You are on page 1of 5

Microelectronics Reliability 126 (2021) 114211

Contents lists available at ScienceDirect

Microelectronics Reliability
journal homepage: www.elsevier.com/locate/microrel

Improved HV-H3TRB robustness of a 1700 V IGBT chip set in standard


power modules
J.-H. Peters a, *, M. Hanf a, S. Clausner a, C. Zorn b, N. Kaminski a
a
Institute for Electrical Drives, Power Electronics, and Devices, University of Bremen, 28359 Bremen, Germany
b
ForWind - Center for Wind Energy Research, University of Bremen, 28359 Bremen, Germany

A R T I C L E I N F O A B S T R A C T

Keywords: High Voltage-High Humidity High Temperature Reverse Bias (HV-H3TRB) is the standard to test power modules
HV-H3TRB for humidity driven degradation. This test has contributed significantly to detect and fix weak points in device
Power modules designs, especially of the junction termination. Thus, the latest junction termination designs offer unprecedented
Reliability
humidity robustness. This work reports on a comparative HV-H3TRB test on 1.7 kV IGBT modules with chips sets
Humidity
Moisture
of two consecutive generations tested at two different test voltages each. The progress in the chip design and
material composition provides more than an order of magnitude better performance in HV-H3TRB. Failure an­
alyses have indicated vastly reduced degrees of aluminium corrosion in the junction termination area, leading to
a slowed down failure mechanism.

1. Background 1.1. Accelerated testing

Power semiconductor devices are conquering more and more fields In order to estimate the useful lifetime of their power devices,
of application. Besides handling high electrical and thermal loads, the manufacturers perform accelerated tests by exposing the devices to
devices have to operate reliably, even under harsh environmental con­ much harsher conditions than the devices would encounter in the field.
ditions. This includes warm and humid climate, although the vast ma­ Well-designed tests can find failures within e.g. 1000 h, which would
jority of devices is not hermetically sealed (see Fig. 1). Consequently, occur only after decades of field operation. The test of choice to find
high humidity raises the risk of performance degradation and failures in humidity driven degradation in power semiconductor devices is the
application. Depending on the application, humidity might even show High Voltage-High Humidity High Temperature Reverse Bias (HV-
up under the significant failure reasons [1]. H3TRB). In decades of application to power devices, the HV-H3TRB has
The most humidity sensitive area of a power semiconductor is the contributed significantly to detect and fix weak points in the device
chip’s junction termination (JT) area, which can suffer from charge design, especially of the JT [2–6]. In an HV-H3TRB, power semi­
accumulation, metal corrosion as well as decomposition of the insulator conductor devices are biased with at least their usual DC-link or pref­
structure when biased. In general, the JT optimises the electric field erably higher voltage, while stored in a climate chamber at typically
distribution at the surface by spreading out the space charge region. 85 ◦ C and 85% relative humidity (“85/85”). The test duration for a
Damages introduced on the surface lead to an uneven field distribution qualification test is usually 1000 h, while for scientific purposes an end-
in the chip volume below, hence, causing very localised over-stress. of-life test is preferred.
Consequently, humidity-induced failure mechanisms deteriorate the The leakage current monitoring during the HV-H3TRB provides a
blocking characteristics of power semiconductors, either by increased first impression about the state-of-health of a power device, but is not
leakage currents or decreased blocking capability, i.e. premature precise enough for a detailed analysis. The blocking characteristics,
avalanche, if not flash over. especially the avalanche behaviour and the reduction of the avalanche
voltage over time are more accurate to investigate and separate failure
modes and mechanisms. However, to obtain a precise blocking curve at
room temperature, the modules need to be dried to establish a micro-

* Corresponding author.
E-mail address: j.peters@uni-bremen.de (J.-H. Peters).

https://doi.org/10.1016/j.microrel.2021.114211
Received 7 June 2021; Accepted 17 June 2021
Available online 11 October 2021
0026-2714/© 2021 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/4.0/).
J.-H. Peters et al. Microelectronics Reliability 126 (2021) 114211

Fig. 1. Schematic of an IGBT module. Humidity intrudes by diffusion or creeps


along interfaces (blue arrows). With respect to moisture, the chips’ JT handling
the high electric fields are the most delicate spots. (For interpretation of the
references to colour in this figure legend, the reader is referred to the web
version of this article.)
Fig. 2. Climate profile and procedure for HV-H3TRB.
climate inside comparable to the initial state [7,8]. Admittedly, this has
an impact on the progress of the degradation. 2. HV-H3TRB results

1.2. Design of experiment 2.1. Standard chip technology

Recent HV-H3TRB tests have revealed a general progress in moisture Fig. 3 shows the leakage current monitoring of Ps65/80 devices
performance of latest power modules compared to their predecessors during the HV-H3TRB and reveals for the Ps80 devices either a sudden
[2,3]. In order to confirm the effectiveness of the latest improvements breakdown (DUT3) with little oscillations before the failure event or an
with respect to humidity robustness, 1.7 kV IGBT modules with different increase of the leakage current over time (DUT2), which would most
chip technologies were tested in HV-H3TRB. Within the first test, a total likely lead to a shutdown of the respective test-channel due to even
of 24 650 A PrimePACK™ 2 modules (FF650R17IE4), featuring an further increasing leakage currents on continuation of the HV-H3TRB.
improved JT design, were biased at 65% of the nominal voltage level DUT1 exhibits an increasing amplitude of the oscillations over the tested
Vnom (Pi65, 16 pcs), and 80% Vnom (Pi80, 8 pcs), respectively. The bias time with an increased leakage current. The noise of a few microampere
split was meant to investigate a voltage acceleration observed in HV- at the beginning of the test (up to roughly 700 h) is due to the capability
H3TRB before [7,8]. For comparison, another 16 1.7 kV, 650 A Prime­ limit of the logging system, while the later oscillations are a result of
PACK™ 2 modules, equipped with the standard IGBT4 chip design, were electro-chemical reactions responsible for the humidity driven degra­
tested in a second test at the same two voltage levels (Ps65 8 pcs and dation [9]. In contrast, DUT4, typical for split Ps65, shows neither a
Ps80 8 pcs). The entire split chart is given in Table 1. catastrophic failure nor an increasing leakage current after 1300 h in the
The stress profile shown in Fig. 2 represents the applied test pro­ HV-H3TRB.
cedure. The climatic conditions of 85/85 are slowly built up within 1 h Fig. 4 shows the blocking curves of Ps80/DUT3 achieved after
and kept constant for 24 h, before the bias is applied to the DUTs designated testing times. The measured results indicate an initial
(moderate ramp-up) and the effective test time starts to elapse. From reduction in the blocking capability already becoming detectable at the
then on, the leakage current is continuously logged and monitored. To first IM after 47 h. For the time being, the blocking capability remains at
avoid a massive destruction of the DUTs at failure, they are disconnected this value until it decreases below the nominal voltage of 1.7 kV after
from the high voltage within microseconds, in case the leakage level 708 h. Depending on the JT-design, generally two different modes of
exceeds 10 mA. blocking degradation are found: 1. increasing leakage at fixed voltage
In order to investigate the ongoing degradation of the modules even and/or 2. decreasing avalanche inception voltage at fixed current
closer than the leakage monitoring allows, intermediate blocking curve (premature avalanche) [7]. For all Ps65/80-DUTs the later behaviour
measurements (IM) were carried out after certain time intervals (50 h, can be observed. DUT3 failed catastrophically after 772 h with a
150 h, 300 h, …). To achieve reasonable blocking measurements com­ remaining blocking capability of less than 300 V.
parable to the initial state and to reduce the risk of arcing due to In case of the split Ps65, none of the devices failed catastrophically in
remaining moisture inside the modules, a drying procedure of 50 ◦ C and HV-H3TRB within the tested time of 1300 h, but the blocking curves
10% rh was applied for 24 h (cf. Fig. 2) previous to the IMs. The fail
criterion applied to the blocking characteristic was exceeding 3 μA
below 1.7 kV. In this HV-H3TRB, only one switch of the half-bridge
configuration was connected to the test voltage each. Thus, each un­
connected switch served as a chamber reference to determine the in­
fluence of temperature and humidity without voltage applied to the
chips.

Table 1
Test splits and voltage conditions during the HV-H3TRB tests.
Test Split Package Chips Test voltage DUTs

1 Pi65 PrimePACK™ 2 Improved 65% Vnom/1105 V 16 pcs.


1 Pi80 PrimePACK™ 2 Improved 80% Vnom/1360 V 8 pcs. Fig. 3. Leakage monitoring of Ps65/80 DUTs in HV-H3TRB documenting one
2 Ps65 PrimePACK™ 2 Standard 65% Vnom/1105 V 8 pcs.
sudden breakdown (DUT3) and increasing leakage current over time (DUT1
2 Ps80 PrimePACK™ 2 Standard 80% Vnom/1360 V 8 pcs.
& DUT2).

2
J.-H. Peters et al. Microelectronics Reliability 126 (2021) 114211

Fig. 4. Blocking curves of DUT3, a Ps80 device, measured up or 3 μA with Fig. 6. Blocking curves of a Pi80 device, measured up to 3 μA with temperature
temperature impact on leakage compensated. Blocking capability reduces over impact on leakage compensated. Even after a testing time of more than 4000 h,
time to under the nominal voltage of 1.7 kV at the last measurement. the blocking voltage is only slightly reduced and remains well above the
nominal voltage of 1.7 kV.
show an initial reduction of the blocking capability. The devices of the
Ps80 split started to fail after only 800 h and after 1300 h 5 out of 8
devices had failed. Subsequent blocking curve measurements confirmed
catastrophic failures as all of these modules had a remaining blocking
capability of below 300 V. Additionally, the surviving modules of Ps80
have a reduced blocking capability below 1.7 kV.

2.2. Improved junction termination

In contrast, the modules of split Pi65 survived 5300 h effective test


time with 65% Vnom applied and the ones of split Pi80 survived 4100 h
with 80% Vnom. An example of the leakage current monitoring of these
two splits is shown in Fig. 5 and reveals neither a catastrophic failure
event nor an increase in the leakage level, but only measurement noise
of a few 10 μA. However, there was one unexplained early failure (in
Pi80 after about 15 h, removed from statistics). This excellent stability is
also confirmed by the intermediate blocking measurements, which show
a breakdown voltage only slightly decreasing over time (cf. Fig. 6). The
remaining blocking capability of only two modules (one Pi65 and Pi80
each) falls below the nominal voltage of 1.7 kV and this happens only
after more than 3000 h.
To compare the remaining blocking capability of both chip sets, the
breakdown voltages of the modules were extracted at a threshold of 2 μA
for each intermediate measurement. For modules which did not reach
that leakage level, the voltage value of the last data point was taken
instead. The median as well as upper and lower quartiles of these values Fig. 7. Comparison of the remaining blocking capability. Blocking voltages of
are plotted in Fig. 7. After a few hours already, both the Ps65 and Ps80 intermediate measurements at a threshold of 2 μA or last voltage datapoint of
splits show a drop in their remaining blocking capability, most probably all DUTs compared. Enlarged first 500 h tested time, voltage dependency of the
initial drop for Ps65/80. Z65/90 from [8].

due to ion movement on the chip surface [4]. In this experiment, even
the initial loss of blocking capability appears to be voltage-dependent.
As illustrated in Fig. 7, the remaining voltage level of split Ps80 is
lower compared to Ps65 in the first three IMs. With the intermediate
measurement 5 (Table 2), the Ps80 devices start to fail and the
remaining blocking capability is drastically decreasing. Then, all devices
fail within a short time window, so that one dominant failure mecha­
nism can be assumed. Compared to Ps80, the modules of Ps65 start to
drop with a delay and the blocking curves of two devices drop below the
nominal voltage at IM 6 and 7, respectively (see Table 2), but the tested
time was not sufficient to produce first catastrophic failures.
In [7], the equation for the acceleration factor in humidity testing
[10,11] was extended by a voltage acceleration factor, of which the y-
Fig. 5. 85/85 leakage monitoring of Pi65 and Pi80. The higher leakage current component has to be determined empirically:
level of the Pi65 is due to two modules connected in parallel per channel, no
failure events of increasing leakage current observable.

3
J.-H. Peters et al. Microelectronics Reliability 126 (2021) 114211

Table 2
Summarized IM results achieved on the Ps65/80.
IM Cumulated Fail criteria Fail criteria Catastrophic fail
no. test-time/h Ps65 (V < Ps80 (V < criteria Ps80 (V <
Vnom) Vnom) 300 V)

0 0 0/8 0/8 0/8


1 47 0/8 0/8 0/8
2 143 0/8 0/8 0/8
3 285 0/8 0/8 0/8
4 544 0/8 0/8 0/8
5 708 0/8 1/8 0/8
6 1017 1/8 7/8 4/8
7 1297 2/8 8/8 5/8

( )x ( [ ] ) ( )y
RHa EA 1 1 Va
af (RH, T, V) = ⋅exp ⋅ − ⋅ (1)
RHu k Tu Ta Vu
To get an idea about the course of Ps65, two data sets of [8] of 1.2 kV
modules and test voltages of 65% Vnom (Z65) and 90% Vnom (Z90) are
added in Fig. 7. The voltage drops of Ps80 and Z90 around 1000 h are
nearly the same and the behaviour of Ps65 and Z65 might be similar.
Therefore, if the two points at about 90% of the normalised blocking
voltage, for Ps65 at 1297 h and Ps80 at 708 h, are taken, a factor of 1.83
for the voltage acceleration can be extracted. This leads to a y-exponent
of 2.91. This value is in reasonable agreement with the acceleration
factor of 2.1 and y-exponent of 2.2 in [8] for 65% Vnom and 90% Vnom
respectively. The difference between the values can be explained by the
rather inaccurate estimation of the acceleration factor from the device
drops and the different remaining blocking capability of 90% in this
paper and 75% in [8] taken for the extraction.
By contrast, the modules of the Pi65 and Pi80 splits show no initial
drop and carry on for more than 4000 h. The blocking voltage starts to
drop slightly from ca. 3000 h onwards, but the time until a significant
degradation is at least an order of magnitude longer than with Ps65/80.
Furthermore, no influence of the test voltage can be observed anymore,
at least not within the tested time.

3. Failure analyses

The good agreement between the Z65/90 and Ps65/80 data suggests
that aluminium corrosion, which was determined to be the predominant
failure mechanism in [8], is the main degradation mechanism for Ps65/
80 as well. Directly after the final blocking characterisation, three of the
five failed devices of the Ps80 split were subjected to failure analysis. In
subsequent steps after module decapsulation, the failed substrate as well
as the damaged chips on it were identified and disconnected. After­
wards, the silicone gel was removed by a non-chlorinated silicone rub­
ber remover (ARDROX 2312) accelerated by higher temperature and
storing the modules upside down in a stainless-steel basin on a motion
table. After the first microscopic inspection, the remaining polyimide
serving as the top hard passivation layer on the JTs was removed by
plasma etching to prevent further material decomposition, e.g. etching
of aluminium. The result is shown in Fig. 8.
Optical inspection revealed no visible aluminium corrosion spots on Fig. 8. Optical analysis of the JT after silicone gel and polyimide removal, top:
the JTs of the chamber references (Fig. 8a). On the contrary, without detail of Ps80 diode JT without bias (chamber reference), middle: detail of Ps80
applied voltage during HV-H3TRB the chips look almost pristine. diode JT with bias applied, bottom: Pi80 IGBT JT with bias applied. All pictures
In contrast to that, all JTs of Ps80 diode and IGBT chips show dis­ roughly to the same horizontal scale. The chip edge is to the top, active cells to
the bottom.
colorations and corroded spots (Fig. 8b). The burn mark at the outer part
of the JT indicates one of the failure spots of the module, which caused
the reduced blocking capability of DUT3. For all modules analysed, corrosion of Al field plates is one of the most common moisture-driven
aluminium corrosion could be confirmed as the main failure mechanism. degradation mechanisms in power modules [7,8,12] and design im­
Unfortunately, just omitting aluminium is not an option. It is by far provements have to take care of this part of the JT.
the most commonly used material for the chip metallisation, as it allows Thus, the design improvements for the Pi splits concern the JT layout
for creating an ohmic contact on both p- and n-doped Si. An Al metal­ and material composition. One Pi65 module with a reduced blocking
lisation provides good electrical, but above all excellent mechanical voltage under 1.7 kV after more than 3700 h of tested time were ana­
properties. Its amorphous structure promotes adhesion between semi­ lysed. Only one small spot on an IGBT chip showed signs of flashovers
conductor, dielectric insulator, and the soft-mould. Consequently, the and seems to be the cause for the reduced blocking capability. However,

4
J.-H. Peters et al. Microelectronics Reliability 126 (2021) 114211

the origin of this spot is unclear and it was not related to aluminium interests or personal relationships that could have appeared to influence
corrosion. In fact, the JTs of the Pi65/80 modules contain less the work reported in this paper.
aluminium, which results in the absence of aluminium corrosion even
after such a long-testing time, with none of the JT (extracted area in Acknowledgements
Fig. 8c) show any discolouration or corrosion traces but look pristine.
In other words, the main failure mechanism for these modules seems This work has been funded by the German Federal Ministry for
to be no longer aluminium corrosion. Therefore, the known lifetime Economic Affairs and Energy (BMWi) under grant 0324336C.
model with its estimation of acceleration factors based on aluminium Special thanks go to Infineon Technologies AG for providing the
corrosion is no longer valid or at least lost its physical justification. Thus, modules and supporting the failure analyses.
it still might serve as a purely mathematical fit or has to be replaced
altogether.
References
4. Conclusions [1] K. Fischer, et al., Reliability of power converters in wind turbines: exploratory
analysis of failure and operating data from a worldwide turbine fleet, IEEE Trans.
The ambient humidity is one important factor to estimate the useful Power Electron. 34 (7) (2019) 6332–6344.
[2] S. Kremp, O. Schilling, Humidity robustness for high voltage power modules:
life or predict the remaining lifetime of power modules [13] and the HV- limiting mechanisms and improvement of lifetime, Microelectron. Reliab. 88–90
H3TRB is the primary test for humidity driven degradation in such (2018) 447–452.
power modules. [3] C. Papadopoulos, et al., The influence of humidity on the high voltage blocking
reliability of power IGBT modules and means of protection, Microelectron. Reliab.
Recent test results revealed a general progress in the humidity
88–90 (2018) 470–475.
robustness of power modules. The tests and results discussed in this [4] N. Tanaka, et al., Robust HVIGBT module design against high humidity, in: PCIM
work confirm the ongoing improvements, but go significantly beyond. Europe, 2015, pp. 19–21.
[5] S. Honda, et al., High voltage device edge termination for wide temperature range
While standard 1.7 kV chips failed during a highly accelerated HV-
plus humidity with surface charge control (SCC) technology, in: ISPSD, 2016,
H3TRB test (80% Vnom) around 1000 h, the same standard modules with pp. 291–294.
an improved chip set lasted for more than 4000 h in that test. [6] C. Zorn, M. Piton, N. Kaminski, Impact of humidity on railway converters, in: PCIM
The detailed analysis of the remaining blocking capability showed Europe, 2017, pp. 16–18.
[7] C. Zorn, N. Kaminski, Temperature humidity bias (THB) testing on IGBT modules at
that the improved chip set offers at least an order of magnitude better high bias levels, in: CIPS, 2014, pp. 25–27.
performance in the HV-H3TRB test and that the dependence on the [8] C. Zorn, N. Kaminski, Acceleration of temperature humidity bias (THB) testing on
applied voltage, observed previously and with the Ps65/80 split, is no IGBT modules by high bias levels, in: IEEE 27th International Symposium on Power
Semiconductor Devices & IC&apos;s (ISPSD), 2015, pp. 385–388.
longer present. Thus, under usual mission profiles humidity related field [9] I.B. Obot, et al., Electrochemical noise (EN) technique: review of recent practical
failures of power modules should no longer be an issue. In addition, applications to corrosion electrochemistry research, J. Adhes. Sci. Technol. 33 (13)
these improvements could be an explanation for the unexpectedly good (2019) 1453–1496.
[10] D.S. Peck, Ö. Hallberg, Recent humidity accelerations, a base for testing standards,
performance of SiC devices in HV-H3TRB tests, which should have been Qual. Reliab. Eng. Int. 7 (1991) 12–21.
inferior to silicon devices because of their smaller dimensions and high [11] D.S. Peck, Comprehensive model for humidity testing correlation, in: 24th Int.
electric fields, but were even superior [14,15]. Reliability Physics Symposium, 1986, pp. 44–50.
[12] R. Ambat, S. Garder Jensen, P. Møller, Corrosion reliability of electronic systems,
However, extreme environments or extreme events causing e.g. ECS Trans. 6 (2008) 17–28.
condensation inside power modules especially under the silicone gel [13] A. Brunko, et al., Model-based condition monitoring of power semiconductor
layer might still put the modules at risk [16] and the impact of such devices in wind turbines, in: EPE&’19 ECCE Europe, 2019.
[14] M. Hanf, et al., H3TRB test on 1.2 kV SiC MOSFETs, in: PCIM Europe, 2018,
operation condition has to be investigated further [17] and quantified
pp. 1506–1511.
by advanced humidity test methods. [15] D. Sadik, et al., Humidity testing of SiC power MOSFETs, in: IEEE 8th International
Power Electronics and Motion Control Conference (IPEMC-ECCE Asia), 2016.
Declaration of competing interest [16] K. Fischer, et al., Humidity in power converters of wind Turbines—field conditions
and their relation with failures, Energies 2021 (2019) 14.
[17] S. Kremp, O. Schilling, V. Mueller, Empirical study on humidity conditions inside
The authors declare that they have no known competing financial of power modules under varying external conditions, in: CIPS 2016, 2016.

You might also like