You are on page 1of 6

76 RELIABILITY AND

ROUTINE TESTING

Electrical Testing
of Dry-Type
Transformers
by Mark Pustejovsky

Photo by Shutterstock
Transformer Technology June 2019 77

Issue 2

Mark Pustejovsky graduated with a Bach-


elor of Science in Electronics Engineering
Technology from Texas A&M University in
1993. He has worked in the electrical testing
ƒGNFUKPEGITCFWCVKQP/CTMJCU [GCTU
QH GZRGTKGPEG KP GNGEVTKECN VGUVKPI RQYGT
SWCNKV[ CTE HNCUJ GXCNWCVKQPU CPF RTQVGE-
tive relaying. In his role as Senior Vice Presi-
dent of Workforce Development at Shermco
+PFWUVTKGU JG JGNRU VTCKP TGVCKP CPF TG-
cruit Shermco employees to continue to be
a leader in the most technical workforce in
the industry.

Dry-type transformers are a large part of the electrical infrastructure for many industrial and
commercial sites. Therefore, ensuring the performance of electrical testing and maintenance on
critical transformers is very important to electrical system reliability. This article covers electrical
testing and maintenance items recommended by the InterNational Electrical Testing Association
(NETA) and other industry best practices for transformers above 500 kVA. NETA has two standards,
one for acceptance testing of new units (ANSI/NETA ATS-2017, Standard for Acceptance Testing
6SHFLͧFDWLRQVIRU(OHFWULFDO3RZHU(TXLSPHQW 6\VWHPV and one for maintenance testing of service-
aged units, (ANSI/NETA MTS-2019, 6WDQGDUGIRU0DLQWHQDQFH7HVWLQJ6SHFLͧFDWLRQVIRU(OHFWULFDO
3RZHU(TXLSPHQW 6\VWHPV :HZLOOIRFXVRQPDLQWHQDQFHWHVWLQJVSHFL̨FDWLRQVLQWKLVDUWLFOH
$OVRWKHUHFRPPHQGHGWHVWLQJRIGU\W\SHWUDQVIRUPHUVLVYHU\VLPLODUWROLTXLG̨OOHGWUDQVIRUPHUV
with a few key differences.
78 RELIABILITY AND
ROUTINE TESTING

For large dry-type transformers (500 test results can vary greatly between Temperature may influence the
kVA and above), ANSI/NETA MTS-2019 different types of transformers. power-factor results, but there
recommends visual and mechanical Moisture or humidity can also are too many different types of
inspections and electrical tests influence the test results, as the insulation to assemble a “standard
similar to the tests recommended for insulating materials of dry-type temperature correction factor”
NKSWKFƒNNGFVTCPUHQTOGTU*QYGXGT transformers are exposed to the chart, and for the most part the
determining the health and reliability atmosphere and can be greatly temperature characteristic curve
of a dry-type transformer can be affected by the surrounding should be relatively flat. If power-
OWEJJCTFGTVJCPVJCVQHCNKSWKFƒNNGF environment. When the transformer factor results are questionable at high
WPKV+PNKSWKFƒNNGFVTCPUHQTOGTUQKN is energized, it will be elevated in temperatures, allow the unit to cool
typically makes up a large part of the temperature, and as it cools, it will and retest when the temperature is
insulation system. Being that most absorb moisture. Therefore, it is best closer to 20°C.
insulating oils have relatively similar to test soon after it is de-energized.
dielectric values, expected insulation When performing power-factor
values are very similar in most liquid- Per Table 100.5 in ANSI/NETA MTS- testing, a “tip-up” test should also
ƒNNGFVTCPUHQTOGTU(QTFT[V[RG 2019, insulation resistance values be performed on all windings
transformers, however, the primary for windings of dry-type transformers greater than 2.5 kV. This will aid
insulation is made up of different (greater than 5,000 V) should in determining the presence of
types of dry insulation, depending be 25,000 Megohms or greater. partial discharge (PD) anomalies.
on the manufacturer and In dry insulation, partial
URGEKƒECVKQPU5KPEGFT[ discharges can occur
type transformers do not within voids in the
have oil to cool them during insulation. Partial discharge
operation, they must be There are various is a localized dielectric
constructed of materials breakdown of a small
that can withstand higher construction methods portion of the electrical
temperatures without insulation. Over time,
sustaining damage. Dry- for the manufacturing a series of these small
type transformers can be
constructed of Insulation of dry-type insulation breakdowns
will eventually lead to an
Class B (130°C), Class C
(220°C), or Class H (180°C)
transformers, and insulation failure. Therefore,
it is important to detect
materials. The typical oil- each type is suited for when PD is occurring,
ƒNNGFVTCPUHQTOGTJCUC before it leads to failure.
rated temperature rise of different environments A tip-up test is conducted
65°C and Insulation Class A at two voltages; a lower
materials are used. and applications voltage (something below
the PD inception point)
There are various typically 2 kV or below, and
construction methods for then at operating voltage.
the manufacturing of dry- If no PD is occurring,
type transformers, and each type Insulation power factor results the power-factor values at the two
is suited for different environments vary depending on the material and voltages will be similar. If PD is
and applications. These various construction, and it is recommended occurring, the power factor at the
construction methods include to compare to similar units and high voltage will be higher than it
Open Wound, Vacuum Pressure previous base line tests results. is at the lower voltage. ANSI/NETA
Impregnated (VPI), Vacuum Pressure Capacitance should be recorded MTS-2019 recommends that this
Encapsulated (VPE), and Cast-Coil whenever a power-factor test is difference be less than 1.0 % for an
Resin. performed. The capacitance is acceptable test. A tip-up test can be
dependent on the shape of the RGTHQTOGFQPCPQKNƒNNGFVTCPUHQTOGT
Insulation Tests windings, and if the transformer but it is much more important with
ever feeds a high-level fault, these dry insulation.
When testing a transformer’s readings can be compared to
insulation integrity, there are two previous results to determine if there Visual and Mechanical
main types of tests recommended: was damage to the transformer due Inspection
to winding movement during the
1) Insulation-resistance tests and fault. When performing acceptance
2) insulation power-factor or maintenance testing on dry-
Photo by Shutterstock

(or dissipation-factor) tests. It is also worth noting that it is type transformers, visual and
FKHƒEWNVVQEQTTGEVRQYGTHCEVQT mechanical inspections are very
Because of the different types of readings to a base temperature on important. Transformers are shipped
materials and methods used, the dry-type transformers. with shipping bolts that keep the
Transformer Technology June 2019 79

Issue 2

transformer core and coil assembly that winding. This test will evaluate Transformer Turns Ratio Test
secured to the base frame. During for possible winding damage (such
testing it is often found that the as short circuits between windings The transformer turns ratio test, or
shipping bolts are still in place and or between turns), open circuits, or 664EQPƒTOUVJCVVJGVTCPUHQTOGT
secured, which causes high noise connection issues. ANSI/NETA MTS- has the correct number of primary
and vibration when the transformer 2019 recommends comparing your and secondary turns. This test can
is energized. This excessive vibration test results to previous results and identify shorted turns, open windings,
can cause the bracing in the core being within 1.0% of previous readings. and incorrect winding connections.
assembly to become loose over time. It may not be possible to locate TTR test sets come in a variety of
Leave the bolts in place but loosen previous results, so another means styles and test connections; however,
them, to allow the transformer to float to evaluate is to compare results all test sets will have at least two
on the isolation pads. This will reduce between phases. Variances between high-side leads and two low-side
transformer noise and vibration. The phases should be investigated. Note leads. Turns ratio results should
noise difference can be dramatic. that for low-voltage windings, the not deviate by more than 0.5 %
Also inspect that the transformer winding resistance values are typically from either the adjacent coils or the
is properly grounded, that the unit in milliohms, and small differences in nameplate calculated ratio.
is clean, and that all cooling fans the amount of copper or bus length
operate properly. can affect readings between phases. Excitation Tests
For medium-voltage windings, the
Winding Resistance Test value is typically in ohms, and small Excitation testing is performed
differences in the amount of bus or by energizing one phase of a
Winding resistance is another test cable connections do not greatly transformer at a time and measuring
recommended by ANSI/NETA MTS- affect the readings. the amount of current drawn. A
2019. A winding resistance typical excitation current
test injects a DC current test pattern for a three-
through the winding to be legged core is two similar
measured, and then reads readings and one lower
the voltage drop across ,WLVGL̪FXOWWRFRUUHFW reading.
power factor readings to
a base temperature on
dry-type transformers
80 RELIABILITY AND
ROUTINE TESTING

6JGCKOQHVJKUVGUVKUVQƒPFRQQT Core Ground Test recognized by the protective system


electrical connections, inter-turn short of the power supply/line (and quickly
circuits, abnormal core faults and The transformer core, which is disconnect the line), the transformer
winding problems. It gives information effectively a conductor that is not core must be grounded to provide
for an electrical and mechanical intended as a current-carrying path, an electrical (fault) path back to the
assessment of transformer may develop potential [voltage] source. A core is typically grounded
conditions. The test is performed due to capacitive coupling with at a single point only, as multiple core
on each phase by exciting the the innermost winding when the grounds may result in circulating
transformer with all other windings transformer is energized, resulting in currents and overheating in the core.
being open-circuited. Excitation partial discharges that may damage The core ground test is performed to
tests must be performed before any the transformer and induced potential ensure that the core is only grounded
other DC tests (such as winding when the transformer is carrying load. at the grounding point. Not all dry-
resistance) are performed, as DC This can occur and be detrimental to type transformers have the ability
testing can magnetize the core and the transformer’s useful life unless to lift the core ground, but when
cause erroneous test results during the core is solidly connected to earth available, the grounding bond to the
the excitation test. If a pattern of two ground. The core ground also assures core should be lifted and an insulation
similar readings and one low reading protective device operation in the test of 500 Vdc should be performed.
is not obtained, one possibility is core event of a winding to core insulation The core insulation-resistance values
magnetization. The core should be failure. For such a fault to be should not be less than one megohm.
demagnetized, and the
test performed again to
see if the results change.
Many manufacturers of
electrical test equipment When performing
offer stand-alone test sets
for this function, or have acceptance or
this function built into the
winding resistance test set.
maintenance testing on
dry-type transformers,
visual and mechanical
inspections are very
important

Photo by Shutterstock
Transformer Technology June 2019 81

Issue 2

Lightning (Surge) Arresters manufacturer’s recommendations for perform on-line partial discharge
the type of grounding system used scans and thermographic (IR) scans
Many transformers have surge at the site. Watts-loss testing (using of the electrical connections at regular
arresters on the high side to protect an insulation power factor test set) intervals as a cost-effective means to
the windings from transients that is commonly performed on surge monitor the health of the transformer.
might occur from switching or arresters to verify insulation integrity. The temperature gauges, cooling fans,
external sources such as lightning. Compare results between the phases output voltage readings, and loading
The proper voltage rating of the and similar arresters. should also be monitored regularly.
arrester is critical and should be
XGTKƒGFFWTKPIVGUVKPI/GVCNQZKFG On-line Inspection and Test In Summary
varistor (MOV) type arresters have
two voltage ratings: maximum 9KVJNKSWKFƒNNGFVTCPUHQTOGTUKVKU There are many tests that can be
continuous operating voltage (MCOV) very easy to pull oil samples and get a performed routinely on dry-type
and rated voltage. The MCOV rating is very cost-effective analysis of what is transformers to keep the electrical
chosen by what type of grounding is going on inside the transformer. Since system at your site safe and reliable.
used on the electrical system. When it is not possible to sample the air in Since there are many different
the system is solidly grounded, the a dry-type transformer in the same transformer construction techniques
MCOV rating of the arrestor can be manner, regular off-line maintenance and materials used, trending test
lower than if the system is a Delta or is important. However, you can data can be very valuable. No one
ungrounded system. On electrical test can tell
an ungrounded system, you if a transformer is in
the phase voltage on one overall good condition, but
phase can become as high performing the battery of
as phase-to-phase voltage When performing tests outlined in this article
during a fault on anther
phase. Therefore, ensure acceptance or can give you reasonable
EQPƒFGPEGCDQWVVJG
the proper MCOV rating
was selected based on the
maintenance testing on health of the transformer.

dry-type transformers,
visual and mechanical
inspections are very
important

You might also like