Professional Documents
Culture Documents
TT Mag Issue 1 2019 02
TT Mag Issue 1 2019 02
Photo by Shutterstock
Transformer Technology March 2019 35
Issue 1
Eddy Currents
Application of non-sinusoidal due to the crowding effect of the The resultant increase in eddy
excitation voltages to transformers OHDNDJHPDJQHWLFͤHOGVDWWKHFRLO currents increases the operating
increase the iron losses in the extremities. The eddy current losses temperature of the core iron, which
magnetic core of the transformer in increase as the square of the current in turn begins to deteriorate the
much the same way as in a motor. in the conductor and the square insulation between the core iron
A more serious effect of harmonic of its frequency. The increase in laminations. This leads to greatly
loads served by transformers transformer eddy current loss due to increased I2R losses, beyond the
is due to an increase in winding KDUPRQLFVKDVDVLJQLͤFDQWHIIHFW design limits of the transformer,
eddy current losses. Eddy currents on the operating temperature of the and overheating of the actual
are circulating currents in the transformer. Transformers that are winding insulation. Once the winding
conductors induced by the sweeping required to supply power to nonlinear insulation allows the energized
DFWLRQRIWKHOHDNDJHPDJQHWLFͤHOG loads must be de-rated based copper winding to contact the
on the conductors. Eddy current on the percentages of harmonic grounded core-iron, an internal
concentrations are higher at the components in the load current and failure will result. This process is
ends of the transformer windings the rated winding eddy current loss. illustrated in Figure 1.
and damaged.
Transformer Technology March 2019 37
Issue 1
Eddy
1 1 1 1 1 1 1 1 1 1
Current
Impedance 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Heating
I2R 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 5.0
Eddy
1 1 1 1 10 1 1 1 1 1
Current
Impedance 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Heating
I2R 0 0 0 0 50 0 0 0 0 0 50.0
Transformer Technology March 2019 39
Issue 1
Solutions
new loads will hopefully not fail the voltage distortion exceeds 3%,
within days of the new loads being the utility should provide some form
installed. of mitigation to correct the problem.
40 DIELECTRIC
RESPONSE
Photo by Shutterstock
Transformer Technology March 2019 41
Issue 1
DFR References
As mentioned previously, since the The practical application of DFR in the solid insulation by dielectric
beginning of the use of insulation LQWKHͤHOGJHQHUDWHGWKHLQWHUHVW response methods.
materials, a method to determine in the industry and international
an acceptable condition for its organizations took lead on Considering the great acceptance
use in electrical applications was the investigation of this “new RIWKHWHFKQRORJ\LQWKHͤHOGWKH
required. The dielectric response technology” revolutionizing the CIGRE Working Group (WG) A2.34
of any insulation material can be WHVWLQJSUDFWLFHVLQWKHͤHOG incorporates dielectric response
obtained in the time domain or in methods in time and frequency
the frequency domain. Time domain In 2002, CIGRE developed the domain in section 5.1.3 in the
dielectric response has been in Technical Brochure 254 – “Dielectric Technical Brochure 454 published
place for over 100 years and the Response Methods for Diagnostics in 2011. Dielectric response
typical “Insulation Resistance” test of Power Transformers”. This report methods are included as “Special
became, by far, the easiest and most from the Task Force (TF) D1.01.09 or Advanced Measurements”. DFR
practical approach to understand the focused on three dielectric response or FDS is an advanced testing
condition of the solid insulation. techniques: WHFKQLTXHXVHGLQWKHͤHOGWR
determine the water content in the
̽Return Voltage solid cellulose insulation of oil-
The complex impedance Measurements (RVM) paper insulation, insulation failures,
Peter Werelius and Bjorn Bengtsson maybe the most important part, case
introduced IDA (Insulation Diagnostics studies and comparative analysis
Analyzer) mainly for cable and using Karl Fisher Titration (KFT) to
transformer testing. validate the moisture estimation
Transformer Technology March 2019 43
Issue 1
In the North American world, the IEEE The work carried out by the IEEE
Transformer Committee revised the transformer committee ended up
document IEEE 62 Part 1– “Guide for with the publication in 2013 of
Diagnostic Field Testing of Electric the IEEE Std. C57.152 – “Guide
Power Apparatus – OilͤOOHG3RZHU for Diagnostic Field Testing of
Transformers, Regulators, and Fluid-Filled Power Transformers,
Reactors”. One of the fundamental Regulators and Reactors”. The
reasons to revise this document amount of information put together
was the application of new testing LQWKLVGRFXPHQWLVGLͦFXOWWR
techniques not described in this describe in just a few lines, but
document and considered important this guide added the Informative
for the current requirements of ANNEX G introducing to the IEEE
manufacturers and end-users references the Dielectric Frequency
HVSHFLDOO\LQWKHͤHOG,WLVLQWHUHVWLQJ Response Method. Annex G provides
to notice that IEEE 62 (R2005) a brief description of the DFR
provided in section 6.3.12 two method and its interpretation for oil-
tables with general guidelines for paper insulation systems in power
interpreting data expressed in transformers.
percent saturation of water in oil and Enough about history. Let us focus
in percent moisture by dry weight of now on the recently published guide
paper. for DFR testing.
44 DIELECTRIC
RESPONSE
Issue 1
The modelling algorithm requires Besides the modelling part, it is As any other electrical test, the
VSHFLͤFLQIRUPDWLRQWRHYDOXDWHWKH important to understand that the test YHU\ͤUVWUHFRPPHQGDWLRQVDUH
condition of the insulation system. LVSHUIRUPHGLQWKHͤHOGIROORZLQJWKH related to safety. For many readers,
7KHQRUPDOO\ͤ[HGLQIRUPDWLRQLV same instrument-to-object hook up safety is not just a best practice
a. Liquid Insulation relative principles as those used for power but also a life style. Therefore, local
SHUPLWWLYLW\Ər factor / dissipation factor testing at and federal regulations required to
b. Thermal activation energy for line frequency. Figure 1 shows the perform the test as well as safety
solid and liquid insulation hook up diagram of the DFR test set instructions provided by the test set
c. Temperature of the insulation to a commonly used two-winding manufacturer must be followed. One
under test transformer. more advantage of DFR is that the
test involves a LV excitation signal
The outcome of the test will provide: Section 5 provides the best practices W\SLFDOO\͠9RMS.
D/LTXLGLQVXODWLRQFRQGXFWLYLW\ Ɲ DQGFRQͤJXUDWLRQVWRSHUIRUPWKHWHVW
b. Moisture in solid insulation (m) LQWKHͤHOG
,QWKHͤHOGZRUNLQJFRQGLWLRQV Section 6 provides the guidelines to Overcome the effect of noise (EMI)
might not be optimal. Section 5 generate the test report, including an on the measurement signal, the use
provides guidelines to minimize example of the report. RIDYROWDJHDPSOLͤHULVFRQVLGHUHG
the effect of external factors on DVRSWLRQDOLQWKHͤHOGHVSHFLDOO\
the test performance as well as the Maybe the most important part for low capacitance specimens and
PHDVXUHPHQWFRQͤJXUDWLRQV$WWKLV of the guide is without a doubt tests at temperatures close to zero
stage, the reader should be aware Section 7 – Measurement Analysis degrees Celsius.
that the most accurate estimation and Interpretation. In this section,
of moisture in the solid insulation the guide provides the differences The Annexes included in the
is related to the test between between the dielectric response document cover:
windings in a UST (ungrounded of liquid and solid insulation A. Dielectric Frequency Response
specimen test) test mode. In a two- graphically represented in Figure 2. Analysis – Theory and validation
winding transformer, the capacitance The liquid insulation dielectric B. Non-moisture related
of interest is the inter-winding properties can be described by IDFWRUVLQͥXHQFLQJWKH')5
insulation between high and low a simple parallel RC-circuit, the measurements
voltage windings represented in capacitance representing the liquid C. Examples of typical measurement
Figure 1 as CHL. Other insulation permittivity and the resistance the challenges
systems, between high voltage liquid conductivity. The dielectric D. Bibliography
winding and ground (CH) or between properties of solid insulation are
the low voltage winding and ground more complex, both capacitance Closing Note
(CL DUHVXVFHSWLEOHWRWKHLQͥXHQFH and losses vary with frequency in a
of bushings and sometimes-other manner that cannot be described by This article is a brief summary
components inside the transformer a simple parallel or series RC-circuit. of a well-developed document
such as tap changers. Nevertheless, provided by IEEE and its members.
the GST measurements are often After a clear understanding of the Authors consider imperative for
taken to identify non-typical behavior of the materials under an asset managers, utility operators,
responses related to contamination alternating excitation signal in a wide transformer manufacturers and
or degradation of the insulation frequency spectrum, different factors testing service providers to acquire
system. affecting the dielectric response are this document and follow the
described. One of the most important guidelines given.
factors to take into account is the The article is co-authored by Dr.
Figure 2. DFR of mineral oil (left); presence of EMI in the surrounding Roberts Neimanis, Product Manager
DFR of paper only (right) test area. at Megger Sweden.
10000 100
1000
100
10
10
1
1
0.1
0.01
Photo by Shutterstock
0.001 0.1
0.0010 0..010 0..1 11 01 00 1000 0.0010 0..010 0..1 11 01 00 1000