Professional Documents
Culture Documents
Power Transformers
Need for
Transformer Condition Monitoring
• Expensive capital equipment
• Not easy to repair or replace
• Advanced computer aided design practices.
• Transformers operation.
• Condition Monitoring imperative.
• A corrective/preventive action can be initiated.
Transformer Ageing
• Life of transformer depends on the
condition of insulation system (kraft
paper and oil) with time under impact of:
– Thermal stresses
– Electromagnetic stresses
– Electro-dynamic stresses
– Contamination and natural ageing processes
effecting the tensile strength of paper
Transformer Ageing
• Rate of deterioration depends upon the
operating conditions - loading pattern,
incipient faults, maintenance
Terminals (29%)
• Mechanical Faults:
– Tank, fittings and accessories
– damaged porcelain insulators
– clogged oil piping, damaged gaskets
– mechanical damage of the windings.
Types of Transformer Faults
• Electrical Faults:
– Low insulation resistance
– Punctured insulation between turns,
sections, windings and various high
potential points.
Types of Transformer Faults
• Magnetic Faults:
– Abnormal heating
– Breakdown of insulation between
core laminations core fixtures and
clamping
– Non-uniform distribution of magnetic
flux.
Reliability
• BS:4778/1991 Section 3.1 defines reliability
as ‘the characteristic of an item expressed by
the probability that it performs required
conditions for a stated period of time’.
• Reliability of a transformer is determined by:
– Design of transformer
– Quality of materials
– Quality of manufacturing processes
– Operation and maintenance
‘Why’ Condition Monitoring?
Early detection of incipient faults
Avoid catastrophic outage
Provide basis for economic repair
decision
Maintenance Management
Maintenance management based on
measurements and trend analysis
Ageing process and residual life
under control
Improve safety to personnel and
environment
‘Purpose’ ….
• Purpose of Condition Monitoring:
– Avoid forced outages
– Minimize failures
– Optimize maintenance costs
Often used techniques
Tests To detect
E F G
Ratios < 1 are designated as ‘0’ ; Ratios > 1 are designated as ‘1’
DGA - IEC : 599 Method
Code of range of
Ratios
C2H2/ CH4/ C2H4/
C2H4 H2 C2H6
Ratios of Characteristic gases
< 0.1
0.1 – 1 0 1 0
1-3 1 0 0
>3 1 2 1
2 2 2
Case No Characteristic fault Typical examples
0 No fault 0 0 0 Normal ageing
1 PD of low energy density 0 1 0 Discharges in gas-filled cavities resulting from
incomplete impregnation or super-
Saturation or cavitation or high humidity
2 PD of high energy density 1 1 0 As above, but leading to tracking or perforation
of solid insulation
3 Discharges of low energy (See 1→2 0 1→2 Continuous sparking in oil between bad
note 1) connections of different potential or to floating
potential. Breakdown coils to earth. Selector
breaking current
4 Discharge of high energy 1 0 2 Discharges with power follow-through. Arcing –
breakdown of oil between windings or coils to
earth. Selector breaking current.
5 Thermal fault of low temp. 0 0 1 General insulated conductor overheating.
<1500C (See bite 2)
6 Thermal fault of low temp. 0 2 0 Local overheating of the core due to
range 150–3000C. (See note 3) concentration of flux. Increasing hot spot
7 Thermal fault of medium temp. 0 2 1 temperatures; varying from small hot spots in
300 – 7000C core, shorting links in core, overheating of
8 Thermal fault of high temp. 0 2 2 copper due to eddy currents, bad contacts/joints
> 7000C (See note 4) up to core and tank circulating currents
DGA - IEC : 599 Method
Notes:
1. For the purpose of this table, C2H2/C2H4 to rise
from a value between 0.1 and 3 to above 3 and the
ratio C2H4/C2H6 from a value between 0.1 and 3 to
above 3 as the spark develops in intensity.
2. In this case the gases come mainly from the
decomposition of the solid insulation, this explains
the value of the ratio C2H4/C2H6.
3. This fault condition is normally indicated by
increasing gas concentrations. Ratio CH4/H2 is
normally about 1; the actual value above or below
unity is dependent on many factors such as design
of oil preservation system, actual level of
temperature and oil quality.
4. An increasing value of the amount of C2H2 may
indicate that the hot point temperature is higher
than 10000C.
Dissolved Gas Analysis (DGA)
Acceptable limits of Dissolved Gases (Trafo-Tech 2006)
Gases in PPM Age of transformer in years
0 - 5 6 - 10 11 - 15 > 15
Hydrogen 100 100 100 100
Carbon Dioxide 9000 9000 9000 15000
Carbon 500 700 1500 1500
Monoxide
Methane 70 70 200 200
Ethane 40 40 200 200
Ethylene 40 100 200 200
Acetylene 10 10 20 50
Dissolved Gas Analysis (DGA)
• Limitations of the DGA:
– It cannot detect the incipient faults
– Values measured are the average values
over a period of time.
• On line monitoring of H2 is quite popular.
• Sensors have also been developed for
on-line monitoring of CO, CO2 and C2H2.
Furfuraldehyde Analysis
• Prolonged action of heat on cellulose paper causes
de-polymerization, which is aggravated by presence of
moisture, forming furanic compounds.
• Thermal degradation of oil-paper insulation system
yields different amounts of furanic derivatives, the
most common being 2-furfuraldehyde.
• Such deterioration of paper on winding conductor can
be assessed by subjecting the paper to various tests.
• Windings of oil filled transformers are not accessible.
Can be accessed after draining oil which is a tedious
process.
• The furfural derivatives produced due to degradation
of paper dissolve in oil.
Furfuraldehyde Analysis
• Hence, the chemical analysis of transformer oil gives
the evidence of changes that are taking place in the
winding during normal operation.
• The main advantage of using furan analysis as a
diagnostic tool is that these compounds are
degradation products specific to paper and can not be
produced by oil.
• It has been estimated that new paper under normal
running conditions will generate furfural at the rate of
1.7 ng/g of paper/hour. The rate of production increases
with increasing degree of degradation to 0.5 mg/g of
paper in about 100,000 hours or 15-20 years.
Furfuraldehyde Analysis
• Elevated temperatures or presence of
oxygen or water increase this rate. The
limits of detection of furfural are about
0.02 mg/l of oil.
• Acceptable levels of furfural in
transformer oil:
– <0.1 mg/l – acceptable;
– >0.1 mg/l – questionable and
– 0.25 mg/l – unacceptable.
Degree of Polymerization (DP)
• Paper insulation of conductor is subjected
the maximum operating temperature
• Life of transformer depends on the extent of
degradation of conductor insulation.
• DP closely relates to the mechanical
properties of paper. Life of paper is
considered to have been expired once tensile
strength of paper drops to approximately 50
to 60% of initial tensile strength which is
reached when DP reaches a level of nearly
20% of the initial degree of polymerization.
Degree of Polymerization (DP)
• Computation of the percentage
remaining life is calculated by:
% Remnant life = {(DP-200)x100}
(1200-200)
The new paper has a DP of 1200 and
end of life is found to be 200.
Degree of Polymerization (DP)
• Another method used is to measure the
specific viscosity of a solution of paper in
cupriethylene diamine. From this, the
intrinsic viscosity of the solution is
calculated by:
ns = (Viscosity of paper solution – viscosity
of solvent) / Viscosity of solvent.
The degree of polymerisation is calculated
from the intrinsic viscosity using Martin’s
tables.
Degree of Polymerization (DP)
• The correlation between the furfural
content and the DP value and the
residual life is given by the formulae:
Log (fur) = 1.51 – 0.0035DP
Log (fur) = -1.83 + 0.058T where T is
the residual life.
Degree of Polymerization (DP)
Correlation between furan concentration and DP
Total furan level (ppb) Range of DP Recommended retest
period (months)
100 444-1200 12
101-250 333-443 6
251-1000 237-332 3
1001-2500 217-236 1
Test Periodicity
Winding resistance