents characteristics.
 Ambient temperature.
 Applicable standards agency required, such as UL, CSA, and VDE.
 Considerations: Reduce installation cost, ease of removal, mounting type/form factor, etc...

Recommended UL Current Limiting Fuse Classes:

TIME DELAY FUSE TYPE


Class Voltage Current
Class-L (LCL) 600V AC 601 – 6000A
Class RK1 (LENRK) 250V AC 0.6 -600A
Class RK1 (LESRK) 600V AC 0.5 -600A
Class RK5 (ECNR) 250V AC 0.1 -600A
Class RK5 (ECSR) 600V AC 0.1 -600A
Class J (JDL) 600V AC 1 -600A
Class CC (HCTR) 600V AC 0.25 -10A

FAST ACTING TYPE FUSE(Non/time-delay)


Class Voltage Current
Class-T (TJN) 300V AC 1 – 800A
Class-T (TJS) 600V AC 1 – 800A
Class-L (LCU) 600V AC 601– 6000A
Class-RK1(NCLR) 250V AC 1 – 600A
Class-RK1(SCLR) 600V AC 1 – 600A
Class J (JFL) 600V AC 1 -600A
Class CC (HCLR) 600V AC 0.1 -30A

Fuse Class:
(1) Class L, fuses

 They provide a minimum time delay of 4 seconds at 500% of their rated current to handle harmless inrush
currents, plus they are 20% more current limiting than any other Class L fuse.
 That means optimal over current protection for service entrances, large motors, feeders and other circuits.
 Range from 601 to 6000 amperes, 600V AC, 300kA
 I.R., and an exclusive 500V DC, 100kA I.R., through 3000A.
Features:
 Fastest operation under short circuit conditions
 Most current limiting for lowest peak let-thru current
 Replaces all older Class L fuses
 Pure silver links for long fuse life
 AC and DC ratings
 High-grade silica filler for fast arc quenching
Applications:
 Mains and feeders
 Large motors
 Lighting, heating and general loads
 Power circuit breaker backup
 UPS DC links, battery disconnects and other DC applications

Application notes:
 Mains and feeders — Can size at 100% of expected full load, unless equipment manufacturers specify
 Motor starters — Consult your motor control manufacturer’s recommendations.
 Lighting, heating and general loads — can size at 100% to 125%, depending on load make-up.
 Transformers — Due to the high inrush currents that can be experienced with transformers, size fuse to carry 12 times
transformer full load for 0.1 second and 25 times full load for 0.01 second.

(2) Class J, fuses

 The most current-limiting UL-class fuse, provide optimal performance, prevent interchangeability with old
fuses, and save valuable panel space. So you can use smaller, more economical fuse blocks and IEC
contactors to provide superior protection for dedicated or combined motor, lighting, heating and
transformer loads.
 Plus their time delay characteristic allows for use in a wide range of applications.
 Rated from 1 to 600 amperes, 600V AC, 300kA I.R., and 500V DC, 100kA I.R., listed to UL 248-8, they’re
the right fuses for any new installation.
Features:
 Most current-limiting UL-class fuses
 Timesaving Smart Spot™ indicator
 Unique dimensions prevent misapplications
 Optional mechanical indicator available on 70A to 600A AJT fuses
Applications:
 Motor circuits
 Mains and feeders
 Branch circuits
 Lighting, heating and general loads
 Transformers and control panels
 Circuit breaker backup
 Bus duct
 Load centers
Application notes:
 Mains and feeders: Can size at 125% of load for NEC and CEC code compliance.
 Motor starters: For typical starting duty and optimal coordination, fuse rating should not exceed 150% of
motor FLA. Where “no-damage” tests have been conducted, follow the control gear manufacturer’s fuse
ampere rating recommendations.
 Lighting, heating and general loads: Can size at 125% of combined load for NEC and CEC code
compliance.
 Transformers: Due to the high inrush currents that can be experienced with transformers, size fuse to carry
12 times transformer full load for 0.1 second and 25 times full load for 0.01 second.

(3) Class RK1 fuses:

 Significantly more current limiting than Class RK5, K and H fuses, upgrading your existing feeder and
branch circuits to arc flash category “0”. They also offer plenty of application flexibility, with ratings from
1/10A to 600A (250V or 600V), 300kA I.R.

Features:
 Highly current limiting to achieve HRC “0”
 Timesaving Smart Spot™ indicator
 Brass end caps (blade style) for cooler operation and superior performance
 Rejection-style design
Applications:
 Motors
 Safety switches
 Transformers
 Branch circuit protection
 Disconnects
 Control panels
 General-purpose circuits
Application notes:
 Mains and feeders: Can size at 125% of load for NEC and CEC code compliance.
 Motor starters: For typical starting duty and optimal coordination, fuse rating should not exceed 150% of
motor FLA. Where “no damage” tests have been conducted, follows the control gear manufacturer’s fuse
ampere rating recommendations.
 Lighting, heating and general loads: Can size at 125% of combined load for NEC and CEC code
compliance.
 Transformers :Due to the high inrush currents that can be experienced with transformers, size fuse to carry
12 times transformer full load for 0.1 second and 25 times full load for 0.01 second.

(4) Class CC, fuses

 Choose our highly current-limiting fuses when you need maximum fault protection for sensitive branch
circuit components and small motors. They deliver the best time delay characteristics and exceptional
cycling ability for frequent motor starts and stops without nuisance opening. They’re available in 1/4A to
30A, 600VAC, 200kA I.R.

Features:
 Highly current limiting
 Best time-delay characteristics in a Class CC fuse
 Exceptional cycling ability for frequent motor stops and starts
 Rejection-style design
Applications:
 Small motors
 Contactors
 Branch circuit protection
Application notes:
 Motor starters: for typical starting duty. Where “no damage” tests have been conducted, follows the control
gear manufacturer’s fuse ampere rating recommendations.
 Lighting, heating and general loads: Can size at 125% of combined load for NEC and CEC code
compliance.

(5) Class CC, fuses

 Class CC fuses provides the time delay needed to handle the high inrush currents of control transformers,
solenoids, and similar inductive loads.
 They’re available in 1/10A to 30A, 600V AC, 200kA I.R.
Features:
 Highly current limiting
 Rejection-style design
 Special time-delay characteristics for transformer loads
Applications:
 Control transformers
 Solenoids
 Inductive loads
 Branch circuit protection
Application notes:
 Control transformers, solenoids and similar inductive loads: For control transformers 600V AC or less with
ratings up to 2000VA.fuses are designed to handle 40 times the transformer’s primary full load amperes for
0.01 second.
 Lighting, heating and general loads: Can size at 125% of combined load for NEC and CEC code
compliance.

(6) Class RK5, fuses:

 Voltage / Ampere: 250V (1A to 200Amp), 600V (3A to 200A)


Description:
 The time delay characteristics of these fuses typically allows them to be sized closer to the running
ampacity of inductive loads to reduce cost and improve over current protection
Application:
 Use in AC power distribution system mains, feeders, and branch circuits.
 Recommended for high inrush inductive loads, like motors and transformers, and non inductive loads like
lighting, and heating loads.

(7) Class Midget fuses (600V, 0.5To 50A):

Description:
 Provides supplemental protection to end-use equipment with a 100KA interruption rating, 600VAC. Fast
acting design responds quickly to both overloads and short-circuit protection.
Application:
 Recommended for control circuits, street lighting, HID lighting, and electronic equipment protection

(8) Class Midget fuses (250V, 0.5To 50A)


Description:
 Provides supplemental protection to end-use equipment with a 10,000A interruption rating, economical
laminated paper tube
Application:
 Recommended to use as supplemental protection for non-inductive control loads and lighting circuits

(9) Class Midget fuses (500V, 0.25To 30A)

Description:
 Provides supplemental protection to high inrush loads. has a 10,000A interruption rating, 500VAC. Fiber
tube construction.
Application:
 Recommended to use as supplemental protection for inductive control loads such as transformers and
solenoids.

(10) Class Midget fuses (250V, 0.5To 30A)

Description:
 Provides supplemental protection to high inrush loads. has a 10,000A interruption rating, fiber tube
construction. Dual element allows harmless inductive surges to pass without opening
Application:
 Recommended to use as supplemental protection for inductive control loads such as transformers and
solenoid

(11) Class 1 1/4″ x 1/4″ Ceramic (250,125V, 0.5To 30A)

Description:
 Fast acting 1/4″ x 1-1/4″ ceramic tube construction.
Application:
 Recommended to use as supplemental protection for inductive control loads such as transformers and
solenoids.

(12) Class 1 1/4″ x 1/4″ Glass (250,32V, 0.5To 30A)

Description:
 Fast acting 1/4″ x 1-1/4″ glass tube construction.
Application:
 Recommended as supplemental protection for electronic applications.

(13) Class 5mmx20mm Glass (250,125V, 0.063To 15A)


Description:
 Fast acting 5mmx20mm glass tube construction.
Application:
 Recommended as supplemental protection for electronic applications.
(14) Class 5mmx20mm Glass (250,125V, 0.5To 10A)

Description:
 Medium Time Delay 5mm x 20mm glass tube construction.
Application:
 Recommended as supplemental protection for electronic applications.

(15) Class 1 1/4″ x 1/4″ Ceramic (250, 0.5To 20A)

Description:
 Time Delay 1/4″ x 1-1/4″ ceramic tube construction.
Application:
 Recommended as supplemental protection for electronic applications.

(16) Class 1 1/4″ x 1/4″ Glass (250,32V, 0.0625To 20A)

Description:
 Time Delay 1/4″ x 1-1/4″ glass tube construction.
Application:
 Recommended as supplemental protection for electronic applications

(17) Class 5mmx20mm Glass (250, 0.5To 10A)

Description:
 Fast acting 5mm x 20mm glass tube construction
Application:
 Recommended as supplemental protection for electronic applications.

(18) Class 5mmx20mm Glass (250, 0.25To 6.3A)

Description:
 Time Delay 5mm x 20mm glass tube construction.
Application:
 Recommended as supplemental protection for electronic applications.

Selection of Fuse for Main and Branch Circuits:

1 Main Service Conductor Cable Limiters (NEC 240,230.82):


 Select by cable size and mounting terminal configurations required.

2 Main Service Circuit Fuses–Mixed Loads:


 Size fuses same as item 6.

3 Transformer Circuit Fuses (NEC 450.3b, 240.3, 240.21, 430.72 (c) as required):*
 (a) PRIMARY FUSES: Size fuses not over 125%. As exceptions exist, refer to the appropriate NEC®
paragraphs.
 Recommended fuses. Time Delay- Class RK1, Class RK5, Class L, Class J)
 (b) SECONDARY FUSES (Sum of following): 125% of the continuous load + 100% of non-continuous
load. Fuse size not to exceed 125% of transformer secondary rated amps.
 RECOMMENDED FUSES: Class RK1, Class RK5, Class-J LENRK, ECNR, NCLR, JDL or LCU.

4 Branch Circuit Fuse Size, No Motor Load (NEC 240.3, 210.20):
 100% of non-continuous load, +125% of continuous load.
 *Do not exceed conductor ampacity. Recommended fuses: LENRK, ECNR, NCLR, JDL, LCU, or LCL.
5 Branch Circuit Fuse Size, No Motor Load (NEC240.3, 210.20):
 100% of non-continuous load, + 125% of continuous load. Fuse may be sized 100% when used with a
continuous rated switch. Recommended fuses same as 4.
6 Feeder Circuit Fuse Size, Mixed Load (NEC 240.3, 430.63, 430.24):
 (a) 100% of non-continuous, non-motor load + 125% of continuous, non-motor load.
 (b) Determine non-continuous motor load (NEC430.22 (e).1.) Add to “a” above.
 (c) Determine A/C or refrigeration load. (NEC 440.6). Add to “a” above.
 (d) Feeder protective device shall have a rating or setting not greater than the rating of the largest branch
device and sum of the FLCs of the other motors.(NEC 430.62)
 (e) Recommended fuses: LENRK/LESRK, JDL, ECNR/ECSR, LCU, LCL.

7 Feeder Circuit Fuse Size, 100% Motor Load (NEC 240.3, 430.62 (a).
 (a)Determine non-continuous motor load (NEC430.22 (e).
 (b)Determine load of A/C or refrigeration equipment (NEC 440.6). Add to “a” above.
 (c) Feeder protective device shall have a rating or setting not greater than the rating of the largest branch
device and sum of the FLCs of the other motors.(NEC 430.62)
 (d) Recommended fuses: LENRK/LESRK, JDL, ECNR/ECSR or LCL.

8 Branch Circuit Fuse Size, Individual Motor Load, With Fuse Overload Protection (No Starter Overload
Relays): (NEC 430.32, 430.36):
 (a) Motors with 1.15 Service Factor or temperature rise not over 40 Degrees C., size fuses at not more
than 125% of the motor nameplate current rating.
 (b) For all other A-C motors, size fuses at not more than 115 %.
 (c) Best protection is obtained by measuring motor running current and sizing fuses at 125% of measured
current for normal motor operation. Reference to “Average Time/Current Curves” is recommended.
 (d) Recommended Fuses: LENRK/LESRK, JDL, or ECNR/ECSR

9 Branch Circuit Fuse Size, Individual Motor Load, With Starter Overload Relays: (NEC 430.32, 430.52):
 (a) For “back-up” NEC® overload, ground fault and short circuit protection size the fuses the same as (8 a,
b) above, or the next standard size larger.
 (b) The fuse sizes in a) above may be increased as allowed by NEC® references. Generally, dual element
fuses should not exceed 175% of motor nameplate F.L.A. and non-UL defined time-delay fuses not more
than 300 %.
 (c) Recommended fuses: LENRK/LESRK, JDL, ECNR/ ECSR or LCL.

10 Fuse Sizing for Individual Large Motors With F.L.A. Above 480 Amps or Otherwise Require Class L
Fuses – (NEC 430.52):
 Application Tips:
 Size fuses as closely as practical to the ampacity of the protected circuit components without the
probability of unnecessary fuse opening from harmless, transient current surges. This usually requires a
choice between time-delay and non-time-delay fuses.
 Use Class R fuse clips with Class R fuses to prevent installation of fuses with less interrupting rating or
current limitation. Class H fuse reducers cannot be used with Class R fuse clips.
 When a conductor is oversized to prevent excess voltage drop, size the fuses for the ampacity of
protected circuit components instead of over sizing fuses for the larger conductor.

Selection of Fuse for Motor Protection:

 Group installation is an approach to building multi-motor control systems in accordance with Section 430-
53 of the National Electrical Code. The selection of components used in group installations is a simple
process which consists of several steps.
 First is the selection of the appropriate fuse as Branch Circuit Protective Device (BCPD).
 Second is the selection of the appropriate motor starter and protector.
 Third, the selected MMP must be checked for UL listing with the selected BCPD and the available short
circuit current at the application location.

1. Fused disconnect
 Calculate maximum fuse size according to NEC 430-53 (c).
 Imax (fuse size) =175% x FLC (full load current for largest motor) + the sum of FLC (full load current for
largest motor) + the sum of FLC values for other motors on that branch using NEC Table 430-150 on the
right.
 Select fuse from NEC Table 240-6 below. Where Imax falls between two fuse ampere ratings NEC 430-53
(c) permits going to the next high ampere rating.

2. Motor protector selection


 Select the proper MMP catalog number for each motor load from the based on the actual motor full load
current (FLA) using the “Thermal setting range” column for reference.

3. MMP Interruption ratings


 Using the interruption ratings table on the next page, identify the system application voltage and
interrupting capacity for the type of fuse selected in step1 above.
 NEC 240-6 Standard fuse amperes 15, 20, 25, 30, 40, 45, 50, 60, 70, 80, 90, 110, 125, 150, 175, 200,
225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600
 Examples: Select components for protecting the following 3-phase, 460VAC, squirrel cage induction
motors. The nameplate data are: 1/2 HP, 1.0 FLA; 3 HP, 4.8 FLA; 5 HP, 7.6 FLA; 7.5 HP, 11 FLA; 10 HP,
14 FLA.
 Example: using fused disconnect
 Imax = 175% x 14 + (11 + 7.6 + 4.8 + 1) = 48.9A
 Fuse rating using Table NEC 240-6 = 50A
 Minimum disconnect size = 115% x Total FLA
 NEC 430-150 table = 115% x (14+ 11 + 7.6 + 4.8 + 1) = 44.16
 Disconnect for 50A fuses is ok

 NEC Table 430-150 full load current, 3ph AC motor


H.P Induction Type Motor (Squirrel Cage, Wound Type)

230V Amp 460V Amp 575V Amp

½ 2 1 0.8

¾ 2.8 1.4 1.1

1 3.6 1.8 1.4

1.5 5.2 2.6 2.1

2 6.8 3.4 2.7

3 9.6 4.8 3.9

5 15.2 7.6 6.1

7.5 22 11 9

10 28 14 11

15 42 21 17

20 54 27 22

25 68 34 27

Fuse Ratings

 Fuses with an A-C voltage rating may be applied at system voltages below the fuse voltage rating, but not
at voltages above the fuse voltage rating.
 The other A-C fuse ratings remain the same at applied voltages below the fuse voltage rating.
 A-C rated fuses should not be applied in D-C voltage circuits unless D-C application ratings are provided
by the fuse manufacturer.
 Except for some special purpose fuses, D-C ratings are not usually shown on fuse labels.
 The operating frequency (Hertz) will affect fuse characteristics in various ways.
 Time/Current Curves will not shift and fuse ratings will not change from 1-100 Hertz in normal applications.
If ferrous hardware is used to mount the fuses, eddy current heating could alter the ratings.
 Above 100 Hertz, “skin effect” could alter the fuses’ rating characteristics. This effect must be analyzed on
an individual application basis.

Technical Specification for Rewire able Porcelain Cutout Fuse Unit


Electrical Characteristics & Performance:

 The rated currents of fuse carriers & fuse bases are 16A, 32A, 63A, 100A, 200A, 300A, 400A & 500A.
 The re- wire able fuses shall comply with IS : 2086 as amended from time to time up to date unless
otherwise stated elsewhere in this specification.
 The rated breaking capacity of the fuses up to 16A rating is 2 KA and for above 16A rating the same shall
be 4 KA, at a P.f not exceeding 0.4 (lag).
 The fuses wire shall conform to IS: 9962:1981 or latest amendment thereof, if any.
 The fuses wire shall be surrounded by an asbestos/porcelain tube for tending distribution of temperature
symmetrically. However, it may not be necessary for rating up to 100Amps.
 The ends of the tubes shall be baffled by the construction of the body & holder so that flame cannot emit.
 The length of the fuse wire & mass of the terminals shall be so designed to give desired current- time
characteristics of the fuse wire.
 The continuous rating of tinned-copper fuse wire in semi-enclosed fuses shall not be greater than 60% of
their minimum fusing current.
 The fuse shall glow within 30 minutes when carrying 1.9 times its rated current.
 The fuse shall carry 1.6 times rated current for at least 30 minutes.
 The fuses unit shall be capable of withstanding the let through fault current corresponding to prospective
fault current.
 The fuse carrier shall be capable to carry following size of fuse wires(tinned Copper Wire):

Rated Current Size of Fuse (mm) Fusing Current

16Amps 0.5 mm 25 Amp

32Amps 0.9 mm 50 Amp

63Amps 1.6 mm 100 Amp

100Amps 2.0 mm 160 Amp

200Amps 2X2.3 mm 300 Amp

300Amps 2X3.2 mm 480 Amp

400Amps 2X3.66 mm 600 Amp

500Amps 2X4.0mm 800 Amp

Technical Specification for L.T Rewire able Porcelain Fuse Unit

Mounting-of Fuse Unit:


 The Fuse Unit can be mounted in an enclosed or open state at any angle on a vertical plain without
impairing their performance.

Contacts:
 The contacts of Fuse Unit shall be robust construction and securely fixed on porcelain fuse base/ carrier
and shall conform to the; provision of IE Rule 1956 with latest amendments.
 Fixed and Moving Contact materials & other requirements: Annealed Electrolytic Copper duly electroplated
with tin or silver to avoid oxidization above 500 C. For fuse up to 100A tin plating shall be used with 8-10
micron thickness of plating.
 Fixed contacts shall be of spring loaded reversible loop type for base & that for Moving contact (carrier) is
knife contact type of ‘U‘SHAPE.
 The current density of contact material shall not exceed limit as per IS; 2086:1993 or other applicable
standard.
 The resistivity of contact material shall be less than0.017 micro ohm/meter.
 The melting point and specific heat of contact shall be 10800C & 375 J/KGK respectively.
 The magnitude of temperature rise of contacts at maximum ambient temperature of 40 0C for fixed & for
carrier is 550C.
 The voltage drop cross contacts with carrier fully engaged with contacts shall not exceed the limit as stated
in IS; 2086; 1993 or other applicable standards.
 The spring material of reversible loop base shall be of phosphor bronze.

Terminal Blocks:
 The terminal blocks shall be made of solid brass/solid copper alloy block of adequate mass to keep down
the temperature of the fuse unit. The temperature rise of fuse contacts and terminals need be limited to
lower values as far as possible up to 100% rated current for continuous operation to keep down the rate of
contacts.
 Terminal blocks shall be of following sectional area and lengths to take cable connections by means of
standard terminal screws up to 100A only. Above termination of Incoming/outgoing cables will be made
extended copper strips of thickness not below the size specified as follows and also as stated in Annexure.

Rating Min Acceptable Length Dia of hole in Size of Extended


Section (Min) Terminal Block and in Terminal Plate
Area(Including extended Plate
area of Hole)

16 Amps 60 mm2 9 mm. 4.5 mm Nil

32 Amps 80 mm2 9 mm. 5.5 mm Nil

63 Amps 200 mm2 9 mm. 9.5 mm Nil

100Amps 300 mm2 9 mm. 12.6 mm Nil

200 Amps 700 mm2 9 mm. 10 mm (In Ex.Plate) 5 x31 mm2

300 Amps 1000 mm2 9 mm. 12 mm (In Ex.Plate) 6 x41 mm2

400 Amps 1100 mm2 9 mm. 12 mm (In Ex.Plate) 6 x46 mm2

500 Amps 1200 mm2 9 mm. 16 mm (In Ex.Plate) 7 x50 mm2

 The hole in the Terminal Block shall be of appropriate diameter to receive Aluminum Conductor of rated
current carrying capacity.
 The brass socket of alum cable should have identical curre4nt carrying capacity of that of the cable. The
extended plates should be adequately electro-tinned and provided with hole/brass bolts and nuts/washer
for termination of Incoming/outgoing cable.
 To eliminate hazards of accidentally touching live parts, the extended terminals may be either provided
with protective enclosure (for extended pert only) or duly insulated with heat shrinkage PVC Tube.
 The heat shrinkage PVC covering should be of 1.1 KV Grade.
 The following are the recommended cable size for different current rating of fuse.

Fuse Rating Size of Aluminum Overall Dia of Conductor

16Amp 1X6 mm2 2.80 mm

16Amp 1X6 mm2 5.10 mm

32Amp 1X35 mm2 7.50 mm

100Amp 1X70 mm2 11.2 mm

200Amp 1X95 mm2 12.50 mm


300Amp 1X120 mm2 (2 No Parallel) 14.5 mm

400Amp 1X185 mm2 (2 No Parallel) 17.5 mm

500Amp 1X300 mm2 (2 No Parallel) 22.5 mm

Withdrawal Force:
Fuse Rating Withdrawal Force

16Amp 0.5 To 2.5 Kg

32Amp 1.5 To 5.5 Kg

63Amp 3 To 10 Kg

100Amp 4 To 10 Kg

200Amp 15 To 70 Kg

300Amp 15 To 70 Kg

400Amp 20 To 80 Kg

500Amp 20 To 80 Kg

Insulation Resistance:
 The insulation resistance of the fuse carrier & base contacts measured at a voltage of 500V D.C. between
the following parts shall be as under;
 Between live terminals and exposed metal parts-10 Meg.Ohm.
 Between live terminals and outgoing terminals-10 Meg.Ohm
 The power frequency withstand value shall be 2 KV r. m. s. for 1 minute for 1-phase 240V, 16A & for all
rating of 500A, 3- Ph. ,4- Wire shall be 2.5 KV r. m. s. for 1 minute.

Constructional Features of the Fuse Unit:


 The Fuse unit can be mounted in enclosed or open state at any angle on a vertical plain without comparing
their performance.
 The fuse unit shall be manufactured from the best quality of materials available indigenous.
 The constructional features of the fuse unit shall be in accordance with the following stipulations in
general.
 One Fuse base made of porcelain containing fixed contact which shall be connected to fixed terminal and
shall be so constructed to engage suitably with the carrier contact.
 The fixed contacts shall be of reverse loop type to prevent any tendency to throughout the fuse carrier
under service conditions specified in IS; 2086:1993.
 The phosphor bronze leaf shall be used to achieve the desired pressure of contacts.
 One Fuse base made of porcelain containing contacts with fuse element. The carrier contacts shall be
suitable for engaging with fixed contact and capable of having a fuse element attached to it.
 The fuse holder shall be of grip type. The carrier contacts shall be ‘U’ shaped and of knife contact design.

Porcelain:
 The fuse and carrier shall be made from good quality porcelain which is made from felspar (It serves as
the fluxing or melting constituents), Quarts and chins clay.
 The thickness of porcelain shall be 15 mm. minimum at fuse base and 20 mm. minimum for the grip of the
handle for the fuse carrier.

Thickness of Porcelain:
 The fuse base and carrier shall be of robust design so as to impart sufficient mechanical endurance
strength and withdrawal force to sustain impact from blown fuse and handling throughout its life.
 The thickness of porcelain shall be 15 mm. minimum at fuse base and 20 mm. minimum for the grip of the
handle for the fuse carrier.
Marking On Ceramics:
 Every fuse carrier shall have marking clearly and indelibly cast, attached or permanently marked in the
intended manner outside surface visible to operator.
 Rated Current.
 Rated voltage.
 Size of Fuse Wire.
 Nature of Supply.
 Manufacturers Trade/ Brand Name Mark.

Sealing:
 The holes in fuse carriers for fixing contacts shall be filled up with insulating grad ligur/epoxy based
compounds to avoid accidental contact with the live parts.
 Live parts on the underside of the fuse base shall be either covered by a shield or barrier 3mm. below the
surface of the base and covered with a water-proof insulating sealing compound which will not deteriorated
or flow at a temperature lower than 1000C.