Professional Documents
Culture Documents
1 Scope............................................................. 3
2 References..................................................... 3
3 Purpose.......................................................... 3
4 Responsibilities.............................................. 4
5 Introduction to Cleaning................................. 6
6 Preparations for Chemical Cleaning............... 6
7 Criteria for Cleaning....................................... 9
8 Chemical Cleaning Treatment Selection...... 10
9 Alkaline Treatments...................................... 13
10 Acid Cleaning and Neutralization................. 16
11 Passivation................................................... 26
12 Evaluating Cleaning Performance
by Inspection........................................ 28
13 Equipment Lay-Up....................................... 28
14 Corrosion Control, Water and
Chemical Treatment Subcommittee..... 29
Page 2 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
1 Scope
This procedure defines the responsibilities of the various departments involved in the
pre commission and operational cleaning. It outlines methods to determine the need for
cleaning, the criteria for selecting specific cleaning procedures, and steps involved in
various cleaning procedure alternatives.
The use of high pressure water jetting is covered in Appendix 5 and on-stream cleaning
in Appendix 6. Advice is available from Materials Engineering & Corrosion Control
Division/Consulting Services Department (ME&CCD/CSD) to draft detailed
procedures for cleaning specific equipment.
The procedures listed herein are applicable to clean undesirable deposits in heat
exchangers and other unfired plant equipment such as piping, columns, vessels,
Multiple Effect Distillation (MED) units, etc.
For evaluation and recommendation of alternative cleaning procedures not listed herein
contact ME&CCD/CSD.
2 References
3 Purpose
It is necessary to clean a new equipment initially and periodically thereafter for its
efficient operation, corrosion control and prevention of fouling related failures.
Cleaning is accomplished by a combination of (not necessarily in the sequence listed):
• Mechanical cleaning
• High pressure water jetting (HPJ)
• Hot alkaline treatment
• Acid cleaning and Neutralization
• Passivation
• Cleaning with Solvents
Page 3 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
For some equipment it may not be necessary to use all of the above steps since the
degree of contamination will vary from unit to unit. Scale severity, and its analysis,
tube failures, inspection and consultation with the various departments outlined in
Section 4 will determine the exact procedure to be used. This procedure does not
override an equipment manufacturer's cleaning recommendations, especially where
warranty rights are involved. Differences shall be questioned and resolved by the
proponent.
4 Responsibilities
4.1 The Project Construction Agency is responsible for cleaning new equipment.
4.2.1 Maintenance
• Prepares the equipment mechanically.
• Provides maintenance support during the cleaning operation.
• Coordinates cleaning and obtains approved contractor services.
Page 4 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
4.7 ME&CCD/CSD
• Reviews and approves the cleaning procedures and subsequent changes
necessitated by the field conditions.
• Provides specialist/consultant advice on request.
• Witnesses the cleaning operation on request.
Page 5 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
5 Introduction to Cleaning
The cleaning process may involve a combination of several stages. Plan the stages of
cleaning in advance.
5.1 Mechanically remove, using power brushes or reamers as much of the deposits
as possible from the equipment.
5.2 Remove deposits if access is available with high-pressure water jetting. See
Appendix 5 for details.
5.4 Remove oil, grease, and organic deposits and to neutralize pyrophoric material
with hot permanganate, alkaline treatment, or surfactants.
5.5 Removal of tarry and polymerized deposits by cleaning with organic solvents
such as heavy aromatic naphtha (HAN), kerosene, diesel, gas oil, or proprietary
solvents.
5.6 Acid clean to chemically remove, mill scale, mineral deposits from water,
process side deposits and corrosion products.
5.7 Neutralize acids and passivate to form a strongly adherent protective oxide layer
on the wetted metal surface.
6.1 General
2. Isolate the equipment from the process side by blinds. Install vents and
adequately sized temporary valves to permit draining acids with in 30
minutes. Use temporary plugs or slip blinds to isolate sections that do not
require cleaning.
3. Store all chemicals needed for the procedure on-site prior to commencing
cleaning, including emergency neutralizing agents and nitrogen as well as
wet lay-up chemicals.
Page 6 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
6. Install fittings for liquid sampling, flow elements, temperature probes, pipe
spools with on-line access fittings for corrosion monitoring probes.
8. Plan for the disposal of wastewater and spent chemical solutions per
SAEP-327.
13. Check and ensure that the flow design includes: flow reversal manifold
and valves, control valves and bypass to control circulation within
specified limits, blend filling of corrosive chemicals (acids and chelants)
without exposure to the atmosphere.
14. Test the cleaning circuit hydrostatically at 1.25 times the dead head
discharge pressure of the circulating pump, after installation of all
temporary piping and connections, prior to chemical cleaning.
15. Ensure that an external heat source is available to maintain the cleaning
fluid temperature, within the limits specified.
16. Ensure spare pumps are available in case of a pump failure to maintain
circulation, and nitrogen pressure connection to drain the acid within
fifteen minutes in case of an emergency. Ensure sufficient holding tank
capacity is available for draining and neutralizing cleaning solutions if
necessary.
Page 7 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
19. Determine the volume of the equipment by filling with water and draining
it through a flow meter.
20. Be aware of the safety hazards (see Appendix 9) associated with chemical
cleaning and take adequate safety measures.
21. Ensure chemical feed lines are a minimum of 1/12th the diameter of the
vessel or exchanger; drains and vents are clear.
22. Ensure that the chemical cleaning contractor is on-site with mixing tanks,
chemicals, flow meter, corrosion monitoring equipment, pH and
temperature probes, and pumping equipment to blend fill and circulate
chemicals.
23. Flush the equipment with water until it runs clear to remove all loose and
soluble deposits.
24. Use commercial grade quality for all chemicals except where austenitic
materials are present in the equipment to be cleaned. In this case, the total
chlorides of all the chemicals in the mixture must not yield a final solution
containing greater than 50 mg/L as chloride.
25. Install at least one corrosion probe in the circulating loop for on line
monitoring and control of corrosion rates.
Page 8 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
5. Rope off the area where the blending and heating of chemical solutions is
performed and post "DANGER" signs. Do not let unauthorized personnel
enter the roped off area.
7. Ensure all nitrogen cylinders if in use, have individual regulators and are
adequately secured. Also, ensure the nitrogen manifold has a safety relief
valve attached.
10. Be aware and prepared for safety hazards with equipment deposits, noted
in Appendix 9.
Use any one of the following criteria to determine when to schedule cleaning.
1. Inspection: On every T & I, check inside the tubes and shell for corrosion and
scale. Note down the location and amount of scale buildup and check tube ends
for pits, and deposit. Scrape off deposits to determine its composition. Low flow
rate areas, boots, drains are particularly susceptible to heavy deposit buildup.
Visual inspection will indicate the condition of the equipment and will be one of
Page 9 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
the primary factors in determining the need for cleaning. Inspect tubes inside and
on shell side for total blockage. Blocked tubes cannot be chemically cleaned until
a flow path is made for chemical circulation.
2. Clean whenever the actual heat transfer coefficient ( Uactual) drops to 60 % of the
Udesign at heat exchanger design operating conditions. (See Appendix 7).
4. Clean when the total fouling related expenditure (TFRE) is at the minimum. (See
Appendix 8).
8.1.1 Primarily select chemicals that: a) are safe to use, b) are compatible with
the materials of construction (see Appendix 10), c) will remove > 70% of
the undesired deposits, d) will achieve the desired degree cleaning.
8.1.2 With these criteria satisfied, make the final selection, with due reference
to other constraints including cost, environmental restriction on disposal
of waste solutions, and cleaning time available. Responsibility for the
final procedure of the treatment(s) is defined in Section 4. For on stream
cleaning see Appendix 6. Off stream chemical cleaning will involve one
or more of the following steps: Hot alkaline degreasing (see section 9),
acid cleaning (see section 10), followed by neutralization and passivation
treatment (see section 11). Laboratory analyses of deposit samples will
determine the above sequence.
8.1.3 High pressure water jetting (HPJ) may precede or follow to remove
loosened scale (see Appendix 5). HPJ is very effective to remove most
brittle deposits. The use of HPJ is recommended alone, or before
chemical cleaning.
Page 10 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
8.2.2 Solubility in Dilute HCl - This figure represents the weight percent of the
deposit, which will dissolve in boiling 7.5% wt., inhibited hydrochloric
acid.
8.2.3 Loss on Ignition - This figure represents the weight percentage of the
deposit that can be removed by heating the insoluble residue from 8.2.1
above to 315°C in a laboratory furnace. The result is indicative of the
organic content of the deposit in the forms of oil, grease, degraded
polymers and carbon. If the figure is high (greater than 10%) further
definition of the organic content can be determined by refluxing the
sample with a suitable organic solvent, which will indicate the relative
proportions of oil and grease, and carbon. These proportions assist in the
selection of a suitable hot alkaline or permanganate treatment.
8.2.5 Metals - The metal ions present in the deposit, are analyzed for iron (Fe),
copper (Cu), calcium (Ca), magnesium (Mg), nickel (Ni), zinc (Zn),
manganese (Mn) and sodium (Na). These results are useful to determine
the number of cleaning stages that are likely to remove all the deposits
from the system.
8.2.6 Anions - Phosphate, sulfate, carbonate and sulfide are also determined in
the scale. This information is useful to determine the need for
sulfate/sulfide conversion treatment or the need to suppress the evolution
of H2S during acid cleaning.
8.3.1 Where oil, grease, carbon, or other organic compounds are present, these
must be removed during cleaning. Selection depends on the degree of
contamination. Use hot alkaline treatment only when organic deposits
Page 11 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
8.3.3 Caustic degreasing (NaOH) is the treatment used for all new equipment,
and where mill scale is present, or organic contamination is 5% to 25%.
See Section 9.2.
8.4.1 Hydrochloric Acid: Inhibited hydrochloric acid is the most widely used
acid since it produces good solubility with a wide variety of scales, is
economic, and easy to handle. It exhibits good corrosion characteristics
when correctly inhibited and the process is controlled within the
accepted limits. The process is flexible and can be modified to enhance
silica removal by the addition of ammonium bifluoride, or to remove
organics by addition of surfactants. It is not compatible with stainless
steels.
8.4.2 Citric Acid: Citric acid is compatible with stainless steels, and presents
good handling, safety, and corrosion characteristics. It is less aggressive
in its attack of some iron oxide scales and therefore usually requires
higher temperatures or longer contact times. It has little effect on
calcium salts present in deposits. In general it is more expensive than
hydrochloric acid treatment. The normal reasons for its selection are: a)
presence of austenitic materials of construction. b) rust removal,
neutralization and passivation can be carried out using a single solution,
thereby considerably reducing cleaning time by eliminating the need to
drain, flush, and refill the equipment between stages.
8.4.3 EDTA: Disodium or tetra sodium EDTA salts, are used to remove
calcium sulfate deposits. Corrosion rates are low under controlled
conditions.
Page 12 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
8.4.4 Sulfuric acid: Sulfuric acid is an effective acid for iron oxides, iron
sulfides and is lower in cost than hydrochloric acid. It is also compatible
with stainless steels. However, it is dangerous to handle. In its
concentrated form, it is aggressive to organic material, and contact with
the skin or eyes are extremely dangerous. Its use is not recommended
where scales contain significant calcium, due to the formation of
insoluble calcium sulfate.
8.4.5 Sulfamic acid: Sulfamic acid has the advantage of being a crystalline
solid, which is simple, to store, handle, and mix. It is frequently sold
mixed with an inhibitor and a color indicator to show effective acid
strength. It is compatible with stainless steels and is a moderately
aggressive acid for iron oxide and calcium carbonate. Due to its
relatively high cost, it is mainly used on low volume equipment. It is not
recommended to clean copper alloys due to their susceptibility to stress
corrosion cracking.
9 Alkaline Treatments
Page 13 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
9.1.2 Testing
The solution can react violently with acids. Heating the solution will
expand its volume. Be prepared to open drain valves to maintain desired
levels.
9.1.4 Procedure
1. Verify volume of equipment to appropriate level by filling and
draining through a flow meter.
2. Dissolve the chemicals externally and blend fill through the
chemical feed connection. Open vent and fill the equipment from
the bottom to ensure adequate contact of degreasing solution with
the contaminated metal surfaces.
3. Provide external heating to control temperature.
4. Circulate for 2 to 3 hours reversing flow every 30 minutes.
5. Drain the solution quickly with air pressure (5 psig max) into a
holding tank.
6. Fill the equipment with water heated to 77°C and drain quickly to
rinse.
7. Inspect
8. If no further cleaning is required, then reconnect all instrument
lines.
9. Replace all hand and manhole covers, using new gaskets.
10. Remove blinds, temporary piping and instruments.
11. Place the equipment in service.
Page 14 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
9.2.2 Testing
9.2.4 Procedure
9.3.2 Testing
Page 15 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
9.3.4 Precautions
9.3.5 Procedure
1. Verify volume of equipment to appropriate level by filling and
draining through a flow meter.
2. Dissolve the chemicals externally and blend through the chemical
feed connection. Fill the equipment from the bottom to ensure the
cleaning solution wets all contaminated surfaces.
3. Provide heat externally to bring to desired temperature range.
4. Circulate for 2 to 4 hours reversing flow every 30 minutes.
Monitor until permanganate concentration stabilizes.
5. Drain the solution quickly under air pressure (5 psig max) into a
holding tank.
6. Fill the equipment with water heated to 77°C and drain quickly to
rinse. Inspect.
7. If no further cleaning is required then reconnect all instrument
lines.
8. Replace all hand and manhole covers, using new gaskets.
9. Remove blinds, temporary piping and instruments.
10. Place the equipment in service.
10.1 General
Page 16 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Commercial grade quality for all listed chemicals is adequate. The concentrated
acid must not contain greater than 100 mg/L of iron. Where austenitic materials
are present in the system to be cleaned the total chlorides of all the chemicals in
the mixture must not yield a final solution containing greater than 50 mg/L as
chloride.
Perform a hydrostatic pressure test of the cleaning circuit at 1.25 times the dead
head pressure of the circulating pump before acid addition.
10.2.1 Do not use this procedure in equipment with mixed metallurgy or with
stainless steel. More than one acid cleaning cycle may be required to
clean.
10.2.3 Testing
Page 17 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
10.2.5 Precautions
10.2.6 Procedure
2. Fill the equipment from the bottom with water to the top
eliminating all air in the system. If the water is sufficiently hot,
circulate by chemical cleaning pumps to achieve uniform metal
temperatures throughout the equipment, and adjust to 70-82°C. If
the water is not at a high enough temperature, use an external heat
exchanger, or inject steam, to raise and adjust temperature by
circulation.
Page 18 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
7. Check for acid leaks in the circulation system, and if the leaks
cannot be contained drain as in step 8.
9. Fill to the top of the equipment with hot water mixed with 2 to 3 %
of soda ash. Drain the equipment under nitrogen as before and
refill with water, for a second rinse. Drain the second rinse under a
positive nitrogen pressure. Soda ash may have to be added to the
solution drained directly into the sewer, to ensure that its pH is
above 7. When no repeat acid cleaning is required about 0.1% by
weight of citric acid should be added to the second rinse to assure
more thorough rust removal.
10. If the acid is drained because of any one of the three reasons cited
in step 6,or 7 above, water flush to clear drains and repeat steps
from 2.
Commentary Note:
Page 19 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
the hydrochloric acid to prevent this. The liberation of chlorine gas in the
low pH HCl environment will result in accelerated corrosion in the form of
severe pitting attack.
10.3.1 More than one acid cleaning cycle may be required to remove all the
rust. Citric acid is not effective to remove water scales or iron sulfides.
10.3.3 Testing
10.3.5 Precautions
10.3.6 Procedure
1. Fill the equipment from the bottom with water to the top
eliminating all air in the system. If the water is sufficiently hot,
circulate by chemical cleaning pumps to achieve uniform metal
temperatures throughout the equipment, and adjust to 93°C. If the
Page 20 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
5. Check for acid leaks in the circulation system. If the leaks cannot
be contained, or if the total iron exceeds 10,000 mg/L, drain the
equipment immediately into a holding tank under nitrogen pressure
of 10 psig, rinse the equipment with water, water flush to clear
drains and repeat steps from 1.
8. Drain under air and fill the equipment with hot water to the top.
Drain the equipment under air as before and refill with water, for a
second rinse. At this point the equipment is both neutralized and
passivated.
Page 21 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
10.4.2 Testing
10.4.3 Procedure
3. Drain the solution with air pressure into a holding tank. Fill and
drain, twice with water.
More than one acid cleaning cycle may be required to remove all the rust. Do
not use H2SO4 to clean exchangers with ferrous and nonferrous metals that are
not electrically isolated.
Page 22 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
10.5.2 Testing
Sulfuric acid is a strong mineral acid, and must be handled with care,
particularly in the concentrated form. Considerable heat is evolved
during dilution. Never add water to concentrated sulfuric acid. Add the
acid slowly to water mixing thoroughly.
10.5.4 Precautions
10.5.5 Procedure
2. Fill the equipment from the bottom with water to the top
eliminating all air in the system. If the water is sufficiently hot,
circulate by chemical cleaning pumps to achieve uniform metal
temperatures throughout the equipment, and adjust to 82°C. If the
water is not at a high enough temperature, use an external heat
exchanger, or inject steam, to raise and adjust temperature by
circulation.
Page 23 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
8. Fill the equipment with hot water mixed with 2 to 3 % of soda ash
to the top. Drain the equipment under nitrogen as before and refill
with water, for a second rinse. Drain the second rinse under a
positive nitrogen pressure. Soda ash may have to be added to the
solution drained directly into the sewer, to ensure that its pH is
above 7. When no repeat acid cleaning is required about 0.1% by
weight of citric acid should be added to the second rinse to assure
more thorough rust removal.
Page 24 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
More than one acid cycle may be required to clean. Do not use sulfamic acid to
clean exchangers with copper alloys due to possibility of stress corrosion
cracking. Approximately 1 kg of sulfamic acid will dissolve 0.5 kg of CaCO3.
10.6.2 Testing
10.6.3 Precautions
10.6.4 Procedure
1. Fill the equipment from the bottom with water to the top
eliminating all air in the system. If the water is sufficiently hot,
circulate by chemical cleaning pumps to achieve uniform metal
temperatures throughout the equipment, and adjust to 65°C. If the
water is not at a high enough temperature, use an external heat
exchanger, or inject steam, to raise and adjust temperature by
circulation. Use nitrogen to drain back sufficient volume of water
to accommodate inhibited acid. Check inhibitor effectiveness in
the acid on-site. As quickly as possible, blend inhibited acid
Page 25 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
5. Fill the equipment from the bottom with water to the top. Drain the
equipment under nitrogen as before and refill with water, for a
second rinse. Drain the second rinse under a positive nitrogen
pressure. Soda ash may have to be added to the solution drained
directly into the sewer, to ensure that its pH is above 7. When no
repeat acid cleaning is required about 0.1% by weight of citric acid
should be added to the second rinse to assure more thorough rust
removal.
11 Passivation
11.1 General
Immediately after cleaning with mineral acids and rinsing of the equipment, the
final step is passivation of the freshly cleaned steel surfaces. Passivation is not
required after hydro jetting, or for equipment made of non-ferrous alloys or
Page 26 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
stainless steels. Use commercial grade quality for listed chemicals except where
austenitic materials are present in the system to be cleaned, the total chlorides of
all the chemicals in the mixture must not yield a final solution containing greater
than 50 mg/L as chloride.
11.2 Inspection
Page 27 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
11.4 Testing
11.6 Procedure
1. Blend fill the equipment to the top, and circulate by chemical cleaning
pumps.
2. At the end of the six hours, drain the equipment under air pressure.
3. Open vents, drain and inspect internals for completion of work.
Plant Inspection, Operations, Operations Engineering and the cleaning contractor are to
inspect after the cleaning, to ascertain that the job has been successfully completed.
Visual and video boroscope inspections are carried out to determine the effectiveness of
cleaning. No visible traces of water, loose or adherent deposits inside the equipment are
acceptable.
13 Equipment Lay-Up
If the startup of the equipment after cleaning is likely to be delayed by more than five
days, dry it with nitrogen to a dew point of 1°C and store it under a positive pressure of
nitrogen for corrosion protection.
Page 28 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Revision Summary
31 January 2005 Revised the "Next Planned Update". Reaffirmed the contents of the document, and
reissued with editorial changes.
Page 29 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Austenitic Stainless Steels: Chromium and nickel bearing ferrous alloys noted for
their resistance to corrosion.
Blend (Filling): A method of filling a vessel with chemical acid in which the chemical
concentrate in liquid form is metered into the filling line at such a rate as to maintain the
desired concentration level in the liquid entering the vessel.
M-Alkalinity: Methyl orange alkalinity, which exists above the pH range of 4.2 to 4.4.
Mill Scale: A layer of iron oxide consisting of magnetite (Fe3O4) on the surface of hot
rolled steel.
pH: A value between 0 and 14 taken to represent the acidity or basicity of an aqueous
solution.
Water: Good quality water having a conductivity of less than 1000 microsiemens.
Page 30 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Equipment details
1. Location, fill volume, materials of construction of shell and tubes or plates and
gaskets
2. Components isolated, blinded, plugged, or removed
3. Scale composition and solubility in the proposed solvent
Equipment details
12. Pumps and capacities
13. Piping, fittings, and valves
14. Tanks and capacities
15. Power source
Control parameters
16. Circulation rate, temperature limits, chemical concentrations, pH, M-alkalinity,
iron, corrosion
17. Sketch of circulation path, showing locations of: pumps, control valves, chemical
injection, flow and temperature instruments, vents, drains, blinds, plugs, etc.
18. Waste disposal plan and approvals, Chemical Hazard Bulletins.
19. Chemical analysis procedures
Page 31 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Page 32 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
MANUFACTURER OR DISTRIBUTOR
(1) (2) (3) (4)
Acid & Max. Corr. Henkel AKZO HALLIBURTON NAVDEEP
Max. Rate (7) at suggested suggested suggested conc. % suggested conc. %
Conc. Max. Temp. conc. % (6) conc. % (6) (6) (6)
HCl, 300 mpy Rodine213 Armohib 28, HAI 50**, 0.2% v/v Nevamine CP 20,
6 % v/v at 82°C or 426, 0.2% v/v 0.2% v/v
0.2% v/v
H2SO4, 200 mpy Rodine 95 Armohib 31, OSI-1A , 0.2% v/v Nevamine CP 20,
8 % v/v at 82°C or 31A, 0.2% v/v 0.2% v/v
0.2% v/v
Citric, 200 mpy Rodine 31A, Armohib 31, OSI-1A , 0.2% w/w None
5 % v/v at 93°C 0.2% w/w 0.2% w/w
Sulfamic 200 mpy Rodine 95, Armohib 31, OSI-1A , 0.2% w/w None
10 % v/v at 65°C 0.2% w/w 0.2% w/w
Na-EDTA 50 mpy Rodine 241, None OSI-1A , 0.2% w/w None
10 % w/w at 95°C 0.2% w/w
MANUFACTURER
Application Concentration Maximum Henkel (1) (6) Sharp (5) (6)
Protection
HPJ 0.001% to 0.003 % 3 days Flash Rust inhibitor Flash Shield 2000 A/B
Notes:
** Surfactant must also be added
(1) Henkel Surface Technologies, U.S.A., http://www.hstna.com, phone: 800-235-2172, Fax: 248 588-4383.
(2) Akzo Chemicals Inc, Chicago, Ill. U.S.A., http://www.surface.akzonobel.com, phone: 312 906-7500.
(3) Halliburton Services, Dhahran, Saudi Arabia, 31932, http://www.halliburton.com, phone: 03 856-1616/-
1544, Fax: 03-856-1591.
(4) Navdeep Chemicals, Bombay, India, http://www.navdeep.com, phone: 009122-261-3855/-7715/-2804,
Fax: 009122-286-2735.
(5) Sharp Performance Products, 5921 Plainview Street, Houston, phone: 713-641-110, Fax: 713-641-9898
(6) Suggested concentrations are shown. Adjust the actual concentration such that the maximum corrosion rate
is not exceeded. Also refer to manufacturer's recommendations for flash rust inhibitor concentrations.
(7) Use the corrosion rates shown here to check inhibitor effectiveness in static solution. While cleaning the
circulation rate, temperature and the inhibitor concentration are adjusted such that the maximum corrosion
rate does not exceed 600 mpy in acids and 50 mpy in Na-EDTA.
Page 33 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
PO43- /
Date Time Temp Acid Total iron pH CO32- Corrosion rate Remarks
°C % mg/L mg/L mpy
Page 34 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Use HPJ either alone or to supplement chemical cleaning if inspection reveals deposits are
present in the equipment after acid cleaning and neutralization.
Introduction
High Pressure Jetting (HPJ) is a highly effective and adaptable cleaning technique, using
specialized equipment capable of developing 8,000 psig or more. During high pressure
jetting the fouling is stripped from the equipment being cleaned by a combination of
mechanisms. The direct impact of the jet provides a shattering effect, and hydraulic
pressure produces a disruptive shearing force. The shearing force may be applied in two
ways; firstly, by the penetration of water between the fouling and metal surface to break the
bond between them, and secondly, by penetration of the water into a porous foulant to
cause the break up of the foulant mass.
In high pressure jetting the total cleaning action is a function of the available energy and the
efficiency with which it is applied. The cleaning energy is related to the pressure and
volume of the water, whereas the efficiency is determined by the nozzle design and angle of
impingement of the water jet to the fouling.
When attempting to remove thin oils from metal surfaces, the water jet may drive these
films across the surface without detaching them; or if the oil is removed, it may well spread
to an adjacent surface. An emulsifier or detergent will assist in removing and sequestering
the fouling.
HPJ is usually successful if chipping, scraping or wire brushing can remove the deposit.
Some tarry or gummy deposits smear when impacted by a water jet and are not removed.
HPJ is not effective with certain types of firmly bonded nonporous scales that usually occur
in equipment, and scales deep inside the heat exchanger tubes that cannot be reached by the
high pressure water jet. Then chemical or solvent cleaning is essential.
Though HPJ leaves a clean surface, flash rusting of carbon steel equipment will occur due
to the moisture and oxygen present. Chemical additives are available to minimize flash
rusting. (See Appendix 3)
Line friction is another factor to consider when jet cleaning and much of the effective pump
pressure is lost when pumping through a long hose and lance. Special organic polymers to
reduce the friction losses by as much as 90% are added to the water. In addition, some
Page 35 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
polymers make the water more cohesive; that is, they maintain the water in tight cylindrical
jet that strikes the target with much more force than untreated water at the same pressure.
By reducing the tendency of the water to fan out or spray, the effective cleaning distance
between the nozzle and the target is increased. Thus impact stress and cleaning power are
increased.
Polymers are typically added at a concentration of 0.3 % by volume based on water flow.
The polymers should be injected into the water flow directly before the high pressure pump.
Recirculation is not practical because the shear stress at the nozzle destroys the polymer.
Do not attempt HPJ unless a fail safe system is used, since controlling the pressure by
shutting down the pump takes too much time in case of an accident. High pressure jetting
is a skilled operation. Use only a trained crew and supervise the work to carry out HPJ
safely and effectively.
Equipment Specification
Pump Capacities 750 kW, 10,000 psig; 1500 kW, 20,000 psig
Water Volume 30 L/minute to 50 L/minute
Nozzle orifice diameter 0.8 to 2.4 mm
Number of Nozzles & Orientation 4 each, facing 45° rearwards, and 90° to
the direction of lance advancement
Maximum distance between nozzle tip and surface to be 25 mm
cleaned
Flexible Hose diameter 19 mm minimum
Water for jetting Cold steam condensate
Additives Concentration
Polymer 0.3% by volume
Surfactant 0.1 to 0.2 % by volume
Flash rust inhibitor 0.001 to 0.005 % by volume
* While cleaning aluminum fins in fin-fan coolers keep the HPJ pressure below 700 psig and use the lowest effective pressure
necessary to clean with out damaging the fins.
Page 36 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Offstream cleaning requires that at least a part of the plant be shutdown during the operation.
Since downtime costs money, there is a lot of incentive to perform as much cleaning as is
possible without shutdowns. Several onstream techniques have been developed as follows:
This method is effective to remove scales soluble in HCl. The treatment consists of injecting
inhibited acid into the cooling water at relatively low concentration for a short time period
while the cooler remains in service.
If the fouling is predominantly scale the cooling water flow is reduced and the acid
concentration is kept about 0.5% acid in the effluent for hardness deposits or about 3% for iron
oxides. If the fouling contains appreciable quantities of mud and weed, the cooling flow is
maximized and acid concentration reduced. Acid slugging is a rapid method of cleaning, and
most bundles can be cleaned in 20 minutes to 1 hour. Preparation work is minimum and often
consists of providing only 1½" valve connection at a cooler inlet. Sampling connections and
temperature monitors are required for good control of the cleaning.
In general, acid slugging cleans once-through cooling systems, particularly where salt water is
used as the cooling medium. Onstream cleaning has been extended to include recirculated
systems, but the effluent acid must be diverted to the sewer or neutralized to avoid upsetting the
cooling tower operation.
In all cases where chemical injection is used, precautions must be taken to ensure that the
injected cleaning agent and dissolved fouling are not allowed to remain in the system in any
form which will be incompatible with the water treating chemicals, etc. The pH for instance,
must be readjusted to a normal level as soon as possible after acid injection. Inhibitor dosage
should be increased to passivate metal surfaces. The materials of construction must be checked
before adding any cleaning agent. Inhibited hydrochloric acid has little or no action on carbon
steel or the majority of copper alloys at temperatures up to 80°C but can lead to stress cracking
on 300 series stainless steels. The metal surface temperatures may be considerably higher than
the temperature of the circulating water and that materials such as the cast iron in compressor
jackets are liable to be attacked more readily than carbon steel.
An alternative to acid slugging for the onstream cleaning of coolers is a modification of the
circulation procedure used offstream. This procedure requires care to ensure that temperature
guidelines are not exceeded but has the advantage that the effluent cleaning solvents are
discharged to the sewer and, therefore, will not interfere with closed circuit cooling water
corrosion control. Procedure requires the installation of tees in the cooling water inlet and
return lines that can be connected via hoses to conventional pump and chemical cleaning tank
facilities. In addition, connections from the firewater system must be made with sewer
connections on both the inlet and outlet. Cleaning volumes should be as large as practical in
Page 37 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
order to provide as large a heat sink as possible because the idea is to circulate the cleaning
solution during normal cooler operation.
Firewater is used to backflush the system to the sewer and to make up the solutions because it
is higher pressure and cold. Unit is circulated from bottom to top until unit is clean or solution
temperature rises to 80°C. If temperature reaches 80°C, stop the chemical pump and use
cooling water to displace the acid back to the tank with additional flushing to the sewer.
Ensure that process side temperatures and pressures will not exceed allowable. Units with high
process temperatures will permit short contact times before solution temperatures reach the
allowable maximum and should be cleaned only with extreme caution.
Sulfuric acid, is much cheaper and more readily available, to periodically reduce the pH of the
system or segment of a system to about 1.5 to 2.0 for a period of 6 to 8 hours or until the acid is
no longer being consumed. At this pH the calcium carbonate hardness deposits, which are the
primary foulants in the salt water system, are readily dissolved. If substantial iron oxide were
present, a lower pH would be required for adequate removal.
Chemical cleaners for the offstream removal of calcium hardness deposits have not used
sulfuric acid because the resultant calcium sulfate is not soluble in the acid solution and the
reaction quickly stifles itself. However, calcium sulfate is soluble up to about 1500 mg/L in
fresh water at 60°C. In the onstream once through treatment with dilute acid the concentration
of calcium sulfate is so low that the solubility is not exceeded. However, it has been
established that calcium sulfate is more soluble in high ionic strength seawater than it is in fresh
water. Therefore, the scheme is more applicable to salt water systems than to fresh water
systems.
Onstream cleaning of an entire recirculating system has been attempted in areas where a
shutdown was intolerable by reducing the pH with acid while adding polyelectrolytes. The
technique can be successful if carefully executed but is employed as a last resort. It probably
will not be very effective on deposits high in iron oxide, but can be effective if iron oxide is
bound by mud, silt, etc. For best results, the cleaning encompasses several days as is illustrated
in the following typical procedure:
2nd day
1. Shot feed polyelectrolyte to obtain desired concentration in system
(usually about 25 mg/L)
2. Add dispersant continuously to compensate for that lost in blowdown
3. Decrease pH to range of 5.0 to 5.5
Page 38 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
4th day
1. Maintain dispersant concentration at recommended level
2. Decrease pH to 4.0 for eight consecutive hours; otherwise maintain
range of 5.0 to 5.5.
3. Maintain cycles of concentration to 2.0
4. Air bump or backflush, as above
5th day
1. Discontinue feed of dispersant and raise pH to normal range
2. Decrease blowdown to normal level
6th day Triple the feed rate of corrosion inhibitor to passivate system metals
The procedure below has been found to work well in several locations in minimizing the
adverse affects of process contaminants that have just leaked into the cooling water system.
The procedure is not effective for removing deposits from old or persistent leaks.
1. Locate and shut off leaking equipment immediately after leak are observed. This
is a crucial step. The following techniques may be useful to locate leaks:
- Sample water from outlet of equipment, headers, gas traps, etc.
- Check loss of chlorine residual across suspect exchanger or other areas
- Measure oil-in-water content daily
- Use GC analysis to identify possible sources of oil
2. If visible fouling exists clean wooden members at top distribution deck of tower
with steam lances. Clean structural and demister chevrons from basin level using
water hoses.
3. Skim oil at top distribution deck and at cooling tower basin. During this time:
Page 39 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
- Ensure 2 mg/L free tolyltriazole copper inhibitor if brass bundles are present.
- Add an initial 100 mg/L (as product) shock dosage of non-ionic surfactant
(polysiloxane and polyoxyalkylene, fatty acid alkylamines, or polyoxylated
ethylene and alkoxylated phenol).
4. Blowdown system for 3 - 4 days at highest rate possible and at as many different
points as possible (cooling tower hot return, basin, and at pump cooling jackets,
etc.):
- Operate oil skimmer at cooling tower pump suction bay (if available)
Page 40 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
- For two days per cell, shut off one cooling tower cell in sequence so that flow
is maximized through other cells (to flush oil off structures).
- Chlorinate continuously (0.1 - 0.3 mg/L residual) or once per day to 0.5 to 1.0
mg/L free chlorine residual.
Page 41 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Uactual = Q/(Ao.ΔTLMTD.F)
Where,
Uactual = the actual heat transfer coefficient of the exchanger at operating conditions,
based on the outside heat transfer surface area
Q = the quantity of heat transferred
Ao = the total outside area of tubes for heat transfer
ΔTLMTD = the log mean temperature difference = [(T1-t2)-(T2-t1)] / ln[(T1-t2)/(T2-t1)]
T1 = the hot stream inlet temperature, T2 = the hot stream outlet temperature
t1 = the cold stream inlet temperature, t2 = the cold stream outlet temperature
F = the temperature correction factor based on the geometry of the exchanger
(number of shell and tube passes) and obtained from TEMA charts
Definition of Udesign:
Udesign = 1/{(1/Uclean) + Rfdesign}
Page 42 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
The fouling factor actually realized in the heat exchanger is given by:
Rf = (1/Uactual) – (1/Uclean)
Note: The Rf is independent of the fluctuations in the flow rates during the service period.
Use at least a ten day average value of Rf for decision criteria.
Page 43 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Calculate the total fouling related expenses (TFRE) and clean when TFRE is at a minimum.
Graph 1 illustrates the concept of Total Fouling-Related Expense (TFRE) to optimize the
cleaning cycle for a fictitious unit. Note that TFRE (SR/yr) is plotted as a function of months
since cleaning. The onstream energy loss and the associated process debits both increase
directly as the time between cleaning are extended. The cleaning costs and the offstream
energy loss are reduced as the cleaning interval is extended. Summing all of these costs helps
in selecting an optimum cleaning frequency to minimize cost for this unit.
50000 Ei(onstream) x n
40000 TFRE (total of above)
30000
20000
10000
0
1 2 3 4 5 6 7 8 9 10 11 12
Months since cleaning (n)
Page 44 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Step A For each value of n = 1 to 12 , calculate the TFRE by adding the costs for:
• Energy loss due to fouling.
• Direct expenses of cleaning
• Indirect costs of lost production during cleaning
• Indirect costs of lost production due to fouling (process debit)
Step B Determine the optimum cleaning interval by picking the minimum in the TFRE curve.
Step 1 Obtain from plant operations and maintenance personnel the costs associated
with:
• Energy loss due to fouling (Qloss).
• Monetary equivalent per unit of energy loss (Meq).
• Direct expenses of cleaning (Ed).
• Indirect costs of lost production during cleaning (Ei offstream).
• Indirect costs of lost production due to fouling (Ei onstream).
• Number of months since cleaning (n = 1 to 12)
• Number of cleanings per year N =12/n (n = 1 to 12)
Step 2 Establish a graph representing for a one year period "Cost" on the Y-axis and
"Months Since Cleaning" on the X-axis. On this graph, plot the following
lines per the instructions given:
• Cumulative cost of lost energy at n month intervals:
Cost after n months = Qloss x Meq x n
• Cumulative cost of onstream production loss:
Cost after n months = Ei onstream x n
• Cost of offstream production loss (i.e., during cleaning):
Cost after N cleanings = Ei offstream x (number of days for cleaning)
x 12/n
• Direct expense of cleaning:
• Cost after N cleanings = Ed x 12/n
Page 45 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
For example, Graph I is obtained using the above steps given the following
information.
• Qloss x Meq = $3,000 per month.
• Ed (cost of cleaning) = $4,000 chemical + $1,000 mechanical.
• Ei onstream (production loss) = $1,000/month.
• Ei offstream (production loss) = $1,000/day.
• Cleaning time = 2 days.
Page 46 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Provided for information only. Contact Saudi Aramco Industrial Hygiene Services, Preventive
Medicine Services Division, Dhahran (phone: 877-8222) to determine the need for the
precautions and develop procedures.
Safety
Plan for safety in the operation at all stages. Material Safety Data Sheets are required for the
transport and handling of chemicals. Review the data sheets before any cleaning jobs using
solvents or additives is undertaken.
Principal Hazards
• Chemical burns - caused by contact with the chemicals, fouling or their products.
Chemical burns are associated with acids or caustic and usually occur during
transportation and mixing of the concentrated chemicals. Less frequently, incidents
occur due to a leak developing during the cleaning operation.
Take steps to protect personnel eyes, face and hands with the correct clothing. Insist on
gloves and goggles as a minimum when handling any chemical irrespective of its
corrosive nature.
Control loading and transportation of corrosive chemicals and use suitable containers.
Check these to ensure that they are in good condition, firmly secured, labeled clearly,
leak proof and that there are no loose stoppers. Transfer of concentrated liquids, etc.,
by a small pump rather than by manually pouring from containers, and exercise caution
during mixing and dilution.
Page 47 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Some chemicals, particularly concentrated sulfuric acid and caustic soda, evolve heat
when diluted. Dilute gradually by adding the chemical to water in order to dissipate the
heat and avoid fuming, spitting and boiling. Stir continuously during dilution, as dense
materials may sink to the bottom of the mixing tank. Add acids to water. For
concentrated solution's, (5% or more), monitor temperature while mixing. Use a
metered pump to add the acid and minimize heat evolution by controlling the flow of
acid during mixing.
Toxicity
Toxicity incidents with chemicals are relatively rare providing the toxicity limits are
known and handling is supervised. There is, however, a real risk that during the
cleaning operation new toxic compounds may be formed by reaction between the
cleaning chemicals and the fouling. The most common case is the production of
hydrogen sulfide gas by dissolving sulfide scales in acid. This and other gases can be
deadly and anticipate their formation prior to the cleaning operation. Plans adequately
all operations for the safe disposal of gases formed and the disposal of spent cleaning
chemicals. This is particularly important where cleaning may be carried out in confined
spaces. Keep suitable gas testing equipment and breathing apparatus in the event of an
emergency.
Flammability and explosion
Flammability and explosion problems usually arise from gas production by overheating
the solvent, gas given off from the fouling or gas evolved by chemical reaction during
the solution of the fouling, e.g., hydrogen evolved by metal dissolving in acid. There
are also certain cases where the fouling itself may be pyrophoric or even explosive.
Pressure hazards
Pressure hazards are due to the evolution of large volumes of gas or overheating of a
closed system with out vents. Provide adequate venting to eliminate this problem.
Remember that vents can become blocked by loose scale, and install a pressure gage in
the system if this could occur.
Follow safety procedures to safeguard equipment on every chemical cleaning job. Hydrogen is
liberated by the cleaning reaction and, under certain conditions it is possible to confine the
hydrogen and set up an explosive mixture in the vessel. Venting the vessels permits the escape
of most of the hydrogen from the system as fast as it is formed.
Take precautionary procedures to avoid toxic hazards, which may occur during chemical
cleaning operations. These hazards sometimes include the cleaning agent itself, for example
Page 48 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
when a concentrated sulfuric acid, a strong caustic, etc., is being used. In such cases, adhere to
recommended handling practices and wear proper protective clothing.
Guidelines for the safe handling of chemicals are covered on specific chemical hazard bulletins,
and available from Environmental Protection Department.
Many of the deposits encountered in the refinery contain sulfide, cyanide, arsenide, and
fluoride scales that will liberate large quantities of dangerous gases such as H2S when
exposed to acidic solvents. Provision should be made to dispose of these lethal gases.
One way to limit the amount of H2S released by contact with acids is to first circulate
water, then slowly add acid to build up concentration. This prevents rapid gas
evolution.
One way to dispose of H2S gas is to discharge into the flare system to burn the gas in
the flare to form SO2, which is toxic but less dangerous than H2S if no vents are high
enough in the air. If no wind exists and large quantities are liberated, however, there is
the possibility of the heavier-than-air gas settling around the equipment. A preferred
technique is to scrub out the H2S by bubbling the gas through a sparger into a drum
containing caustic. Caustic volume is 80 L of 25% NAOH to every 400 L acid 10%
H2SO4. A typical scrubber for a large job is 1.4 meter diameter by 2.3 meter height. A
minimum height of 1.3 meters is recommended.
Caustic concentrations of 50% have resulted in plugged spargers. Therefore, keep the
sparger off the bottom of the drum, containing relatively large diameter sparger holes.
Maintain a caustic concentration of 25% to prevent serious plugging. The resultant
sodium sulfide reaction product is a precipitate. Dispose it in an approved land farm or
disposal pond where it cannot later react to regenerate the hydrogen sulfide, (i.e., by
contacting acid). At the completion of the job, sparge nitrogen into the spent acid to
strip H2S out of the acid and push it into the scrubber.
Another new technique for suppressing H2S is by adding formaldehyde to sulfuric acid.
The reaction product formed is trithiane, which can form a flocculent, and precipitate on
metal surfaces, especially when heavy sulfide deposits are present.
Spent acid contains dissolved H2S, which can be released upon entry into a vacuum
disposal truck. Since vents on vacuum trucks are at ground level, there is the possibility
of flooding the area with H2S. A caustic scrubber can be installed on the exhaust line
from the vacuum truck, or formaldehyde can be added to the truck (1 L per 1000 L
capacity) prior to the entry of spent sulfuric acid.
Page 49 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Other gases may be liberated during the cleaning cycle including hydrogen cyanide in
units containing cyanide deposits such as Vapor Recovery Units. A/C units, FCCU,
Catalytic Light Ends, Coker, and Sour Water Strippers may also have fluoride, cyanide-
containing deposits. A caustic wash can be employed to remove the salt. Arsine and
phosphine are other gases, which have been found in vent gases from acid cleaning
jobs. Generally, precautions for hydrogen sulfide will also take care of the other gases
formed.
Other toxic gases that can be produced during acid cleaning include nitrogen dioxide
and hydrogen cyanide.
Page 50 of 51
Document Responsibility: Materials and Corrosion Control SAEP-1662
Issue Date: 31 January 2005 Cleaning of Heat Exchangers
Next Planned Update: 1 February 2010 and Unfired Plant Equipment
Citric Ammonium
Materials H2SO4 HCl Sulfamic EDTA Alkalies
+NH3 biflouride
Aluminum Alloys NR NR A A C NR
Austenitic C NR C C A C NR
Stainless Steels
Brasses A A C A C C NR
Carbon steels (cs) A A A A A C C
Cast irons C C A C C A C
Ferritic C C C C A C C
Stainless Steels
Low Alloy Steels C C A C C A C
Titanium C C A C A C NR
Zinc (including NR NR NR C NR NR NR
Galvanized steel)
Galvanic Couples:
cs / brass C C C C C A NR
cs / ferritic ss A C A A A C C
cs /austenitic ss C NR C C A C NR
Page 51 of 51