Professional Documents
Culture Documents
NETA World Spring 2019 - The Value of Performing Power Factor Sweep Measurements
NETA World Spring 2019 - The Value of Performing Power Factor Sweep Measurements
SPRING2019
CIRCUIT BREAKER
AND TRANSDUCER:
WHERE DO I CONNECT?
THE VALUE OF
PERFORMING
POWER
FACTOR SWEEP
MEASUREMENTS
ON
BUSHINGS
BY BRANDON DUP UIS, OMICRON
Power factor measurement has long been accepted as an invaluable tool for
identifying insulation defects such as aging, deterioration, moisture ingress,
and localized failures involving the winding and bushing insulation of a
power transformer. Historically, power factor measurements have been
performed at a single test frequency (typically 60Hz) and at a single test
voltage (typically 10kV). However, modern test instruments can perform
power factor measurements at several different test frequencies and at
several different test voltages with minimal additional time and effort.
2 • SPRING 2019 THE VALUE OF PERFORMING POWER FACTOR SWEEP MEASUREMENTS ON BUSHINGS
INDUSTRY TOPICS
ground connection — so a simple tool that The Engineer
allows a user to better detect a bad power factor In most cases, a test equipment operator
measurement is useful. performs power factor measurements in the
field and distributes a test report to an engineer,
Although power factor sweep measurements can who assesses the test results in the office. Based
be performed on the overall winding insulation on the results, the engineer is responsible for
of a power transformer, this paper focuses on the assessing the condition of the insulation system
benefits of applying sweep measurements to the to determine the appropriate course of action.
C1 insulation of bushings. While power factor
sweep measurements are not the silver bullet of A disconnect often exists between the test
power factor testing, they can be beneficial for equipment operator and the engineer. In
the maintenance testing industry. most cases, the engineer is not on site when
the measurements are performed, making it
difficult to be confident that the measurements
W H O C A N B E NE F IT
are valid. However, an engineer who has the
F ROM P E R FORM ING
power factor sweep results in hand can better
PO W E R FAC T OR S W E E P
identify invalid measurements, which helps
M E A S U R E ME NT S?
prevent an incorrect condition assessment.
Power factor measurement is highly sensitive.
Therefore, obtaining correct (i.e., valid) power It is widely known that the best way to assess
factor measurements in the field is challenging. a power factor measurement is to compare the
In many cases, a questionable power factor most recent measurement to a series of previous
measurement is not caused by compromised baseline measurements that were obtained at
insulation, but is due to either user error or the consistent test intervals. However, many asset
influence of the test environment. owners do not have a collection of reliable baseline
test results for their transformer fleet, which
Unfortunately, an invalid measurement is makes assessing the condition of an insulation
often not identified until the user leaves the job system and determining the appropriate course
site, places the transformer back into service, of action a challenge. Fortunately, power factor
and returns to the office. The user often has sweep measurements can be used to better assess
only a short window of time to test a power the condition of an insulation system at a given
transformer — only one shot to obtain the point in time, especially when there are no
correct measurements. historical test results for comparison.
0.50 •400
As an oil-and-paper insulation system
%
0.45 380
deteriorates, the frequency sweep trace
0.4 H1 H2 H3 360 H1
typically becomes flat, or worse, decreases H2 H3
0.35 340
versus frequency. If the trace decreases
versus frequency throughout all or most of
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350
the frequency sweep, then the insulation
Hz Hz
system is typically considered questionable
Figure 1: Acceptable C1 Power Factor Frequency Sweep Traces and is either investigated further and/or
4 • SPRING 2019 THE VALUE OF PERFORMING POWER FACTOR SWEEP MEASUREMENTS ON BUSHINGS
PF fequency sweep
INDUSTRY TOPICS
tested more frequently in the future. Case Study #1: Haefely 115kV
• Another characteristic of compromised Bushings
insulation is a distinct fishhook shape in The first case involves power factor
the lower frequency range of the sweep measurements that were performed on three
(i.e., at frequencies below 60Hz). If this Haefely 115kV bushings (Figure 2).
occurs, the insulation system is typically
considered questionable and is investigated Based on the results in Figure 2, the 10kV
further and/or tested more frequently in power factor for H3 is higher than its
the future. nameplate value, whereas the 10kV power
factor for the other two bushings is below their
• One advantage of performing power factor respective nameplate values. Notice that the
frequency sweep measurements on the C1 2kV and 10kV power factor measurements
insulation system of a bushing is that, in for the H3 bushing are dissimilar. In contrast,
most cases, a bushing mounted on a power the 2kV and 10kV power factor measurements
transformer has two or three similar-unit for the H1 and H2 bushings are reasonably
bushings that can be tested and compared similar, which further suggests that the H3
to each other. In general, power factor measurements are abnormal.
sweep measurements should behave
similarly when comparing similar-unit When comparing the power factor frequency
PF fequency sweep
bushings. Ideally, the traces for similar-unit sweep traces among similar-unit bushings, the
shape0.7
of the traces should be reasonably similar. 480
bushings overlay or overlap when plotted 460
0.65 the shape of the H3 trace is dissimilar
Clearly,
against each other. Most important, the 440
0.6 to the traces of the other two bushings.
relative
shape of the frequency sweep traces should 420
0.55
Moreover, the H3 trace decreases versus
pF
be reasonably similar when comparing 400
0.50
%
similar-unit bushings. If the shape of the 0.45 115kV BUSHINGS (2000) 380
HAEFELY
trace of one bushing is dissimilar relative to 0.4 H1 H2 H3 360
the shape of the traces of the other similar- 2kV Power 10kV Power 10kV PF – Nameplate
0.35 Factor Factor 2kV PF 340
Power Factor
unit bushings, then the dissimilar bushing
should be investigated further and/or H1 0 0.34%
50 100 150 0.34% 0.00%
200 250 300 350 400 0.38% 0 50
tested more frequently in the future. H2 0.32% Hz
0.32% 0.00% 0.37%
H3 0.38% 0.41% 0.03% 0.35%
The C1 power factor frequency sweep
*Note, the measured capacitance for each bushing compared well to its respec-
measurements for three sister-unit bushings are tive nameplate value
provided in Figure 1. Notice that the shape of
the traces is similar when comparing the similar- PF fequency sweep
unit bushings, and in all the traces in Figure
0.6
1, the measured power factor increases versus
0.55 H1 H2 H3
frequency (from left-to-right). This is typically
indicative of healthy insulation. 0.5
0.45
%
0.4
C A S E S T U DIE S
0.35
Several case studies involving power factor 0.3
sweep measurements helped identify
0.25
both compromised insulation and invalid
0 50 100 150 200 250 300 350 400
measurements and demonstrated the value of Hz
performing power factor sweep tests on the C1
insulation of a bushing. Figure 2: C1 Power Factor Results for Three Haefely 115kV Bushings
0.38
INDUSTRY TOPICS
frequency and has the distinctive fish-hook
PF fequency sweep Cap. fequency sweep
in the lower frequency range; this is typically
0.7 indicative of compromised insulation. 480
0.65 460
0.6 Interestingly, the 10kV power factor for440 H3
0.55 is below 1.5 to 2 times its nameplate value,420
pF
0.50 which the industry generally considers400to
%
0.4
Series 2 115kV bushings (Figure 3). H3 bushing. In other words, the power factor
0.35
frequency sweep trace for the H3 bushing only
0.3 confirms what we already know. Additionally,
LAPP POC SERIES 2 115kV BUSHINGS
0.25 the 2kV and 10kV power factor values for
0 2kV Power
50 10010kV150
Power 200 10kV
250 PF – 300 Nameplate
350 400 the H3 bushing differ significantly — further
Factor Factor Hz 2kV PF Power Factor
evidence to condemn the H3 bushing.
H1 0.27% 0.28% 0.01% 0.25%
H2 0.25% 0.25% 0.00% 0.25% Based on the results in Figure 3, the 10kV
H3 0.66% 0.76% 0.10% 0.24% power factor value for H1 is higher than its
nameplate value, whereas the 10kV power
PF fequency sweep
factor value for the H2 bushing is the same
0.38 as its nameplate value. Additionally, the
0.36 H1 H2 frequency sweep trace for the H1 bushing is
0.34
clearly dissimilar relative to the frequency
0.32
0.30
sweep trace for the H2 bushing. The H1 trace
decreases versus frequency and has developed
%
0.28
0.26 the distinctive fish-hook in the low-frequency
0.24 range — typically indicative of compromised
0.22 insulation. Although the 10kV power factor for
H1 is well below 1.5 to 2 times its nameplate
0 50 100 150 200 250 300 350 400
Hz value, the H1 bushing is clearly behaving
differently than the H2 bushing. As a result, the
Figure 3: C1 Power Factor Results for Lapp POC Series 2 115kV H1 bushing should be tested more frequently
Bushings to gauge the severity of the situation.
1.6 200
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400
Hz Hz
INDUSTRY TOPICS
Case Study #3: Westinghouse to the other sister-unit bushings. For this
Electric Type S 37kV Bushings type of insulation failure, in addition to the
PF fequency sweep measured capacitance (pF) value being different
The third case involves power factor
0.6 than expected, the power factor frequency
measurements performed on three
sweep trace becomes more-or-less linear and
Westinghouse
0.55 Electric Type-S H1 37kV H2 H3 a steep incline from left-to-right (as
exhibits
bushings.
0.5 The power factor measurements are
demonstrated by the H3 bushing in Figure 4).
summarized
0.45 in Figure 4.
%
0.28
measured capacitance (pF) value of the bushing Based on the results in Figure 5, the power
0.26
is dissimilar relative to its nameplate value and factor values for all three bushings are higher
0.24
0.22
WESTINGHOUSE ELECTRIC TYPE S 37kV BUSHINGS
02kV Power
50 100 150
10kV Power 20010kV250
PF – 300Nameplate
350 400 Measured Nameplate
Factor Factor Hz 2kV PF Power Factor Capacitance Capacitance
H1 0.60% 0.58% -0.02% 0.65% 169pF 182pF
H2 0.79% 0.78% -0.01% 0.72% 184pF 197pF
H3 0.69% 0.69% 0.00% 0.66% 203pF 198pF
1.6 200
1.4 H1 H2 H3 150
1.2
pF
100
%
1.0
0.8 50
0.6 0
H1 H2 H3
0 50 100 150 200 250 300 350 400 Measured values Nameplate values
Hz
Figure 4: C1 Power Factor Results for Three Westinghouse Type-S 37kV Bushings
INDUSTRY TOPICS
% 0.30
0.28
0.26
0.24 than their respective nameplate values. Notice power factor measurements are invalid. In
0.22 that the power factor measurement for the this case, the customer determined that the
H2 bushing is clearly voltage sensitive. primary-side bushing terminals were not short-
0 50 100 150 200
Furthermore, the 250
power 300
factor350 400
frequency circuited together when the C1 power factor
Hz
sweep traces for the three bushings are erratic measurements were performed; this identified
and jagged. In general, jagged power factor the cause of the abnormal power factor
frequency sweep traces are indicative of invalid measurements.
power factor measurements. Regardless of
whether an insulation system is healthy or
compromised, its power
PF fequency sweepfactor frequency sweep CONCLUSI ON
Cap. at 60.00 Hz
trace should be smooth. With both the voltage and frequency sweep
1.6 200
measurements on hand, invalid measurements
1.4 H1By analyzing
H2 H3only the 10kV power factor are easier to identify. The equipment operator
150
measurements, it is not obvious that the power can use the sweep measurements to quickly
1.2
factor measurements for the three bushings are identify
100 and correct invalid measurements in
pF
invalid; however, the voltage and frequency the field before the transformer is placed back
%
1.0
0.8
sweep test results make it obvious that the into service.
50 The engineer can use the sweep
measurements to identify invalid power factor
0.6 0
measurements, especially when they must rely
LAPP POC 138kV BUSHINGS H1 H2 H3
on the data provided within a test report.
02kV Power
50 10010kV150
Power 200 10kV
250 PF – 300 350 400
Nameplate Measured values Nameplate values
Factor Factor Hz 2kV PF Power Factor
Finally, power factor sweep measurements help
H1 0.34% 0.36% 0.02% 0.29% to accurately assess the condition of a bushing’s
H2 0.52% 0.24% -0.28% 0.23% insulation system. This helps the engineer
H3 0.34% 0.35% 0.01% 0.23% choose the best course of action.
PF fequency sweep
REFERENCES
0.38
IEEE Std. C57.152-2013, IEEE Guide for
0.36
Diagnostic Field Testing of Fluid-Filled Power
0.34 H1 H2 H3
0.32
Transformers, Regulators, and Reactors.
0.30
%
0.28
0.26 Brandon Dupuis joined OMICRON
0.24 in 2013 and presently holds the position
0.22 of Regional Application Specialist for
transformer testing. Brandon’s focus is
0 50 100 150 200 250 300 350 400 currently on standard and advanced
Hz electrical diagnostics for power transformers
and circuit breakers.He is a well-known
Figure 5: C1 Power Factor Results for Three Lapp POC 138kV OMICRON instructor teaching electrical transformer
diagnostic testing theory, application, and test result analysis.
Bushings
Brandon received a BSEE from the University of Maine.
8 • SPRING 2019 THE VALUE OF PERFORMING POWER FACTOR SWEEP MEASUREMENTS ON BUSHINGS