Without going into Fourier equations or requiring an electrical engineering level of knowledge,
let’s look at the cause of harmonics in today’s power systems, and how a power engineering
review of your facilities can help solve the problem.
The usual waveform of alternating current in most electric power circuits is a sine wave that
changes directions at a specific frequency, usually 50 or 60 hertz. A linear electrical load draws
current at the same frequency and sinusoidal wave shape as the voltage frequency and wave
shape, although the timing or phase between current and voltage may change.
Examples of linear loads include incandescent lighting and electric heaters. The load for
constant-speed AC motors is almost linear, and the load current is a sine wave with very little
distortion because linear loads are relatively steady and don’t produce any new frequencies
(harmonics).
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 1/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Non-linear loads, however, cause harmonics because they draw current at frequencies other
than 60 Hz, in abrupt and uneven pulses. These non-sinusoidal distortions in the current and
voltage waveforms then layer themselves as multiple frequencies upon the fundamental
frequency. These multiple frequencies are called harmonics.
Offices have many sources of nonlinear loads that are harmonic generators, such as
computers, printers, copiers, and LED drivers for fluorescent lighting. Industrial sources of
nonlinear loads include uninterruptible power supplies, rectifiers, variable frequency/speed
drives for motors, programmable controllers, and fluorescent lighting.
ERAHS
The percent of non-linear loads in office buildings and industrial facilities has increased over
the last decade as incandescent lighting is replaced by fluorescent lighting, as more
computers and programmable controllers are connected to the electrical system, and as more
electric motors use variable frequency drives (VFDs). Harmonic disturbances can also be
transmitted from the network if you have an unfiltered power factor correction capacitor on
your incoming power.
Third harmonics are caused by power supplies in computers and electronic ballasts, and can
result in a neutral current greater than the phase currents.
The fifth and seventh harmonics produced by the three phase bridge rectifiers in the power
supplies of six-pulse VFDs create pulsating torques that can cause shaft vibrations, and
damage motor bearings and couplings.
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 2/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Higher harmonic distortions can also lead to the nuisance tripping of circuit breakers, the
overheating of cables and equipment, and the premature failure of electrical equipment.
Transformers can quickly overheat and fail after load changes due to replacing or adding
electrical equipment, installing VFDs, and upgrading electronic ballasts. Plant manufacturing
safety may be at risk.
IEEE standard 519 provides guidelines for acceptable values of total harmonic distortion
(THD). Its focus is on the point of common coupling. The standard also seeks to limit damage
to power factor correction (PFC) capacitors and harmonic filter systems from excessive
harmonics, and to prevent series or parallel resonance in the electrical system.
The goal is to limit the THD to less than 5% where an industrial power system is connected to
the utility network. If your THD values exceed the IEEE 519 values, it’s important to determine
whether harmonics are causing problems.
Harmonics and power factor are not directly related but taking action to cure power factor
could enhance the problem of harmonics. The power factor is the ratio (from -1 to +1) of the
ERAHS
actual power used by the load compared to the apparent power available in the circuit. A
change from unity or power factor of 1 to some other number leading or lagging means that
current is shifted relative to the voltage applied.
A power factor of 1 means that no current is lost or distorted. A power factor of 1 says that all
of the current is going into doing useful work. Any number less than 1 indicates that some of
the applied voltage goes into magnetic or other forms of energy that are not lost but when it is
given back it shifts the current. A low power factor means that you are not fully using the
electric power you are buying when your local utility charges a “power factor penalty” or bills
you for your kVA usage instead of your KW demand. This current is increased and causes
system losses and this is what the utility is trying to cover these losses with higher demand
charges or power factor penalties.
To understand the power factor, let’s look at a glass of beer. The glass represents the
apparent power, or kVA. The actual beer in your glass is the actual power or kW. Any foam at
the top of your glass is the reactive power, or kVAR. It doesn’t perform useful work, but is
used to maintain a magnetic flux in motors, for example.
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 3/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
The more foam you have, the less beer you have, but you still paid for a full glass. Similarly,
your utility company will charge you for the apparent power, which is the sum of the actual
power plus the reactive power.
A thorough energy audit by an electrical engineer can yield impressive paybacks on power
factor improvements. But without expert guidance, attempts to improve your power factor
may make your harmonics worse. Installing components like capacitors for power factor
correction may actually amplify the harmonic resonance voltage distortion. This can cause
high spikes of voltage at capacitor terminals and lead to their premature failure. The very
item installed to reduce power factor penalties (the capacitor) could self-destruct because the
harmonic currents are amplified by just the right system electrical conditions.
If you do not have more than 20% of your electrical load from harmonic generators and there
are no power factor correction capacitors, you should not have significant harmonic issues.
However, if non filtered power factor correction capacitors are installed on a system with
significant harmonic generators, Matrix can analyze the susceptibility of your facility’s
electrical power system to total harmonic distortion. We can also review the myriad utility
rates and determine if your costs are significantly impacted by a poor power factor.
ERAHS
Matrix Technologies is one of the largest independent process design, power systems
engineering, industrial automation engineering, and manufacturing operations management
companies in North America. To learn more about our electrical power system capabilities
and manufacturing process control solutions, contact Vince Trejchel, PE.
Tags: Vince Trejchel, PE / Harmonics / IEEE / Manufacturing Plant Safety / Power Engineering
/ Power Factor Correction / Power System
« Previous I Next »
Instrumentation
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 4/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Vince Trejchel, PE
> vltrejchel@matrixti.com Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 5/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Vince Trejchel is a Project Engineer in the Engineering Systems Division of Matrix Technologies. Vince (aka
Volt) is responsible for the successful design of electrical power projects. He has extensive background in a
variety of commercial, institutional and industrial power systems. He has experience in classroom
instruction and has a passion to preach electrical safety through awareness of NFPA 70E Electrical Safety in
the workplace. He joined Matrix in 2014.
Industry
Projects
Technology
ERAHS
Related Articles
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 6/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Contact Us
Office Locations
ERAHS
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 7/8
2/14/22, 12:45 PM Reducing Harmonics in Electrical Power Systems
Terms of Use
Privacy - Terms
https://matrixti.com/matrix-on-manufacturing/how-to-handle-harmonics-in-electrical-power-systems/ 8/8