INTERNATIONAL JOURNAL OF CONTROL, AUTOMATION AND SYSTEMS VOL.4 NO.

2 APRIL 2015
ISSN 2165-8277 (Print) ISSN 2165-8285 (Online) http://www.researchpub.org/journal/jac/jac.html

Artificial Neural Networks for Power Transformers Fault Diagnosis Based on


IEC Code Using Dissolved Gas Analysis

Sherif S. M. Ghoneim1, 2 and Ibrahim B. Taha1, 3

Abstract—Transformer is the main important equipment in The most five criteria that are commonly used for
electrical power system. Early stage detection of the dissolved gas analysis are the International Electro-
transformer faults has great economic significance because technical Commission standard (IEC) Code, the Central
it considered expensive equipment and it helps to maintain Electric Generating Board (CEGB) Code based on Rogers
the continuous operation of the electrical power system.
four ratios, Rogers’ method, Dornenburg method and
Transformer oil is used for two main purposes, one for
insulating liquid and the other for cooling. Some physical- Duval triangle according to the Institute of Electrical and
chemical tests are carried out to determine the physical and Electronics Engineers standard (IEEE-C57) [3].
chemical properties of the oil. Dissolved Gas Analysis (DGA) The above criteria do not involve any mathematical
is now considered a common practice method for detection formulation and their interpretations are based on
of the transformer incipient fault. This paper focuses on the heuristic methods that may vary based on experience of
employment of the Artificial Neural Network techniques the analyst, results in unreliable analysis [4]. To
(ANN) to diagnose dissolved gas in transformers, in order to overcome the drawbacks come from these criteria,
determine the fault causes based on the IEC standard various computational models using Artificial
method. The ANN on IEC Code results meets the similar
Intelligence (AI) have been used to analysis the incipient
results of the other techniques that use to diagnose the
transformer fault. Therefore, this method is very reliable to fault in power transformer. Application of AI in
use as a diagnostic tool for transformer fault detection. transformer incipient fault diagnosis requires real DGA
data. During the period of 1987-2012, there were over
Keywords—Transformer faults, Dissolved gas analysis, 400 research published on IEEE (26 EPSs, 72 ANNs, 58
Neural Networks. FL and ANN-FL, 20 ANN-EPS; 248 DGA and related
ones) [5]. Several AI methods have been developed for
I. INTRODUCTION more accurate diagnosis. These methods are mostly
Power transformer is considered as one of the most vital, suitable for transformers with a single fault or a dominant
important and expensive components in electric power fault. These AI methods are: Artificial Neural Network
systems. Any fault in power transformer may result in (ANN) [6,7], Fuzzy Logic [8, 9], Neuro–Fuzzy [10, 11],
power outages and black-outs of the electrical power Genetic [12, 13], Hidden Markov Model (HMM) [14],
system. Therefore, the early detection of the power Support Vector Machine (SVM) [15, 16], and Graphical
transformer incipient faults lead to an improvement in Techniques [17, 18]. They were developed as a novel
power system reliability and operation. Moreover, the technique to interpret the faults in power transformers.
replacement of a power transformer is very costly and In this paper, back propagation ANN model is
time consuming; hence it is very important to diagnose constructed based on DGA of the IEC Standard rules
incipient faults as soon as possible to prevent an increase method. A comparison between the results of the ANN
of the transformer faults and that obtained from the literatures is presented. The
Dissolved Gas Analysis (DGA) in the transformer oil is a results refer to the reliability of the proposed ANN model
wide spread method that is used to identify the incipient as a diagnostic tool for incipient power transformer fault.
faults in oil-filled power transformers. There are different
stresses affect on the insulating transformer oil, which are II. DISSOLVED GAS ANALYSIS (DGA): IEC
electrical and thermal stresses due to arcing, corona STANDARD CODE
discharges, sparking, or overheating fault. As a result of The IEC three-ratio method is widely used as a guideline
these stresses, insulating materials may be damaged and and a standard in diagnosis stage as it is being one of the
several gases are released. The main dissolved gases in effective and convenient guidelines and available
the transformer oil are: hydrogen (H2), methane (CH4), standards [4]. Table 1 shows the relations between the
ethane (C2H6), ethylene (C2H4), acetylene (C2H2), three-ratios and the method codes while Table 2 tabulates
carbon monoxide (CO) and carbon dioxide (CO2). The the IEC standard fault types in power transformer. It
detection methods based on dissolved gas analysis are consists of three key-gas ratios corresponding to the
used to diagnose the incipient fault in power transformer suggested fault diagnosis.
before deteriorating to a severe state [1-2].
1
College of Engineering Taif University, Saudi Arabia Kingdom
2
Faculty of Industrial Education, Suez University, Suez, Egypt,
ghoneim_sherif2003@yahoo.com, 3Faculty of Engineering,
Tanta University, Tanta, Egypt. ibm_taha_2013@yahoo.com

18
INTERNATIONAL JOURNAL OF CONTROL, AUTOMATION AND SYSTEMS VOL.4 NO.2 APRIL 2015
ISSN 2165-8277 (Print) ISSN 2165-8285 (Online) http://www.researchpub.org/journal/jac/jac.html

Table 1 IEC Code [1] working with the back-propagation learning algorithm
Gas Ratio Value Code [21, 22].
R1<0.1 0
x1 y1
R1=C2H2/C2H4 0.1≤R1≤3 1 b1
R1>3 2
x2 y2
R2<0.1 1 b2
Inputs Outputs
R2=CH4/H2 0.1≤R2≤1 0
R2>1 2
R3<1 0
xn yn
R3=C2H4/C2H6 1≤R3≤3 1 bn

R3>3 2
Input Layer Hidden Layers Output Layer
Table 2 Fault diagnosis using IEC Code
Fig. 1: MLP neural network training
Code The output from the sigmoid function lies between 0 and
No. Fault Type 1. The mean square error is proposed to a level of 0.0001,
R1 R2 R3
where a satisfactory agreement is found between the
training set results and the network result. In this study 74
samples of DGA were provided by the electrical utility
1 No fault 0 0 0
and 125 samples were taken from DGA results published
in the literatures [23, 30]. All 199 samples are used for
Partial discharge with low energy
3
density
0 1 0 validating the neural network model.

Partial discharge with high energy


The input and output patterns are required for Neural
4 1 1 0 network validity. Input patterns are considered the
density
dissolved gas ratios codes according to each fault state.
5 Arcing discharge with low energy 1or 2 0 1 For each input pattern, there exists an output pattern that
describes the fault type. Both input and output patterns
constitute ANN training set.
6 Arcing discharge with high energy 1 0 2
Input and output patterns are defined as follows:
Thermal fault with temperature This diagnosis criterion uses basically Rogers input
7 0 0 1
less than 150 oC
vector as follows:
Thermal fault with temperature [𝐼𝑛𝑝𝑢𝑡] = [𝑅1 , 𝑅2 , 𝑅3 ]𝑇 (1)
8 0 2 0
between 150 to 300 oC
The output vector is build up with ten elements according
Thermal fault with temperature
9
between 300 to 700 oC
0 2 1 to Table 2. Ten neurons are utilized in the output layer.
IV. VALIDATION OF THE PROPOSED SMART
Thermal fault with temperature
10
greater than 700 oC
0 2 2 DIAGNOSTIC DECISION SYSTEM
The validation of the proposed model is achieved by
Undetermined fault (fail to For above codes not
2
determine the fault type) obtained comparing its results with the results in literatures. Some
samples are collected from some researches and
III. APPLICATION OF ARTIFICIAL NEURAL laboratory analysis then compare them with the results in
NETWORK (ANN) FOR TRANSFORMER FAULT literatures. Table 3 illustrates the agreement between the
DETECTION ANN results and the results in literatures. It is agreement
percentage between the results from ANN and that in
ANN model is constructed using MATLAB software for Literatures as shown in Table 3 is more than 90%. It
IEC Standard code interpretation method. Figure 1 shows appears that a conflict among the results comes from the
the multilayer feed forward back-propagation is chosen as No fault identification as well as normal operation state
the network architecture because it considers the most with the thermal state in literatures. The results refer to
popular ANN Architecture [19] and its ability for pattern the reliability of the proposed ANN model as a diagnostic
recognition [20]. The ANN architecture model consists of tool for incipient fault detection.
four layer networks (one input layer, two hidden layer
and one output layer). V. CONCLUSION
An artificial neural network (ANN) model is constructed
A two layer perception has been utilized because of two for IEC Standard code method that based on dissolved
reasons. These are; the highly nonlinearity between the gas analysis. To test the NN model based on IEC rules,
input and due to a good performance of ANN when 102 samples are used. The agreement of NN model with

19
INTERNATIONAL JOURNAL OF CONTROL, AUTOMATION AND SYSTEMS VOL.4 NO.2 APRIL 2015
ISSN 2165-8277 (Print) ISSN 2165-8285 (Online) http://www.researchpub.org/journal/jac/jac.html

the literatures is more than 90% of the tested cases. The ACKNOWLEDGMENT
problem is experienced, the difference between the results
The authors thank Prof. Dr. Ayman A. Aly for his
from the proposed model and the results from literatures
valuable Discussion in construction ANN model.
come from No fault and No fault identification states with
the thermal fault for the literatures results.
REFERENCES
Table 3 Comparison between the results from ANN based on IEC
Standard interpretation method and the results from literatures and lab [1] IEC Publication 599, “Interpretation of the analysis of gases in
analysis transformers and other oil-filled electrical equipment in service”,
First Edition 1978.
H2 CH4 C2H6 C2H4 C2H2 CO IEC state Ref Ref. state
[2] IEEE Guide for the Interpretation of Gases Generated in Oil-
269 1081 347 1725 25 360 HTH [23] HTH Immersed Transformers, IEEE StandARCd C57.104-2008,
Feb.2009.
10 10 8 1 0.01 334 NF [23] LTH [3] Rahmat-Allah Hooshmand, and Mahdi Banejad, “Fuzzy Logic
Application in Fault Diagnosis of Transformers Using Dissolved
30 22 14 4.1 0.1 400 NF [24] NF
Gases”, Journal of Electrical Engineering & Technology, Vol. 3, No.
2.9 2 1.5 0.3 0.1 200 UD [24] NF 3, pp. 293~299, 2008.
[4] Fathiah Zakaria, Dalina JohARCi and Ismail Musirin, “Artificial
4 99 82 4.2 0.1 200 LTH [24] TH Neural Network (ANN) Application in Dissolved Gas Analysis
21 34 5 47 62 390 UD [24] HAD (DGA) Methods for the Detection of Incipient Faults in Oil-Filled
Power Transformer”, 2012 IEEE International Conference on
50 100 51 305 9 400 HTH [24] TH Control System, Computing and Engineering, Penang, Malaysia, 23
- 25 Nov. 2012.
120 17 32 4 23 350 UD [24] NF
[5] Nguyen Van Le, "Application of Artificial Intelligence in Diagnosis
980 73 58 12 0.01 243 PD [24] PD of Power Transformer Incipient Faults", 26th IEEE Canadian
Conference Of Electrical And Computer Engineering (CCECE),
30.8 149 47.9 146 0.1 350 HTH [24] TH Regina, Saskatchewan, Canada, 2013.
27 136 46.9 131 0.1 360 MTH [24] TH [6] J. L. Guardado, J. L. Nared, P. Moreno, and C. R. Fuerte, “A
Comparative Study of Neural Network Efficiency in Power
1607 615 80 916 1294 380 HAD [24] HAD Transformers Diagnosis Using Dissolved Gas Analysis”, IEEE
Transactions on Power Delivery, Vol. 16, No. 4, October 2001.
14.7 3.7 10.5 2.7 0.2 1046 NF [25] NF
[7] Vladimiro Miranda, Adriana R. Garez Castro, and Shigeaki Lima,
181 262 41 28 0.01 415 LTH [25] TH “Diagnosing Faults in Power Transformers With Autoassociative
Neural Networks and Mean Shift”, IEEE Transactions on Power
173 334 172 812.5 37.7 404 HTH [25] TH Delivery, Vol. 27, No. 3, July 2012.
127 107 11 154 224 478 HAD [25] HAD [8] Rahmatollah Hooshmand, and Mahdi Banejad, “Application of
Fuzzy Logic in Fault Diagnosis in Transformers using Dissolved
60 40 6.9 110 70 678 HAD [25] HAD Gas based on Different Standards”, World Academy of Science,
Engineering and Technology, 17, 2006.
27 90 42 63 0.2 470 MTH [25] TH
[9] Yann-Chang Huang and Huo-Ching Sun, “Dissolved Gas Analysis
980 73 58 12 0.01 243 PD [25] PD of Mineral Oil for Power Transformer Fault Diagnosis Using Fuzzy
Logic”, IEEE Transactions on Dielectrics and Electrical Insulation
86 187 136 363 0.01 26 MTH [26] HTH Vol. 20, No. 3; pp. 974-981, June 2013.
10 24 372 24 0.01 343 LTH [26] MTH [10] M. Allahbakhshi and A. Akbari, "Novel Fusion Approaches for the
Dissolved Gas Analysis of Insulating Oil", IJST, Transactions of
30.4 117 44.2 138 0.1 380 HTH [27] TH Electrical Engineering, Vol. 35, No. E1, pp 13-24, 2011.
[11] J. P. Lee, D. J. Lee, S. S. Kim, P. S. Jiand J.Y. Lim, “Dissolved Gas
260 3 18 2 0.01 350 PD [28] PD
Analysis of Power Transformer Using Fuzzy Clustering and Radial
586 19 77 6 0.01 370 PD [28] PD Basis Function Neural Network”, Journal of Electrical Engineering
& Technology, Vol. 2, No. 2, pp. 157~164, 2007.
200 700 250 740 1 415 MTH [29] TH [12] Alamuru Vani, and Pessapaty Sree Rama Chandra Murthy, “A
33 26 6 53 0.2 678 UD
[29]
NF
Hybrid Neuro Genetic Approach for Analyzing Dissolved Gases in
Power Transformers”, International Journal of Advanced Research
[29]
34.45 21.3 3.19 45 19.62 211 HAD HAD in Electrical, Electronics and Instrumentation Engineering, Vol. 3,
[29] Issue 11, November 2014.
180.85 0.5 0.234 0.18 0.0001 252 PD PD
[13]Wei Chang, and Ning Hao, “Prediction of Dissolved Gas Content in
[29] Transformer Oil Based on Genetic Programming and DGA”,
12 8 40 5 0.01 436 NF NF
[29]
International Conference on Transportation, Mechanical, and
16 25 19 39 0.01 383 MTH TH Electrical Engineering (TMEE), December 16-18, Changchun,
22 40 36 6 1 422 UD
[29]
TH
China, 2011.
[14]Qian Suxiang, Jiao Weidong, Hu Hongsheng, and Yan Gongbiao,
[29]
1770 3630 1070 8480 78 350 HTH TH "Transformer Power Fault Diagnosis System Design Based on the
[29] HMM Method", Proceedings of the IEEE International Conference
86 30 10 35 29 1014 HAD HAD
on Automation and Logistics, August 18 - 21, 2007, Jinan, China,
59.3 41 9.9 111 70 224 HAD [30] HAD pp. 1077-1082, 2007.
[30]
[15]Chenghao Wei, Wenhu Tang, and Qinghua Wu, "Dissolved Gas
239 27.5 5.5 25.5 85 317 LAD LAD Analysis Method Based on Novel Feature Prioritisation and Support
469 147 12.5 265 520 211 HAD
[30]
HAD
Vector Machine", IET Electric Power Applications, Vol. 8, Issue 8,
pp. 320–328, 2014.
[30]
56 5.5 92 34.5 27.5 436 PD LDA [16]Seifeddine Souahlia, Khmais Bacha, and Abdelkader Chaari,
[30] "SVM-Based Decision for Power Transformers Fault Diagnosis
14 237 92 470 0.01 365 HTH HTH
Using Rogers and Doemenburg Ratios DGA", 10th International
157 127 34 96 0.01 422 LTH
[30]
LTH Multi-Conference on Systems, Signals & Devices (SSD),
Hammamet, Tunisia, March 18-21,pp. 1-6, 2013.

20
INTERNATIONAL JOURNAL OF CONTROL, AUTOMATION AND SYSTEMS VOL.4 NO.2 APRIL 2015
ISSN 2165-8277 (Print) ISSN 2165-8285 (Online) http://www.researchpub.org/journal/jac/jac.html

[17] Diaa-Eldin A. Mansour, “A New Graphical Technique for the Appendix


Interpretation of Dissolved Gas Analysis in Power Transformers”, ARC: discharge arcing
2012 Annual Report Conference on Electrical Insulation and UD: undetermined fault or no fault identification
Dielectric Phenomena (CEIDP), pp.195 – 198, 14-17 Oct. 2012. TH: thermal fault
[18] Y.M.Kim, S.J.Lee, H.D.Seo, J.R.Jung and H.J.Yang, PD: partial discharge
“Development of Dissolved Gas Analysis (DGA) Expert System NF: no fault (normal operation)
Using New Diagnostic Algorithm for Oil immersed Transformers”, HAD: high discharge energy arcing
Journal of Electrical Engineering & Technology, Vol. 3, No. 3, pp. LAD: low discharge energy arcing
293~299, 2008. HTH: high temperature thermal fault
[19] Wan Mohd Fahmi Wan Mamat,; Nor Ashidi Mat Isa,; Zamli, LTH: low temperature thermal fault
Kamal Zuhairi; Wan Mohd Fairuz Wan Mamat,; , "Hybrid Version MTH: medium temperature
of MLP Neural Network for Transformer Fault Diagnosis System",
International Symposium on Information Technology, Vol.2, No., Author' profile:
pp.1-6, 26-28 Aug. 2008.
[20] Sánchez and Lau, "Artificial Neural Networks," New York, USA: Sherif S. M. Ghoneim Received B.Sc. and M.Sc.
IEEE Press, 1992. degrees from the Faculty of Engineering at
[21] L. Haykin, "Neural Networks: A Comprehensive Foundation," Shoubra, Zagazig University, Egypt, in 1994 and
Montreal, Canada: Macmillan College Publishing Company Inc., 2000, respectively. Starting from 1996 he was a
1994. teaching staff at the Faculty of Industrial
[22] J. Hilera and V. Martínez, "Redes Neuronales Artificiales," Education, Suez Canal University, Egypt. Since
Addison- Wesley Iberoamérica, RA-MA, 1995. end of 2005 to end of 2007, he is a guest
[23] Sherif Ghoneim, and Nadjim Merabtine, “Early Stage Transformer researcher at the Institute of Energy Transport and
Fault Detection Based on Expertise Method”, International Journal Storage (ETS) of the University of Duisburg-
of Electrical Electronics and Telecommunication Engineering, Vol. Essen-Germany. In 2008, he got Ph.D Degree in Electrical power and
44, pp.1289 – 1294, Aug. 2013. machines, Faculty of Engineering-Cairo University (2008). He joins
[24] Souahlia Seifeddine, Bacha Khmais, and Chaari Abdelkader, now the Taif University as an assistant professor in the Electrical
"Power Transformer Fault Diagnosis Based on Dissolved Gas Engineering Department, Faculty of Engineering. His research focuses
Analysis by Artificial Neural Network", First International in the area of Grounding systems, Dissolved gases analysis,
Conference on Renewable Energies and Vehicular Technology, Breakdown in SF6 gas and artificial intelligent technique applications.
2012.
[25] Mang-Hui Wang,"A Novel Extension Method for Transformer Ibrahim B. Taha Received B.Sc. degree from
Fault Diagnosis", IEEE Transactions on Power Delivery, vol. 18, the Faculty of Engineering at Tanta, Tanta
no. 1, January 2003. University, Egypt, in 1995. He received M.Sc.
[26] Sherif S. M. Ghoneim, and Sayed A. Ward, " Dissolved Gas degree from the Faculty of Engineering at
Analysis as a Diagnostic Tools for Early Detection of Transformer Mansoura, Mansoura University, Egypt, in
Faults", Advances in Electrical Engineering Systems (AEES), Vol. 1999. Starting from 1996 he was a teaching
1, No. 3, 2012, pp. 152-156. staff at the Faculty of Engineering, Tanta
[27] Khmais Bacha, Seifeddine Souahlia, and Moncef Gossa, "Power University, Egypt. In 2007, he got Ph.D
Transformer Fault Diagnosis Based on Dissolved Gas Analysis by Degree in Electrical power and machines,
Support Vector Machine", Electric Power System Research, pp. 73- Faculty of Engineering-Tanta University (2007). He joins now the Taif
79, 2012. University as an assistant professor in the Electrical Engineering
[28] M. R. Ahmed, M. A. Geliel, and A. Khalil, "Power transformer Department, Faculty of Engineering. His research focuses in the area
Fault Diagnosis using Fuzzy Logic Technique Based on Dissolved of steady state and transient stability of HVDC systems, FACTS,
Gas Analysis", 21st Mediterranean Conference on Multi Level Inverters, Dissolved gases analysis, and artificial
Control&Automation (MED), Platanias-Chania, Crete, Greece, June intelligent technique applications.
25-28, 2013, pp. 584-589, 2013.
[29] Mehrdad Beykverdi, F. Faghihi, and A. MoArefian pour, "A New
Approach for Transformer Incipient Fault Diagnosis Based on
Dissolved Gas Analysis (DGA)", Nova Explore Publications, Nova
Journal of Engineering and Applied Sciences, Vol. 2(3), pp. 1-8,
March 2014.
[30] Amit Kumar Mehta, R. N. Sharma, Sushil Chauhan, and Satyabrata
Saho, "Transformer Diagnostics under Gas Analysis Using Support
Vector Machine", International conference on Power, Energy and
Control (ICPEC), pp. 181-186, 2013.

21

You might also like