APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -1 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -2 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -3 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -4 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set 2-Wire, ATCL, Nuovo Pignone, Puma LAN Baud Rate – Function Code 2
40.2 -> 1 Baud Rate 5787 bps ......................... 2-Wire, WCL
40.2 -> 2 Baud Rate 4800 bps ......................... 2-Wire, .. ATCL,.....Puma LAN
40.2 -> 3 Baud Rate 1200 bps ......................... .............. ATCL......
40.2 -> 4 Baud Rate 9600 bps ......................... 2-Wire, .. ATCL
40.2 -> 5 Baud Rate 19200 bps ....................... 2-Wire
40.2 -> 6 Baud Rate 2400 bps ......................... Nuovo Pignone
40.2 -> 7 Baud Rate 10 Mbps .......................... 2-wire TCP/IP
40.2 -> 8 Baud Rate 100 Mbps ........................ 2-wire TCP/IP
If Operation Mode: 2-Wire, ER3 Default -> 1
If Operation Mode: ATCL, Australia Two-Wire, Puma LAN Default -> 2
If Operation Mode: Nuovo Pignone Default -> 6
Set Volume Pulse Scale (Multi Wire Interface) – Function Code 6 (*) Level 4 Command
40.6 -> 100 100 Pulses / Liter Default -> 100
40.6 -> 50 50 Pulses / Liter
40.6 -> 10 10 Pulses / Liter
Set Amount Pulses (Multi Wire Interface) – Function Code 7 (*) Level 4 Command
40.7 -> 1 Amount Pulses enabled Default -> 1
40.7 -> 2 Amount Pulses disabled
Set Auto Authorization (Multi Wire Interface) – Function Code 8 Level 4 Command
40.8 -> 1 Auto Authorization enabled Default -> 1
40.8 -> 2 Auto Authorization disabled
Set start position of Pulse Channels (Multi Wire Interface) – Function Code 9 Level 4 Command
40.9 -> 1 Both Pulse Channels start with “low” Default -> 1
40.9 -> 2 Both Pulse Channels start with “high”
Set Pulse Format (Multi Wire Interface) – Function Code 10 (*) Level 4 Command
40.10 -> 1 Channel B lags channel A by 90°” Default -> 1
Set Keypad Preset with Remote Preset (Australia or Standard Two-Wire) – Function Code 13
40.13 -> 1 Keypad Preset Allowed with Remote Preset Default -> 1
40.13 -> 2 Keypad Preset NOT Allowed with Remote Preset
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -5 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Special EOT with 2-wire (CC24= 1) and Preset – Function Code 14
40.14 -> 1 EOT corporate 2-wire Default -> 1
40.14 -> 2 EOT with nozzle out (2-wire (CC24= 1) and Preset only)
40.14 -> 3 EOT with nozzle out (ER3 (CC24= 5) and 53.12 Maximum Fill Timeout reached)
Set Special parameter for SNIP & Fusion Master POS (Nuovo Pignone) – Function Code 17
40.17 -> 1 POS : SINP system
40.17 -> 2 POS : Fusion Master Default -> 2
Set Reported Volume Decimal Point Location (Standard Two-Wire)– Function Code 24
40.24 -> 1 Same as on the volume display
40.24 -> 2 3 Decimal figures: XXX.XXX Default -> 2
Set 2-Wire Reported VRC Error States in Transaction Data– Function Code 26
40.26 -> 1 Report VRC Error States in Transaction Data disabled Default -> 1
40.26 -> 2 Report VRC Error States in Transaction Data enabled
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -6 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Nozzle Changing Time between UHF Nozzle and Sat Nozzle per Side- Function Code 6 (new)
53.6.1 -> 0 Nozzle Changing Time Side 1 disabled Default -> 0
53.6.1 -> 15 Nozzle Changing Time Side 1 enabled (15…120 sec.)
53.6.2 -> 0 Nozzle Changing Time Side 2 disabled Default -> 0
53.6.2 -> 15 Nozzle Changing Time Side 2 enabled (15…120 sec.)
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -7 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -8 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Fuel Density (Vapour Recovery and ATC) – Command Code 75 (*)
75.1 -> 1 Grade 1 Unleaded 95 Fuel Type and density
75.2 -> 4 Grade 2 Unleaded 98 0 = Invalid (default)
75.3 -> 5 Grade 3 Diesel 1 = Gasoline - North America (730)
75.4 -> 7 Grade 4 E85 (Ethanol) 2 = Diesel - North America (840)
75.5 -> 6 Grade 5 Leaded 98 3 = Unleaded 90/92/95 – Europe (745)
75.6 -> 11 Grade 6 LPG 4 = Unleaded 98 – Europe (745)
Default -> 0 for all Grades 5 = Diesel – Europe (833)
6 = Leaded Substitute 98 – Europe (755)
Remark: 7 = E85 Ethanol – Europe (785)
Density of 1 means no compensation with ATC 8 = Lamp Oil – Europe (800)
Density of “k0E” means: 9 = Gas Oil – Europe (850)
Calculation with Formula 1 from PTB 10 = Uncompensated with VR (1)
V0 = VT*(1-kOE*ΔT) ΔT= T-15°C 11 = LPG – Europe *) (537)
E0…E20: kOE = 1,21*10-3 1/K 12 = Uncompensated without VR (1)
E80...E100: kOE = 1,14*10-3 1/K 13 = LPG – Belgium (510)
B0…B100 kOE = 0,84*10-3 1/K (Heizöl) 14 = LPG – UK (512)
B0…B100: kOE = 0,85*10-3 1/K (Diesel/Bio-DK) 15 = E85 Ethanol without VR– Europe (785)
Care Diesel: kOE = 0,89*10-3 1/K (Care Diesel) 16 = E0…E20 w. VR – Germany (k0E)
* Für eine einwandfreie Funktion der 17 = E80…E100 w. VR – Germany (k0E)
Temperaturkompensation muss das LPG in einem 18 = B0…B100 – Germany (k0E)
Verhältnis von 70/30 (Propan zu Butan) vorliegen! 19 = LPG – 50 / 50 (546)
Special Function for Coriolis Mass Meter (AdBlue-/ CNG) – Function Code 5
76.5 -> Initial Installation AdBlue (AdBlue-MassMeter) (CC97.x.x =8)
76.5 -> CNG 5kg fuelling for testing
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 -9 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 10 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
80.2.1 -> 40 Flow Rate Side 2 Grade 1 = 40 l/min or 40 GPM Default -> 40
80.2.2 -> 80 Flow Rate Side 2 Grade 2 = 80 l/min or 80 GPM Default -> 40
80.2.3 -> 40 Flow Rate Side 2 Grade 3 = 40 l/min or 40 GPM Default -> 40
80.2.4 -> 38 Flow Rate Side 2 Grade 4 = 38 l/min or 38 GPM Default -> 40
80.2.5 -> 40 Flow Rate Side 2 Grade 5 = 40 l/min or 40 GPM Default -> 40
80.2.6 -> 40 Flow Rate Side 2 Grade 6 = 40 l/min or 40 GPM Default -> 40
Set Not prepay delivery duration expressed in dozen of sec. Only new Passport– Function Code 14
82.14 -> 0 Prepay delivery duration (0-250 sec.) 1 10 Seconds Default -> 0
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 11 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Min. delivered milliliters number to change the nozzle – Function Code 17
82.17 -> 100 delivered ml number to change the nozzle (1-250 ml) Default -> 100
Set Max. number of times the same nozzle can be pulled out in a prepay case – Function Code 18
82.18 -> 3 Max. number of times the same nozzle can be pulled out in a prepay case (2 - 9)
Default -> 3
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 12 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 13 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Volume Decimal Point Position For Display – Function Code 2 (*)
85.2 -> 1 XXXXXX
85.2 -> 2 XXXXX.X
85.2 -> 3 XXXX.XX Default -> 3
85.2 -> 4 XXX.XXX
Set PPU Decimal Point Position For Calculations – Function Code 3 (*)
85.3 -> 1 XXXX
85.3 -> 2 XXX.X
85.3 -> 3 XX.XX
85.3 -> 4 X.XXX Default -> 4
Set PPU Decimal Point Position For Display – Function Code 4 (*)
85.4 -> 1 XXXX
85.4 -> 2 XXX.X
85.4 -> 3 XX.XX
85.4 -> 4 X.XXX Default -> 4
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 14 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Leak Test Time Car – Function Code 2 (Only Active if CC 89.47 is enable)
89.2 -> 16 Leak Test Time Car *0.5 (1…99) value in *0,5 sec Default -> 5
Leak Test Time Bus – Function Code 3 (Only Active if CC 89.47 is enable)
89.3 -> 16 Leak Test Time Bus *0.5 (1…99) value in *0,5 sec Default -> 5
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 15 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Min Flow Rate to Stop Filling on High Bank Car – Function Code 20
89.20 -> 12 Min Flow Rate to Stop Filling on High Bank Car Default -> 12
(1…100) value in 0,1 kg/min
Min Flow Rate to Stop Filling on High Bank Bus – Function Code 21
89.21 -> 24 Min Flow Rate to Stop Filling on High Bank Bus Default -> 24
(1…100) value in 0,1 kg/min
Correction Factor for the Calculation of Max Mass Car – Function Code 22
89.22 -> 85 Correction Factor for the Calculation of Default -> 85
Max Mass Car (1…130)
Correction Factor for the Calculation of Max Mass Bus – Function Code 23
89.23 -> 85 Correction Factor for the Calculation of Default -> 85
Max Mass Bus (1…130)
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 16 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Leak Test Pressure Loss Car – Function Code 30 (Only Active if CC 89.47 is enable)
89.30 -> 10 Leak Test Pressure Loss Car Default -> 10
(1…50) value in *0,1 bar
Leak Test Pressure Loss Bus – Function Code 31 (Only Active if CC 89.47 is enable)
89.31 -> 10 Leak Test Pressure Loss Bus Default -> 10
(1…50) value in *0,1 bar
Transition level between mass and pressure filling procedure Car – Function Code 39
89.39 -> 0 from the beginning pressure controlled
89.39 -> xx% start with mass controlled filling and after xx% Default ->50 ??
Change to pressure controlled filling (0…80)
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 17 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Transition level between mass and pressure filling procedure Bus – Function Code 40
89.40 -> 0 from the beginning pressure controlled
89.40 -> xx% start with mass controlled filling and after xx% Default ->50 ??
Change to pressure controlled filling (0…80)
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 18 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 19 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
12 34
5 6 654321 1 2 3 4 1 2 3 4
90 -> 1 Grade 1 Default -> 1
90 -> 2 Grade 1, 2
90 -> 3 Grade 1, 2, 3
90 -> 4 Grade 1, 2, 3, 4
90 -> 27 Grade 1 and/or 1, 2 (120N40S)* .......................................................... * see CC91.17
90 -> 28 Grade 1, 2, 3, 5, 6
90 -> 29 Grade 1, 2, 3, 4, 5, 6
90 -> 30 Grade 1, 2 VK Button Select
90 -> 31 Grade 1, 2 VK Button Select ........+ Grade 3 DK
90 -> 32 Grade 1, 2, 3 VK Button Select
90 -> 33 Grade 1, 2, 3 VK Button Select ....+ Grade 4 DK
90 -> 34 Grade 1, 2 VK Button Select ........+ Grade 3,4 DK
90 -> 35 Grade 1, 2 (120N40S) ...................................... + Grade 5 (AdBlue) * see CC91.17
90 -> 36 Grade 1, 2 (120N40S)*.................+ Grade 3 ................................ * see CC91.17
90 -> 37 Grade 1, 2 (120N40)* ...................+ Grade 3, 4 ................................ * see CC91.17
90 -> 38 Grade 1, 2 (120N40S)*.................+ Grade 3 + Grade 5 (AdBlue) * see CC91.17
90 -> 39 Grade 1, 2 (120N40)* ...................+ Grade 3, 4 + Grade 5 (AdBlue) * see CC91.17
90 -> 41 Grade 1 ............................................................ + Grade 5 (LPG, AdBlue)
90 -> 42 Grade 1, 2 ........................................................ + Grade 5 (LPG, AdBlue)
90 -> 43 Grade 1, 2, 3 .................................................... + Grade 5 (LPG, AdBlue)
90 -> 44 Grade 1, 2, 3, 4 ................................................ + Grade 5 (LPG, AdBlue)
90 -> 51 Grade 1 ............................................................ + Grade 5 and/or 5, 6 (120N40S)
90 -> 52 Grade 1, 2 ........................................................ + Grade 5 and/or 5, 6 (120N40S)
90 -> 53 Grade 1, 2, 3 .................................................... + Grade 5 and/or 5, 6 (120N40S)
90 -> 54 Grade 1, 2, 3, 4 ................................................ + Grade 5 and/or 5, 6 (120N40S)
90 -> 62 2+1 (blender + super-Hi) ................................. (Not used in EU)
90 -> 63 3+1 (blender + Super-Hi) ................................. (Not used in EU)
90 -> 64 2+2 (blender + Super-Hi Low and High Speed) (Not used in EU)
90 -> 65 3+2 (blender + Super-Hi Low and High Speed) (Not used in EU)
90 -> 70 Hybrid Blenders ............................................... (Not used in EU)
90 -> 71 Hybrid Blenders ............................................... (Not used in EU)
90 -> 72 Three Meter Blenders....................................... (Not used in EU)
90 -> 72 Three Meter Blenders....................................... (Not used in EU)
90 -> 77 Grade 1 and/or 1, 2 (120N40S) ........................ + Grade 5 and/or 5, 6 (120N40S)
90 -> 78 Grade 1 and/or 1, 2 (120N40S) + Grade 3 ... + Grade 5 and/or 5, 6 (120N40S)
90 -> 79 Grade 1 and/or 1, 2 (120N40S) + Grade 3, 4 + Grade 5 and/or 5, 6 (120N40S)
90 -> 80 Each Side: 1 Grade (397_G)
90 -> 81 Each Side: 1 Grade (397_G) ........................... Grade 1 (120N40S), Grade 2 (40S)
90 -> 82 Grade 1 AdBlue, Grade 2 UHF ........................ Grade 1 (AdBlue), Grade 2 (120N40S)
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 20 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 21 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set UHF Unit Type for CC90 = 27, 35, 36, 37, 38, 39 – Function Code 17 (*)
91.17 -> 1 120N40S Default -> 1
91.17 -> 2 120N40
91.17 -> 3 120S
91.17 -> 4 120
Set tank low level presence (AAB-Board necessary) – Function Code 21 (*)
91.21 -> 1 Set tank low level presence not installed Default -> 1
91.21 -> 2 Set tank low level presence installed with local handling
91.21 -> 3 Set tank low level presence installed with remote handling
Set Kiosk Switched Stand Alone Mode (AAB-Board necessary) – Function Code 22 (*)
91.22 -> 1 Kiosk Switched Stand Alone Mode not present Default -> 1
91.22 -> 2 Kiosk Switched Stand Alone Mode present
Set ATC Probes for LPG (CC90 = 1, 2, 3, 4, 41, 42, 43, 44, 51, 52 and 53) – Function Code 25 (*)
91.25 > 1 1 ATC Probe per Hydraulic Default -> 1
91.25 -> 2 2 ATC Probes per Hydraulic (probes per meter).
91.25 -> 3 ATC Probe for Australia
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 22 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Set Nozzle Select for AdBlue for Selected Grade – Function Code 35 (*)
91.35 -> x Set Nozzle Select for AdBlue for Selected Grade Default -> 0
x = Grade;
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 23 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 24 -
SK700 II - Parameter
Software Release ” A030203”
(English) D-33154 Salzkotten
Remark
(*) Before changing CC or FC or Value of a Parameter the Security Switch needs to be opened
(**) ECAL Switch needs to be opened
(***) It’s only possible to set CC95 once with open Security Switch.
For a new setting a hardware coldstart (CC95 is set to 000) is required.
APOLLO_DRAFT_30.2.03_ENGLISCH.DOC 24.11.2010 - 25 -