You are on page 1of 14

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/288484922

Harmonics in electrical power systems: Effects of new technologies

Conference Paper · October 2014


DOI: 10.1109/IAS.2014.6978493

CITATIONS READS
2 2,190

1 author:

P.E. Sutherland
ABB
67 PUBLICATIONS   487 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Renewables View project

Standards View project

All content following this page was uploaded by P.E. Sutherland on 03 January 2018.

The user has requested enhancement of the downloaded file.


Harmonics in Electrical Power Systems:
Effects of New Technologies
Peter E. Sutherland, Ph.D., PE, Fellow, IEEE
GE Energy
1 River Road
Schenectady, NY 12345
Peter.Sutherland@ieee.org

Abstract— The purpose of this paper is to bring engineers up


to date and give them new tools for solving harmonic problems. II. FUNDAMENTALS OF HARMONICS
Variable Frequency Drive (VFD) technologies previously used Harmonics in alternating current (ac) electrical power
only in high power applications, such as Pulse Width
systems are voltages and currents at frequencies other than
Modulation (PWM) Drives, Active Front Ends, and 18-pulse
rectifiers have moved to lower voltage and power levels. They the base, or fundamental frequency of the sinusoidal voltage
are now widely used in industrial and commercial power and current waves.
systems. The techniques used in conventional harmonic analysis Distorted voltage and current waves will give rise to
for the 6-pulse SCR drive no longer apply in many cases. New voltage and current harmonics. In an electrical power system
harmonic limitation devices, such as broadband and active which is designed for normal functioning at a single
filters are replacing the conventional notch filter. fundamental frequency with sinusoidal voltage and currents,
the system characteristics may be significantly different for
Index Terms-- Harmonics, Power system harmonics, Variable voltages and currents at non-fundamental frequencies than at
Frequency Drive, Pulse Width Modulation Drive, Active Front
the fundamental. In particular, series and parallel
End, 18-pulse rectifiers.
combinations of inductive and capacitive elements may
I. INTRODUCTION create resonant frequencies which coincide with, or are close
to, frequencies of harmonics generated by power electronic
The majority of the harmonics of concern in electrical
equipment.
distribution systems are caused by distortion of the normally
When a resonant circuit is excited by a harmonic, the
sinusoidal voltage or current wave due to the switching of
result is a significant multiplication of the exciting quantity.
power electronic devices. For many years, the primary such
Resonances in power systems can cause overvoltages
source was the three-phase bridge rectifier with an inductive
resulting in insulation failure and short circuits. Resonances
load. Harmonic Analysis Studies were focused on this device
can also increase currents, typically resulting in capacitor
and its characteristic harmonics. Mitigation techniques were
failure or the opening of capacitor protection devices, such as
primarily the 5th harmonic notch filter. As Pulse Width
fuses. Traditionally, harmonic remediation has consisted of
Modulated (PWM) motor drives became prevalent the typical
replacing capacitor banks with tuned filters which change the
harmonic spectra have changed significantly, and in some
frequency response characteristics of the system such that
cases become much greater in magnitude. Concurrent with
voltage and current magnification are eliminated or greatly
the new PWM drives, new harmonic mitigation technology
reduced.
has been developed, such as Bandpass Filters and Active
Filters. New drive topologies with reduced harmonics have III. HARMONICS STANDARDS
been developed, such as Active Front Ends and 18 pulse
rectifiers with autotransformers. As this transition has Harmonic analysis studies are conducted in accordance
occurred, attempts to solve new harmonic problems with old with the recommendations of IEEE Std 519-1992, IEEE
techniques have been tried and failed, resulting in sometimes Recommended Practices and Requirements for Harmonic
difficult and expensive remediation. Harmonic analysis Control in Electrical Power Systems [1]. This standard
software used with older types of VFDs has been found not provides recommended limits for both current and voltage
suitable for use with newer VFDs, and different approaches distortion. A draft revised standard P519/D6a. Draft
must be used. The purpose of this paper is to explain these Recommended Practice and Requirements for Harmonic
developments and provide case histories of how harmonics Control in Electric Power Systems [2] has been issued in
can be successfully reduced. September 2013, but is not yet approved. The major
difference is that the new standard includes only the tables,
while the explanatory and background material will be
published separately.

1
Current distortion limits, Table 1, are considered the Table 3 Draft D6a Standard 519 Voltage Distortion Limits, in percent of
nominal fundamental frequency voltage [2]
responsibility of the energy user, or customer of the electric
utility system. The Total Demand Distortion (TDD) is used Voltage Individual  THD  
as a measure of Current Distortion: (kV)  Harmonic (%)  (%) 
 1.0   5.0 8.0 

1.0 <V  69  3.0 5.0 
(1)
69 < V  161   1.5 2.5 
where > 161 1.0 1.5 
IL is the rms magnitude of the maximum demand load
current, based on a 15 or 30 minute demand interval IV. TRADITIONAL HARMONICS ANALYSIS
Ih is the rms magnitude of the hth harmonic current A. Six Pulse SCR Rectifier
The TDD is different from the total harmonic distortion
(ITHD) which is: Many references still consider the standard six-pulse
∑ rectifier as the typical harmonic load [3]. The derivation of
(2) the waveforms and calculation of current harmonic
magnitudes is a standard exercise. This may lead to
Voltage distortion limits, Table 2 for the existing standard application errors by severely underestimating or
and Table 3 for the new draft standard, are considered the overestimating harmonic current magnitudes and power
responsibility of the energy provider or electric utility system. factor. Newer systems have actually existed for a long time.
The Voltage Total Harmonic Distortion (VTHD) is used as a The older systems are still in use. Yet the new systems are
measure of Voltage Distortion: often poorly understood.

The traditional six-pulse rectifier or three-phase Graetz
(3) bridge rectifier, [4] [5], Figure 1, has been the mainstay of
power conversion for over a century. The first were built
where with mercury-arc rectifiers, and, beginning in the 1960s, by
V1 is the rms magnitude of the fundamental voltage silicon controlled rectifier (SCR) bridges. SCRs are used for
Vh is the rms magnitude of the hth harmonic voltage power control. Typical ac input and dc output voltages are
The junction between these two systems is called the shown in Figure 2. When there is an inductive load, such as a
Point of Common Coupling or PCC. The applicable current DC motor or the DC link inductor of a current source inverter
and voltage distortion limits are applied at the PCC. Within (CSI), the DC current is smoothed, and the ripple is greatly
an industrial plant, the PCC is considered to be the point of reduced. The AC line current from a six-pulse rectifier with
interconnection between the nonlinear load and the other inductive load is essentially a square wave. The individual
loads. This last requirement has been dropped by in the draft harmonic currents produced by a square wave are
of the new standard, considerably simplifying the application approximately 1/h magnitude, where h is the harmonic order.
of the standard. The firing pulse triggers each SCR, six pulses per cycle. The
Table 1 Current Distortion Limits for Odd Harmonics, %IL, 0.12  kV  harmonics generated are:
69 [1]

11h<1 17h<2 23h<3 1 (4)


Isc/IL  <11  7  3  5  35h  TDD 
<20  4.0  2.0  1.5  0.6  0.3  5.0 
where n=1, 2, 3 ….
With p=6, h=5, 7, 11, 13 …. This results in a current THD 
20 < 50  7.0  3.5  2.5  1.0  0.5  8.0  25% and a Displacement Power Factor, defined as the phase
50 < 
100  10.0  4.5  4.0  1.5  0.7  12.0 
angle between voltage and current at the fundamental
100 <  frequency,  80%. The typical harmonic magnitudes, Table
1000  12.0  5.5  5.0  2.0  1.0  15.0  4, differ slightly from 1/h because of commutation (transfer
of current from an SCR turning off to one turning on) and
> 1000  15.0  7.0  6.0  2.5  1.4  20.0 
other effects. Figure 3 shows the sum of harmonics according
Table 2 Std. 519-1992 Voltage Distortion Limits, in percent of nominal to 1/h and typical values.
fundamental frequency voltage [1]
Voltage  Individual  THD  
(kV)  Harmonic (%)  (%) 
 69  3.0  5.0 
69 < V  161   1.5  2.5 
> 161  1.0  1.5 

2
Figure 1 Six Pulse Rectifier Schematic

Figure 3 AC Line Current of Six Pulse Rectifier

B. Fifth harmonic notch filter


The fifth harmonic notch filter has been used in the vast
majority of harmonic mitigation schemes. Placed on the
system bus, it effectively reduces harmonics for most 6-pulse
drives, as well as providing power factor compensation.
Tuned for h=4.7, it is relatively immune to variations in
component values. The equivalent circuit in Figure 4 shows
the reactances of the capacitor and inductor and the internal
resistance of the inductor. As a series circuit, the total
Figure 2 Six Pulse Rectifier DC Output Voltage Waveform.
impedance of the filter is:
Table 4 Magnitudes of typical line current harmonics of six pulse
rectifier Z R j X X (5)
Harmonic  1/h  Typical 
order  [1]  where
1  1.000  1.000  RL is the internal resistance of the inductor ()
5  0.200  0.192 
XL is the reactance of the inductor ()
7  0.143  0.132 
11  0.091  0.073  XC is the reactance of the capacitor ()
13  0.077  0.057  This characteristic is plotted in Figure 5.
17  0.059  0.035 
19  0.053  0.027 
23  0.043  0.020 
25  0.040  0.016 
29  0.034  0.014 
31  0.032  0.012 
35  0.029  0.011 
36  0.028  0.010 
41  0.024  0.009 
43  0.023  0.008  Figure 4 Notch filter equivalent circuit.
47  0.021  0.008 
49  0.020  0.007 

3
Figure 5 Impedance of fifth harmonic notch filter versus harmonic Figure 7 Resonance of PFC with system inductance
order.

Power factor correction (PFC) capacitors are often


applied to improve the typically low PF of induction motor
loads. The capacitors will have a resonant frequency with the
inductance of the power system. If an adjustable speed drive
(ASD) with a six-pulse rectifier is added to that system, the
harmonics produced may excite the resonant frequency of the
system, resulting in unacceptable overcurrents and/or
overvoltages. The single line diagram is shown in Figure 6
(a), and the frequency scan in Figure 7. Without the
capacitor, the system impedance is resistive and inductive,
resulting in the sloped frequency response shown. The
presence of a capacitor causes the resonant peak. In this
example, the resonance is at the sixth harmonic, with
significant amplification of the fifth. When the harmonic
filter is substituted for the capacitor, Figure 6(b), the Figure 8 Effect of harmonic filter on resonance point.
resonance point is moved from the sixth harmonic to the
eighth, Figure 7, where there are no harmonics injected by the
ASD. The harmonic impedance is significantly lowered for
the fifth harmonic.

(a) (b)
Figure 6 Power factor correction capacitor (a) and harmonic filter (b)
with SCR drive.

Figure 9 Water treatment plant single line diagram. Line reactor


impedance is 3%.

4
but with harmonic data based upon these factors, the PWM
C. Case study: water treatment plant. VFD can be analyzed using a harmonic analysis program
with the harmonic magnitudes entered at each frequency.
A power system study was performed for a small water
treatment plant. The relevant portion of the single line
diagrams is shown in Figure 9. The study was to evaluate the
harmonics produced by two 480 V, 300 HP VFDs. The
drawing specified that the line impedance of the VFDs should
be at least 3%, with external line reactors provided if
necessary. The harmonic study work scope included the
variable frequency drives of pumps P-1 and P-2. These are
the only harmonic producing devices in the system. The
results of this study provided in this report are based on the
Figure 10 PWM Drive with Diode Front End
scenario of P-1 online and P-2 offline and the 800A main
breaker of MDP-1 being the point of common coupling. Unlike the CSI, the AC line current waveform from a VSI
A harmonic spectrum report could not be provided by the has two modes, continuous current (CCM) and discontinuous
drive manufacturer for the 800 HP drives, so typical current (DCM), Figure 11. The waveform has two distinct
harmonic spectrum values for 6-pulse rectifiers, Table 4, peaks, which are produced when the AC line voltage exceeds
were used for this study. the DC link voltage [12]. When the diodes cease to conduct
It was determined that a notch filter installed at bus MDP- between the peaks, the current is discontinuous, when they
1 which is tuned to the 4.7th harmonic will reduce all of the stay conducting the current is continuous. The harmonic
harmonic current values as well as the total harmonic current currents produced by these two waveforms can be
distortion to within IEEE 519 standards. Recommended filter significantly different.
specifications were developed, resulting in the frequency
plots shown in Figure 7.
When the harmonic filter was installed, it was found that
the power factor went leading. The voltage on 480 Volt Bus
rose by 10%. The harmonic filter had to be disconnected
immediately. The actual drive was 6-Pulse PWM type with
98% power factor, and no additional power factor correction (a) (b)
was required. The study had to be re-done with PWM
Harmonics and no power factor correction. Possible solutions Figure 11 Line current waveforms for PWM Drive with Diode Front
End (a) discontinuous mode (b) continuous mode.
which were considered were broadband or active filters (to be
discussed later). A number of the references [8] [9] [10] derive analytical
equations for the line side current, and in some cases for the
individual harmonics, these equations are unwieldy and do
V. PWM DRIVE WITH DIODE FRONT END not lend themselves an evaluation of the factors which cause
The pulse width modulated (PWM) drive controls the variation in the harmonic magnitudes. The time domain
motor speed by generating a variable frequency supply methods used in [6] and [7] can be used to readily determine
voltage, thus it may be called a Variable Frequency Drive the effects of changes in system and load parameters on the
(VFD) or an Adjustable Speed Drive (ASD). PWM drive harmonic spectrum. In this case, a Fourier transform is used
harmonics are discussed in [6] [7] [8] [9] [10], and mitigation to calculate the harmonic magnitudes based on the simulated
methods in [11]. The configuration of a PWM drive from the waveform.
AC line perspective is that of a Voltage Source Inverter Referring to Figure 12, the magnitudes of the 5th and 11th
(VSI), as shown in Figure 10. The rectifier is simply a diode harmonics are plotted vs. the normalized source reactance xv
bridge, since all control is performed by the inverter. The [6], which is the source reactance divided by the fundamental
inverter and its load may be modeled as a resistance or DC frequency power. The plot can be read at power levels other
current source. The voltage in the DC link is held by the DC than 100% by dividing xv by the per unit fundamental power.
link capacitor, which is a high capacitance, high voltage Similar charts in the reference cover other harmonics. The
capacitor or bank of capacitors. Additional filtering may take second parameter, 0, is the resonant frequency of the
place using an AC line reactor and optional DC link reactor. inductance with the DC link capacitor. In the discontinuous
The total value of reactance consisting of the source current mode, the 5th harmonic can have a magnitude as high
impedance, AC line and DC link reactors is a significant as 90% of the fundamental, and the 11th harmonic
factor in the performance of the drive and the production of approximately 40%. These values go down to less than 25%
AC line current harmonics. The magnitude of the harmonics and approximately 4% at high values of xv. This compares
depend upon the source impedance and the percent loading, with maximums of 20% and 9% for the CSI drive. The

5
figure shows that by increasing the line reactance, the The power factor in a non-sinusoidal system is actually
magnitude of the harmonics is decreased, sometimes composed of two different power factors, the displacement
significantly. In practice, this can be controlled by the power factor and the distortion power factor [13]. The
addition of AC line and DC link reactors. Decreasing the displacement power factor, cos , is the fundamental power
1
resonant frequency will decrease harmonics in most cases,
factor, the cosine of the angle between voltage and current.
except for areas like the 11th harmonic at high reactance. The
The total power factor, , is the ratio between real and
resonant frequency will decrease by increasing reactance,
apparent power:
which already decreases harmonics, or by increasing the DC
link capacitance, which is a fixed design parameter. (6)
The harmonic magnitudes also depend upon the motor, or where P is the real power in kW and S is the apparent power
load, power, Figure 13 [6]. The curves are based upon a fixed in kVA. The portion of the total power factor which is due to
0. At powers above rated, the 5th harmonic can exceed the harmonics is the distortion power factor. The displacement
fundamental in magnitude. Tables of harmonic magnitudes power factor is fairly constant at above 90% for most values
for VSI inverters are usually given vs. power output at a of xv, Figure 15 [6]. This is very different from the poor
given source impedance. The boundary between the DCM power factor ( 80%) of the CSI drives. The total power
and CCM is a function of both xv and 0, Figure 14 [6], and is factor is very low in the DCM, increasing with xv, and
indicated by the dashed lines in Figure 12. The high exceeding 90% in the CCM. It is this high power factor of the
magnitudes of the PWM drive harmonics and their variability PWM drives which prevents the use of highly capacitive
due to load is one reason that mitigation methods used for harmonic filters, such as the notch filter, for harmonic
CSI drives are not only ineffective but counterproductive. mitigation.

Discontinuous
Current Mode
CCM

0 DCM

Figure 13 Harmonics vs. motor power, = 5, = 7, 0=2.3 [6]

Continuous
Current Mode

Figure 14 Waveforms: (a) Discontinuous current mode xv = 0.3 and 1.2,


Figure 12 Fifth and eleventh harmonic magnitudes vs. AC line reactance continuous current mode xv = 3 and 10, (b) boundary between modes. [6]
xv and natural frequency 0.  = 0, = 2, = 3, = 4,  = 5. [6]

6
VI. PWM DRIVE WITH ACTIVE FRONT END
In order to reduce the high level of harmonics produced
with the VSI and a diode front end, the Active Front End
(AFE) has been developed [14]. The rectifier consists of an
IGBT bridge operated in PWM mode, Figure 16. The line
current harmonics generated are centered on the inverter and
rectifier switching frequencies, which are generally above 1
kHz. The AFE also can control the fundamental power factor
to be lagging, leading or unity. AFE rectifiers must use AC
line reactors in order to shape the input current waveform to
be sinusoidal. The high frequency switching produces
voltages which capacitively couple to ground, producing
distorted voltage waves, Figure 17. The current distortion is Figure 17 PWM Drive with Active Front End - Waveforms
typically less than 3% and the voltage distortion less than 6%,
VII. 18-PULSE DRIVE FOR HARMONIC REDUCTION
enabling AFE drives to meet IEEE Std. 519-1992 [1] without
harmonic filters. This type of VFD can be analyzed using a A. Introduction to 18-pulse drives
harmonic analysis program with the harmonic magnitudes
entered at each frequency. Higher order rectifiers have p in equation (1), p being a
multiple of six for three-phase systems. Thus, the first two
harmonics of a 12-pulse drive will be 11 and 13, and for an
18-pulse drive 17 and 19, and 23 and 25 for a 24-pulse drive.
Harmonic currents will have 1/h magnitudes as with the 6-
pulse rectifier. In the past, multi-pulse rectifiers have been
used for high power applications such as motors over 1000
Hp and rectifiers for electrochemical plants. Due to new
technology, such as the 9-phase autotransformer and
improved power electronics, they have migrated to low
power, low voltage applications where low harmonics are
required. Higher pulse rectifiers are highly susceptible to
voltage unbalance, typically requiring significantly less than
1% unbalance in order to provide the expected low harmonic
levels.
The harmonic analysis based on these assumptions is
conducted using the 18-pulse drive topology found in nearly
all textbooks. Three transformers providing phase shifts of -
20, 0 and +20 connect to the DC bus through three 3-phase
bridges connected in series, Figure 18. The resulting current
waveform is nearly sinusoidal, Figure 19, and the harmonic
spectrum is minimal, as shown in Figure 20.

Figure 15 Power factor vs. ac line reactance, cos1 = fundamental,  =


total. [6]

Figure 16 PWM Drive with Active Front End - Schematic


Figure 18 18-Pulse Drive with 3 transformers [11]

7
voltage unbalance was found to be nearly one percent. The
measured line-to-neutral voltages were:
VA = 258.6, VB = 256.5 and VC = 257.9 Volts
The voltage unbalance may be calculated as:
% 100% 0.8% (7)

Figure 19 Current waveform of ideal 18-pulse drive.

Figure 20 Ideal 18-pulse rectifier current harmonics.

B. Case study: two 440 Volt, 700 HP 18-pulse drives

An example of a pair of 440 Volt, 700 HP induction


motor drives, shown in Figure 21 will be considered here. Figure 21 Two 700HP 440V Cooling Water Pumps in a Power Plant.
The customer specification for the drives had the following These are 18-pulse drives with 9-phase transformers.
requirements:
 The VFDs should comply with IEEE 519
 The VTHD is <3% with utility source
 The TDD is <5% at the PCC
 VFD is to be 18 or higher pulse
 Harmonic filters will not be used
 The PCC is defined as the input to the VFD transformer
The initial analysis conducted as described above. A
harmonic analysis computer program was used to model the
drives injecting the theoretical harmonic currents into the
system. The results showed minimal harmonics, which were
within the limits of IEEE-519.
When harmonic measurements were made at the site, the
current waveform was found to be highly distorted, as shown
in Figure 22. The resulting harmonic spectrum, Figure 23,
showed harmonic current levels which significantly exceeded Figure 22 Measured 18-pulse VFD current waveform
the IEEE 519 limits. The TDD was equal to 36.7%. The most
significant of the current harmonics, as well as the TDD,
were greater than the 5% contractual specification. The

8
models pieced together. This model was used to compute the
waveform and spectrum in Figure 19 and Figure 20.

Figure 23 Measured 18-pulse VFD current spectrum

Figure 25 Schematic of windmill type 9-phase autotransformer for 18-


pulse drive [15]

Using the simulation, it was possible to determine that


inserting AC line reactors would decrease the current
distortion. The line reactors have two effects. First, they will
Figure 24 Photo of typical 9-phase autotransformer for 18-pulse drive cause an equalization of the input voltage to the transformer
by causing a higher voltage drop on phases with higher
The drive was not constructed with three phase-shifting current and a lower voltage drop on phases with lower
transformers, such as was shown in Figure 18, but with a 9- current, where the higher current may have been caused by a
phase autotransformer. A photograph of a typical unit is in higher phase voltage and the lower current by a lower phase
Figure 24, and a typical winding configuration in Figure 25. voltage. Secondly, the added inductance will decrease the
This configuration is called the “windmill topology” [15]. effects of commutation.
Other delta-type topologies are also in widespread use. These The solution of installing AC line reactors was hampered
units have been designed to reduce the size and weight of 18- by the fact that they had not been included in the original
pulse drives, and come in a great variety of configurations design, Figure 21, unlike the system in the first example
[15]. The system should be analyzed with a simulation shown in Figure 9. This resulted in having to install the line
program such as MATLAB or EMTP, rather than a reactors in another room, mounted high on the wall, and
conventional harmonic analysis program. The ITHD is having long and difficult cable connections with great
designed to be <5%, however source voltage unbalance will expense in installation.
increase this. It was reported in [15] that an instance of 0.6% Figure 26 shows a comparison of the measured results
voltage unbalance resulted in ITHD = 5.9%, compared with without line reactors and simulated results with line reactors.
5% with balanced input voltage. ITHD can be much higher Field measurement showed that this was an effective
for small amounts of unbalance during lightly loaded solution.
operation as seen in Figure 30.
Modeling the system in a conventional harmonic program
would give none of the detail of the actual harmonic currents,
which are assumed as an input, and have no possibility of
including three-phase effects such as unbalance.
Constructing an EMTP model with twenty degree phase
shifts in two-winding transformers or 9-phase
autotransformers is possible with multiple transformer
9
of IEEE 519 at the point where it connects to the supply bus.
The LCL design shown in Figure 27 and Figure 28 is typical.
Without Reactors A transfer function calculated from the data in [16] is shown
in Figure 29. The designs of LCL filters are typically
proprietary, and harmonics analysis programs may not
include models. They could be modeled in EMTP simulations
With Reactors but this is not practical for day to day work. In most cases,
harmonics analysis studies are not required for the application
of broadband filters. For practical applications, manufacturers
provide spreadsheets for calculating the performance of these
filters.
The performance of a six-pulse diode based VSI drive
with a broadband filter is better than that of an 18-pulse
Figure 26 Harmonic reduction using line reactors. rectifier under varying conditions of loading and voltage
imbalance, as plotted in Figure 30 [17].
The characteristics of the types of VFDs considered here
are summarized in Table 5. Starting with the current source
SCR drive with inductive load as the baseline, it can be seen
that the VSI with diode rectifiers is comparable in the CCM,
but far worse in the DCM. These problems can be avoided
by using the more expensive active rectifier, or the more
complex 18-pulse rectifier. In the next section, harmonic
filter solutions will be discussed.

Table 5 Summary of Drive Characteristics Figure 27 LCL filter schematic

Rectifier  Inverter  AC Line  DC  VTHD  ITHD PF


Current  Link  (%)  (%)  (%) 

SCR  CSI  Square   L  5  25 80

Diode  VSI  DCM  C  37  97 95

Diode  VSI  CCM  C  11  25 98

Active  VSI  Sine   C  <6  <3 100

18‐p   VSI  Sine   C  <5  <3 >90

VIII. HARMONIC FILTERS

Figure 28 Typical LCL filter [17]


A. Broadband Filters

Two problems need to be addressed to reduce the high


harmonics produced by the VSI diode front end. Since there
is a nearly unity power factor, the filter cannot introduce
additional capacitance into the system. The filter must also
be far more effective than the conventional notch filter to
remove harmonics of 90 - 125% of the fundamental current.
These requirements can be met by using an inline filter
which is installed on each drive, instead of on the bus. A
broadband filter is used, which has significant inductive
component such that it does not change the power factor. A
broadband, low-pass filter approach is used to reduce all
harmonics, not just the fifth, reducing the overall THD. Such
a filter will ensure that the drive will meet the requirements
10
Figure 29 LCL filter frequency response
Figure 32 Current injected by active harmonic filter [18]

LCL Filter

Figure 30 LCL filter and 18-pulse drive harmonics vs. load at 1% and
3% voltage unbalance. [17]

B. Active Filters
Figure 33 Corrected current waveform [18]

Active harmonic filters are a power electronic device The active filter is installed on the bus in parallel with the
which is designed to cancel out the nonsinusoidal elements of harmonic producing load, Figure 34, with a current sensor
a current waveform, returning it to a sinusoidal shape. This (CT) to measure the distorted current of Figure 31.
process is illustrated in Figure 31, Figure 32 and Figure 33. Alternatively, the sensor can measure the corrected current,
Figure 33, and make changes to maintain it as sinusoidal.

Figure 34 Typical installation of active filter [18].

Figure 31 Distorted current produced by PWM drive [18]

11
The active filter is designed as a PWM inverter, as in drives and rectifiers fully compliant with IEEE 519 and
Figure 35, which produces the current waveshape needed to operate at unity power factor without large capacitive filters.
compensate the distorted current. The bridge will act as an
active rectifier to charge the capacitor, and then as an inverter X. REFERENCES
to produce the correcting waveform of Figure 32. Active [1] IEEE Std 519-1992. IEEE Recommended Practices and Requirements
filters are being produced for low-voltage, low HP for Harmonic Control in Electrical Power Systems, New York: IEEE,
1992.
applications, as can be seen in the small device shown in
[2] P519/D6a. Draft Recommended Practice and Requirements for
Figure 36. This effectively reduces something which had Harmonic Control in Electric Power Systems. New York: IEEE, 2013.
been once a large piece of equipment only feasible for high [3] St. Pierre, C. R. Harmonic Misconceptions, Schenectady, NY: Electric
voltage, multi-megawatt applications to something which can Power Consultants, undated.
be used in even the smallest facility. In most cases, harmonics [4] Stevenson, A.C. Power Converter Handbook: Theory Design
analysis studies are not required for the application of active Application, GE Publication PGEI-10355A, Peterborough, ON:
General Electric Canada, Inc. 1976
filters. For practical applications, manufacturers provide
[5] Stevenson, A.C. Power Converter Handbook: Theory Design
spreadsheets for calculating the performance of these filters. Application, 5th Edition, IB-1132, Cleveland, OH: Darrah Electric
Company, 2009
[6] Grötzbach, M. and Redmann, R., “Line Current Harmonics of VSI-Fed
Adjustable-Speed Drives”, IEEE Transactions on Industry
Applications, Vol. 36, No. 2, Mar/Apr 2000. pp.683-690.
[7] Xu, W.; Dommel, H.W.; Hughes, M.B.; Chang, G.W.K. and Tan, L.,
“Modelling of Adjustable Speed Drives for Power System Harmonic
Analysis,” IEEE Transactions on Power Delivery, Vol. 14, No. 2, April
1999, pp. 595-601
[8] Chang, G.W. and Chen, S-K, “An Analytical Approach for
Characterizing Harmonic and Interharmonic Currents Generated by
VSI-Fed Adjustable Speed Drives,” IEEE Transactions on Power
Delivery, Vol. 20, No. 4, October 2005, pp.2585-2593
[9] Carpinelli, G.; Iacovone, F.; Russo, A.; Varilone, P. and Verde, P.,
“Analytical Modeling for Harmonic Analysis of Line Current of VSI-
Figure 35 Low Voltage active filter design [18] Fed Drives,” IEEE Transactions on Power Delivery, Vol. 19, No. 3,
July 2004, pp.1212-1224
[10] Dell'Aquila, A.; Lassandro, A. and Zanchetta, P., “Modeling of Line
Side Harmonic Currents Produced by Variable Speed Induction Motor
Drives,” IEEE Transactions on Energy Conversion, Vol. 13, No. 3,
September 1998, pp. 263-269
[11] A. H. Hoevenaars, Michael Fahrney, Michael James, and Michael
McGraw, “Design Considerations When Applying Various LV ASD
Topologies to Meet Harmonic Compliance,” IEEE Transactions on
Industry Applications, Vol. 47, No. 4, Jul/Aug 2011. pp1578-1585
[12] Hoadley, F.L., “Curb the Disturbance,” IEEE Industry Applications
Magazine, Sept /Oct 2008, pp.25-33
[13] IEEE Std. 1459-2010, IEEE Standard Definitions for the Measurement
of Electric Power Quantities Under Sinusoidal, Nonsinusoidal,
Balanced, or Unbalanced Conditions, New York: IEEE, 2010.
[14] Morán, L.; Espinoza, J.; Ortíz, M.; Rodríguez, J. and Dixon, J.,
“Practical Problems Associated With The Operation of ASDS Based on
Active Front End Converters in Power Distribution Systems,” 2004
IEEE Industry Applications Society Annual Meeting, pp. 2568-2572.
[15] Lee, K.; Paice, D.A. and Armes, J.E., “The Windmill Topology:
Evaluation of adjustable speed drive systems,” IEEE Industry
Figure 36 Low Voltage active filter construction [18] Applications Magazine, Mar /Apr 2009, pp.43-53.
[16] Reznik, A.; Simões, M.G.; Al-Durra, A. and Muyeen, S. M., “LCL
Filter Design and Performance Analysis for Grid Interconnected
Systems,” Accepted 2013 by IEEE Transactions on Industry
IX. CONCLUSIONS Applications
This paper has described the fundamentals of harmonic [17] Matrix Harmonic Filter Series B, GE Publication DET-374A, Fort
generation in electrical power systems, and the responses Edward, NY: General Electric Co., 2003.
needed as PWM drives become the dominant technology. A [18] GEMActive Active Filter System, GE Publication DET-376, Fort
variety of remediation techniques and preventative measures Edward, NY: General Electric Co., 2003.
such as AC Line Reactors, DC Link Reactors, Active Filters,
Active Front Ends, LCL filters and 18-pulse drives were
considered, along with some case studies. With the wide
variety of devices available, it is possible to make nearly all

12
XI. BIOGRAPHY

Peter E. Sutherland (Fellow, IEEE) received the B.S. degree in


Electrical Engineering from the University of Maine, Orono, and the Ph.D.
degree in Electric Power Engineering at Rensselaer Polytechnic Institute,
Troy, NY.
In 1987, he joined General Electric Company, Schenectady, NY, and
held a variety of positions, becoming a Senior Engineer in the GE Power
Systems Energy Consulting Department. In 2001, he joined SuperPower,
Inc., Schenectady, N.Y., where he worked on applications of
superconductivity to electric power systems. Dr. Sutherland then joined
EPRI PEAC Corporation’s (now EPRI Solutions, Inc.), Schenectady, NY
office as a Consulting Engineer. He is currently a Lead Consultant with GE
Energy Services in Schenectady NY. Author of numerous technical papers,
he is active in the IEEE Industry Applications Society, and in the IEEE
Schenectady Section. Dr. Sutherland is a member of CIGRE and the IET
(formerly IEE). He is a Registered Professional Engineer in Pennsylvania,
Maine, New Jersey and New York and is a Chartered Engineer in the UK.

13

View publication stats

You might also like