You are on page 1of 396

KALSELTENG-2 COAL FIRED STEAM POWER PROJECT

DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

TABLE OF CONTENTS

1.0 GENERAL PAGE


1.1 Design Basis --------------------------------------------4
1.2 Design Code & Reference --------------------------------------------4
1.3 Material Properties --------------------------------------------4
1.4 Load Combinations --------------------------------------------5
1.5 Pile Data --------------------------------------------5
1.6 Spring Constant of Pile --------------------------------------------7

2.0 GENERAL SKETCH


2.1 General Layout 12
--------------------------------------------

3.0 DESIGN DATA


3.1 Application Load 20
--------------------------------------------
3.2 Load Application 34
--------------------------------------------
3.3 Load Combination 51
--------------------------------------------
3.4 Subgrade Reactions Modulus 53
--------------------------------------------

4.0 MODELING
4.1 Modeling Birds-eye View 54
--------------------------------------------

5.0 PILE STABILITY CHECK - PA & FD FAN Foundation


5.1 Pile Spring Joint Modal Data 56
--------------------------------------------
58
5.2 Pile Compression Capacity Check (P.A FAN TYPE-1) --------------------------------------------
5.3 Pile Lateral Capacity Check (P.A FAN TYPE-1) 60
--------------------------------------------
5.4 Pile Tension Capacity Check (P.A FAN TYPE-1) 62
--------------------------------------------
64
5.5 Pile Compression Capacity Check (P.A FAN TYPE-2) --------------------------------------------
5.6 Pile Lateral Capacity Check (P.A FAN TYPE-2) 66
--------------------------------------------
5.7 Pile Tension Capacity Check (P.A FAN TYPE-2) 68
--------------------------------------------
70
5.8 Pile Compression Capacity Check (F.D FAN TYPE-1) --------------------------------------------
5.9 Pile Lateral Capacity Check (F.D FAN TYPE-1) 72
--------------------------------------------
5.10 Pile Tension Capacity Check (F.D FAN TYPE-1) 74
--------------------------------------------
5.11 Pile Compression Capacity Check (F.D FAN TYPE-2) 76
--------------------------------------------
5.12 Pile Lateral Capacity Check (F.D FAN TYPE-2) 78
--------------------------------------------
5.13 Pile Tension Capacity Check (F.D FAN TYPE-2) 80
--------------------------------------------
5.14 Pile Punching Shear Check 82
--------------------------------------------

6.0 PILE STABILITY CHECK - Duct Support Foundation


6.1 Pile Spring Joint Modal Data 86
--------------------------------------------
6.2 Pile Compression Capacity Check 88
--------------------------------------------
6.3 Pile Lateral Capacity Check 90
--------------------------------------------
6.4 Pile Tension Capacity Check 92
--------------------------------------------
6.5 Pile Punching Shear Check 94
--------------------------------------------

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 FOUNDATION DESIGN


7.1 General Sketch 95
-----------------------------------------
7.2 Calculation Summary 97
-----------------------------------------
7.3 Moment & Shear Contour For USD Design 98
-----------------------------------------
7.4 Moment Contour For ASD Design 113
-----------------------------------------
7.5 Flexure & Shear Check (P.A FAN FDN-1) 123
-----------------------------------------
7.6 Flexure & Shear Check (P.A FAN FDN-2) 127
-----------------------------------------
7.7 Flexure & Shear Check (F.D FAN FDN-1) 131
-----------------------------------------
7.7 Flexure & Shear Check (F.D FAN FDN-2) 135
-----------------------------------------
7.9 Flexure & Shear Check ( Duct support & Platform , PILE FDN ) 139
-----------------------------------------
7.10 Bottom Slab Punching Shear Check 143
-----------------------------------------
7.11 Re-Bar Sketck 158
-----------------------------------------

8.0 PEDESTAL DESIGN


8.1 General 161
--------------------------------------------
8.2 Section Calculation 163
--------------------------------------------
8.3 Ductile Design for Anchor bolt 208
--------------------------------------------

# ATTACHMENT

#1. EQUIPMENT VENDOR DATA

#2. Foundation Check for Vibration Machinery (P.A FAN)

#3. Foundation Check for Vibration Machinery (F.D FAN)

#4. RECOMMENDED PARMETER OF SOIL

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.0 GENERAL

1.1 Design Basis

This calculation is intended to design for Other Foundation(PA, FD, ETC) nearby Boiler
foundation which is performed in accordance with ACI ultimate strength design method
and meets the requirements of standards and regulations.

1.2 Design Code & Reference

1) ACI 318-14 : Building Code Requirements for Structural Concrete


2) ASCE 7-10 : Minimum Design Loads for Buildings and other Structures
3) IKCP0-YYZ-C-04-0001 : Design Criteria for Civil & Building

1.3 Material Properties

1) Concrete
Strength at 28 days (f'c) = 30 Mpa
Modulus of elasticity (Ec) = 25,740 Mpa
Unit weight (γc) = 25 kN/m³

2) Reinforcing bar
Modulus of elasticity (Es) = 200,000 Mpa
Minimum yield strength (fy) = 390 Mpa

3) Soil
Unit weight of backfilled soil on slab(γs) = 19.0 kN/m³
Submerged weight of backfilled soil(γsub) = 9.0 kN/m³
Internal friction angle(° ) = 30.0 Deg.
Coeff. of lateral at rest pressure = 0.5 = 1 - sin30

DOCUMENT No. : IKCP0-UHA-C-06-0002


-4-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.4 Load Combinations

The load combinations are prepared considering Technical Project Specification, ASCE 7-10.
Allowable Stress Design (ASD) shall be applied for Soil bearing check
Ultimate Strength Design (USD) shall be applied for the strength design of concrete structures.

Design
Load Combination Reference
Method
1) D + F
2) D + H + F + L + T
3) D + H + F + Lr
4) D + H + F + 0.75(L+T) + 0.75Lr
ASD 5) D + H + F + (0.6W or 0.7E) 1)~9) ASCE 7-10
6) D + H + F + 0.75(0.6W) + 0.75L + 0.75Lr
7) D + H + F + 0.75(0.7E) + 0.75L
8) 0.6D + 0.6W + H
9) 0.6D + 0.7E + H
1) 1.4(D + F)
2) 1.2(D + F + T) + 1.6(L + H) + 0.5Lr
3) 1.2(D + F) + 1.6H + 1.6Lr + (L or 0.5W)
USD 4) 1.2(D + F) + 1.6H +1.0W + L + 0.5Lr 1)~7) ASCE 7-10
5) 1.2(D + F) + 1.6H + 1.0E + L
6) 0.9D + 1.0W + 1.6H
7) 0.9(D + F) + 1.0E + 1.6H
Where: (Basic Load Cases)
D: Dead Load
L: Live Load
Lr : Roof live Load
H: Lateral soil pressure or ground water pressure
F: Fluids with well-defined pressures and maximum heights
T: Thermal Load
W: Wind Load
E: Seismic Load

1.5 Pile Data

1) Properties
· Type = P.C PILE (Φ600) and P.C PILE (Φ600)
· Pile Length = 22.6 m

2) Allowable Bearing Capacity (Refer to IKCP0-YYZ-C-07-0002)

- Summary on axial behavior of pile (Refer to IKCP0-YYZ-C-07-0002, Table 5.1)


Minimum Design Pile Capacity
Pile tip from Allowable Structural
Dia.
platform Bearing Capacity
Capacity Normal Temporary

mm m kN kN kN kN
400 17~24 701 1168 700 1168
600 18~24 1409 2405 1350 2405

DOCUMENT No. : IKCP0-UHA-C-06-0002


-5-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

- Summary on uplift behavior of pile (Refer to IKCP0-YYZ-C-07-0002, Table 5.2)


Minimum Design Pile Capacity
Pile tip from Allowable Structural
Dia.
platform Bearing Capacity
Capacity Normal Temporary

mm m kN kN kN kN
400 17~24 282 352 200 352
600 18~24 491 691 400 691

- Summary of Analysis Result for Pile Groups

Lateral Resistance (kN)


Dia. Cut-Off
(mm) Elevation (m)
s/D=3.0 s/D=4.0 s/D=5.0

EL. -2.0m 45.0 47.0 48.0


400 EL. -3.5m 45.0 47.0 48.0
EL. -5.0m 37.0 39.0 39.0
EL. -2.0m 104.0 107.0 109.0
600 EL. -3.5m 100.0 104.0 107.0
EL. -5.0m 82.0 84.0 85.0

- Summary of Analysis Result for Pile Groups in Temporary Condition

Lateral Resistance (kN)


Dia. Cut-Off
(mm) Elevation (m)
s/D=3.0 s/D=4.0 s/D=5.0

EL. -2.0m 52.0 53.0 55.0


400 EL. -3.5m 52.0 53.0 54.0
EL. -5.0m 42.0 42.0 42.0
EL. -2.0m 118.0 122.0 124.0
600 EL. -3.5m 117.0 121.0 123.0
EL. -5.0m 88.0 88.0 88.0

- PA & FD FAN Foundation


Design Capacity
Pile (Φ600) Remark
Normal Temporary
Compression 1350 kN/pile 2405 kN/pile
Lateral (s/D=5.0) 107 kN/pile 123 kN/pile
Uplift 400 kN/pile 691 kN/pile
* These allowable pile capacity values were verified by pile tests

- Duct Support Foundation


Design Capacity
Pile (Φ600) Remark
Normal Temporary
Compression 1350 kN/pile 2405 kN/pile
Lateral (s/D=5.0) 107 kN/pile 123 kN/pile
Uplift 400 kN/pile 691 kN/pile
* These allowable pile capacity values were verified by pile tests

DOCUMENT No. : IKCP0-UHA-C-06-0002


-6-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.6 Spring Constant of Pile

1.6.1 Normal Condition (Φ600) - For PA & FD FAN Foundation

1) Vertical Spring Constant

Ap x Ep 0.16 m² x 32900 Mpa


kv = α = 1.247 x = 285220 kN/m
L 22.60 m

Where, α : Proportional coefficient = 0.014 ( L / D ) + 0.72 = 0.014 x ( 22.60 m / 0.60 m ) + 0.72


= 1.2473
Ap : Pile cross-sectional area = 157079.63 mm2 = 0.15708 m2
Ep : Pile elastic modulus = 32900 Mpa
L : Length of pile = 22.60 m
D : Diameter of pile = 600 mm = 0.600 m

2) Horizontal Spring Coefficient of Pile

-3/4
BH -3/4 1.235 m
kH = k H0 = 50000 kN/m³ x ( ) = 17300.5 kN/m³
0.3 0.3

Where, α : A correction factor used for estimating KH


1, The Ground at peripheral faces is severely disturbed by immersion
or if contact grouting is impossible for environmental preservation
or other reasons
( Usual 1.0 )
kH0 : Coefficient of horizontal ground reaction derived from follow equation,
1 1
kH0 = · α · E0 = x 1.0 x 15000 = 50000 kN/m³
0.3 0.3
E0 = ( 2.54m x 15 Mpa ) / 2.54m = 15000 kN/m2
(Refet ot Attachment # 5)
BH : Equivalent loading width of foundation
D 0.6 m
BH = = = 1.235 m
β 0.39338 m ⎯¹
β : Characteristic value of foundation,
4 kH x D
β = = 0.39338 m ⎯¹ (Assumed) --ⓐ
4Ep x Ip
β = 0.39338 m-1 = ⓐ -- O.K.
I : Pile moment of inertia = 3293763548 mm4 = 0.00329 m4
2
Ep · I : Bending rigidity of pile = 108365 kN·m

Radial Spring Constant of Pile (K)

Radial Force, K1 = 4 · EP · I · β3
= 4 x 108365 kN·m^2 x ( 0.393 m^-1 )^3 = 26387.25 kN/m
Radial Force, K2 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.39338 m^-1 )^2 = 33538.92 kN/rad
Radial Bending Moment,
K3 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.39338 m^-1 )^2 = 33538.92 kN·m/m
Radial Bending Moment,
K4 = 2 · EP · I · β
= 2 x 108365 kN·m^2 x ( 0.39338 m^-1 ) = 85257.79 kN·m/rad

DOCUMENT No. : IKCP0-UHA-C-06-0002


-7-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.6.2 Seismic Condition (Φ600) - For PA & FD FAN Foundation

1) Vertical Spring Constant

Ap x Ep 0.16 m² x 32900 Mpa


kv = α = 1.247 x = 285220 kN/m
L 22.60 m

Where, α : Proportional coefficient = 0.014 ( L / D ) + 0.72 = 0.014 x ( 22.60 m / 0.60 m ) + 0.72


= 1.2473
Ap : Pile cross-sectional area = 157079.63 mm2 = 0.15708 m2
Ep : Pile elastic modulus = 32900 Mpa
L : Length of pile = 22.60 m
D : Diameter of pile = 600.00 mm = 0.600 m

2) Horizontal Spring Coefficient of Pile

BH -3/4 1.122 m -3/4


kH = k H0 = 100000 kN/m³ x ( ) = 37173.5 kN/m³
0.3 0.3

Where, α : A correction factor used for estimating KH


1, The Ground at peripheral faces is severely disturbed by immersion
or if contact grouting is impossible for environmental preservation
or other reasons
( Usual 2.0 )
kH0 : Coefficient of horizontal ground reaction derived from follow equation,
1 1
kH0 = · α · E0 = x 2.0 x 15000 = 100000 kN/m³
0.3 0.3
E0 = ( 2.10m x 15 Mpa ) / 2.10m = 15000 kN/m2
(Refet ot Attachment # 5)
BH : Equivalent loading width of foundation
D 0.6 m
BH = = = 1.122 m
β 0.47628 m ⎯¹
β : Characteristic value of foundation,
4 kH x D
β = = 0.47628 m ⎯¹ (Assumed) --ⓐ
4Ep x Ip
β = 0.47628 m-1 = ⓐ -- O.K.
I : Pile moment of inertia = 3293763548 mm4 = 0.00329 m4
2
Ep · I : Bending rigidity of pile = 108365 kN·m

Radial Spring Constant of Pile (K)

Radial Force, K1 = 4 · EP · I · β3
= 4 x 108365 kN·m^2 x ( 0.476 m^-1 )^3 = 46830.13 kN/m
Radial Force, K2 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.47628 m^-1 )^2 = 49162.8 kN/rad
Radial Bending Moment,
K3 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.47628 m^-1 )^2 = 49162.8 kN·m/m
Radial Bending Moment,
K4 = 2 · EP · I · β
= 2 x 108365 kN·m^2 x ( 0.47628 m^-1 ) = 103223.3 kN·m/rad

DOCUMENT No. : IKCP0-UHA-C-06-0002


-8-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.6.3 Normal Condition (Φ600) - For Duct Support

1) Vertical Spring Constant

Ap x Ep 0.16 m² x 32900 Mpa


kv = α = 1.247 x = 285220 kN/m
L 22.60 m

Where, α : Proportional coefficient = 0.014 ( L / D ) + 0.72 = 0.014 x ( 22.40 m / 0.60 m ) + 0.72


= 1.2427
Ap : Pile cross-sectional area = 157079.63 mm2 = 0.15708 m2
Ep : Pile elastic modulus = 32900 Mpa
L : Length of pile = 22.40 m
D : Diameter of pile = 600 mm = 0.600 m

2) Horizontal Spring Coefficient of Pile

-3/4
BH -3/4 0.999 m
kH = k H0 = 50000 kN/m³ x ( ) = 20279.9 kN/m³
0.3 0.3

Where, α : A correction factor used for estimating KH


1, The Ground at peripheral faces is severely disturbed by immersion
or if contact grouting is impossible for environmental preservation
or other reasons
( Usual 1.0 )
kH0 : Coefficient of horizontal ground reaction derived from follow equation,
1 1
kH0 = · α · E0 = x 1.0 x 15000 = 50000 kN/m³
0.3 0.3
E0 = ( 1.66m x 15 Mpa ) / 1.66m = 15000 kN/m2
(Refet ot Attachment # 5)
BH : Equivalent loading width of foundation
D 0.6 m
BH = = = 0.999 m
β 0.60094 m ⎯¹
β : Characteristic value of foundation,
4 kH x D
β = = 0.60094 m ⎯¹ (Assumed) --ⓐ
4Ep x Ip
β = 0.60094 m-1 = ⓐ -- O.K.
I : Pile moment of inertia = 708986745 mm4 = 0.00071 m4
2
Ep · I : Bending rigidity of pile = 23325.7 kN·m

Radial Spring Constant of Pile (K)

Radial Force, K1 = 4 · EP · I · β3
= 4 x 108365 kN·m^2 x ( 0.601 m^-1 )^3 = 20248.17 kN/m
Radial Force, K2 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.60094 m^-1 )^2 = 16847.11 kN/rad
Radial Bending Moment,
K3 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.60094 m^-1 )^2 = 16847.11 kN·m/m
Radial Bending Moment,
K4 = 2 · EP · I · β
= 2 x 108365 kN·m^2 x ( 0.60094 m^-1 ) = 28034.65 kN·m/rad

DOCUMENT No. : IKCP0-UHA-C-06-0002


-9-
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.6.4 Seismic Condition (Φ600) - For Duct Support

1) Vertical Spring Constant

Ap x Ep 0.16 m² x 32900 Mpa


kv = α = 1.247 x = 287766 kN/m
L 22.60 m

Where, α : Proportional coefficient = 0.014 ( L / D ) + 0.72 = 0.014 x ( 22.40 m / 0.60 m ) + 0.72


= 1.2427
Ap : Pile cross-sectional area = 157079.63 mm2 = 0.15708 m2
Ep : Pile elastic modulus = 32900 Mpa
L : Length of pile = 22.40 m
D : Diameter of pile = 600.00 mm = 0.600 m

2) Horizontal Spring Coefficient of Pile

BH -3/4 0.908 m -3/4


kH = k H0 = 100000 kN/m³ x ( ) = 43575.0 kN/m³
0.3 0.3

Where, α : A correction factor used for estimating KH


1, The Ground at peripheral faces is severely disturbed by immersion
or if contact grouting is impossible for environmental preservation
or other reasons
( Usual 2.0 )
kH0 : Coefficient of horizontal ground reaction derived from follow equation,
1 1
kH0 = · α · E0 = x 2.0 x 15000 = 100000 kN/m³
0.3 0.3
E0 = ( 1.37m x 15 Mpa ) / 1.37m = 15000 kN/m2
(Refet ot Attachment # 5)
BH : Equivalent loading width of foundation
D 0.6 m
BH = = = 0.908 m
β 0.72757 m ⎯¹
β : Characteristic value of foundation,
4 kH x D
β = = 0.72757 m ⎯¹ (Assumed) --ⓐ
4Ep x Ip
β = 0.72757 m-1 = ⓐ -- O.K.
I : Pile moment of inertia = 708986745 mm4 = 0.00329 m4
2
Ep · I : Bending rigidity of pile = 23325.7 kN·m

Radial Spring Constant of Pile (K)

Radial Force, K1 = 4 · EP · I · β3
= 4 x 108365 kN·m^2 x ( 0.728 m^-1 )^3 = 35934.77 kN/m
Radial Force, K2 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.72757 m^-1 )^2 = 24695.14 kN/rad
Radial Bending Moment,
K3 = 2 · EP · I · β2
= 2 x 108365 kN·m^2 x ( 0.72757 m^-1 )^2 = 24695.14 kN·m/m
Radial Bending Moment,
K4 = 2 · EP · I · β
= 2 x 108365 kN·m^2 x ( 0.72757 m^-1 ) = 33942.05 kN·m/rad

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 10 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.6.5 Application SAP2000 Model

[SIGN CONVENTION]

1) Normal Condition(Φ600) for PA & FD FAN Foundation

UX UY UZ RX RY RZ
UX 26387.25 -33538.92
UY 26387.25 33538.92
UZ 285219.54
RX 33538.92 85257.79
RY -33538.92 85257.79
RZ

2) Seismic Condition(Φ600) for PA & FD FAN Foundation

UX UY UZ RX RY RZ
UX 46830.13 -49162.8
UY 46830.13 49162.80
UZ 285219.54
RX 49162.80 103223.32
RY -49162.8 103223.32
RZ

3) Normal Condition(Φ600) for Duct Support

UX UY UZ RX RY RZ
UX 20248.17 -16847.11
UY 20248.17 16847.11
UZ 285219.54
RX 16847.11 28034.65
RY -16847.11 28034.65
RZ

4) Seismic Condition(Φ600) for Duct Support

UX UY UZ RX RY RZ
UX 35934.77 -24695.14
UY 35934.77 24695.14
UZ 287766.14
RX 24695.14 33942.05
RY -24695.14 33942.05
RZ
Spring constant input mode for program SAP2000
Upper Stiffness Matrix - GLOBAL Coodinate System

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 11 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2.0 GENERAL SKETCH

2.1 General Layout

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 12 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 13 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 14 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 15 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 16 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 17 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 18 -
MIRFA INDEPENDENT WATER AND POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 19 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.0 DESIGN DATA

3.1 Application Load

The applied load for foundation modeling is obtained from vendor data.
(Refer to attachment.#1 "Equipment Vendor Data")

1) Loading Location Plan

PA-H
B05 B03 B01
PA-H
PA-G PA-F

PA-G PA-F PA-Bb PA-Ba PA-A


PA-Bb PA-Ba PA-A PA-E PA-D

PA-E PA-D B02


B06 B04

PA FAN-1 PA FAN-2

C05 C03 C01

FD-E FD-D

FD-C FD-B FD-A


FD-F FD-E
FD-G FD-F
FD-A FD-B FD-C

FD-D FD-G C06 C04 C02

FD FAN-1 FD FAN-2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 20 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Duct-1

PA07 PA03
Plaform-1

PA08 PA04 A05 A01

Duct-2

SA05 SA01
Plaform-1

Duct-3
SA06 SA02 A06 A02

SA09

SA10

Duct support fdn Plaform fdn

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 21 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1) Dead Load (D)

(1) Structure Weight


- Structure weight applied by self weight option in SAP2000 program.

(2) Surcharge Load


Ws1 = γs · h1 + γc · h2
= 19.0 × 0.10 + 25.0 × 0.20 = 6.90 kN/㎡

(3) Dead Load for Equipment

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 20.60 0.00 -79.80 SA01 39.40 0.00 -91.30
PA04 20.40 0.00 -76.50 SA02 38.60 0.00 -98.10
PA07 -20.60 -0.20 -66.50 SA05 -39.50 0.50 -90.00
PA08 -20.40 0.00 -62.80 SA06 -38.60 1.70 -99.40
SA09 0.00 9.80 -31.50
SA10 0.00 -9.80 -20.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.20 0.50 -7.10 A05 -0.30 0.60 -7.70
A02 0.30 -0.20 -12.40 A06 -0.30 -0.60 -8.20

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA-A 0.00 0.00 -72.00 PA-E 0.00 0.00 -28.50
PA-Ba 0.00 0.00 -19.50 PA-F 0.00 0.00 -25.50
PA-Bb 0.00 0.00 -19.50 PA-G 0.00 0.00 -9.50
PA-D 0.00 0.00 -34.50 PA-H 0.00 0.00 -4.40

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 -0.10 2.70 -67.70 B04 0.30 -3.50 -140.60
B02 -0.10 -2.50 -67.90 B05 -0.60 2.00 -91.50
B03 0.40 2.50 -152.20 B06 0.00 -1.20 -73.00

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
FD-A 0.00 0.00 -30.00 FD-E 0.00 0.00 -10.00
FD-B 0.00 0.00 -13.00 FD-F 0.00 0.00 -10.50
FD-C 0.00 0.00 -19.50 FD-G 0.00 0.00 -9.50
FD-D 0.00 0.00 -12.00 FD-H 0.00 0.00 -3.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 22 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 -0.10 1.80 -44.10 C04 0.30 -2.10 -97.90
C02 -0.10 -1.40 -42.90 C05 -0.20 1.10 -70.10
C03 0.30 1.40 -95.90 C06 -0.20 -0.80 -69.30

2) Live Load (L)

(1) Live Load for Boiler Area (Refer to Design Criteria for Civil & Building Chapter 2.3)
☞ Ground concrete floor (S.O.G) : 10.0kN/m2

(2) Live Load


A) FDF / PAF OUTLET AIR DUCT SUPPORT
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 1.00 0.00 -1.00 SA01 0.00 -6.00 8.00
PA04 0.00 0.00 0.00 SA02 0.00 -7.00 -1.00
PA07 -1.00 -1.00 -43.00 SA05 0.00 -4.00 9.00
PA08 0.00 0.00 0.00 SA06 0.00 -18.00 4.00
SA09 0.00 -7.00 5.00
SA10 0.00 -6.00 -5.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.60 1.40 -19.80 A05 -0.60 2.00 -22.10
A02 0.90 -0.90 -36.40 A06 -0.80 -2.00 -23.50

C) PA FAN (Dynamic load)


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA-A 0.00 0.00 -72.00 PA-Bb 0.00 0.00 -10.50
PA-Ba 0.00 0.00 -10.50 - - - -

D) FD FAN (Dynamic load)


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
FD-A 0.00 0.00 -30.00 FD-C 0.00 0.00 -10.50
FD-B 0.00 0.00 -8.50 - - - -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 23 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) Wind Load (W)

(1) W(+X)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 9.00 0.00 -13.00 SA01 0.00 0.00 0.00
PA04 -1.00 0.00 1.00 SA02 0.00 0.00 0.00
PA07 17.00 0.00 12.00 SA05 0.00 0.00 -1.00
PA08 -1.00 0.00 -1.00 SA06 0.00 1.00 -3.00
SA09 0.00 4.00 -5.00
SA10 0.00 -4.00 -33.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 1.60 0.00 -2.80 A05 1.60 0.00 2.80
A02 2.30 0.00 -4.00 A06 2.30 0.00 4.00

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 4.00 0.00 0.00 0.00 4.00 0.00
PA-Ba 1.00 0.00 0.00 0.00 1.00 0.00
PA-Bb 1.00 0.00 0.00 0.00 1.00 0.00
PA-D 5.00 0.00 12.00 0.00 0.00 0.00
PA-E 5.00 0.00 12.00 0.00 0.00 0.00
PA-F 5.00 0.00 12.00 0.00 0.00 0.00
PA-G 5.00 0.00 10.00 0.00 0.00 0.00
PA-H 1.00 0.00 0.00 0.00 1.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 0.00 -0.10 B04 0.00 -0.10 -17.60
B02 0.00 0.00 0.00 B05 9.50 0.10 17.50
B03 0.00 0.00 -17.40 B06 9.60 0.00 17.70

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 3.00 0.00 0.00 0.00 3.00 0.00
FD-B 1.00 0.00 0.00 0.00 1.00 0.00
FD-C 1.00 0.00 0.00 0.00 1.00 0.00
FD-D 5.00 0.00 -10.00 0.00 0.00 0.00
FD-E 5.00 0.00 10.00 0.00 0.00 0.00
FD-F 5.00 0.00 10.00 0.00 0.00 0.00
FD-G 5.00 0.00 10.00 0.00 0.00 0.00
FD-H 1.00 0.00 0.00 0.00 1.00 0.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 24 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 0.00 0.00 -0.10 C04 0.00 -0.10 -11.70
C02 0.00 0.00 0.00 C05 8.80 0.00 11.70
C03 0.00 0.00 -11.60 C06 8.80 0.00 11.70

(2) W(-X)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 -39.00 0.00 59.00 SA01 24.00 0.00 -24.00
PA04 -12.00 0.00 18.00 SA02 42.00 0.00 -41.00
PA07 -48.00 0.00 -58.00 SA05 24.00 0.00 24.00
PA08 -12.00 0.00 -18.00 SA06 44.00 1.00 39.00
SA09 10.00 0.00 3.00
SA10 0.00 0.00 2.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 -1.60 0.00 2.80 A05 -1.60 0.00 -2.80
A02 -2.30 0.00 4.00 A06 -2.30 0.00 -4.00

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A -4.00 0.00 0.00 0.00 -4.00 0.00
PA-Ba -1.00 0.00 0.00 0.00 -1.00 0.00
PA-Bb -1.00 0.00 0.00 0.00 -1.00 0.00
PA-D -5.00 0.00 -12.00 0.00 0.00 0.00
PA-E -5.00 0.00 -12.00 0.00 0.00 0.00
PA-F -5.00 0.00 -12.00 0.00 0.00 0.00
PA-G -5.00 0.00 -10.00 0.00 0.00 0.00
PA-H -1.00 0.00 0.00 0.00 -1.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 0.00 0.10 B04 0.00 0.10 17.60
B02 0.00 0.00 0.00 B05 -9.50 -0.10 -17.50
B03 0.00 0.00 17.40 B06 -9.60 0.00 -17.70

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 25 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A -3.00 0.00 0.00 0.00 -3.00 0.00
FD-B -1.00 0.00 0.00 0.00 -1.00 0.00
FD-C -1.00 0.00 0.00 0.00 -1.00 0.00
FD-D -5.00 0.00 10.00 0.00 0.00 0.00
FD-E -5.00 0.00 -10.00 0.00 0.00 0.00
FD-F -5.00 0.00 -10.00 0.00 0.00 0.00
FD-G -5.00 0.00 -10.00 0.00 0.00 0.00
FD-H -1.00 0.00 0.00 0.00 -1.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 0.00 0.00 0.10 C04 0.00 0.10 11.70
C02 0.00 0.00 0.00 C05 -8.80 0.00 -11.70
C03 0.00 0.00 11.60 C06 -8.80 0.00 -11.70

(3) W(+Y)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 0.00 0.10 5.90 SA01 -2.40 0.00 -2.40
PA04 0.00 0.10 1.80 SA02 -4.20 0.00 -4.10
PA07 -0.10 2.50 -5.80 SA05 -2.40 0.00 2.40
PA08 0.00 0.60 -1.80 SA06 -4.40 -0.10 3.90
SA09 -1.10 0.10 0.30
SA10 0.00 0.00 0.20

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.00 0.50 2.80 A05 0.00 0.60 -2.80
A02 0.10 0.60 4.00 A06 0.00 0.60 -4.00

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 0.00 4.00 0.00 4.00 0.00 0.00
PA-Ba 0.00 1.00 0.00 1.00 0.00 0.00
PA-Bb 0.00 1.00 0.00 1.00 0.00 0.00
PA-D 0.00 1.00 -1.00 0.00 0.00 0.00
PA-E 0.00 1.00 1.00 0.00 0.00 0.00
PA-F 0.00 7.00 28.00 0.00 0.00 0.00
PA-G 0.00 9.00 -31.00 0.00 0.00 0.00
PA-H 0.00 1.00 0.00 1.00 0.00 0.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 26 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2
D) PA FAN SILENCER SUPPORT
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 -14.10 21.80 B04 0.00 -19.60 -30.00
B02 0.00 0.00 -21.70 B05 0.20 -8.70 13.80
B03 0.00 0.00 29.60 B06 -0.20 0.00 -13.60

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 0.00 3.00 0.00 3.00 0.00 0.00
FD-B 0.00 1.00 0.00 1.00 0.00 0.00
FD-C 0.00 1.00 0.00 1.00 0.00 0.00
FD-D 0.00 2.00 -1.00 0.00 0.00 0.00
FD-E 0.00 9.00 -30.00 0.00 0.00 0.00
FD-F 0.00 2.00 1.00 0.00 0.00 0.00
FD-G 0.00 9.00 -31.00 0.00 0.00 0.00
FD-H 0.00 1.00 0.00 1.00 0.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 0.00 9.50 -16.10 C04 0.00 18.80 31.50
C02 0.00 0.00 15.90 C05 -0.10 12.30 -20.70
C03 0.00 0.00 -31.10 C06 0.00 0.00 20.50

(4) W(-Y)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 0.00 -1.00 1.00 SA01 0.00 5.00 -6.00
PA04 0.00 -1.00 -2.00 SA02 0.00 6.00 1.00
PA07 1.00 -25.00 -7.00 SA05 0.00 8.00 -18.00
PA08 0.00 -6.00 -25.00 SA06 0.00 30.00 -7.00
SA09 0.00 34.00 -19.00
SA10 0.00 32.00 19.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.00 -5.00 4.00 A05 0.00 -6.00 5.00
A02 -1.00 -6.00 5.00 A06 0.00 -6.00 -6.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 27 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 0.00 -4.00 0.00 -4.00 0.00 0.00
PA-Ba 0.00 -1.00 0.00 -1.00 0.00 0.00
PA-Bb 0.00 -1.00 0.00 -1.00 0.00 0.00
PA-D 0.00 -1.00 1.00 0.00 0.00 0.00
PA-E 0.00 -1.00 -1.00 0.00 0.00 0.00
PA-F 0.00 -7.00 -28.00 0.00 0.00 0.00
PA-G 0.00 -9.00 31.00 0.00 0.00 0.00
PA-H 0.00 -1.00 0.00 -1.00 0.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 14.10 21.80 B04 0.00 19.60 -30.00
B02 0.00 0.00 -21.70 B05 -0.20 8.70 13.80
B03 0.00 0.00 29.60 B06 0.20 0.00 -13.60

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 0.00 -3.00 0.00 -3.00 0.00 0.00
FD-B 0.00 -1.00 0.00 -1.00 0.00 0.00
FD-C 0.00 -1.00 0.00 -1.00 0.00 0.00
FD-D 0.00 -2.00 1.00 0.00 0.00 0.00
FD-E 0.00 -9.00 30.00 0.00 0.00 0.00
FD-F 0.00 -2.00 -1.00 0.00 0.00 0.00
FD-G 0.00 -9.00 31.00 0.00 0.00 0.00
FD-H 0.00 -1.00 0.00 -1.00 0.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 0.00 -9.50 -16.10 C04 0.00 -18.80 31.50
C02 0.00 0.00 15.90 C05 0.10 -12.30 -20.70
C03 0.00 0.00 -31.10 C06 0.00 0.00 20.50

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 28 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) Seismic Load ( E )

(1) E(+X)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 -6.70 0.00 -10.00 SA01 -5.80 0.00 -5.70
PA04 -6.90 0.00 -10.30 SA02 -6.30 0.00 -6.20
PA07 -6.90 0.00 -10.00 SA05 -5.80 0.00 -5.70
PA08 -6.90 0.00 -10.30 SA06 -6.30 -0.20 -6.20
SA09 -2.40 -0.40 -1.00
SA10 0.00 -0.10 -1.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 -0.50 -0.10 -0.80 A05 -0.50 -0.10 -0.80
A02 -0.70 -0.10 -1.20 A06 -0.70 -0.10 -1.30

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 10.00 0.00 0.00 0.00 9.00 0.00
PA-Ba 3.00 0.00 0.00 0.00 2.00 0.00
PA-Bb 3.00 0.00 0.00 0.00 2.00 0.00
PA-D 10.00 0.00 -24.00 0.00 0.00 0.00
PA-E 10.00 0.00 24.00 0.00 0.00 0.00
PA-F 10.00 0.00 24.00 0.00 0.00 0.00
PA-G 10.00 0.00 -20.00 0.00 0.00 0.00
PA-H 1.00 0.00 0.00 0.00 1.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 -0.20 -0.40 B04 0.00 -3.20 -28.40
B02 0.00 0.00 -0.30 B05 19.30 1.30 36.80
B03 0.00 0.00 -37.60 B06 15.30 0.00 27.90

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 4.00 0.00 0.00 0.00 4.00 0.00
FD-B 2.00 0.00 0.00 0.00 2.00 0.00
FD-C 3.00 0.00 0.00 0.00 2.00 0.00
FD-D 10.00 0.00 -20.00 0.00 0.00 0.00
FD-E 10.00 0.00 -20.00 0.00 0.00 0.00
FD-F 10.00 0.00 -20.00 0.00 0.00 0.00
FD-G 10.00 0.00 -20.00 0.00 0.00 0.00
FD-H 1.00 0.00 0.00 0.00 1.00 0.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 29 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 0.00 -0.50 0.80 C04 0.00 6.00 -21.40
C02 0.00 0.00 -0.70 C05 12.20 0.50 16.30
C03 0.00 0.00 -23.50 C06 14.10 0.00 18.50

(2) E(-X)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 6.70 0.00 10.00 SA01 5.80 0.00 5.70
PA04 6.90 0.00 10.30 SA02 6.30 0.00 6.20
PA07 6.90 0.00 10.00 SA05 5.80 0.00 5.70
PA08 6.90 0.00 10.30 SA06 6.30 0.20 6.20
SA09 2.40 0.40 1.00
SA10 0.00 0.10 1.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.50 0.10 0.80 A05 0.50 0.10 0.80
A02 0.70 0.10 1.20 A06 0.70 0.10 1.30

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A -10.00 0.00 0.00 0.00 -9.00 0.00
PA-Ba -3.00 0.00 0.00 0.00 -2.00 0.00
PA-Bb -3.00 0.00 0.00 0.00 -2.00 0.00
PA-D -10.00 0.00 24.00 0.00 0.00 0.00
PA-E -10.00 0.00 -24.00 0.00 0.00 0.00
PA-F -10.00 0.00 -24.00 0.00 0.00 0.00
PA-G -10.00 0.00 20.00 0.00 0.00 0.00
PA-H -1.00 0.00 0.00 0.00 -1.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 0.20 0.40 B04 0.00 3.20 28.40
B02 0.00 0.00 0.30 B05 -19.30 -1.30 -36.80
B03 0.00 0.00 37.60 B06 -15.30 0.00 -27.90

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 30 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2
E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A -4.00 0.00 0.00 0.00 -4.00 0.00
FD-B -2.00 0.00 0.00 0.00 -2.00 0.00
FD-C -3.00 0.00 0.00 0.00 -2.00 0.00
FD-D -10.00 0.00 20.00 0.00 0.00 0.00
FD-E -10.00 0.00 20.00 0.00 0.00 0.00
FD-F -10.00 0.00 0.00 0.00 0.00 0.00
FD-G -10.00 0.00 20.00 0.00 0.00 0.00
FD-H -1.00 0.00 0.00 0.00 -1.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 4.20 0.00 -6.60 C04 0.00 -0.10 -0.10
C02 6.50 0.00 -10.30 C05 5.00 0.70 7.00
C03 0.00 0.00 -0.10 C06 7.70 0.00 11.30

(3) E(+Y)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 -0.10 -1.80 -1.60 SA01 0.00 -2.10 -2.90
PA04 0.00 -1.60 -2.60 SA02 0.00 -2.70 -0.10
PA07 -0.20 -2.40 -0.70 SA05 0.00 -1.00 -2.50
PA08 0.00 -0.70 -2.70 SA06 -0.10 -3.20 -0.80
SA09 -0.30 -1.70 -0.90
SA10 0.00 -1.60 -1.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.00 -0.30 -0.30 A05 0.00 -0.40 -0.40
A02 0.00 -0.40 -0.30 A06 0.00 -0.40 -0.30

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 0.00 10.00 0.00 9.00 0.00 0.00
PA-Ba 0.00 3.00 0.00 2.00 0.00 0.00
PA-Bb 0.00 3.00 0.00 2.00 0.00 0.00
PA-D 0.00 10.00 10.00 0.00 0.00 0.00
PA-E 0.00 10.00 -10.00 0.00 0.00 0.00
PA-F 0.00 10.00 -24.00 0.00 0.00 0.00
PA-G 0.00 10.00 54.00 0.00 0.00 0.00
PA-H 0.00 1.00 0.00 1.00 0.00 0.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 31 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 10.00 -15.50 B04 0.00 15.80 23.90
B02 0.00 0.00 15.50 B05 3.90 9.50 -11.70
B03 0.00 0.00 -28.40 B06 0.40 0.00 15.10

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 0.00 4.00 0.00 4.00 0.00 0.00
FD-B 0.00 2.00 0.00 2.00 0.00 0.00
FD-C 0.00 3.00 0.00 2.00 0.00 0.00
FD-D 0.00 10.00 -20.00 0.00 0.00 0.00
FD-E 0.00 10.00 -54.00 0.00 0.00 0.00
FD-F 0.00 10.00 20.00 0.00 0.00 0.00
FD-G 0.00 10.00 54.00 0.00 0.00 0.00
FD-H 0.00 1.00 0.00 1.00 0.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 -2.70 -8.00 13.90 C04 0.00 -9.70 -16.20
C02 -0.60 0.00 -13.40 C05 3.30 -9.40 19.00
C03 0.00 0.00 7.70 C06 -0.70 0.00 -16.10

(4) E(-Y)

A) FDF / PAF OUTLET AIR DUCT SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
PA03 0.10 1.80 1.60 SA01 0.00 2.10 2.90
PA04 0.00 1.60 2.60 SA02 0.00 2.70 0.10
PA07 0.20 2.40 0.70 SA05 0.00 1.00 2.50
PA08 0.00 0.70 2.70 SA06 0.10 3.20 0.80
SA09 0.30 1.70 0.90
SA10 0.00 1.60 1.00

B) PLATFORM
HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
A01 0.00 0.30 0.30 A05 0.00 0.40 0.40
A02 0.00 0.40 0.30 A06 0.00 0.40 0.30

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 32 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

C) PA FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
PA-A 0.00 -10.00 0.00 -9.00 0.00 0.00
PA-Ba 0.00 -3.00 0.00 -2.00 0.00 0.00
PA-Bb 0.00 -3.00 0.00 -2.00 0.00 0.00
PA-D 0.00 -10.00 -10.00 0.00 0.00 0.00
PA-E 0.00 -10.00 10.00 0.00 0.00 0.00
PA-F 0.00 -10.00 24.00 0.00 0.00 0.00
PA-G 0.00 -10.00 -54.00 0.00 0.00 0.00
PA-H 0.00 -1.00 0.00 -1.00 0.00 0.00

D) PA FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
B01 0.00 -10.00 15.50 B04 0.00 -15.80 -23.90
B02 0.00 0.00 -15.50 B05 -3.90 -9.50 11.70
B03 0.00 0.00 28.40 B06 -0.40 0.00 -15.10

E) FD FAN
HOR. (X) HOR. (Y) VER. (Z) MOMENT (X) MOMENT (Y) MOMENT (Z)
Pedestal
kN kN kN kN·m kN·m kN·m
FD-A 0.00 -4.00 0.00 -4.00 0.00 0.00
FD-B 0.00 -2.00 0.00 -2.00 0.00 0.00
FD-C 0.00 -3.00 0.00 -2.00 0.00 0.00
FD-D 0.00 -10.00 20.00 0.00 0.00 0.00
FD-E 0.00 -10.00 54.00 0.00 0.00 0.00
FD-F 0.00 -10.00 -20.00 0.00 0.00 0.00
FD-G 0.00 -10.00 -54.00 0.00 0.00 0.00
FD-H 0.00 -1.00 0.00 -1.00 0.00 0.00

F) FD FAN SILENCER SUPPORT


HOR. (X) HOR. (Y) VER. (Z) Pedestal HOR. (X) HOR. (Y) VER. (Z)
Pedestal
kN kN kN Line kN kN kN
C01 2.70 8.00 -13.90 C04 0.00 9.70 16.20
C02 0.60 0.00 13.40 C05 -3.30 9.40 -19.00
C03 0.00 0.00 -7.70 C06 0.70 0.00 16.10

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 33 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.2 Load Application

Dead Load (Surcharge)

Dead Load (Equipment - P.A FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 34 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Dead Load (Equipment - F.D FDN)

Dead Load (Equipment - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 35 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Live Load (Surcharge - P.A FDN)

Live Load (Surcharge - F.D FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 36 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Live Load (Surcharge - Duct)

Live Load (Equipment - P.A FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 37 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Live Load (Equipment - F.D FDN)

Live Load (Equipment - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 38 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (+X - P.A.FDN)

Wind Load (+X - F.D FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 39 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (+X - Duct)

Wind Load (+Y - P.A.FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 40 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (+Y - F.D FDN)

Wind Load (+Y - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 41 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (-X - P.A.FDN)

Wind Load (-X - F.D FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 42 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (-X - Duct)

Wind Load (-Y - P.A.FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 43 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Wind Load (-Y - F.D FDN)

Wind Load (-Y - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 44 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (+X - P.A FDN)

Seismic Load (+X - F.D FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 45 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (+X - Duct)

Seismic Load (+Y - P.A FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 46 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (+Y - F.D FDN)

Seismic Load (+Y - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 47 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (-X - P.A FDN)

Seismic Load (-X - F.D FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 48 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (-X - Duct)

Seismic Load (-Y - P.A FDN)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 49 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Seismic Load (-Y - F.D FDN)

Seismic Load (-Y - Duct)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 50 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.3 Load Combination

1) Elastic condition

Comb. Basic Load Combination


1 LCOM101 1.0 D + 1.0 De
2 LCOM102 1.0 D + 1.0 De + 1.0 L
3 LCOM103 1.0 D + 1.0 De + 0.75 L
LCOM104 1.0 D + 1.0 De + 0.6 W(+X)
LCOM105 1.0 D + 1.0 De + 0.6 W(-X)
4
LCOM106 1.0 D + 1.0 De + 0.6 W(+Y)
LCOM107 1.0 D + 1.0 De + 0.6 W(-Y)
LCOM108 1.0 D + 1.0 De + 0.75 L + 0.45 W(+X)
LCOM109 1.0 D + 1.0 De + 0.75 L + 0.45 W(-X)
5
LCOM110 1.0 D + 1.0 De + 0.75 L + 0.45 W(+Y)
LCOM111 1.0 D + 1.0 De + 0.75 L + 0.45 W(-Y)
LCOM112 0.6 D + 0.6 De + 0.6 W(+X)
LCOM113 0.6 D + 0.6 De + 0.6 W(-X)
6
LCOM114 0.6 D + 0.6 De + 0.6 W(+Y)
LCOM115 0.6 D + 0.6 De + 0.6 W(-Y)
LCOM116 1.0 D + 1.0 De + 0.7 [ E(+X) + 0.3 E(+Y) ]
LCOM117 1.0 D + 1.0 De + 0.7 [ E(+X) + 0.3 E(-Y) ]
LCOM118 1.0 D + 1.0 De + 0.7 [ E(-X) + 0.3 E(+Y) ]
LCOM119 1.0 D + 1.0 De + 0.7 [ E(-X) + 0.3 E(-Y) ]
7
LCOM120 1.0 D + 1.0 De + 0.7 [ 0.3 E(+X) + E(+Y) ]
LCOM121 1.0 D + 1.0 De + 0.7 [ 0.3 E(+X) + E(-Y) ]
LCOM122 1.0 D + 1.0 De + 0.7 [ 0.3 E(-X) + E(+Y) ]
LCOM123 1.0 D + 1.0 De + 0.7 [ 0.3 E(-X) + E(-Y) ]
LCOM124 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.7 E(+X) + 0.21 E(+Y) ]
LCOM125 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.7 E(+X) + 0.21 E(-Y) ]
LCOM126 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.7 E(-X) + 0.21 E(+Y) ]
LCOM127 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.7 E(-X) + 0.21 E(-Y) ]
8
LCOM128 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.21 E(+X) + 0.7 E(+Y) ]
LCOM129 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.21 E(+X) + 0.7 E(-Y) ]
LCOM130 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.21 E(-X) + 0.7 E(+Y) ]
LCOM131 1.0 D + 1.0 De + 0.75 L + 0.75 [ 0.21 E(-X) + 0.7 E(-Y) ]
LCOM132 0.6 D + 0.6 De + 0.7 [ E(+X) + 0.3 E(+Y) ]
LCOM133 0.6 D + 0.6 De + 0.7 [ E(+X) + 0.3 E(-Y) ]
LCOM134 0.6 D + 0.6 De + 0.7 [ E(-X) + 0.3 E(+Y) ]
LCOM135 0.6 D + 0.6 De + 0.7 [ E(-X) + 0.3 E(-Y) ]
9
LCOM136 0.6 D + 0.6 De + 0.7 [ 0.3 E(+X) + E(+Y) ]
LCOM137 0.6 D + 0.6 De + 0.7 [ 0.3 E(+X) + E(-Y) ]
LCOM138 0.6 D + 0.6 De + 0.7 [ 0.3 E(-X) + E(+Y) ]
LCOM139 0.6 D + 0.6 De + 0.7 [ 0.3 E(-X) + E(-Y) ]
Where, D : Dead load (Self weight)
De : Dead load (Equipment load)
L : Live Load
T : Thermal Load
W : Wind load
E : Earthquake load

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 51 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Ultimate Condition

Comb. Basic Load Combination


1 LCOM201 1.4 D + 1.4 De
2 LCOM202 1.2 D + 1.2 De + 1.6 L
3 LCOM203 1.2 D + 1.2 De + 1.0 L
LCOM204 1.2 D + 1.2 De + 0.5 W(+X)
LCOM205 1.2 D + 1.2 De + 0.5 W(-X)
4
LCOM206 1.2 D + 1.2 De + 0.5 W(+Y)
LCOM207 1.2 D + 1.2 De + 0.5 W(-Y)
LCOM208 1.2 D + 1.2 De + 1.0 L + 1.0 W(+X)
LCOM209 1.2 D + 1.2 De + 1.0 L + 1.0 W(-X)
5
LCOM210 1.2 D + 1.2 De + 1.0 L + 1.0 W(+Y)
LCOM211 1.2 D + 1.2 De + 1.0 L + 1.0 W(-Y)
LCOM212 0.9 D + 0.9 De + 1.0 W(+X)
LCOM213 0.9 D + 0.9 De + 1.0 W(-X)
6
LCOM214 0.9 D + 0.9 De + 1.0 W(+Y)
LCOM215 0.9 D + 0.9 De + 1.0 W(-Y)
LCOM216 1.2 D + 1.2 De + 1.0 L + 1.0 [ E(+X) + 0.3 E(+Y) ]
LCOM217 1.2 D + 1.2 De + 1.0 L + 1.0 [ E(+X) + 0.3 E(-Y) ]
LCOM218 1.2 D + 1.2 De + 1.0 L + 1.0 [ E(-X) + 0.3 E(+Y) ]
LCOM219 1.2 D + 1.2 De + 1.0 L + 1.0 [ E(-X) + 0.3 E(-Y) ]
7
LCOM220 1.2 D + 1.2 De + 1.0 L + 1.0 [ 0.3 E(+X) + E(+Y) ]
LCOM221 1.2 D + 1.2 De + 1.0 L + 1.0 [ 0.3 E(+X) + E(-Y) ]
LCOM222 1.2 D + 1.2 De + 1.0 L + 1.0 [ 0.3 E(-X) + E(+Y) ]
LCOM223 1.2 D + 1.2 De + 1.0 L + 1.0 [ 0.3 E(-X) + E(-Y) ]
LCOM224 0.9 D + 0.9 De + 1.0 [ E(+X) + 0.3 E(+Y) ]
LCOM225 0.9 D + 0.9 De + 1.0 [ E(+X) + 0.3 E(-Y) ]
LCOM226 0.9 D + 0.9 De + 1.0 [ E(-X) + 0.3 E(+Y) ]
LCOM227 0.9 D + 0.9 De + 1.0 [ E(-X) + 0.3 E(-Y) ]
8
LCOM228 0.9 D + 0.9 De + 1.0 [ 0.3 E(+X) + E(+Y) ]
LCOM229 0.9 D + 0.9 De + 1.0 [ 0.3 E(+X) + E(-Y) ]
LCOM230 0.9 D + 0.9 De + 1.0 [ 0.3 E(-X) + E(+Y) ]
LCOM231 0.9 D + 0.9 De + 1.0 [ 0.3 E(-X) + E(-Y) ]

Where, D : Dead load (Self weight)


De : Dead load (Equipment load)
L : Live Load
T : Thermal Load
W : Wind load
E : Earthquake load

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 52 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.4 Subgrade Reactions Modulus

① Vertical Subgrade reaction modulus(Kv)

- Static
Kv = 40 × SF × qa Safety FDctor (SF) : 3
= 10800 kN/m3 Allowable Bearing Capacity, qa : 90.0 kN/m2

- Seismic
Kv = Kv(Static) × 2.5
= 27000 kN/m3

Where, Kv : Coefficient of subgrade reaction applicable to a determined concrete rigid footing o


width B(m) and length L(m)

② Horizontal Shear Subgrade reaction modulus(Ks)

- Static
Ks = λ Kv = 3086 kN/m3

- Seismic
Ks = λ Kv = 7714 kN/m3

λ = Ratio of horizontal shear to vertical subgrade reaction modulus ( 1 / 3.5 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 53 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4.0 MODELING

1. PA FAN & FD FAN FDN and Duct Support FDN are modeled using JOINT SPRING elements with
equivalent spring stiffness for the vertical and horizontal direction of piles, shell elements for mat
foundation and frame elements for column and equipment pedestals in SAP2000.
The piled foundations which support the structure have been defined using spring joints in the
structural model. Vertical spring and lateral spring constants are calculated as shown in Section 1.6.

2. The Duct Support foundation is modeled using equivalent springs for soil, shell elements for
bottom slab and frame elements for pedestal in SAP2000.
Shell elements for mat foundations have the thickness, respectively .

4.1 Modeling Birds-eye View

<P.A FAN >

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 54 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

<F.D FAN >

<DUCT SUPPORT&
PLATFORM >

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 55 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.0 PILE STABILITY CHECK - PA & FD FAN Foundation

5.1 Pile Spring Joint Modal Data

1) Pile Number

P.A FAN TYPE-2

F.D FAN TYPE-2

F.D FAN TYPE-1

P.A FAN TYPE-1

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 56 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Spring Number at the SAP200 Program

95
##
##
7.4 EXTERNAL STABILITY CHECK (Duct Support Foundation TYPE D) ##
7.5 Bearing Capacity Check ##

P.A FAN TYPE-1 P.A FAN TYPE-2

F.D FAN TYPE-1 F.D FAN TYPE-2

Y
Z

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 57 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.2 Pile Compression Capacity Check (P.A FAN TYPE-1)

1) Pile Vertical Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 443.55 O.K
LCOM102 525.17 O.K
LCOM103 504.76 O.K
LCOM104 448.25 O.K
LCOM105 440.15 O.K
LCOM106 448.34 O.K
LCOM107 438.77 O.K
Static LCOM108 508.29 1350 O.K
LCOM109 501.24 O.K
LCOM110 508.35 O.K
LCOM111 501.18 O.K
LCOM112 270.8 O.K
LCOM113 269.72 O.K
LCOM114 270.92 O.K
LCOM115 261.35 O.K
LCOM116 462.26 O.K
LCOM117 451.65 O.K
LCOM118 441.43 O.K
LCOM119 438.97 O.K
LCOM120 464.90 O.K
LCOM121 429.54 O.K
LCOM122 456.56 O.K
LCOM123 424.91 O.K
LCOM124 518.38 O.K
LCOM125 510.43 O.K
LCOM126 498.56 O.K
LCOM127 496.71 O.K
Seismic 2405
LCOM128 520.37 O.K
LCOM129 493.85 O.K
LCOM130 514.11 O.K
LCOM131 487.59 O.K
LCOM132 285.04 O.K
LCOM133 274.43 O.K
LCOM134 271.75 O.K
LCOM135 269.29 O.K
LCOM136 287.68 O.K
LCOM137 252.32 O.K
LCOM138 279.34 O.K
LCOM139 255.23 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 58 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Vertical Spring Reaction Diagram

Vertical Spring Reaction (kN/Pile)

1400

1200
1000

800
600
400

200

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Vertical Spring Reaction (kN/Pile)

2400
2100
1800
1500
1200
900
600
300
0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 59 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.3 Pile Lateral Capacity Check (P.A FAN TYPE-1)

1) Pile Lateral Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.18 O.K
LCOM102 0.24 O.K
LCOM103 0.22 O.K
LCOM104 2.99 O.K
LCOM105 2.92 O.K
LCOM106 3.86 O.K
LCOM107 3.91 O.K
Static LCOM108 2.33 107 O.K
LCOM109 2.22 O.K
LCOM110 2.89 O.K
LCOM111 2.95 O.K
LCOM112 2.92 O.K
LCOM113 2.89 O.K
LCOM114 3.87 O.K
LCOM115 3.90 O.K
LCOM116 7.43 O.K
LCOM117 6.81 O.K
LCOM118 6.96 O.K
LCOM119 7.50 O.K
LCOM120 10.10 O.K
LCOM121 9.75 O.K
LCOM122 9.66 O.K
LCOM123 10.18 O.K
LCOM124 5.71 O.K
LCOM125 5.22 O.K
LCOM126 5.29 O.K
LCOM127 5.68 O.K
Seismic 123
LCOM128 7.55 O.K
LCOM129 7.33 O.K
LCOM130 7.23 O.K
LCOM131 7.66 O.K
LCOM132 7.35 O.K
LCOM133 6.73 O.K
LCOM134 6.90 O.K
LCOM135 7.46 O.K
LCOM136 10.11 O.K
LCOM137 9.74 O.K
LCOM138 9.68 O.K
LCOM139 10.17 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 60 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Lateral Spring Reaction Diagram

Lateral Spring Reaction (kN/Pile)

100

80

60

40

20

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Lateral Spring Reaction (kN/Pile)

120

100

80

60

40

20

0
LCOM11

LCOM11

LCOM11

LCOM11

LCOM12

LCOM12

LCOM12

LCOM12

LCOM12

LCOM12

LCOM12

LCOM12
6

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 61 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.4 Pile Tension Capacity Check (P.A FAN TYPE-1)

1) Pile Tension Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.00 O.K
LCOM102 0.00 O.K
LCOM103 0.00 O.K
LCOM104 0.00 O.K
LCOM105 0.00 O.K
LCOM106 0.00 O.K
LCOM107 0.00 O.K
Static LCOM108 0.00 400 O.K
LCOM109 0.00 O.K
LCOM110 0.00 O.K
LCOM111 0.00 O.K
LCOM112 0.0 O.K
LCOM113 0.00 O.K
LCOM114 0.00 O.K
LCOM115 0.00 O.K
LCOM116 0.00 O.K
LCOM117 0.00 O.K
LCOM118 0.00 O.K
LCOM119 0.00 O.K
LCOM120 0.00 O.K
LCOM121 0.00 O.K
LCOM122 0.00 O.K
LCOM123 0.00 O.K
LCOM124 0.00 O.K
LCOM125 0.00 O.K
LCOM126 0.00 O.K
LCOM127 0.00 O.K
Seismic 691
LCOM128 0.00 O.K
LCOM129 0.00 O.K
LCOM130 0.00 O.K
LCOM131 0.00 O.K
LCOM132 0.00 O.K
LCOM133 0.00 O.K
LCOM134 0.00 O.K
LCOM135 0.00 O.K
LCOM136 0.00 O.K
LCOM137 0.00 O.K
LCOM138 0.00 O.K
LCOM139 0.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 62 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Tension Spring Reaction Diagram

Tension Spring Reaction (kN/Pile)

400
350
300
250
200
150
100
50
0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Tension Spring Reaction (kN/Pile)

700
600

500
400
300

200
100

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 63 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.5 Pile Compression Capacity Check (P.A FAN TYPE-2)

1) Pile Vertical Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 588.79 O.K
LCOM102 723.64 O.K
LCOM103 689.93 O.K
LCOM104 588.74 O.K
LCOM105 588.84 O.K
LCOM106 600.85 O.K
LCOM107 603.68 O.K
Static LCOM108 689.89 1350 O.K
LCOM109 689.97 O.K
LCOM110 698.98 O.K
LCOM111 701.10 O.K
LCOM112 353.2 O.K
LCOM113 353.32 O.K
LCOM114 365.34 O.K
LCOM115 368.17 O.K
LCOM116 584.98 O.K
LCOM117 599.95 O.K
LCOM118 566.70 O.K
LCOM119 581.67 O.K
LCOM120 561.11 O.K
LCOM121 611.03 O.K
LCOM122 555.62 O.K
LCOM123 605.54 O.K
LCOM124 684.74 O.K
LCOM125 695.97 O.K
LCOM126 671.03 O.K
LCOM127 682.26 O.K
Seismic 2405
LCOM128 666.84 O.K
LCOM129 704.28 O.K
LCOM130 662.73 O.K
LCOM131 700.16 O.K
LCOM132 351.65 O.K
LCOM133 366.62 O.K
LCOM134 333.37 O.K
LCOM135 351.39 O.K
LCOM136 327.78 O.K
LCOM137 377.70 O.K
LCOM138 322.29 O.K
LCOM139 372.21 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 64 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Vertical Spring Reaction Diagram

Vertical Spring Reaction (kN/Pile)

1400

1200
1000

800
600
400

200

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Vertical Spring Reaction (kN/Pile)

2400
2100
1800
1500
1200
900
600
300
0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 65 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.6 Pile Lateral Capacity Check (P.A FAN TYPE-2)

1) Pile Lateral Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 9.62 O.K
LCOM102 11.92 O.K
LCOM103 11.35 O.K
LCOM104 11.50 O.K
LCOM105 12.41 O.K
LCOM106 9.55 O.K
LCOM107 10.20 O.K
Static LCOM108 12.33 107 O.K
LCOM109 13.43 O.K
LCOM110 11.03 O.K
LCOM111 11.78 O.K
LCOM112 8.2 O.K
LCOM113 8.56 O.K
LCOM114 5.94 O.K
LCOM115 6.35 O.K
LCOM116 20.92 O.K
LCOM117 21.84 O.K
LCOM118 20.90 O.K
LCOM119 21.79 O.K
LCOM120 15.94 O.K
LCOM121 17.35 O.K
LCOM122 17.65 O.K
LCOM123 19.07 O.K
LCOM124 21.76 O.K
LCOM125 22.45 O.K
LCOM126 21.97 O.K
LCOM127 22.90 O.K
Seismic 123
LCOM128 17.58 O.K
LCOM129 19.08 O.K
LCOM130 19.32 O.K
LCOM131 20.86 O.K
LCOM132 15.70 O.K
LCOM133 16.47 O.K
LCOM134 15.24 O.K
LCOM135 15.70 O.K
LCOM136 12.00 O.K
LCOM137 11.98 O.K
LCOM138 12.26 O.K
LCOM139 12.98 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 66 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Lateral Spring Reaction Diagram

Lateral Spring Reaction (kN/Pile)

100

80

60

40

20

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Lateral Spring Reaction (kN/Pile)

120

100

80

60

40

20

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 67 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.7 Pile Tension Capacity Check (P.A FAN TYPE-2)

1) Pile Tension Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.00 O.K
LCOM102 0.00 O.K
LCOM103 0.00 O.K
LCOM104 0.00 O.K
LCOM105 0.00 O.K
LCOM106 0.00 O.K
LCOM107 0.00 O.K
Static LCOM108 0.00 400 O.K
LCOM109 0.00 O.K
LCOM110 0.00 O.K
LCOM111 0.00 O.K
LCOM112 0.0 O.K
LCOM113 0.00 O.K
LCOM114 0.00 O.K
LCOM115 0.00 O.K
LCOM116 0.00 O.K
LCOM117 0.00 O.K
LCOM118 0.00 O.K
LCOM119 0.00 O.K
LCOM120 0.00 O.K
LCOM121 0.00 O.K
LCOM122 0.00 O.K
LCOM123 0.00 O.K
LCOM124 0.00 O.K
LCOM125 0.00 O.K
LCOM126 0.00 O.K
LCOM127 0.00 O.K
Seismic 691
LCOM128 0.00 O.K
LCOM129 0.00 O.K
LCOM130 0.00 O.K
LCOM131 0.00 O.K
LCOM132 0.00 O.K
LCOM133 0.00 O.K
LCOM134 0.00 O.K
LCOM135 0.00 O.K
LCOM136 0.00 O.K
LCOM137 0.00 O.K
LCOM138 0.00 O.K
LCOM139 0.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 68 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Tension Spring Reaction Diagram

Tension Spring Reaction (kN/Pile)

400
350
300
250
200
150
100
50
0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Tension Spring Reaction (kN/Pile)

700
600

500
400
300

200
100

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 69 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.8 Pile Compression Capacity Check (F.D FAN TYPE-1)

1) Pile Vertical Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 431.97 O.K
LCOM102 495.70 O.K
LCOM103 479.76 O.K
LCOM104 425.76 O.K
LCOM105 438.17 O.K
LCOM106 437.96 O.K
LCOM107 425.98 O.K
Static LCOM108 475.11 1350 O.K
LCOM109 484.42 O.K
LCOM110 484.26 O.K
LCOM111 475.27 O.K
LCOM112 253.0 O.K
LCOM113 265.39 O.K
LCOM114 265.17 O.K
LCOM115 253.19 O.K
LCOM116 424.84 O.K
LCOM117 424.50 O.K
LCOM118 441.69 O.K
LCOM119 441.35 O.K
LCOM120 429.32 O.K
LCOM121 428.16 O.K
LCOM122 434.37 O.K
LCOM123 433.22 O.K
LCOM124 473.91 O.K
LCOM125 473.65 O.K
LCOM126 486.55 O.K
LCOM127 486.29 O.K
Seismic 2405
LCOM128 477.27 O.K
LCOM129 476.40 O.K
LCOM130 481.06 O.K
LCOM131 480.19 O.K
LCOM132 252.65 O.K
LCOM133 252.30 O.K
LCOM134 269.50 O.K
LCOM135 269.16 O.K
LCOM136 257.12 O.K
LCOM137 255.97 O.K
LCOM138 262.18 O.K
LCOM139 261.03 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 70 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Vertical Spring Reaction Diagram

Vertical Spring Reaction (kN/Pile)

1400

1200
1000

800
600
400

200

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Vertical Spring Reaction (kN/Pile)

2400
2100
1800
1500
1200
900
600
300
0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 71 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.9 Pile Lateral Capacity Check (F.D FAN TYPE-1)

1) Pile Lateral Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.73 O.K
LCOM102 0.78 O.K
LCOM103 0.77 O.K
LCOM104 3.14 O.K
LCOM105 3.37 O.K
LCOM106 4.77 O.K
LCOM107 4.83 O.K
Static LCOM108 2.50 107 O.K
LCOM109 2.75 O.K
LCOM110 3.57 O.K
LCOM111 3.64 O.K
LCOM112 2.9 O.K
LCOM113 3.07 O.K
LCOM114 4.79 O.K
LCOM115 4.82 O.K
LCOM116 6.79 O.K
LCOM117 6.83 O.K
LCOM118 7.13 O.K
LCOM119 6.99 O.K
LCOM120 7.94 O.K
LCOM121 8.11 O.K
LCOM122 8.02 O.K
LCOM123 8.02 O.K
LCOM124 5.33 O.K
LCOM125 5.35 O.K
LCOM126 5.68 O.K
LCOM127 5.55 O.K
Seismic 123
LCOM128 5.94 O.K
LCOM129 6.10 O.K
LCOM130 6.00 O.K
LCOM131 6.03 O.K
LCOM132 6.48 O.K
LCOM133 6.54 O.K
LCOM134 6.70 O.K
LCOM135 6.58 O.K
LCOM136 7.95 O.K
LCOM137 8.09 O.K
LCOM138 8.04 O.K
LCOM139 8.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 72 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Lateral Spring Reaction Diagram

Lateral Spring Reaction (kN/Pile)

100

80

60

40

20

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Lateral Spring Reaction (kN/Pile)

120

100

80

60

40

20

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 73 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.10 Pile Tension Capacity Check (F.D FAN TYPE-1)

1) Pile Tension Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.00 O.K
LCOM102 0.00 O.K
LCOM103 0.00 O.K
LCOM104 0.00 O.K
LCOM105 0.00 O.K
LCOM106 0.00 O.K
LCOM107 0.00 O.K
Static LCOM108 0.00 400 O.K
LCOM109 0.00 O.K
LCOM110 0.0 O.K
LCOM111 0.00 O.K
LCOM112 0.00 O.K
LCOM113 0.00 O.K
LCOM114 0.00 O.K
LCOM115 0.00 O.K
LCOM116 0.00 O.K
LCOM117 0.00 O.K
LCOM118 0.00 O.K
LCOM119 0.00 O.K
LCOM120 0.00 O.K
LCOM121 0.00 O.K
LCOM122 0.00 O.K
LCOM123 0.00 O.K
LCOM124 0.00 O.K
LCOM125 0.00 O.K
LCOM126 0.00 O.K
LCOM127 0.00 O.K
Seismic 691
LCOM128 0.00 O.K
LCOM129 0.00 O.K
LCOM130 0.00 O.K
LCOM131 0.00 O.K
LCOM132 0.00 O.K
LCOM133 0.00 O.K
LCOM134 0.00 O.K
LCOM135 0.00 O.K
LCOM136 0.00 O.K
LCOM137 0.00 O.K
LCOM138 0.00 O.K
LCOM139 0.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 74 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Tension Spring Reaction Diagram

Tension Spring Reaction (kN/Pile)

400
350
300
250
200
150
100
50
0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Tension Spring Reaction (kN/Pile)

700
600

500
400
300

200
100

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 75 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.11 Pile Compression Capacity Check (F.D FAN TYPE-2)

1) Pile Vertical Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 607.93 O.K
LCOM102 750.78 O.K
LCOM103 715.07 O.K
LCOM104 607.08 O.K
LCOM105 608.78 O.K
LCOM106 634.39 O.K
LCOM107 607.76 O.K
Static LCOM108 714.43 1350 O.K
LCOM109 715.70 O.K
LCOM110 734.91 O.K
LCOM111 714.94 O.K
LCOM112 363.9 O.K
LCOM113 365.61 O.K
LCOM114 391.21 O.K
LCOM115 364.59 O.K
LCOM116 628.20 O.K
LCOM117 612.79 O.K
LCOM118 604.72 O.K
LCOM119 589.31 O.K
LCOM120 637.05 O.K
LCOM121 611.83 O.K
LCOM122 630.01 O.K
LCOM123 606.10 O.K
LCOM124 730.06 O.K
LCOM125 718.50 O.K
LCOM126 712.45 O.K
LCOM127 700.89 O.K
Seismic 2405
LCOM128 736.70 O.K
LCOM129 710.32 O.K
LCOM130 731.41 O.K
LCOM131 706.02 O.K
LCOM132 385.21 O.K
LCOM133 369.80 O.K
LCOM134 361.73 O.K
LCOM135 349.18 O.K
LCOM136 394.06 O.K
LCOM137 379.78 O.K
LCOM138 387.02 O.K
LCOM139 374.05 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 76 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Vertical Spring Reaction Diagram

Vertical Spring Reaction (kN/Pile)

1400

1200
1000

800
600
400

200

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Vertical Spring Reaction (kN/Pile)

2400
2100
1800
1500
1200
900
600
300
0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 77 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.12 Pile Lateral Capacity Check (F.D FAN TYPE-2)

1) Pile Lateral Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 4.99 O.K
LCOM102 6.58 O.K
LCOM103 6.19 O.K
LCOM104 8.32 O.K
LCOM105 9.29 O.K
LCOM106 9.10 O.K
LCOM107 9.14 O.K
Static LCOM108 8.15 107 O.K
LCOM109 9.40 O.K
LCOM110 6.89 O.K
LCOM111 6.95 O.K
LCOM112 6.8 O.K
LCOM113 7.32 O.K
LCOM114 9.04 O.K
LCOM115 9.06 O.K
LCOM116 14.91 O.K
LCOM117 14.79 O.K
LCOM118 15.85 O.K
LCOM119 15.87 O.K
LCOM120 12.13 O.K
LCOM121 12.21 O.K
LCOM122 12.07 O.K
LCOM123 12.25 O.K
LCOM124 13.96 O.K
LCOM125 13.86 O.K
LCOM126 15.44 O.K
LCOM127 15.40 O.K
Seismic 123
LCOM128 10.12 O.K
LCOM129 10.03 O.K
LCOM130 11.73 O.K
LCOM131 11.83 O.K
LCOM132 12.62 O.K
LCOM133 12.52 O.K
LCOM134 12.95 O.K
LCOM135 13.01 O.K
LCOM136 12.04 O.K
LCOM137 12.09 O.K
LCOM138 11.98 O.K
LCOM139 12.13 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 78 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Lateral Spring Reaction Diagram

Lateral Spring Reaction (kN/Pile)

100

80

60

40

20

0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Lateral Spring Reaction (kN/Pile)

120

100

80

60

40

20

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 79 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.13 Pile Tension Capacity Check (F.D FAN TYPE-2)

1) Pile Tension Spring Reaction Summary

Maximum Load Allowable Pile


Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.00 O.K
LCOM102 0.00 O.K
LCOM103 0.00 O.K
LCOM104 0.00 O.K
LCOM105 0.00 O.K
LCOM106 0.00 O.K
LCOM107 0.00 O.K
Static LCOM108 0.00 400 O.K
LCOM109 0.00 O.K
LCOM110 0.00 O.K
LCOM111 0.00 O.K
LCOM112 0.0 O.K
LCOM113 0.00 O.K
LCOM114 0.00 O.K
LCOM115 0.00 O.K
LCOM116 0.00 O.K
LCOM117 0.00 O.K
LCOM118 0.00 O.K
LCOM119 0.00 O.K
LCOM120 0.00 O.K
LCOM121 0.00 O.K
LCOM122 0.00 O.K
LCOM123 0.00 O.K
LCOM124 0.00 O.K
LCOM125 0.00 O.K
LCOM126 0.00 O.K
LCOM127 0.00 O.K
Seismic 691
LCOM128 0.00 O.K
LCOM129 0.00 O.K
LCOM130 0.00 O.K
LCOM131 0.00 O.K
LCOM132 0.00 O.K
LCOM133 0.00 O.K
LCOM134 0.00 O.K
LCOM135 0.00 O.K
LCOM136 0.00 O.K
LCOM137 0.00 O.K
LCOM138 0.00 O.K
LCOM139 0.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 80 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Tension Spring Reaction Diagram

Tension Spring Reaction (kN/Pile)

400
350
300
250
200
150
100
50
0
LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM10

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11

LCOM11
1

5
Tension Spring Reaction (kN/Pile)

700
600

500
400
300

200
100

0
LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

LCOM1…

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 81 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.14 Pile Punching Shear Check

1) Footing Depth : 1.10 m

bo

1000

1100
100
Pile
Φ 600 mm

Load Maximum Load per Factored Pile reactions


Load Case
Comb. Load case (kN/Pile) Pvmax (kN/Pile)

Static LCOM202 662.85


662.85
Seismic LCOM220 644.12

Vc1 = 0.17 x (1+2/βc) x √fck x bo x d = 7800.61 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x √fck x bo x d = 22754.63 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x √fck x bo x d = 9085.41 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 110 - 10 = 100 cm


bo : the perimeter of critical section about Pile
= π x ( Pile Dia + d)
= π x ( 60 + 100 ) = 502.66 cm
βc : the ratio of long side to short side of the Pile
= 5.4 / 1.8 = 3.0
αs : interior columns = 40

∴ Vc = MIN(Vc1,Vc2,Vc3) = 7800.605 kN

Φv Vc = 0.75 x 7800.605 = 5850.454 kN > Vu = 662.849 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 82 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Footing Depth : 0.80 m

bo

700

800
100
Pile
Φ 600 mm

Load Maximum Load per Factored Pile reactions


Load Case
Comb. Load case (kN/Pile) Pvmax (kN/Pile)

Static LCOM202 922.31


922.31
Seismic LCOM221 873.13

Vc1 = 0.17 x (1+2/βc) x √fck x bo x d = 4436.59 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x √fck x bo x d = 11509.67 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x √fck x bo x d = 5167.33 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 80 - 10 = 70 cm


bo : the perimeter of critical section about Pile
= π x ( Pile Dia + d)
= π x ( 60 + 70 ) = 408.41 cm
βc : the ratio of long side to short side of the Pile
= 5.4 / 1.8 = 3.0
αs : interior columns = 40

∴ Vc = MIN(Vc1,Vc2,Vc3) = 4436.592 kN

Φv Vc = 0.75 x 4436.592 = 3327.444 kN > Vu = 922.313 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 83 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) Footing Depth : 1.45 m

bo

1350

1450
100
Pile
Φ 600 mm

Load Maximum Load per Factored Pile reactions


Load Case
Comb. Load case (kN/Pile) Pvmax (kN/Pile)

Static LCOM202 620.33


620.33
Seismic LCOM218 596.14

Vc1 = 0.17 x (1+2/βc) x √fck x bo x d = 11965.65 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x √fck x bo x d = 40660.52 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x √fck x bo x d = 14948.35 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 145 - 10 = 135 cm


bo : the perimeter of critical section about Pile
= π x ( Pile Dia + d)
= π x ( 60 + 135 ) = 612.61 cm
βc : the ratio of long side to short side of the Pile
= 6.5 / 1.8 = 3.6
αs : interior columns = 40

∴ Vc = MIN(Vc1,Vc2,Vc3) = 11965.645 kN

Φv Vc = 0.75 x 11965.645 = 8974.234 kN > Vu = 620.326 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 84 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) Footing Depth : 1.00 m

bo

900

1000
100
Pile
Φ 600 mm

Load Maximum Load per Factored Pile reactions


Load Case
Comb. Load case (kN/Pile) Pvmax (kN/Pile)

Static LCOM202 958.07


958.07
Seismic LCOM220 913.95

Vc1 = 0.17 x (1+2/βc) x √fck x bo x d = 6136.23 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x √fck x bo x d = 18585.49 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x √fck x bo x d = 7665.81 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 100 - 10 = 90 cm


bo : the perimeter of critical section about Pile
= π x ( Pile Dia + d)
= π x ( 60 + 90 ) = 471.24 cm
βc : the ratio of long side to short side of the Pile
= 6.5 / 1.8 = 3.6
αs : interior columns = 40

∴ Vc = MIN(Vc1,Vc2,Vc3) = 6136.225 kN

Φv Vc = 0.75 x 6136.225 = 4602.169 kN > Vu = 958.072 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 85 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.0 PILE STABILITY CHECK - Duct Support & Platform Foundation

6.1 Pile Spring Joint Modal Data

1) Pile Number

DUCT SUPPRT

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 86 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Spring Number at the SAP200 Program

Duct-1

PA07 PA03
Plaform-1

PA08 PA04 A05 A01

Duct-2

SA05 SA01
Plaform-1

Duct-3
SA06 SA02 A06 A02

SA09

SA10

Z X

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 87 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.2 Pile Compression Capacity Check

1) Pile Vertical Spring Reaction Summary


Maximum Load Allowable Pile
Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 301.49 O.K
LCOM102 359.07 O.K
LCOM103 344.65 O.K
LCOM104 301.76 O.K
LCOM105 310.39 O.K
LCOM106 302.24 O.K
LCOM107 303.15 O.K
Static LCOM108 344.63 1350 O.K
LCOM109 351.40 O.K
LCOM110 345.29 O.K
LCOM111 345.42 O.K
LCOM112 181.2 O.K
LCOM113 189.83 O.K
LCOM114 181.69 O.K
LCOM115 182.55 O.K
LCOM116 318.25 O.K
LCOM117 316.82 O.K
LCOM118 301.40 O.K
LCOM119 300.17 O.K
LCOM120 308.67 O.K
LCOM121 303.93 O.K
LCOM122 303.25 O.K
LCOM123 299.17 O.K
LCOM124 356.75 O.K
LCOM125 355.68 O.K
LCOM126 344.66 O.K
LCOM127 343.74 O.K
Seismic 2405
LCOM128 349.57 O.K
LCOM129 346.01 O.K
LCOM130 346.05 O.K
LCOM131 342.99 O.K
LCOM132 197.65 O.K
LCOM133 196.23 O.K
LCOM134 180.84 O.K
LCOM135 179.62 O.K
LCOM136 188.08 O.K
LCOM137 183.33 O.K
LCOM138 182.69 O.K
LCOM139 178.61 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 88 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Vertical Spring Reaction Diagram

Vertical Spring Reaction (kN/Pile)

1200

1000

800

600

400

200

0
LCOM101

LCOM102

LCOM103

LCOM104

LCOM105

LCOM106

LCOM107

LCOM108

LCOM109

LCOM110

LCOM111

LCOM112

LCOM113

LCOM114

LCOM115
Vertical Spring Reaction (kN/Pile)

2400
2100
1800
1500
1200
900
600
300
0
LCOM116

LCOM117

LCOM118

LCOM119

LCOM120

LCOM121

LCOM122

LCOM123

LCOM124

LCOM125

LCOM126

LCOM127

LCOM128

LCOM129

LCOM130

LCOM131

LCOM132

LCOM133

LCOM134

LCOM135

LCOM136

LCOM137

LCOM138

LCOM139

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 89 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.3 Pile Lateral Capacity Check

1) Pile Lateral Spring Reaction Summary


Maximum Load Allowable Pile
Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 6.98 O.K
LCOM102 6.23 O.K
LCOM103 6.42 O.K
LCOM104 6.98 O.K
LCOM105 7.52 O.K
LCOM106 11.00 O.K
LCOM107 7.00 O.K
Static LCOM108 6.42 107 O.K
LCOM109 6.65 O.K
LCOM110 9.44 O.K
LCOM111 6.44 O.K
LCOM112 4.2 O.K
LCOM113 5.85 O.K
LCOM114 8.21 O.K
LCOM115 4.21 O.K
LCOM116 18.69 O.K
LCOM117 18.63 O.K
LCOM118 1.21 O.K
LCOM119 1.15 O.K
LCOM120 12.64 O.K
LCOM121 12.45 O.K
LCOM122 7.40 O.K
LCOM123 7.20 O.K
LCOM124 15.70 O.K
LCOM125 15.66 O.K
LCOM126 2.59 O.K
LCOM127 2.55 O.K
Seismic 123
LCOM128 11.16 O.K
LCOM129 11.02 O.K
LCOM130 7.23 O.K
LCOM131 7.08 O.K
LCOM132 14.72 O.K
LCOM133 14.66 O.K
LCOM134 0.39 O.K
LCOM135 0.42 O.K
LCOM136 8.68 O.K
LCOM137 8.48 O.K
LCOM138 3.43 O.K
LCOM139 3.23 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 90 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Lateral Spring Reaction Diagram

Lateral Spring Reaction (kN/Pile)

100

80

60

40

20

0
LCOM101

LCOM102

LCOM103

LCOM104

LCOM105

LCOM106

LCOM107

LCOM108

LCOM109

LCOM110

LCOM111

LCOM112

LCOM113

LCOM114

LCOM115
Lateral Spring Reaction (kN/Pile)

120

100

80

60

40

20

0
LCOM116

LCOM117

LCOM118

LCOM119

LCOM120

LCOM121

LCOM122

LCOM123

LCOM124

LCOM125

LCOM126

LCOM127

LCOM128

LCOM129

LCOM130

LCOM131

LCOM132

LCOM133

LCOM134

LCOM135

LCOM136

LCOM137

LCOM138

LCOM139

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 91 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.4 Pile Tension Capacity Check

1) Pile Tension Spring Reaction Summary


Maximum Load Allowable Pile
Load
Load Case per Load case Compression Capacity Remark
Comb.
(kN) (kN)
LCOM101 0.00 O.K
LCOM102 0.00 O.K
LCOM103 0.00 O.K
LCOM104 0.00 O.K
LCOM105 0.00 O.K
LCOM106 0.00 O.K
LCOM107 0.00 O.K
Static LCOM108 0.00 400 O.K
LCOM109 0.00 O.K
LCOM110 0.00 O.K
LCOM111 0.00 O.K
LCOM112 0.0 O.K
LCOM113 0.00 O.K
LCOM114 0.00 O.K
LCOM115 0.00 O.K
LCOM116 0.00 O.K
LCOM117 0.00 O.K
LCOM118 0.00 O.K
LCOM119 0.00 O.K
LCOM120 0.00 O.K
LCOM121 0.00 O.K
LCOM122 0.00 O.K
LCOM123 0.00 O.K
LCOM124 0.00 O.K
LCOM125 0.00 O.K
LCOM126 0.00 O.K
LCOM127 0.00 O.K
Seismic 691
LCOM128 0.00 O.K
LCOM129 0.00 O.K
LCOM130 0.00 O.K
LCOM131 0.00 O.K
LCOM132 0.00 O.K
LCOM133 0.00 O.K
LCOM134 0.00 O.K
LCOM135 0.00 O.K
LCOM136 0.00 O.K
LCOM137 0.00 O.K
LCOM138 0.00 O.K
LCOM139 0.00 O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 92 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pile Tension Spring Reaction Diagram

Tension Spring Reaction (kN/Pile)

400
350
300
250
200
150
100
50
0
LCOM101

LCOM102

LCOM103

LCOM104

LCOM105

LCOM106

LCOM107

LCOM108

LCOM109

LCOM110

LCOM111

LCOM112

LCOM113

LCOM114

LCOM115
Tension Spring Reaction (kN/Pile)

700

600

500

400

300

200

100

0
LCOM116

LCOM117

LCOM118

LCOM119

LCOM120

LCOM121

LCOM122

LCOM123

LCOM124

LCOM125

LCOM126

LCOM127

LCOM128

LCOM129

LCOM130

LCOM131

LCOM132

LCOM133

LCOM134

LCOM135

LCOM136

LCOM137

LCOM138

LCOM139

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 93 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.5 Pile Punching Shear Check

1) Footing Depth : 0.4 m

bo

300

400
100
Pile
Φ 600 mm

Load Maximum Load per Factored Pile reactions


Load Case
Comb. Load case (kN/Pile) Pvmax (kN/Pile)

Static LCOM202 453.96


453.96
Seismic LCOM216 442.65

Vc1 = 0.17 x (1+2/βc) x √fck x bo x d = 1316.35 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x √fck x bo x d = 2407.82 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x √fck x bo x d = 1533.16 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 40 - 10 = 30 cm


bo : the perimeter of critical section about Pile
= π x ( Pile Dia + d)
= π x ( 60 + 30 ) = 282.74 cm
βc : the ratio of long side to short side of the Pile
= 5.4 / 1.8 = 3.0
αs : interior columns = 40

∴ Vc = MIN(Vc1,Vc2,Vc3) = 1316.350 kN

Φv Vc = 0.75 x 1316.350 = 987.263 kN > Vu = 453.958 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 94 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 FOUNDATION DESIGN

7.1 General Sketch

PA FAN-1 PA FAN-2
(Pile fdn.) (Pile fdn.)

FD FAN-1 FD FAN-2
(Pile fdn.) (Pile fdn.)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 95 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Duct-1

Plaform-1

Duct-2

Plaform-1

Duct-3

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 96 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.2 Calculation Summary

Summary of Bending Moment Summary of Shear force


Part Direction Location ΦMn Mu Arranged ΦVc Φ(Vc+Vs) Vu Arranged
(kN·m) (kN·m) Re-Bar (kN) (kN) (kN) Re-Bar
TOP
478.10 106.74 D16@150 Shear bar
(M22-Min)
Y-dir 646.7 - 189.8 is not
BOTTOM Required.
431.03 40.06 D16@150
P.A FAN-1 (M22-Max)
(T=1.00m) TOP
485.63 108.41 D16@150 Shear bar
(M11-Min)
X-dir 657.8 - 137.7 is not
BOTTOM Required.
438.56 45.71 D16@150
(M11-Max)
TOP
336.89 187.40 D16@150 Shear bar
(M22-Min)
Y-dir 430.9 - 426.8 is not
BOTTOM Required.
531.55 150.49 D22@150
P.A FAN-2 (M22-Max)
(T=0.80m) TOP
344.43 207.75 D16@150 Shear bar
(M11-Min)
X-dir 446.2 - 409.8 is not
BOTTOM Required.
551.11 500.31 D22@150
(M11-Max)
TOP
900.25 119.41 D19@150 Shear bar
(M22-Min)
Y-dir 887.9 - 119.4 is not
BOTTOM Required.
833.91 114.00 D19@150
F.D FAN-1 (M22-Max)
(T=1.60m) TOP
912.86 286.91 D19@150 Shear bar
(M11-Min)
X-dir 901.2 - 235.6 is not
BOTTOM Required.
846.52 114.73 D19@150
(M11-Max)
TOP
431.03 148.31 D16@150 Shear bar
(M22-Min)
Y-dir 576.8 - 320.8 is not
BOTTOM Required.
383.96 121.26 D16@150
F.D FAN-2 (M22-Max)
(T=1.20m) TOP
438.56 150.54 D16@150 Shear bar
(M11-Min)
X-dir 588.0 - 256.1 is not
BOTTOM Required.
391.50 224.87 D16@150
(M11-Max)
TOP
156.15 116.81 D16@150 Shear bar
(M22-Min)
Y-dir 169.0 - 152.3 is not
Duct BOTTOM
109.08 24.94 D16@150 Required.
& (M22-Max)
Platform
FDN TOP
148.62 108.41 D16@150 Shear bar
(T=0.40m) (M11-Min)
X-dir 157.8 - 88.6 is not
BOTTOM Required.
101.55 22.65 D16@150
(M11-Max)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 97 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.3 Moment & Shear Contour for USD Design


1) P.A FAN-1 (T=1.1m)
Top Min Mu Contour Range Use As ΦMn
Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Min) 106.74 -106.74 ~ 0 D16@150 478.10

Bottom Max Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Max) 40.06 0 ~ 40.06 D16@150 431.03

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 98 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Min) 108.41 -108.41 ~ 0 D16@150 485.63

Bottom Max Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Max) 45.71 0 ~ 45.71 D16@150 438.56

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 99 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V23(Max) 189.79 646.67 0 ~ 189.79 Shear bar is not Required. -

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V13(Max) 137.74 657.84 0 ~ 137.74 Shear bar is not Required. -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 100 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) P.A FAN-2 (T=0.8m)

Top Min Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Min) 187.40 -187.40 ~ 0 D16@150 336.89

Bottom Max Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Max) 150.49 0 ~ 150.49 D22@150 531.55

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 101 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Min) 207.75 -207.75 ~ 0 D16@150 344.43

Bottom Max Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Max) 500.31 0 ~ 500.31 D22@150 551.11

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 102 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V23(Max) 426.85 430.88 0 ~ 426.85 Shear bar is not Required. -

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V13(Max) 409.77 446.24 0 ~ 409.77 Shear bar is not Required. -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 103 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) F.D FAN-1 (T=1.45m)

Top Min Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Min) 119.41 -119.41 ~ 0 D19@150 900.25

Bottom Max Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Max) 114.00 0 ~ 114.00 D19@150 833.91

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 104 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Min) 286.91 -286.91 ~ 0 D19@150 912.86

Bottom Max Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Max) 114.73 0 ~ 114.73 D19@150 846.52

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 105 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V23(Max) 119.39 887.95 0 ~ 119.39 Shear bar is not Required. -

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V13(Max) 235.59 901.22 0 ~ 235.59 Shear bar is not Required. -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 106 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) F.D FAN (T=1.0m)

Top Min Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Min) 148.31 -148.31 ~ 0 D16@150 431.03

Bottom Max Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Max) 121.26 0 ~ 121.26 D16@150 383.96

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 107 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Min) 150.54 -150.54 ~ 0 D16@150 438.56

Bottom Max Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Max) 224.87 0 ~ 224.87 D16@150 391.50

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 108 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V23(Max) 320.84 576.83 0 ~ 320.84 Shear bar is not Required. -

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V13(Max) 256.11 588.01 0 ~ 256.11 Shear bar is not Required. -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 109 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) Duct & Platform FDN. (T=0.4m)

Top Min Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Min) 116.81 -116.81 ~ 0 D16@150 156.15

Bottom Max Mu Contour Range Use As ΦMn


Y-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M22(Max) 24.94 0 ~ 24.94 D16@150 109.08

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 110 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Min) 108.41 -108.41 ~ 0 D16@150 148.62

Bottom Max Mu Contour Range Use As ΦMn


X-dir (kN·m) (kN·m) (1-Layer) (kN·m)
M11(Max) 22.65 0 ~ 22.65 D16@150 101.55

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 111 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V23(Max) 152.32 169.00 0 ~ 152.32 Shear bar is not Required. -

Top & Max Vu ΦVc Contour Range Φ(Vc+Vs)


Use As
Bottom (kN) (kN) (kN·m) (kN)
V13(Max) 88.58 157.83 0 ~ 88.58 Shear bar is not Required. -

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 112 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.4 Moment Contour for ASD Design


1) P.A FAN-1
Top Min Mu Contour Range Apply Load Combination
Y-dir (kN·m) (kN·m) (Static)
M22(Min) 84.39 -84.39 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Max) 31.63 0 ~ 31.63 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 113 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Min) 85.73 -85.73 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Max) 31.87 0 ~ 31.87 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 114 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) P.A FAN-2

Top Min Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Min) 144.10 -144.10 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Max) 119.39 0 ~ 119.39 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 115 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Min) 162.18 -162.18 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Max) 394.73 0 ~ 394.73 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 116 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) F.D FAN-1

Top Min Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Min) 95.52 -95.52 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Max) 86.06 0 ~ 86.06 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 117 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Min) 228.85 -228.85 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Max) 86.63 0 ~ 86.63 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 118 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) F.D FAN-2

Top Min Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Min) 116.36 -116.36 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Max) 93.03 0 ~ 93.03 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 119 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Min) 117.36 -117.36 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Max) 173.24 0 ~ 173.24 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 120 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) Duct & Platform FDN.

Top Min Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Min) 93.21 -93.21 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


Y-dir (kN·m) (kN·m) (Static)
M22(Max) 18.54 0 ~ 18.54 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 121 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Top Min Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Min) 85.12 -85.12 ~ 0 LCOM101 ~115

Bottom Max Mu Contour Range Apply Load Combination


X-dir (kN·m) (kN·m) (Static)
M11(Max) 16.57 0 ~ 16.57 LCOM101 ~115

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 122 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.5 Flexure & Shear Check ( P.A FAN FDN-1 )

1) Foundation Depth : T=1100mm ( Y- direction )


(1) Design Condition
fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00
Height of Section : H = 110.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 7.40 ㎝
: [ BOT ] dc = 17.40 ㎝
Effective Depth : [ TOP ] d = 102.60 ㎝

H
d
: [ BOT ] d = 92.60 ㎝
Factored Moment : [ TOP ] Mu = 106.7 kN·m BOT
: [ BOT ] Mu = 40.1 kN·m
Factored Shear force : Vu = 189.8 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1100 - 24.532 - 74) / 24.532 = 0.0030 x (1100 - 24.532 - 174) / 24.532
= 0.1225 > 0.0040 ---- O.K = 0.1102 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 2.971 cm2 ∴ As(req) = 1.234 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0003 P(req) = As/(b×d) = 0.0001 (Controlled)
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0004 (Controlled) Pmin(2) = 4/3 x Preq = 0.0001 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / ( b×d ) = 13.41 / (100 x 102.6 ) Puse = As (used) / ( b×d ) = 13.41 / (100 x 92.6 )
= 0.0013 ≥ Pmin(2) = 0.0004 --- O.K = 0.0014 ≥ P(req) = 0.0001 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 478.10 kN·m > Mu = 106.742 kN·m = 431.03 kN·m > Mu = 40.055 kN·m
E) Check of Thermal & Shrinkage
As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 22.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 123 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 189.793 = kN
φVc = 0.75 × 0.17 × λ ×√fck ×bo ×d 646.669 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 84.4 kN·m (unfactored Moment) Ms = 31.6 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H = 110 cm H = 110 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 7.40 cm dcg = 17.40 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 105.00 cm ( = H - Cc ) d₁= 95.00 cm ( = H - Cc )
d₂= 102.60 cm ( = H - dcg ) d₂= 92.60 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 102.6 = 12.50 cm = 0.119 × 92.6 = 11.31 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ]
= 0.119 = 0.119
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 102.6 ) p : As / (B × d2) = 13.41 / ( 100 × 92.6 )
= 0.0010 = 0.0010

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 62.406 ) - 2.5 × 5 = 380 × (280 / 25.855 ) - 2.5 × 15
= 1,692.5 mm > 300(280/fs) = 1,346 mm = 4,077.8 mm > 300(280/fs) = 3,249 mm
∴ s= 1,346 mm > 150 mm ------ O.K ∴ s= 3,249 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 84.39 / [ 13.41 × ( 105 - 12.495 / 3 )] fs = 31.63 / [ 13.41 × ( 95 - 11.305 / 3 )]
= 6,241 N/cm2 = 2,586 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 124 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Foundation Depth : T=1100mm ( X- direction )


(1) Design Condition

fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00


Height of Section : H = 110.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 5.80 ㎝
: [ BOT ] dc = 15.80 ㎝
Effective Depth : [ TOP ] d = 104.20 ㎝

H
d
: [ BOT ] d = 94.20 ㎝
Factored Moment : [ TOP ] Mu = 108.4 kN·m BOT
: [ BOT ] Mu = 45.7 kN·m
Factored Shear force : Vu = 137.7 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1100 - 24.532 - 58) / 24.532 = 0.0030 x (1100 - 24.532 - 158) / 24.532
= 0.1244 > 0.0040 ---- O.K = 0.1122 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 2.971 cm2 ∴ As(req) = 1.384 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0003 P(req) = As/(b×d) = 0.0001 (Controlled)
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0004 (Controlled) Pmin(2) = 4/3 x Preq = 0.0001 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1- D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / (b × d) = 13.41 / (100 x 104.2 ) Puse = As (used) / (b × d) = 13.41 / (100 x 94.2 )
= 0.0013 ≥ Pmin(2) = 0.0004 --- O.K = 0.0014 ≥ P(req) = 0.0001 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 485.63 kN·m > Mu = 108.410 kN·m = 438.56 kN·m > Mu = 45.711 kN·m

E) Check of Thermal & Shrinkage


As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 22.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 125 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 137.740 = kN
φVc = 0.75 × 0.17 ×√fck ×bo ×d 657.842 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 85.7 kN·m (unfactored Moment) Ms = 31.9 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H = 110 cm H = 110 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 5.80 cm dcg = 15.80 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 105.00 cm ( = H - Cc ) d₁= 95.00 cm ( = H - Cc )
d₂= 104.20 cm ( = H - dcg ) d₂= 94.20 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 104.2 = 12.50 cm = 0.119 × 94.2 = 11.31 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ]
= 0.119 = 0.119
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 104.2 ) p : As / (B × d2) = 13.41 / ( 100 × 94.2 )
= 0.0010 = 0.0010

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 60.885 ) - 2.5 × 5 = 380 × (280 / 25.013 ) - 2.5 × 15
= 1,735.1 mm > 300(280/fs) = 1,380 mm = 4,216.3 mm > 300(280/fs) = 3,358 mm
∴ s= 1,380 mm > 150 mm ------ O.K ∴ s= 3,358 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 85.73 / [ 13.41 × ( 105 - / 3 )] fs = 31.87 / [ 13.41 × ( 95 - / 3 )]
= 6,088 N/cm2 = 2,501 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 126 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.6 Flexure & Shear Check ( P.A FAN FDN-2 )

1) Foundation Depth : T=800mm ( Y- direction )


(1) Design Condition
fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00
Height of Section : H = 80.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 7.40 ㎝
: [ BOT ] dc = 18.30 ㎝
Effective Depth : [ TOP ] d = 72.60 ㎝

H
d
: [ BOT ] d = 61.70 ㎝
Factored Moment : [ TOP ] Mu = 187.4 kN·m BOT
: [ BOT ] Mu = 150.5 kN·m
Factored Shear force : Vu = 426.8 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 2534 · 390 = 988260.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 38.755 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (800 - 24.532 - 74) / 24.532 = 0.0030 x (800 - 46.358 - 183) / 46.358
= 0.0858 > 0.0040 ---- O.K = 0.0369 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 38.755 / 0.836
= 24.532 mm = 46.358 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 7.412 cm2 ∴ As(req) = 7.010 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0010 P(req) = As/(b×d) = 0.0011
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0013 (Controlled) Pmin(2) = 4/3 x Preq = 0.0015 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1 - D 22 @ 150 + D 0 @ 0 = 25.34 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 25.34 ㎠
Puse = As (used) / ( b×d ) = 13.41 / (100 x 72.6 ) Puse = As (used) / ( b×d ) = 25.34 / (100 x 61.7 )
= 0.0018 ≥ Pmin(2) = 0.0013 --- O.K = 0.0041 ≥ Pmin(2) = 0.0015 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 336.89 kN·m > Mu = 187.399 kN·m = 531.55 kN·m > Mu = 150.493 kN·m
E) Check of Thermal & Shrinkage
As (total) = 13.41 + 25.34 = 38.75 ㎠ > As shr.= 0.002 (B x H) = 16.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 127 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 426.848 = kN
φVc = 0.75 × 0.17 × λ ×√fck ×bo ×d 430.880 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 144.1 kN·m (unfactored Moment) Ms = 119.4 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 25.34 cm2 ( 1 lay.- D22 + D0 )
H= 80 cm H= 80 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 7.40 cm dcg = 18.30 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 75.00 cm ( = H - Cc ) d₁= 65.00 cm ( = H - Cc )
d₂= 72.60 cm ( = H - dcg ) d₂= 61.70 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.164 × 72.6 = 12.30 cm = 0.223 × 61.7 = 14.50 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.002 + √ [( 8×0.002 )^2 + 2×8×0.002 ] = -8×0.004 + √ [( 8×0.004 )^2 + 2×8×0.004 ]
= 0.164 = 0.223
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 72.6 ) p : As / (B × d2) = 25.34 / ( 100 × 61.7 )
= 0.0020 = 0.0040

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 151.564 ) - 2.5 × 5 = 380 × (280 / 78.306 ) - 2.5 × 15
= 689.5 mm > 300(280/fs) = 554 mm = 1,321.3 mm > 300(280/fs) = 1,073 mm
∴ s= 554 mm > 150 mm ------ O.K ∴ s= 1,073 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 144.1 / [ 13.41 × ( 75 - 12.3 / 3 )] fs = 119.39 / [ 25.34 × ( 65 - 14.495 / 3 )]
= 15,156 N/cm2 = 7,831 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 128 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Foundation Depth : T=800mm ( X- direction )


(1) Design Condition

fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00


Height of Section : H = 80.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 5.80 ㎝
: [ BOT ] dc = 16.10 ㎝
Effective Depth : [ TOP ] d = 74.20 ㎝

H
d
: [ BOT ] d = 63.90 ㎝
Factored Moment : [ TOP ] Mu = 207.7 kN·m BOT
: [ BOT ] Mu = 500.3 kN·m
Factored Shear force : Vu = 409.8 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 2534 · 390 = 988260.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 38.755 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (800 - 24.532 - 58) / 24.532 = 0.0030 x (800 - 46.358 - 161) / 46.358
= 0.0877 > 0.0040 ---- O.K = 0.0384 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 38.755 / 0.836
= 24.532 mm = 46.358 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 8.043 cm2 ∴ As(req) = 22.936 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0011 P(req) = As/(b×d) = 0.0036 (Controlled)
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036 (Controlled)
Pmin(2) = 4/3 x Preq = 0.0015 (Controlled) Pmin(2) = 4/3 x Preq = 0.0048

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1- D 22 @ 150 + D 0 @ 0 = 25.34 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 25.34 ㎠
Puse = As (used) / (b × d) = 13.41 / (100 x 74.2 ) Puse = As (used) / (b × d) = 25.34 / (100 x 63.9 )
= 0.0018 ≥ Pmin(2) = 0.0015 --- O.K = 0.0040 ≥ P(req) = 0.0036 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 344.43 kN·m > Mu = 207.747 kN·m = 551.11 kN·m > Mu = 500.312 kN·m

E) Check of Thermal & Shrinkage


As (total) = 13.41 + 25.34 = 38.75 ㎠ > As shr.= 0.002 (B x H) = 16.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 129 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 409.768 = kN
φVc = 0.75 × 0.17 ×√fck ×bo ×d 446.243 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 162.2 kN·m (unfactored Moment) Ms = 394.7 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 25.34 cm2 ( 1 lay.- D22 + D0 )
H= 80 cm H= 80 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 5.80 cm dcg = 16.10 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 75.00 cm ( = H - Cc ) d₁= 65.00 cm ( = H - Cc )
d₂= 74.20 cm ( = H - dcg ) d₂= 63.90 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.164 × 74.2 = 12.30 cm = 0.223 × 63.9 = 14.50 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.002 + √ [( 8×0.002 )^2 + 2×8×0.002 ] = -8×0.004 + √ [( 8×0.004 )^2 + 2×8×0.004 ]
= 0.164 = 0.223
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 74.2 ) p : As / (B × d2) = 25.34 / ( 100 × 63.9 )
= 0.0020 = 0.0040

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 161.255 ) - 2.5 × 5 = 380 × (280 / 239.652 ) - 2.5 × 15
= 647.3 mm > 300(280/fs) = 521 mm = 406.5 mm > 300(280/fs) = 351 mm
∴ s= 521 mm > 150 mm ------ O.K ∴ s= 351 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 162.18 / [ 13.41 × ( 75 - / 3 )] fs = 394.73 / [ 25.34 × ( 65 - / 3 )]
= 16,126 N/cm2 = 23,965 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 130 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.7 Flexure & Shear Check ( F.D FAN FDN-1 )

1) Foundation Depth : T=1450mm ( Y- direction )


(1) Design Condition
fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00
Height of Section : H = 145.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 7.85 ㎝
: [ BOT ] dc = 17.85 ㎝
Effective Depth : [ TOP ] d = 137.15 ㎝

H
d
: [ BOT ] d = 127.15 ㎝
Factored Moment : [ TOP ] Mu = 119.4 kN·m BOT
: [ BOT ] Mu = 114.0 kN·m
Factored Shear force : Vu = 119.4 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1890 · 390 = 737100.0 T = As · fy = 1890 · 390 = 737100.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 28.906 mm T = C , then, a = 28.906 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1450 - 34.577 - 78.5) / 34.577 = 0.0030 x (1450 - 34.577 - 178.5) / 34.577
= 0.116 > 0.0040 ---- O.K = 0.1073 > 0.0040 ---- O.K
where, c = a / β1 = 28.906 / 0.836 where, c = a / β1 = 28.906 / 0.836
= 34.577 mm = 34.577 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 2.484 cm2 ∴ As(req) = 2.558 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0002 P(req) = As/(b×d) = 0.0002
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0003 (Controlled) Pmin(2) = 4/3 x Preq = 0.0003 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 19 @ 150 + D 0 @ 0 = 18.90 ㎠ 1 - D 19 @ 150 + D 0 @ 0 = 18.90 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 18.90 ㎠ ∑ = 18.90 ㎠
Puse = As (used) / ( b×d ) = 18.9 / (100 x 137.2 ) Puse = As (used) / ( b×d ) = 18.9 / (100 x 127.15 )
= 0.0014 ≥ Pmin(2) = 0.0003 --- O.K = 0.0015 ≥ Pmin(2) = 0.0003 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 900.25 kN·m > Mu = 119.415 kN·m = 833.91 kN·m > Mu = 113.997 kN·m
E) Check of Thermal & Shrinkage
As (total) = 18.90 + 18.90 = 37.80 ㎠ > As shr.= 0.002 (B x H) = 29.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 131 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 119.394 = kN
φVc = 0.75 × 0.17 × λ ×√fck ×bo ×d 887.947 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 95.5 kN·m (unfactored Moment) Ms = 86.1 kN·m (unfactored Moment)
As = 18.90 cm2 ( 1 lay.- D19 + D0 ) As = 18.90 cm2 ( 1 lay.- D19 + D0 )
H = 145 cm H = 145 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 7.85 cm dcg = 17.85 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 140.00 cm ( = H - Cc ) d₁= 130.00 cm ( = H - Cc )
d₂= 137.15 cm ( = H - dcg ) d₂= 127.15 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 137.15 = 16.66 cm = 0.119 × 127.15 = 15.47 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ]
= 0.119 = 0.119
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 18.9 / ( 100 × 137.15 ) p : As / (B × d2) = 18.9 / ( 100 × 127.15 )
= 0.0010 = 0.0010

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 37.591 ) - 2.5 × 5 = 380 × (280 / 36.472 ) - 2.5 × 15
= 2,818.0 mm > 300(280/fs) = 2,235 mm = 2,879.8 mm > 300(280/fs) = 2,303 mm
∴ s= 2,235 mm > 150 mm ------ O.K ∴ s= 2,303 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 95.52 / [ 18.9 × ( 140 - 16.66 / 3 )] fs = 86.06 / [ 18.9 × ( 130 - 15.47 / 3 )]
= 3,759 N/cm2 = 3,647 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 132 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Foundation Depth : T=1450mm ( X- direction )


(1) Design Condition

fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00


Height of Section : H = 145.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 5.95 ㎝
: [ BOT ] dc = 15.95 ㎝
Effective Depth : [ TOP ] d = 139.05 ㎝

H
d
: [ BOT ] d = 129.05 ㎝
Factored Moment : [ TOP ] Mu = 286.9 kN·m BOT
: [ BOT ] Mu = 114.7 kN·m
Factored Shear force : Vu = 235.6 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1890 · 390 = 737100.0 T = As · fy = 1890 · 390 = 737100.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 28.906 mm T = C , then, a = 28.906 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1450 - 34.577 - 59.5) / 34.577 = 0.0030 x (1450 - 34.577 - 159.5) / 34.577
= 0.1176 > 0.0040 ---- O.K = 0.109 > 0.0040 ---- O.K
where, c = a / β1 = 28.906 / 0.836 where, c = a / β1 = 28.906 / 0.836
= 34.577 mm = 34.577 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 5.898 cm2 ∴ As(req) = 2.537 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0004 P(req) = As/(b×d) = 0.0002
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0005 (Controlled) Pmin(2) = 4/3 x Preq = 0.0003 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 19 @ 150 + D 0 @ 0 = 18.90 ㎠ 1- D 19 @ 150 + D 0 @ 0 = 18.90 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 18.90 ㎠ ∑ = 18.90 ㎠
Puse = As (used) / (b × d) = 18.9 / (100 x 139.05 ) Puse = As (used) / (b × d) = 18.9 / (100 x 129.05 )
= 0.0014 ≥ Pmin(2) = 0.0005 --- O.K = 0.0015 ≥ Pmin(2) = 0.0003 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 912.86 kN·m > Mu = 286.907 kN·m = 846.52 kN·m > Mu = 114.728 kN·m

E) Check of Thermal & Shrinkage


As (total) = 18.90 + 18.90 = 37.80 ㎠ > As shr.= 0.002 (B x H) = 29.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 133 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 235.592 = kN
φVc = 0.75 × 0.17 ×√fck ×bo ×d 901.216 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 228.9 kN·m (unfactored Moment) Ms = 86.6 kN·m (unfactored Moment)
As = 18.90 cm2 ( 1 lay.- D19 + D0 ) As = 18.90 cm2 ( 1 lay.- D19 + D0 )
H = 145 cm H = 145 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 5.95 cm dcg = 15.95 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 140.00 cm ( = H - Cc ) d₁= 130.00 cm ( = H - Cc )
d₂= 139.05 cm ( = H - dcg ) d₂= 129.05 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 139.05 = 16.66 cm = 0.119 × 129.05 = 15.47 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ]
= 0.119 = 0.119
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 18.9 / ( 100 × 139.05 ) p : As / (B × d2) = 18.9 / ( 100 × 129.05 )
= 0.0010 = 0.0010

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 86.49 ) - 2.5 × 5 = 380 × (280 / 35.256 ) - 2.5 × 15
= 1,217.7 mm > 300(280/fs) = 971 mm = 2,980.4 mm > 300(280/fs) = 2,383 mm
∴ s= 971 mm > 150 mm ------ O.K ∴ s= 2,383 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 228.85 / [ 18.9 × ( 140 - / 3 )] fs = 86.63 / [ 18.9 × ( 130 - / 3 )]
= 8,649 N/cm2 = 3,526 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 134 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.8 Flexure & Shear Check ( F.D FAN FDN-2 )

1) Foundation Depth : T=1000mm ( Y- direction )


(1) Design Condition
fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00
Height of Section : H = 100.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 7.40 ㎝
: [ BOT ] dc = 17.40 ㎝
Effective Depth : [ TOP ] d = 92.60 ㎝

H
d
: [ BOT ] d = 82.60 ㎝
Factored Moment : [ TOP ] Mu = 148.3 kN·m BOT
: [ BOT ] Mu = 121.3 kN·m
Factored Shear force : Vu = 320.8 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1000 - 24.532 - 74) / 24.532 = 0.0030 x (1000 - 24.532 - 174) / 24.532
= 0.1102 > 0.0040 ---- O.K = 0.098 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 4.580 cm2 ∴ As(req) = 4.199 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0005 P(req) = As/(b×d) = 0.0005
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0007 (Controlled) Pmin(2) = 4/3 x Preq = 0.0007 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / ( b×d ) = 13.41 / (100 x 92.6 ) Puse = As (used) / ( b×d ) = 13.41 / (100 x 82.6 )
= 0.0014 ≥ Pmin(2) = 0.0007 --- O.K = 0.0016 ≥ Pmin(2) = 0.0007 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 431.03 kN·m > Mu = 148.305 kN·m = 383.96 kN·m > Mu = 121.259 kN·m
E) Check of Thermal & Shrinkage
As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 20.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 135 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 320.840 = kN
φVc = 0.75 × 0.17 × λ ×√fck ×bo ×d 576.834 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 116.4 kN·m (unfactored Moment) Ms = 93.0 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H = 100 cm H = 100 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 7.40 cm dcg = 17.40 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 95.00 cm ( = H - Cc ) d₁= 85.00 cm ( = H - Cc )
d₂= 92.60 cm ( = H - dcg ) d₂= 82.60 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 92.6 = 11.31 cm = 0.164 × 82.6 = 13.94 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.002 + √ [( 8×0.002 )^2 + 2×8×0.002 ]
= 0.119 = 0.164
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 92.6 ) p : As / (B × d2) = 13.41 / ( 100 × 82.6 )
= 0.0010 = 0.0020

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 95.114 ) - 2.5 × 5 = 380 × (280 / 86.339 ) - 2.5 × 15
= 1,106.2 mm > 300(280/fs) = 883 mm = 1,194.9 mm > 300(280/fs) = 973 mm
∴ s= 883 mm > 150 mm ------ O.K ∴ s= 973 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 116.36 / [ 13.41 × ( 95 - 11.305 / 3 )] fs = 93.03 / [ 13.41 × ( 85 - 13.94 / 3 )]
= 9,511 N/cm2 = 8,634 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 136 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Foundation Depth : T=1000mm ( X- direction )


(1) Design Condition

fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00


Height of Section : H = 100.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 5.80 ㎝
: [ BOT ] dc = 15.80 ㎝
Effective Depth : [ TOP ] d = 94.20 ㎝

H
d
: [ BOT ] d = 84.20 ㎝
Factored Moment : [ TOP ] Mu = 150.5 kN·m BOT
: [ BOT ] Mu = 224.9 kN·m
Factored Shear force : Vu = 256.1 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (1000 - 24.532 - 58) / 24.532 = 0.0030 x (1000 - 24.532 - 158) / 24.532
= 0.1122 > 0.0040 ---- O.K = 0.1 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 4.570 cm2 ∴ As(req) = 7.662 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0005 P(req) = As/(b×d) = 0.0009
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 = 0.0036
Pmin(2) = 4/3 x Preq = 0.0007 (Controlled) Pmin(2) = 4/3 x Preq = 0.0012 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1- D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / (b × d) = 13.41 / (100 x 94.2 ) Puse = As (used) / (b × d) = 13.41 / (100 x 84.2 )
= 0.0014 ≥ Pmin(2) = 0.0007 --- O.K = 0.0016 ≥ Pmin(2) = 0.0012 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 438.56 kN·m > Mu = 150.542 kN·m = 391.50 kN·m > Mu = 224.872 kN·m

E) Check of Thermal & Shrinkage


As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 20.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 137 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 256.105 = kN
φVc = 0.75 × 0.17 ×√fck ×bo ×d 588.008 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 117.4 kN·m (unfactored Moment) Ms = 173.2 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H = 100 cm H = 100 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 5.80 cm dcg = 15.80 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 95.00 cm ( = H - Cc ) d₁= 85.00 cm ( = H - Cc )
d₂= 94.20 cm ( = H - dcg ) d₂= 84.20 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.119 × 94.2 = 11.31 cm = 0.164 × 84.2 = 13.94 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.001 + √ [( 8×0.001 )^2 + 2×8×0.001 ] = -8×0.002 + √ [( 8×0.002 )^2 + 2×8×0.002 ]
= 0.119 = 0.164
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 94.2 ) p : As / (B × d2) = 13.41 / ( 100 × 84.2 )
= 0.0010 = 0.0020

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 92.119 ) - 2.5 × 5 = 380 × (280 / 151.985 ) - 2.5 × 15
= 1,142.5 mm > 300(280/fs) = 912 mm = 662.6 mm > 300(280/fs) = 553 mm
∴ s= 912 mm > 150 mm ------ O.K ∴ s= 553 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 117.36 / [ 13.41 × ( 95 - / 3 )] fs = 173.24 / [ 13.41 × ( 85 - / 3 )]
= 9,212 N/cm2 = 15,198 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 138 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.9 Flexure & Shear Check ( Duct support & Platform , PILE FDN )

1) Foundation Depth : T=400mm ( Y- direction )


(1) Design Condition
fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00
Height of Section : H = 40.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 5.80 ㎝
: [ BOT ] dc = 15.80 ㎝
Effective Depth : [ TOP ] d = 34.20 ㎝

H
d
: [ BOT ] d = 24.20 ㎝
Factored Moment : [ TOP ] Mu = 116.8 kN·m BOT
: [ BOT ] Mu = 24.9 kN·m
Factored Shear force : Vu = 152.3 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (400 - 24.532 - 58) / 24.532 = 0.0030 x (400 - 24.532 - 158) / 24.532
= 0.0388 > 0.0040 ---- O.K = 0.0266 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 9.952 cm2 ∴ As(req) = 2.963 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0029 P(req) = As/(b×d) = 0.0012
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 (Controlled) = 0.0036
Pmin(2) = 4/3 x Preq = 0.0039 Pmin(2) = 4/3 x Preq = 0.0016 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / ( b×d ) = 13.41 / (100 x 34.2 ) Puse = As (used) / ( b×d ) = 13.41 / (100 x 24.2 )
= 0.0039 ≥ Pmin(1) = 0.0036 --- O.K = 0.0055 ≥ Pmin(2) = 0.0016 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 156.15 kN·m > Mu = 116.806 kN·m = 109.08 kN·m > Mu = 24.936 kN·m
E) Check of Thermal & Shrinkage
As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 8.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 139 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 152.323 = kN
φVc = 0.75 × 0.17 × λ ×√fck ×bo ×d 169.000 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 93.2 kN·m (unfactored Moment) Ms = 18.5 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H= 40 cm H= 40 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 5.80 cm dcg = 15.80 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 35.00 cm ( = H - Cc ) d₁= 25.00 cm ( = H - Cc )
d₂= 34.20 cm ( = H - dcg ) d₂= 24.20 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.223 × 34.2 = 7.81 cm = 0.266 × 24.2 = 6.65 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.004 + √ [( 8×0.004 )^2 + 2×8×0.004 ] = -8×0.006 + √ [( 8×0.006 )^2 + 2×8×0.006 ]
= 0.223 = 0.266
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 34.2 ) p : As / (B × d2) = 13.41 / ( 100 × 24.2 )
= 0.0040 = 0.0060

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 214.548 ) - 2.5 × 5 = 380 × (280 / 60.668 ) - 2.5 × 15
= 483.4 mm > 300(280/fs) = 392 mm = 1,716.3 mm > 300(280/fs) = 1,385 mm
∴ s= 392 mm > 150 mm ------ O.K ∴ s= 1,385 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 93.21 / [ 13.41 × ( 35 - 7.805 / 3 )] fs = 18.54 / [ 13.41 × ( 25 - 6.65 / 3 )]
= 21,455 N/cm2 = 6,067 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 140 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Foundation Depth : T=400mm ( X- direction )


(1) Design Condition

fck = 30 MPa Φf = 0.90 Φv = 0.75 β1 = 0.836 λ= 1.00


Height of Section : H = 40.0 ㎝
Width of Section : B = 100.0 ㎝ B
Concrete Cover : [ TOP ] Cc = 5.00 ㎝
: [ BOT ] Cc = 15.00 ㎝

dc
TOP
Design Cover : [ TOP ] dc = 7.40 ㎝
: [ BOT ] dc = 17.40 ㎝
Effective Depth : [ TOP ] d = 32.60 ㎝

H
d
: [ BOT ] d = 22.60 ㎝
Factored Moment : [ TOP ] Mu = 108.4 kN·m BOT
: [ BOT ] Mu = 22.7 kN·m
Factored Shear force : Vu = 88.6 kN

(2) Check of Bending Moment

A) As (req)
[ TOP ] fy = 390 MPa [ BOT ] fy = 390 MPa
T = As · fy = 1341 · 390 = 522990.0 T = As · fy = 1341 · 390 = 522990.0
C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000 C = 0.85 · fck · a · B = 0.85 · 30 · a · 1000
= 25500.0 x a = 25500.0 x a
T = C , then, a = 20.509 mm T = C , then, a = 20.509 mm
εy = fy / Es = 390 / 200000 = 0.0020 εy = fy / Es = 390 / 200000 = 0.002
εt = 0.0030 x ( H - c - dc ) / c εt = 0.0030 x ( H - c - dc ) / c
= 0.0030 x (400 - 24.532 - 74) / 24.532 = 0.0030 x (400 - 24.532 - 174) / 24.532
= 0.0369 > 0.0040 ---- O.K = 0.0246 > 0.0040 ---- O.K
where, c = a / β1 = 20.509 / 0.836 where, c = a / β1 = 20.509 / 0.836
= 24.532 mm = 24.532 mm
∴ Φf = 0.90 ∴ Φf = 0.90
( εt ≥ 0.0050 , Tension controlled section) ( εt ≥ 0.0050 , Tension controlled section)
Mu = Φ·As·fy·(d-a/2) , Mu = Φ·As·fy·(d-a/2) ,
a = As·fy / 0.85 ·fck ·B = 0.15294 As a = As·fy / 0.85 ·fck ·B = 0.15294 As
∴ As(req) = 9.694 cm2 ∴ As(req) = 2.884 cm2

B) Check of Rebar ratio


[ TOP ] [ BOT ]
P(req) = As/(b×d) = 0.0030 P(req) = As/(b×d) = 0.0013
Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy ) Pmin(1) = Max( 0.25 × √ fck / fy, 1.4 /fy )
= 0.0036 (Controlled) = 0.0036
Pmin(2) = 4/3 x Preq = 0.0040 Pmin(2) = 4/3 x Preq = 0.0017 (Controlled)

C) As used
[ TOP ] [ BOT ]
1 - D 16 @ 150 + D 0 @ 0 = 13.41 ㎠ 1- D 16 @ 150 + D 0 @ 0 = 13.41 ㎠
2 - D 0 @ 0 + D 0 @ 0 = 0.00 ㎠ 2- D 0 @ 0 + D 0 @ 0 = 0.00 ㎠
∑ = 13.41 ㎠ ∑ = 13.41 ㎠
Puse = As (used) / (b × d) = 13.41 / (100 x 32.6 ) Puse = As (used) / (b × d) = 13.41 / (100 x 22.6 )
= 0.0041 ≥ Pmin(1) = 0.0036 --- O.K = 0.0059 ≥ Pmin(2) = 0.0017 --- O.K

D) Check of Moment Capacity


ΦMn = Φ x As x fy x ( d -a / 2) ΦMn = Φ x As x fy x ( d -a / 2)
= 148.62 kN·m > Mu = 108.407 kN·m = 101.55 kN·m > Mu = 22.651 kN·m

E) Check of Thermal & Shrinkage


As (total) = 13.41 + 13.41 = 26.82 ㎠ > As shr.= 0.002 (B x H) = 8.00 ㎠ --- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 141 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check of Shear force


Factored Shear force Vu 88.583 = kN
φVc = 0.75 × 0.17 ×√fck ×bo ×d 157.826 = kN
0.000
where , φVc > Vu , then No Shear reinforcement is required !!!

4) Check of Crack

[ TOP ] Normal face [ BOT ] Normal face


Ms = 85.1 kN·m (unfactored Moment) Ms = 16.6 kN·m (unfactored Moment)
As = 13.41 cm2 ( 1 lay.- D16 + D0 ) As = 13.41 cm2 ( 1 lay.- D16 + D0 )
H= 40 cm H= 40 cm
B = 100 cm B = 100 cm
Cc = 5.00 cm Cc = 15.00 cm
(Concrete Cover) (Concrete Cover)
dcg = 7.40 cm dcg = 17.40 cm
(Distance to centroid of tension bar group) (Distance to centroid of tension bar group)
d₁= 35.00 cm ( = H - Cc ) d₁= 25.00 cm ( = H - Cc )
d₂= 32.60 cm ( = H - dcg ) d₂= 22.60 cm ( = H - dcg )
n = 6.67 EA : Number of tension bars n = 6.67 EA : Number of tension bars
s= B/n s= B/n
= 100 / 6.67 = 14.99 cm = 100 / 6.67 = 14.99 cm
χ = k × d₂ χ = k × d₂
= 0.223 × 32.6 = 7.81 cm = 0.266 × 22.6 = 6.65 cm
k = - N × p + √{(N × p)^2 + 2 × N × p} k = - N × p + √{(N × p)^2 + 2 × N × p}
= -8×0.004 + √ [( 8×0.004 )^2 + 2×8×0.004 ] = -8×0.006 + √ [( 8×0.006 )^2 + 2×8×0.006 ]
= 0.223 = 0.266
N : Es / Ec = 200000 / 25740 = 8 N : Es / Ec = 200000 / 25740 = 8
p : As / (B × d2) = 13.41 / ( 100 × 32.6 ) p : As / (B × d2) = 13.41 / ( 100 × 22.6 )
= 0.0040 = 0.0060

[ACI 318] [ACI 318]


s = 380 (280 / fs) - 2.5 Cc s = 380 (280 / fs) - 2.5 Cc
= 380 × (280 / 181.353 ) - 2.5 × 5 = 380 × (280 / 49.418 ) - 2.5 × 15
= 574.2 mm > 300(280/fs) = 463 mm = 2,115.6 mm > 300(280/fs) = 1,700 mm
∴ s= 463 mm > 150 mm ------ O.K ∴ s= 1,700 mm > 150 mm ------ O.K
where, fs = Ms / [As × ( d₁ - χ / 3 ) ] where, fs = Ms / [As × ( d₁ - χ / 3 ) ]
(stress in rebar closest to tension face at service load) (stress in rebar closest to tension face at service load)
fs = 85.12 / [ 13.41 × ( 35 - / 3 )] fs = 16.57 / [ 13.41 × ( 25 - / 3 )]
= 18,135 N/cm2 = 4,942 N/cm2
Cc = 5.00 cm Cc = 15.00 cm
(Clear Cover of Reinforcement) (Clear Cover of Reinforcement)

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 142 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.10 Bottom Slab Punching Shear Check

1) P.A FAN FDN-1 (PED-1)

Pedestal Size
4500 mm x 3600 mm

950

1100
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA12 1323.42

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 47231.27 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 33686.58 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 34342.20 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 110 - 15.0 = 95.0 cm


bo : the perimeter of critical section about two way shear
= [( 450 + 95 / 2 x 2 ea ) + ( 360 + 95 / 2 x 2 ea)] x 2
= 2000.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 545.0 / 455.0 = 1.20
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 33686.580 kN

Φv Vc = 0.75 x 33686.580 = 25264.935 kN > Vu = 1323.420 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 143 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) P.A FAN FDN-1 (PED-2)

Pedestal Size
1356 mm x 3600 mm

950

1100
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA11 415.38

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 59994.03 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 28255.27 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 23545.02 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 110 - 15.0 = 95.0 cm


bo : the perimeter of critical section about two way shear
= [( 136 + 95 / 2 x 2 ea ) + ( 360 + 95 / 2 x 2 ea)] x 2
= 1371.20 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 230.6 / 455.0 = 0.51
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 23545.015 kN

Φv Vc = 0.75 x 23545.015 = 17658.761 kN > Vu = 415.378 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 144 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) P.A FAN FDN-1 (PED-3)

Pedestal Size
1200 mm x 1200 mm

950

1100
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA8 21.28

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 22821.96 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 23839.73 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 14767.15 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 110 - 15.0 = 95.0 cm


bo : the perimeter of critical section about two way shear
= [( 120 + 95 / 2 x 2 ea ) + ( 120 + 95 / 2 x 2 ea)] x 2
= 860.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 215.0 / 215.0 = 1.00
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 14767.148 kN

Φv Vc = 0.75 x 14767.148 = 11075.361 kN > Vu = 21.280 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 145 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) P.A FAN FDN-2 (PED-1)

Pedestal Size
4500 mm x 3600 mm

650

800
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA10 1323.42

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 30158.25 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 18793.57 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 22087.46 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 80 - 15.0 = 65.0 cm


bo : the perimeter of critical section about two way shear
= [( 450 + 65 / 2 x 2 ea ) + ( 360 + 65 / 2 x 2 ea)] x 2
= 1880.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 515.0 / 425.0 = 1.21
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 18793.566 kN

Φv Vc = 0.75 x 18793.566 = 14095.174 kN > Vu = 1323.420 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 146 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) P.A FAN FDN-2 (PED-2)

Pedestal Size
1356 mm x 3600 mm

650

800
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA9 415.38

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 39660.31 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 15077.40 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 14699.91 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 80 - 15.0 = 65.0 cm


bo : the perimeter of critical section about two way shear
= [( 136 + 65 / 2 x 2 ea ) + ( 360 + 65 / 2 x 2 ea)] x 2
= 1251.20 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 200.6 / 425.0 = 0.47
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 14699.909 kN

Φv Vc = 0.75 x 14699.909 = 11024.932 kN > Vu = 415.378 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 147 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6) P.A FAN FDN-2 (PED-3)

Pedestal Size
1200 mm x 1200 mm

650

800
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 PA7 18.76

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 13436.18 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 12056.25 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 8694.00 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 80 - 15.0 = 65.0 cm


bo : the perimeter of critical section about two way shear
= [( 120 + 65 / 2 x 2 ea ) + ( 120 + 65 / 2 x 2 ea)] x 2
= 740.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 185.0 / 185.0 = 1.00
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 8694.000 kN

Φv Vc = 0.75 x 8694.000 = 6520.500 kN > Vu = 18.760 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 148 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7) P.A FAN FDN-2 (PED-4)

Pedestal Size
600 mm x 600 mm

650

800
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Seismic LCOM216 PA5 229.84

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 9078.50 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 10637.87 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 5874.32 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 80 - 15.0 = 65.0 cm


bo : the perimeter of critical section about two way shear
= [( 60 + 65 / 2 x 2 ea ) + ( 60 + 65 / 2 x 2 ea)] x 2
= 500.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 125.0 / 125.0 = 1.00
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 5874.324 kN

Φv Vc = 0.75 x 5874.324 = 4405.743 kN > Vu = 229.840 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 149 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8) F.D FAN FDN-1 (PED-1)

Pedestal Size
3690 mm x 3400 mm

1300

1450
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 FD11 706.45

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 67649.86 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 53638.49 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 45537.76 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 145 - 15.0 = 130.0 cm


bo : the perimeter of critical section about two way shear
= [( 369 + 130 / 2 x 2 ea ) + ( 340 + 130 / 2 x 2 ea)] x 2
= 1938.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 499.0 / 470.0 = 1.06
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 45537.763 kN

Φv Vc = 0.75 x 45537.763 = 34153.322 kN > Vu = 706.454 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 150 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9) F.D FAN FDN-1 (PED-2)

Pedestal Size
1720 mm x 3400 mm

1300

1450
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM210 FD12 382.34

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 76862.56 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 48981.47 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 36279.83 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 145 - 15.0 = 130.0 cm


bo : the perimeter of critical section about two way shear
= [( 172 + 130 / 2 x 2 ea ) + ( 340 + 130 / 2 x 2 ea)] x 2
= 1544.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 302.0 / 470.0 = 0.64
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 36279.828 kN

Φv Vc = 0.75 x 36279.828 = 27209.871 kN > Vu = 382.337 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 151 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

10) F.D FAN FDN-1 (PED-2)

Pedestal Size
850 mm x 950 mm

1300

1450
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 FD8 12.68

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 32947.22 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 41133.09 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 20677.62 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 145 - 15.0 = 130.0 cm


bo : the perimeter of critical section about two way shear
= [( 85 + 130 / 2 x 2 ea ) + ( 95 + 130 / 2 x 2 ea)] x 2
= 880.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 215.0 / 225.0 = 0.96
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 20677.622 kN

Φv Vc = 0.75 x 20677.622 = 15508.216 kN > Vu = 12.679 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 152 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

11) F.D FAN FDN-2 (PED-1)

Pedestal Size
3690 mm x 3400 mm

850

1000
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 FD9 684.50

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 39964.01 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 26724.69 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 27009.24 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 100 - 15.0 = 85.0 cm


bo : the perimeter of critical section about two way shear
= [( 369 + 85 / 2 x 2 ea ) + ( 340 + 85 / 2 x 2 ea)] x 2
= 1758.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 454.0 / 425.0 = 1.07
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 26724.687 kN

Φv Vc = 0.75 x 26724.687 = 20043.515 kN > Vu = 684.499 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 153 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

12) F.D FAN FDN-2 (PED-2)

Pedestal Size
1720 mm x 3400 mm

850

1000
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM210 FD10 382.34

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 46500.47 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 23679.71 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 20955.97 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 100 - 15.0 = 85.0 cm


bo : the perimeter of critical section about two way shear
= [( 172 + 85 / 2 x 2 ea ) + ( 340 + 85 / 2 x 2 ea)] x 2
= 1364.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 257.0 / 425.0 = 0.60
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 20955.975 kN

Φv Vc = 0.75 x 20955.975 = 15716.981 kN > Vu = 382.337 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 154 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

13) F.D FAN FDN-2 (PED-3)

Pedestal Size
850 mm x 950 mm

850

1000
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 FD7 12.68

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 17272.43 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 18548.08 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 10754.53 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 100 - 15.0 = 85.0 cm


bo : the perimeter of critical section about two way shear
= [( 85 + 85 / 2 x 2 ea ) + ( 95 + 85 / 2 x 2 ea)] x 2
= 700.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 170.0 / 180.0 = 0.94
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 10754.532 kN

Φv Vc = 0.75 x 10754.532 = 8065.899 kN > Vu = 12.679 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 155 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

14) F.D FAN FDN-2 (PED-4)

Pedestal Size
600 mm x 600 mm

850

1000
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM210 FD4 141.16

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 13771.39 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 17620.67 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 8910.90 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 100 - 15.0 = 85.0 cm


bo : the perimeter of critical section about two way shear
= [( 60 + 85 / 2 x 2 ea ) + ( 60 + 85 / 2 x 2 ea)] x 2
= 580.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 145.0 / 145.0 = 1.00
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 8910.898 kN

Φv Vc = 0.75 x 8910.898 = 6683.174 kN > Vu = 141.160 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 156 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

15) DUCT& PLATFORM FDN

Pedestal Size
600 mm x 600 mm

250

400
150
bo

Load Frame Factored Pedestal reactions


Load Case
Comb. No. Pvmax (kN/Pedestal)
Static LCOM201 D11 146.09

Vc1 = 0.17 x (1+2/βc) x λ x √fck x bo x d = 2374.38 kN (ACI318-14 Chapter 22.6.5.2 (a))

Vc2 = 0.083 x (2+(αs x d)/(bo)) x λ x √fck x bo x d = 1909.36 kN (ACI318-14 Chapter 22.6.5.2 (b))

Vc3 = 0.33 x λ x √fck x bo x d = 1536.36 kN (ACI318-14 Chapter 22.6.5.2 (c))

d : Effective Depth about Bottom Slab = 40 - 15.0 = 25.0 cm


bo : the perimeter of critical section about two way shear
= [( 60 + 25 / 2 x 2 ea ) + ( 60 + 25 / 2 x 2 ea)] x 2
= 340.00 cm
βc : the ratio of long side to short side of the column, concentrated load or reaction area
= 85.0 / 85.0 = 1.00
αs : interior columns = 40
λ : modification factor for lightweight concrete = 1.00

∴ Vc = MIN(Vc1,Vc2,Vc3) = 1536.362 kN

Φv Vc = 0.75 x 1536.362 = 1152.271 kN > Vu = 146.090 kN


OK!. shear reinforcement is not required

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 157 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.11 Re-Bar Sketch

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 158 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 159 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 160 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.0 PEDESTAL DESIGN

8.1 General

Pedestal design is directly performed by using the P-M interaction diagram in SAP2000. To do this, at
first, regardless of the compression and tension loads, Fz, Mx and My of each load combination are
obtained and plotted on the P-M interaction diagram so that one can know whether it is safe or not. Also,
because the capacity of pedestal in each direction (X ,Y) is different according to arrangement of rebar
and geometric configuration, it is checked for the each direction in pedestal of asymmetric shape.

Pedestal stress resultants in ultimate condition for each pedestal are obtained by using the option
"Offset" in SAP2000 in order to consider the location of bottom of pedestal which meets the concrete top
surface of base mat.

1) Location & No. of Pedestal

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 161 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) V2, V3 for Pedestal members subject to axial Compression, Tension case ( Ultimate conditon )

[ Unit : KN. M ]
Load Combination Envelopes Only
Pedestal size fc'xAg Pu.max Additional
Type CONDITION Comp.Min REMARKS
(BXH) Max.V2 Max.V3 x0.1 (comp.) Hoops or Ties
&Tens.Max

P.A Compression 823.770 33.000 33.000


4500 X 3600 48600 1323 not needed
PED-1 Tension 0.000 33.000 33.000

P.A Compression 823.770 33.000 33.000


1356 X 3600 14644.8 415 not needed
PED-2 Tension 0.000 33.000 33.000

P.A Compression 823.770 33.000 33.000


1200 X 1200 4320 21 not needed
PED-3 Tension 0.000 33.000 33.000

P.A Compression 823.770 33.000 33.000


600 X 600 1080 230 not needed
PED-4 Tension 0.000 33.000 33.000

F.D Compression 823.770 33.000 33.000


3690 X 3400 37638 706 not needed
PED-1 Tension 0.000 33.000 33.000

F.D Compression 823.770 33.000 33.000


1720 X 3400 17544 382 not needed
PED-2 Tension 0.000 33.000 33.000

F.D Compression 823.770 33.000 33.000


850 X 950 2422.5 13 not needed
PED-3 Tension 0.000 33.000 33.000

F.D Compression 823.770 33.000 33.000


600 X 600 1080 141 not needed
PED-4 Tension 0.000 33.000 33.000
Compression 7.835 55.300 14.460
Duct 600 X 600 1080 146 not needed
Tension 0.000 55.300 14.460

Table lists the loads to obtain the shear capacity in pedestal members. The values of Comp. Min. in
'Compression' rows result from the min. compression (Fz), max. shear of member in compression (V2, V3)
And those of Tens. Max. in 'Tension' rows result from the max. tension (Fz), max. shear of member in
tension (V2, V3) in order to apply the formula in ACI318-14 Chapter 22.5.6.1 and design the most
unfavorably. The original data is referenced from 'SAP2000 OUTPUT DATA'

For members subject to axial compression and tension, shear strength provided by concrete complies with
ACI 318-14 Section 22.5 "One-way Shear Strength" and it is arranged appropriately with the requirements in
ACI318-14 Chapter 25.7.2.1 "Ties" But in case the factored axial compressive forces do not exceed 0.1f'cAg,
the pedestal can be considered as a flexural member and ACI318-14 Section 25.7.2 "Ties" provisions
corresponding to compression member can be disregarded. Also in case the factored axial compressive
forces do exceed 0.1f'cAg, the pedestal can be considered as a compression member and ACI318-14
Chapter 18.4.3 "Columns" provisions.

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 162 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.2 Section Calculation

1) Pedestal < P.A PED-1 > ( 4500 x 3600 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -222593.0 0.0 0.0 D22 x 108 ea
2 -222593.0 60595.0 -60595.0
3 -220076.0 104282.0 -104282.0 Concrete cover
4 -192009.0 136157.0 -136157.0 : 50 mm
5 -163543.0 156404.0 -156404.0
6 -134447.0 165357.0 -165357.0 Re-bar Arrange
7 -122938.0 184770.0 -184770.0 X: 31 ea
8 -108321.0 195873.0 -195873.0 Y: 25 ea
9 -69407.0 152706.0 -152706.0 Y HOOP
10 -30495.0 91786.0 -91786.0 : D13@200mm
11 14409.0 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of pedestal have
capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it indicates scope of capacity
from Sap2000 containing the re-bar properties.

P (kN)
50000
Tension
M (kN.m)
0
-250000 -200000 -150000 -100000 -50000 0 50000 100000 150000 200000 250000

-50000

-100000

-150000

-200000

-250000 Compression
Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.

Tension (max) = 0 < P = 14409 ··· O.K


Pu
Compression (max) = 1323 < P = 222593 ··· O.K
Moment (max) = 0 < Mx = 195873 ··· O.K
Mu
Moment (min) = -291 < Mx = -195873 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 163 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force

f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00


RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 48600 > 1323.42 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 3550 / 200 + 0.75 x 0 x 390 x 3550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 823.770 kN
Vu.max = 33.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 823770 / (14 x 3600 x 4500 ) ] x 1 x √ 30 x 4500 x 3550
= 11319.607 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 11319.607 + 0
= 11319.607 kN > Vu = 33.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 33.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 4500 x 3600 ) ] x 1 x √ 30 x 4500 x 3550
= 11278.641 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 11278.641 + 0
= 11278.641 kN > Vu = 33.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D22 = 352 mm
d = 3600 = 3600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 164 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -222593.0 0.0 0.0 D22 x 108 ea
2 -222593.0 49037.0 -49037.0
3 -219733.0 84169.0 -84169.0 Concrete cover
4 -191559.0 109804.0 -109804.0 : 50 mm
5 -162968.0 126128.0 -126128.0
6 -133741.0 133426.0 -133426.0 Re-bar Arrange
7 -122539.0 148837.0 -148837.0 X: 31 ea
8 -108359.0 157856.0 -157856.0 Y: 25 ea
9 -69940.0 123518.0 -123518.0 Y HOOP
10 -31521.0 75253.0 -75253.0 : D13@200mm
11 14409.0 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
50000
Tension

0 M (kN.m)
-200000 -150000 -100000 -50000 0 50000 100000 150000 200000

-50000

-100000

-150000

-200000

-250000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.

Tension (max) = 0 < P = 14409 ··· O.K


Pu
Compression (max) = 1323 < P = 222593 ··· O.K
Moment (max) = 163 < Mx = 157856 ··· O.K
Mu
Moment (min) = -81 < Mx = -157856 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 165 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 48600 > 1323.42 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 4450 / 200 + 0.75 x 0 x 390 x 4450 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 823.770 kN
Vu.max = 33.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 823770 / (14 x 3600 x 4500 ) ] x 1 x √ 30 x 3600 x 4450
= 11007.982 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 11007.982 + 0
= 11007.982 kN > Vu = 33.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 33.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 3600 x 4500 ) ] x 1 x √ 30 x 3600 x 4450
= 11187.507 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 11187.507 + 0
= 11187.507 kN > Vu = 33.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D22 = 352 mm
d = 3600 = 3600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 166 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D22 x 108 ea = 41050.8 ㎟


Ag = b x h = 16200000 ㎟
ρ.used = As.used / Ag = 0.0025 ··· O.K ( ∵ 0.002 < ρ.used = 0.0025 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 167 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) Pedestal < P.A PED-2 > ( 1356 x 3600 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -67246.0 0.0 0.0 D16 x 96 ea
2 -67246.0 1447726.0 -1447726.0
3 -66487.0 2499041.0 -2499041.0 Concrete cover
4 -57997.0 3262623.0 -3262623.0 : 50 mm
5 -49370.0 3743505.0 -3743505.0
6 -40539.0 3948023.0 -3948023.0 Re-bar Arrange
7 -36899.0 4414462.0 -4414462.0 X: 14 ea
8 -32265.0 4670571.0 -4670571.0 Y: 36 ea
9 -20328.0 3615985.0 -3615985.0 Y HOOP
10 -8391.0 2123693.0 -2123693.0 : D13@200mm
11 4658.7 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
10000
Tension
M (kN.m)
0
-6000000 -4000000 -2000000 0 2000000 4000000 6000000

-10000

-20000

-30000

-40000

-50000

-60000

-70000

Compression
-80000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 4659 ··· O.K
Pu
Compression (max) = 415 < P = 67246 ··· O.K
Moment (max) = 78 < Mx = 4670571 ··· O.K
Mu
Moment (min) = -32 < Mx = -4670571 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 168 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 14644.8 > 415.378 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 3550 / 200 + 0.75 x 0 x 390 x 3550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 221.829 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 221829 / (14 x 3600 x 1356 ) ] x 1 x √ 30 x 1356 x 3550
= 3412.512 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 3412.512 + 0
= 3412.512 kN > Vu = 23.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 1356 x 3600 ) ] x 1 x √ 30 x 1356 x 3550
= 3401.471 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 3401.471 + 0
= 3401.471 kN > Vu = 23.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D16 = 256 mm
d = 1356 = 1356 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 169 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -67246.0 0.0 0.0 D16 x 96 ea
2 -67246.0 575205.0 -575205.0
3 -65862.0 981795.0 -981795.0 Concrete cover
4 -57116.0 1275678.0 -1275678.0 : 50 mm
5 -48235.0 1459399.0 -1459399.0
6 -39119.0 1537124.0 -1537124.0 Re-bar Arrange
7 -35932.0 1700437.0 -1700437.0 X: 14 ea
8 -31903.0 1797366.0 -1797366.0 Y: 36 ea
9 -20770.0 1410846.0 -1410846.0 Y HOOP
10 -9612.0 875470.0 -875470.0 : D13@200mm
11 4658.7 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
10000
Tension
0
M (kN.m)
-2000000 -1500000 -1000000 -500000 0 500000 1000000 1500000 2000000

-10000

-20000

-30000

-40000

-50000

-60000

-70000

-80000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 4659 ··· O.K
Pu
Compression (max) = 415 < P = 67246 ··· O.K
Moment (max) = 52 < Mx = 1797366 ··· O.K
Mu
Moment (min) = -65 < Mx = -1797366 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 170 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 14644.8 > 415.378 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 1306 / 200 + 0.75 x 0 x 390 x 1306 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 221.829 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 221829 / (14 x 3600 x 1356 ) ] x 1 x √ 30 x 3600 x 1306
= 3229.414 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 3229.414 + 0
= 3229.414 kN > Vu = 23.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 3600 x 1356 ) ] x 1 x √ 30 x 3600 x 1306
= 3283.345 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 3283.345 + 0
= 3283.345 kN > Vu = 23.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D16 = 256 mm
d = 1356 = 1356 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 171 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D16 x 96 ea = 19305.6 ㎟


Ag = b x h = 4881600 ㎟
ρ.used = As.used / Ag = 0.0040 ··· O.K ( ∵ 0.002 < ρ.used = 0.004 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 172 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) Pedestal < P.A PED-3 > ( 1200 x 1200 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -22072.0 0.0 0.0 D25 x 32 ea
2 -22072.0 1900.9 -1900.9
3 -21020.0 3054.9 -3054.9 Concrete cover
4 -18097.0 3939.9 -3939.9 : 50 mm
5 -14996.0 4573.1 -4573.1
6 -11614.0 4995.7 -4995.7 Re-bar Arrange
7 -10236.0 5620.1 -5620.1 X: 9 ea
8 -8379.0 6063.5 -6063.5 Y: 9 ea
9 -4519.0 4934.7 -4934.7 Y HOOP
10 -517.8 3242.3 -3242.3 : D13@200mm
11 5513.8 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
10000
Tension

5000

M (kN.m)
0
-8000 -6000 -4000 -2000 0 2000 4000 6000 8000

-5000

-10000

-15000

-20000

Compression
-25000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 5514 ··· O.K
Pu
Compression (max) = 21 < P = 22072 ··· O.K
Moment (max) = 1 < Mx = 6063 ··· O.K
Mu
Moment (min) = -1 < Mx = -6063 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 173 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 4320 > 21.28 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 1150 / 200 + 0.75 x 0 x 390 x 1150 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 12.060 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 12060 / (14 x 1200 x 1200 ) ] x 1 x √ 30 x 1200 x 1150
= 995.739 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 995.739 + 0
= 995.739 kN > Vu = 1.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 1200 x 1200 ) ] x 1 x √ 30 x 1200 x 1150
= 995.143 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 995.143 + 0
= 995.143 kN > Vu = 1.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D25 = 400 mm
d = 1200 = 1200 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 174 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -22072.0 0.0 0.0 D25 x 32 ea
2 -22072.0 1900.9 -1900.9
3 -21020.0 3054.9 -3054.9 Concrete cover
4 -18097.0 3939.9 -3939.9 : 50 mm
5 -14996.0 4573.1 -4573.1
6 -11614.0 4995.7 -4995.7 Re-bar Arrange
7 -10236.0 5620.1 -5620.1 X: 9 ea
8 -8379.0 6063.5 -6063.5 Y: 9 ea
9 -4519.0 4934.7 -4934.7 Y HOOP
10 -517.8 3242.3 -3242.3 : D13@200mm
11 5513.8 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
10000
Tension

5000

M (kN.m)
0
-8000 -6000 -4000 -2000 0 2000 4000 6000 8000

-5000

-10000

-15000

-20000

-25000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 5514 ··· O.K
Pu
Compression (max) = 21 < P = 22072 ··· O.K
Moment (max) = 1 < Mx = 6063 ··· O.K
Mu
Moment (min) = -1 < Mx = -6063 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 175 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 4320 > 21.28 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 1150 / 200 + 0.75 x 0 x 390 x 1150 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 12.060 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 12060 / (14 x 1200 x 1200 ) ] x 1 x √ 30 x 1200 x 1150
= 945.387 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 945.387 + 0
= 945.387 kN > Vu = 1.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 1200 x 1200 ) ] x 1 x √ 30 x 1200 x 1150
= 963.718 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 963.718 + 0
= 963.718 kN > Vu = 1.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D25 = 400 mm
d = 1200 = 1200 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 176 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D25 x 32 ea = 15708.8 ㎟


Ag = b x h = 1440000 ㎟
ρ.used = As.used / Ag = 0.0109 ··· O.K ( ∵ 0.01 < ρ.used = 0.0109 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 177 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) Pedestal < P.A PED-4 > ( 600 x 600 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
2000
Tension
1000

M (kN.m)
0
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

Compression
-6000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 230 < P = 5633 ··· O.K
Moment (max) = 2 < Mx = 750 ··· O.K
Mu
Moment (min) = -2 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 178 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 229.84 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 34.080 kN
Vu.max = 21.190 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 34080 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 249.097 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 249.097 + 0
= 249.097 kN > Vu = 21.190 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 21.190 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 247.424 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 247.424 + 0
= 247.424 kN > Vu = 21.190 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 179 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
2000
Tension
1000

M (kN.m)
0
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

-6000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 230 < P = 5633 ··· O.K
Moment (max) = 2 < Mx = 750 ··· O.K
Mu
Moment (min) = -2 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 180 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 229.84 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 34.080 kN
Vu.max = 23.800 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 34080 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 227.463 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 227.463 + 0
= 227.463 kN > Vu = 23.800 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 23.800 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 230.454 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 230.454 + 0
= 230.454 kN > Vu = 23.800 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 181 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D19 x 16 ea = 4536 ㎟


Ag = b x h = 360000 ㎟
ρ.used = As.used / Ag = 0.0126 ··· O.K ( ∵ 0.01 < ρ.used = 0.0126 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 182 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) Pedestal < F.D PED-1 > ( 3690 x 3400 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -171304.0 0.0 0.0 D19 x 92 ea
2 -171304.0 37941.0 -37941.0
3 -169535.0 65603.0 -65603.0 Concrete cover
4 -147896.0 85677.0 -85677.0 : 50 mm
5 -125991.0 98278.0 -98278.0
6 -103684.0 103577.0 -103577.0 Re-bar Arrange
7 -95044.0 115460.0 -115460.0 X: 25 ea
8 -84112.0 122110.0 -122110.0 Y: 23 ea
9 -54380.0 94880.0 -94880.0 Y HOOP
10 -24648.0 56599.0 -56599.0 : D13@200mm
11 9154.8 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
20000
Tension
M (kN.m)
0
-150000 -100000 -50000 0 50000 100000 150000
-20000

-40000

-60000

-80000

-100000

-120000

-140000

-160000

-180000
Compression
-200000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 9155 ··· O.K
Pu
Compression (max) = 706 < P = 171304 ··· O.K
Moment (max) = 227 < Mx = 122110 ··· O.K
Mu
Moment (min) = -141 < Mx = -122110 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 183 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 37638 > 706.454 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 3350 / 200 + 0.75 x 0 x 390 x 3350 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 420.035 kN
Vu.max = 26.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 420035 / (14 x 3400 x 3690 ) ] x 1 x √ 30 x 3690 x 3350
= 8757.865 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 8757.865 + 0
= 8757.865 kN > Vu = 26.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 26.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 3690 x 3400 ) ] x 1 x √ 30 x 3690 x 3350
= 8736.972 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 8736.972 + 0
= 8736.972 kN > Vu = 26.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 3400 = 3400 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 184 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -171304.0 0.0 0.0 D19 x 92 ea
2 -171304.0 35110.0 -35110.0
3 -169440.0 60629.0 -60629.0 Concrete cover
4 -147759.0 79164.0 -79164.0 : 50 mm
5 -125821.0 90797.0 -90797.0
6 -103478.0 95702.0 -95702.0 Re-bar Arrange
7 -94922.0 106614.0 -106614.0 X: 25 ea
8 -84084.0 112759.0 -112759.0 Y: 23 ea
9 -54492.0 87718.0 -87718.0 Y HOOP
10 -24899.0 52575.0 -52575.0 : D13@200mm
11 9154.8 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
20000
Tension M (kN.m)
0
-150000 -100000 -50000 0 50000 100000 150000
-20000

-40000

-60000

-80000

-100000

-120000

-140000

-160000

-180000

-200000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 9155 ··· O.K
Pu
Compression (max) = 706 < P = 171304 ··· O.K
Moment (max) = 71 < Mx = 112759 ··· O.K
Mu
Moment (min) = -73 < Mx = -112759 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 185 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 37638 > 706.454 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 3640 / 200 + 0.75 x 0 x 390 x 3640 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 420.035 kN
Vu.max = 26.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 420035 / (14 x 3400 x 3690 ) ] x 1 x √ 30 x 3400 x 3640
= 8493.531 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 8493.531 + 0
= 8493.531 kN > Vu = 26.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 26.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 3400 x 3690 ) ] x 1 x √ 30 x 3400 x 3640
= 8642.733 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 8642.733 + 0
= 8642.733 kN > Vu = 26.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 3400 = 3400 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 186 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D19 x 92 ea = 26082 ㎟


Ag = b x h = 12546000 ㎟
ρ.used = As.used / Ag = 0.0021 ··· O.K ( ∵ 0.002 < ρ.used = 0.0021 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 187 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6) Pedestal < F.D PED-2 > ( 1720 x 3400 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -80060.0 0.0 0.0 D16 x 66 ea
2 -80060.0 8504.0 -8504.0
3 -78762.0 14605.0 -14605.0 Concrete cover
4 -68455.0 19017.0 -19017.0 : 50 mm
5 -58009.0 21760.0 -21760.0
6 -47344.0 22892.0 -22892.0 Re-bar Arrange
7 -43491.0 25367.0 -25367.0 X: 12 ea
8 -38629.0 26791.0 -26791.0 Y: 23 ea
9 -25164.0 20916.0 -20916.0 Y HOOP
10 -11705.0 12765.0 -12765.0 : D13@200mm
11 4658.7 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
10000
Tension
0
M (kN.m)
-30000 -20000 -10000 0 10000 20000 30000
-10000

-20000

-30000

-40000

-50000

-60000

-70000

-80000

Compression
-90000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 4659 ··· O.K
Pu
Compression (max) = 382 < P = 80060 ··· O.K
Moment (max) = 68 < Mx = 26791 ··· O.K
Mu
Moment (min) = -42 < Mx = -26791 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 188 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 17544 > 382.337 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 3350 / 200 + 0.75 x 0 x 390 x 3350 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 172.128 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 172128 / (14 x 3400 x 1720 ) ] x 1 x √ 30 x 1720 x 3350
= 4082.886 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 4082.886 + 0
= 4082.886 kN > Vu = 23.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 1720 x 3400 ) ] x 1 x √ 30 x 1720 x 3350
= 4074.320 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 4074.32 + 0
= 4074.320 kN > Vu = 23.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D16 = 256 mm
d = 1720 = 1720 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 189 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -80060.0 0.0 0.0 D16 x 66 ea
2 -80060.0 16238.0 -16238.0
3 -79231.0 28096.0 -28096.0 Concrete cover
4 -69110.0 36698.0 -36698.0 : 50 mm
5 -58857.0 42072.0 -42072.0
6 -48400.0 44292.0 -44292.0 Re-bar Arrange
7 -44219.0 49419.0 -49419.0 X: 12 ea
8 -38899.0 52215.0 -52215.0 Y: 23 ea
9 -24844.0 40405.0 -40405.0 Y HOOP
10 -10789.0 23765.0 -23765.0 : D13@200mm
11 4658.7 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
10000
Tension
0 M (kN.m)
-60000 -40000 -20000 0 20000 40000 60000
-10000

-20000

-30000

-40000

-50000

-60000

-70000

-80000

-90000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 4659 ··· O.K
Pu
Compression (max) = 382 < P = 80060 ··· O.K
Moment (max) = 132 < Mx = 52215 ··· O.K
Mu
Moment (min) = -131 < Mx = -52215 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 190 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 17544 > 382.337 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 1670 / 200 + 0.75 x 0 x 390 x 1670 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 172.128 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 172128 / (14 x 3400 x 1720 ) ] x 1 x √ 30 x 3400 x 1670
= 3895.634 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 3895.634 + 0
= 3895.634 kN > Vu = 23.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 23.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 3400 x 1720 ) ] x 1 x √ 30 x 3400 x 1670
= 3965.210 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 3965.21 + 0
= 3965.210 kN > Vu = 23.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D16 = 256 mm
d = 1720 = 1720 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 191 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D16 x 66 ea = 13272.6 ㎟


Ag = b x h = 5848000 ㎟
ρ.used = As.used / Ag = 0.0023 ··· O.K ( ∵ 0.002 < ρ.used = 0.0023 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 192 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7) Pedestal < F.D PED-3 > ( 850 x 950 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -12534.0 0.0 0.0 D19 x 34 ea
2 -12534.0 773.3 -773.3
3 -11860.0 1239.9 -1239.9 Concrete cover
4 -10168.0 1597.0 -1597.0 : 50 mm
5 -8360.0 1852.1 -1852.1
6 -6371.0 2025.5 -2025.5 Re-bar Arrange
7 -5581.0 2268.1 -2268.1 X: 6 ea
8 -4539.0 2446.3 -2446.3 Y: 7 ea
9 -2389.0 1994.7 -1994.7 Y HOOP
10 111.3 1227.9 -1227.9 : D13@200mm
11 3383.3 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
6000
Tension
4000

2000

M (kN.m)
0
-3000 -2000 -1000 0 1000 2000 3000
-2000

-4000

-6000

-8000

-10000

-12000

Compression
-14000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 3383 ··· O.K
Pu
Compression (max) = 13 < P = 12534 ··· O.K
Moment (max) = 1 < Mx = 2446 ··· O.K
Mu
Moment (min) = -1 < Mx = -2446 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 193 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 2422.5 > 12.679 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 900 / 200 + 0.75 x 0 x 390 x 900 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 8.151 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 8151 / (14 x 950 x 850 ) ] x 1 x √ 30 x 850 x 900
= 558.678 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 558.678 + 0
= 558.678 kN > Vu = 1.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 850 x 950 ) ] x 1 x √ 30 x 850 x 900
= 558.275 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 558.275 + 0
= 558.275 kN > Vu = 1.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 850 = 850 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 194 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -12534.0 0.0 0.0 D19 x 34 ea
2 -12534.0 854.9 -854.9
3 -11890.0 1372.3 -1372.3 Concrete cover
4 -10208.0 1767.6 -1767.6 : 50 mm
5 -8419.0 2050.9 -2050.9
6 -6446.0 2239.5 -2239.5 Re-bar Arrange
7 -5618.0 2517.7 -2517.7 X: 6 ea
8 -4516.0 2711.7 -2711.7 Y: 7 ea
9 -2318.0 2200.0 -2200.0 Y HOOP
10 101.1 1382.4 -1382.4 : D13@200mm
11 3383.3 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
6000
Tension
4000

2000

M (kN.m)
0
-3000 -2000 -1000 0 1000 2000 3000

-2000

-4000

-6000

-8000

-10000

-12000

-14000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 3383 ··· O.K
Pu
Compression (max) = 13 < P = 12534 ··· O.K
Moment (max) = 1 < Mx = 2712 ··· O.K
Mu
Moment (min) = -1 < Mx = -2712 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 195 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 2422.5 > 12.679 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 800 / 200 + 0.75 x 0 x 390 x 800 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 8.151 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 8151 / (14 x 950 x 850 ) ] x 1 x √ 30 x 950 x 800
= 520.712 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 520.712 + 0
= 520.712 kN > Vu = 1.000 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 1.000 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 950 x 850 ) ] x 1 x √ 30 x 950 x 800
= 530.743 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 530.743 + 0
= 530.743 kN > Vu = 1.000 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 850 = 850 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 196 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D19 x 34 ea = 9639 ㎟


Ag = b x h = 807500 ㎟
ρ.used = As.used / Ag = 0.0119 ··· O.K ( ∵ 0.01 < ρ.used = 0.0119 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 197 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8) Pedestal < F.D PED-4 > ( 600 x 600 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
2000
Tension
1000

M (kN.m)
0
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

-6000 Compression
Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 141 < P = 5633 ··· O.K
Moment (max) = 3 < Mx = 750 ··· O.K
Mu
Moment (min) = -3 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 198 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 141.16 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 15.480 kN
Vu.max = 28.790 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 15480 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 248.184 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 248.184 + 0
= 248.184 kN > Vu = 28.790 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 28.790 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 247.424 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 247.424 + 0
= 247.424 kN > Vu = 28.790 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 199 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
2000
Tension
1000

M (kN.m)
0
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

-6000 Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 141 < P = 5633 ··· O.K
Moment (max) = 2 < Mx = 750 ··· O.K
Mu
Moment (min) = -2 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 200 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 141.16 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 15.480 kN
Vu.max = 21.060 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 15480 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 226.629 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 226.629 + 0
= 226.629 kN > Vu = 21.060 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 21.060 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 230.454 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 230.454 + 0
= 230.454 kN > Vu = 21.060 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 201 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D19 x 16 ea = 4536 ㎟


Ag = b x h = 360000 ㎟
ρ.used = As.used / Ag = 0.0126 ··· O.K ( ∵ 0.01 < ρ.used = 0.0126 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 202 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9) Pedestal < Duct > ( 600 x 600 )

(1) FOR M33, V22 (My, Vx)

A) Capacity of Pedestal

NO. P Mx -Mx FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.
P (kN)
2000
Tension
1000

M (kN.m)
0
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

Compression
-6000

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 146 < P = 5633 ··· O.K
Moment (max) = 30 < Mx = 750 ··· O.K
Mu
Moment (min) = -30 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 203 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 146.09 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 7.835 kN
Vu.max = 55.300 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 7835 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 247.809 kN
ΦVn.min = Φ ( Vc.min + Vs.tie )
= 247.809 + 0
= 247.809 kN > Vu = 55.300 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 55.300 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 247.424 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 247.424 + 0
= 247.424 kN > Vu = 55.300 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 204 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) FOR M22, V33 (Mx, Vy)

A) Capacity of Pedestal

NO. P My -My FROM SAP2000


1 -5633.0 0.0 0.0 D19 x 16 ea
2 -5633.0 241.8 -241.8
3 -5298.0 391.3 -391.3 Concrete cover
4 -4520.0 502.2 -502.2 : 50 mm
5 -3670.0 579.6 -579.6
6 -2734.0 629.4 -629.4 Re-bar Arrange
7 -2359.0 699.0 -699.0 X: 5 ea
8 -1886.0 750.1 -750.1 Y: 5 ea
9 -877.6 591.2 -591.2 Y HOOP
10 273.5 341.3 -341.3 : D13@200mm
11 1592.1 0.0 0.0 X
※ REF. PEDESTAL DWG.
* Above values in the table mean the capacity of pedestal itself. The other words, above size of
pedestal have capacity as shown below diagram. Above value of Numbers ①~⑪ in the table, it
indicates scope of capacity from Sap2000 containing the re-bar properties.

P (kN)
2000
Tension
1000

0
M (kN.m)
-1000 -800 -600 -400 -200 0 200 400 600 800 1000

-1000

-2000

-3000

-4000

-5000

-6000
Compression

Φ(Pn-Mn+) Φ(Pn-Mn-) P-M3(Static) P-M3(Seismic)

P-M Interaction Diagram

Above Diagram contains Static & Seismic Case for comparison of the each case.
These dots in the circle line mean safe at the each load condition.
Tension (max) = 0 < P = 1592 ··· O.K
Pu
Compression (max) = 146 < P = 5633 ··· O.K
Moment (max) = 8 < Mx = 750 ··· O.K
Mu
Moment (min) = -8 < Mx = -750 ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 205 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

B) Reinforcement for Shear Force


f'c = 30 MPa fy = 390 MPa Φ = 0.75 λ = 1.00
RE-Bar for Shear Force : D13 x 0ea @ C.T.C 200
Additional Hoops or Ties : D13 x 0ea @ C.T.C 200

fc' x Ag x 0.1 > Pu.max (compression) ··· ACI318-14 Chapter 18.4.2.5


= 1080 > 146.09 ··· Additional Hoops or Ties is not needed.

ΦVs = Φ x Av x fy x d / s
= 0.75 x 0 x 390 x 550 / 200 + 0.75 x 0 x 390 x 550 / 200
= 0.000 kN

(A) For members subject to axial Compression


Nu.min = 7.835 kN
Vu.max = 14.460 kN

ΦVc = Φ x 0.17 [ 1 + Nu / (14 x Ag) ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.6.1


ΦVc.min = Φ x 0.17 [ 1 + Nu.min / (14 x Ag) ] x λ x √f'c x bw x d
= 0.75 x 0.17 [ 1 + 7835 / (14 x 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 226.287 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 226.287 + 0
= 226.287 kN > Vu = 14.460 kN ··· O.K

(B) For members subject to axial Tension


Nu.max = 0.000 kN
Vu.max = 14.460 kN

ΦVc = Φ x 0.17 [ 1 + (0.29 x Nu ) / Ag ] x λ x √f'c x bw x d ··· ACI318-14 Chapter 22.5.7.1


ΦVc.min = Φ x 0.17 [ 1 + (0.29 x Nu.max ) / Ag ] x λ x √f'c x bw x d ≥ 0
= 0.75 x 0.17 [ 1 + (0.29 x 0 ) / ( 600 x 600 ) ] x 1 x √ 30 x 600 x 550
= 230.454 kN

ΦVn.min = Φ ( Vc.min + Vs.tie )


= 230.454 + 0
= 230.454 kN > Vu = 14.460 kN ··· O.K

C) Check Tie bar vertical spaceing by the ACI318-14 Reinforcement Detaile Provisions

(A) Vertical spaceing ( S ) ··· ACI318-14 Chapter 25.7.2.1


16 d b = 16 x D19 = 304 mm
d = 600 = 600 mm
48 d h = 48 x D13 = 624 mm
S = 200 mm ··· O.K

Where, db : longitudinal bar diameter


d : smallest cross-section of member
dh : tie bar diameter

(B) Vertical spaceing ( S1 ) ··· ACI318-14 Chapter 10.7.6.2.2


S1 = 75 mm ≤ Max S1 = 75 mm ··· O.K

(C) Vertical spaceing ( S2 ) ··· ACI318-14 Chapter 10.7.6.1.6


S2 = Con'c cover ( Cc=50mm) + Tie bar space (Ts=75mm)
= 125 mm ≤ Max S2 = 125 mm ··· O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 206 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(3) Check applied steel ratio, ρ.used ··· ACI318-14 Chapter 10.6.1.1

As.used = D19 x 16 ea = 4536 ㎟


Ag = b x h = 360000 ㎟
ρ.used = As.used / Ag = 0.0126 ··· O.K ( ∵ 0.01 < ρ.used = 0.0126 < 0.08 )

DOCUMENT No. : IKCP0-UHA-C-06-0002


- 207 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.3 Ductile Design for Anchor bolt

1) General

Tension check of anchor bolt is based on ACI318-14 Chaper17 "Anchoring to Concrete".


The concept of tension design is that anchors should be failed by steel itself prior to concrete
breakout failure. Therefore, tension design requirement for anchor bolt referred to the drawings
( Attachment #1. "Equipment Vendor Data : K1A0-103(1~8)")

The anchorage length of bars which are arranged additionally beyond the expected failure surface
to avoid the failure of concrete is calculated according to the ACI318-14, Chapter 25.4 Development of
reinforcement, Chapter 25.5 Splices ". But this can be reduced by applying the modification factor for
concrete cover, ties or strrups and excess reinforcement etc.

Side-face blow out needs be considered when the edge distance from the centerline of the anchor
to the nearest free edge is less than 0.4hef, where hef is embedment depth of anchor.

2) Summary for Ductile Design of Anchor Bolt


Unit = kN, mm
Anchor Tension Concrete Breakout Concrete Side-face
Pullout Strength
PED Dia. Strength Strength Blowout Strength
NO. do Nsa Ncbg Additional Npn Nsa' Nsb
Check Check
(mm) (kN) [kN] Reinforcement [kN] [kN] [kN]
PA FAN(1) 30 750 875 28 - D25 243 N.G 500 N.A O.K
PA FAN(2) 30 1500 539 15 - D16 486 N.G 500 N.A O.K
PA FAN(3) 30 750 875 28 - D25 243 N.G 500 N.A O.K
PA FAN(4) 30 1500 539 15 - D16 486 N.G 500 N.A O.K
PA FAN(2) 30 1500 539 15 - D16 486 N.G 500 N.A O.K
PA FAN(5) 20 477 498 32 - D29 3022 O.K 239 N.A O.K
PA FAN(6) 20 477 219 16 - D19 3022 O.K 239 N.A O.K
FD FAN(1) 24 469 656 28 - D25 156 N.G 313 N.A O.K
FD FAN(2) 24 782 452 12 - D16 259 N.G 313 N.A O.K
FD FAN(3) 24 469 656 28 - D25 156 N.G 313 N.A O.K
FD FAN(4) 24 782 452 12 - D16 259 N.G 313 N.A O.K
FD FAN(5) 20 477 327 34 - D19 3022 O.K 239 N.A O.K
FD FAN(6) 20 477 219 16 - D19 3022 O.K 239 N.A O.K
DUCT & PLATFORM 20 477 219 16 - D19 3022 O.K 239 N.A O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 208 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) Pedestal identification = PA FAN(1)

(1) Design information

A) Anchor bolt Property

B'

L'

□ Pedestal Size B' x L' = 2590 x 1295


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 30 mm
1(1/4) in.
□ Number of anchors in group n = 3 Nos.
Arrangement = 3 x 1
□ Anchor spacing s1 = 1150 mm ( 2@ 575 )
s2 = 0 mm ( 0@ #DIV/0!
□ Effective cross sectional area Ase = 625 mm
2

□ Effective embedment depth hef = 480 mm


□ Edge distance ca1 = 720 mm
if Ca ≥ 1.5·hef, ca2 = 575 mm
value of Ca is 1.5·hef (= 720 ) ca3 = 720 mm
ca4 = 720 mm
□ Bearing area of the hook of anchor eh = 100 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 209 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 750 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 875 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 480 mm
□ ANc / ANco = 1.6
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 2,073,600 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 3,354,050 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 480 ^(1.5)
= 576 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.94 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg > Nsa, ∴ OK

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 243 kN
Np = 0.9·fc'·eh·do = 81 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 750 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2564 mm2 fy = 390 Mpa

Used : 0 - D 16 ---------- As = - mm2


Additional : 30 - D 16 ---------- As = 6,030 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.43 )

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 210 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 137 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 307 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.43


a=175 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 710 x 0.43 = 305 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 480 - 175 x tan 35 - 50
= 307 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 211 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

□ Development Length ldh for Deformed Bars in Tension


f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa α D10 D13 D16 D19 D22 D25 D29 D32
1.3 450 580 710 840 1200 1370 1580 1750
a
1.0 340 450 550 650 930 1050 1220 1350
ld
1.3 670 860 1060 1260 1860 2110 2450 2700
b
1.0 510 670 820 970 1430 1620 1880 2080

Case a : Clear spacing of bars being developed or spliced not less than db, clear cover
not less than db, and stirrups or ties throughout ld not less than the code
minimum, or clear spacing of bars being developed or spliced not less than
2db and clear cover not less than db

Case b : All other cases, except for case a

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 212 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 450 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 698 kN

□ AVc / AVco = 1.0


AVco = 4.5·ca12 = 2,332,800 mm2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 2,332,800 mm2 , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 240 / 30 )^(0.2) x 30^(1/2) x 1 x 30^(1/2) x 720 ^(1.5)
= 580 kN
ℓe = 8 do = 240 < 480

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.86 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg > Vsa ∴ OK

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 750 = 1,500 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 213 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 33.00 kN

Min (φVsa, φVcbg, φVcpg) = 293 kN


Vua = 33 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 214 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) Pedestal identification = PA FAN(2)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 1100 x 2250


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 30 mm
1(1/4) in.
□ Number of anchors in group n = 6 Nos.
Arrangement = 2 + 4
□ Anchor spacing s1 = 250 mm ( 1@ 250 )
s2 = 810 mm ( 3@ 270 )
□ Effective cross sectional area Ase = 625 mm
2

□ Effective embedment depth hef = 480 mm


□ Edge distance ca1 = 200 mm
if Ca ≥ 1.5·hef, ca2 = 720 mm
value of Ca is 1.5·hef (= 720 ) ca3 = 650 mm
ca4 = 720 mm
□ Bearing area of the hook of anchor eh = 100 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 215 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 1,500 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 539 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 480 mm
□ ANc / ANco = 1.2
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 2,073,600 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 2,475,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 480 ^(1.5)
= 576 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.78 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 1500 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 5128 mm2 fy = 390 Mpa

Used : 15 - D 16 ---------- As = 3,015 mm2


Additional : 15 - D 16 ---------- As = 3,015 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.85 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 486 kN
Np = 0.9·fc'·eh·do = 81 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 216 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 1500 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 5128 mm2 fy = 390 Mpa

Used : 15 - D 16 ---------- As = 3,015 mm2


Additional : 15 - D 16 ---------- As = 3,015 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.85 )

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 273 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 445 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.85

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 71.0 mm ( Hoof Dia= D13 )


□ Required Development Length = 273 x 0.85 = 232 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 480 - (100 - 100/2 - 71) x tan 35 - 50
= 445 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 217 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

In this section, the development length is checked for the additional vertical reinforcement of pedestal
which is expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 293 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.85


a=195 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 273 x 0.85 = 232 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 480 - 195 x tan 35 - 50
= 293 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 218 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 900 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 279 kN

□ AVc / AVco = 2.4


AVco = 4.5·ca12 = 180,000 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 423,000 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 240 / 30 )^(0.2) x 30^(1/2) x 1 x 30^(1/2) x 200 ^(1.5)
= 85 kN
ℓe = 8 do = 240 < 480

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 1.00 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 1500 = 3,000 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 219 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 900 /( 0.75 x 390 )x 1000
= 300 mm

2
= 3077 mm
1.5xCa1

As,prov. = Use 20 - D 16
2
= 4020 mm

As,req./As,prov = 0.77 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 23.00 kN

Min (φVsa, φVcbg, φVcpg) = 585 kN


Vua = 23 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 220 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) Pedestal identification = PA FAN(3)

(1) Design information

A) Anchor bolt Property

B'

L'

□ Pedestal Size B' x L' = 2590 x 1295


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 30 mm
1(1/4) in.
□ Number of anchors in group n = 3 Nos.
Arrangement = 3 x 1
□ Anchor spacing s1 = 1150 mm ( 2@ 575 )
s2 = 0 mm ( 0@ #DIV/0!
□ Effective cross sectional area Ase = 625 mm
2

□ Effective embedment depth hef = 480 mm


□ Edge distance ca1 = 720 mm
if Ca ≥ 1.5·hef, ca2 = 575 mm
value of Ca is 1.5·hef (= 720 ) ca3 = 720 mm
ca4 = 720 mm
□ Bearing area of the hook of anchor eh = 100 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 221 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 750 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 875 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 480 mm
□ ANc / ANco = 1.6
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 2,073,600 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 3,354,050 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 480 ^(1.5)
= 576 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.94 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg > Nsa, ∴ OK

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 243 kN
Np = 0.9·fc'·eh·do = 81 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 750 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2564 mm2 fy = 390 Mpa

Used : 0 - D 16 ---------- As = - mm2


Additional : 30 - D 16 ---------- As = 6,030 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.43 )

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 222 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 137 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the additional vertical reinforcement of pedestal
which is expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 307 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.43


a=175 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 710 x 0.43 = 305 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 480 - 175 x tan 35 - 50
= 307 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 223 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

□ Development Length ldh for Deformed Bars in Tension


f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa α D10 D13 D16 D19 D22 D25 D29 D32
1.3 450 580 710 840 1200 1370 1580 1750
a
1.0 340 450 550 650 930 1050 1220 1350
ld
1.3 670 860 1060 1260 1860 2110 2450 2700
b
1.0 510 670 820 970 1430 1620 1880 2080

Case a : Clear spacing of bars being developed or spliced not less than db, clear cover
not less than db, and stirrups or ties throughout ld not less than the code
minimum, or clear spacing of bars being developed or spliced not less than
2db and clear cover not less than db

Case b : All other cases, except for case a

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 224 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 450 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 698 kN

□ AVc / AVco = 1.0


AVco = 4.5·ca12 = 2,332,800 mm2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 2,332,800 mm2 , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 240 / 30 )^(0.2) x 30^(1/2) x 1 x 30^(1/2) x 720 ^(1.5)
= 580 kN
ℓe = 8 do = 240 < 480

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.86 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg > Vsa ∴ OK

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 750 = 1,500 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 225 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 33.00 kN

Min (φVsa, φVcbg, φVcpg) = 293 kN


Vua = 33 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 226 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6) Pedestal identification = PA FAN(4)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 1100 x 2250


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 30 mm
1(1/4) in.
□ Number of anchors in group n = 6 Nos.
Arrangement = 2 + 4
□ Anchor spacing s1 = 250 mm ( 1@ 250 )
s2 = 810 mm ( 3@ 270 )
□ Effective cross sectional area Ase = 625 mm
2

□ Effective embedment depth hef = 480 mm


□ Edge distance ca1 = 200 mm
if Ca ≥ 1.5·hef, ca2 = 720 mm
value of Ca is 1.5·hef (= 720 ) ca3 = 650 mm
ca4 = 720 mm
□ Bearing area of the hook of anchor eh = 100 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 227 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 1,500 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 539 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 480 mm
□ ANc / ANco = 1.2
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 2,073,600 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 2,475,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 480 ^(1.5)
= 576 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.78 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 1500 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 5128 mm2 fy = 390 Mpa

Used : 15 - D 16 ---------- As = 3,015 mm2


Additional : 15 - D 16 ---------- As = 3,015 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.85 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 486 kN
Np = 0.9·fc'·eh·do = 81 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 228 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 1500 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 5128 mm2 fy = 390 Mpa

Used : 15 - D 16 ---------- As = 3,015 mm2


Additional : 15 - D 16 ---------- As = 3,015 mm2
As,prov.= 6030 mm2 (∴ As,req./As,prov= 0.85 )

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 273 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 445 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.85

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 71.0 mm ( Hoof Dia= D13 )


□ Required Development Length = 273 x 0.85 = 232 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 480 - (100 - 100/2 - 71) x tan 35 - 50
= 445 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 229 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

In this section, the development length is checked for the additional vertical reinforcement of pedestal
which is expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 293 mm

of fresh concrete is cast in the member below the


hef = 480 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.85


a=195 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 273 x 0.85 = 232 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 480 - 195 x tan 35 - 50
= 293 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 230 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 900 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 279 kN

□ AVc / AVco = 2.4


AVco = 4.5·ca12 = 180,000 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 423,000 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 240 / 30 )^(0.2) x 30^(1/2) x 1 x 30^(1/2) x 200 ^(1.5)
= 85 kN
ℓe = 8 do = 240 < 480

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 1.00 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 1500 = 3,000 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 231 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 900 /( 0.75 x 390 )x 1000
= 300 mm

2
= 3077 mm
1.5xCa1

As,prov. = Use 20 - D 16
2
= 4020 mm

As,req./As,prov = 0.77 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 23.00 kN

Min (φVsa, φVcbg, φVcpg) = 585 kN


Vua = 23 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 232 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) Pedestal identification = PA FAN(5)

(1) Design information

A) Anchor bolt Property

ca2 s2 ca4

ca3

s1
B'
hef

ca1

L'

□ Pedestal Size B' x L' = 1200 x 1200


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 20 mm
7/8 in.
□ Number of anchors in group n = 4 Nos.
Arrangement = 2 x 2
□ Anchor spacing s1 = 420 mm ( 1@ 420 )
s2 = 320 mm ( 1@ 320 )
□ Effective cross sectional area Ase = 298 mm
2

□ Effective embedment depth hef = 260 mm


□ Edge distance ca1 = 390 mm
if Ca ≥ 1.5·hef, ca2 = 390 mm
value of Ca is 1.5·hef (= 390 ) ca3 = 390 mm
ca4 = 390 mm
□ Bearing area of the head of anchor Abrg = 3148
mm
2

Bearing plate size, W : 60 mm x 60 mm (=60 x 60 - 0.25 x π x 24^2)


Sleeve diameter, SD : D 24 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 233 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 477 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 498 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 260 mm
□ ANc / ANco = 2.2
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 608,400 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 1,320,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 260 ^(1.5)
= 230 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 1.00 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg > Nsa, ∴ OK

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 3,022 kN
Np = 8·Abrg·fc' = 755 kN (for single headed stud & bolt)
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn > Nsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 234 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Check for Concrete Side-Face Blow-out Strength of a headed anchor in tension


(ACI318-14 Chapter 17.4.4)

☞ Tension per Anchor Bolt


Nsa / n (Tension anchor) = 119.3 kN

☞ Tension (Nsa') for Side-Face Blowout Check


119.3 x 2 ea = 238.5 kN

Apply bolt ( 2 ea ) for Side-Face Blowout Check Use

☞ Determine Nominal Concrete Side-Face Blow-out Strength of a headed anchor in tension(Nsb,Nsbg)


For single headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef)
Min. spacing = 320 mm < 6ca1. So, it's considered as a group anchor
0.4hef = 104 mm < ca1. So, blow-out failure is not considered.
ca2/ca1 = 1.0
λa = 1.0

Nsb = {(1+ca2/ca1)/4} · 13 · ca1 · Abrg^0.5 · λa ·f'c^0.5, where 1.0 ≤ ca2/ca1 ≤ 3.0


= N.A
= N.A kN

For multiple headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef) and
anchor spacing(s) < 6·ca1,
Nsbg = (1+s2 / 6·ca1)·Nsb = N.A kN

Not Applicable

E) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 358 kN


Nua ( ≤0, compression) = 0 kN

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 235 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 286 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 303 kN

□ AVc / AVco = 1.3


AVco = 4.5·ca12 = 684,450 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 871,650 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 160 / 20 )^(0.2) x 20^(1/2) x 1 x 30^(1/2) x 390 ^(1.5)
= 189 kN
ℓe = 8 do = 160 < 260

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.90 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg > Vsa ∴ OK

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 477 = 954 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 236 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM213)
= 1 kN

Min (φVsa, φVcbg, φVcpg) = 186 kN


Vua = 1 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 237 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8) Pedestal identification = PA FAN(6)

(1) Design information

A) Anchor bolt Property

ca2 s2 ca4

ca3

s1
B'
hef

ca1

L'

□ Pedestal Size B' x L' = 600 x 600


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 20 mm
7/8 in.
□ Number of anchors in group n = 4 Nos.
Arrangement = 2 x 2
□ Anchor spacing s1 = 300 mm ( 1@ 300 )
s2 = 300 mm ( 1@ 300 )
□ Effective cross sectional area Ase = 298 mm
2

□ Effective embedment depth hef = 350 mm


□ Edge distance ca1 = 150 mm
if Ca ≥ 1.5·hef, ca2 = 150 mm
value of Ca is 1.5·hef (= 525 ) ca3 = 150 mm
ca4 = 150 mm
□ Bearing area of the head of anchor Abrg = 3148
mm
2

Bearing plate size, W : 60 mm x 60 mm (=60 x 60 - 0.25 x π x 24^2)


Sleeve diameter, SD : D 24 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 238 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 477 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 219 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 100 mm
□ ANc / ANco = 4.0
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 90,000 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) = 360,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 100 ^(1.5)
= 55 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 1.00 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 477 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1631 mm2 fy = 390 Mpa

Used : 16 - D 19 ---------- As = 4,544 mm2


Additional : 0 - D 16 ---------- As = - mm2
As,prov.= 4544 mm2 (∴ As,req./As,prov= 0.36 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 3,022 kN
Np = 8·Abrg·fc' = 755 kN (for single headed stud & bolt)
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn > Nsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 239 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Check for Concrete Side-Face Blow-out Strength of a headed anchor in tension


(ACI318-14 Chapter 17.4.4)

☞ Tension per Anchor Bolt


Nsa / n (Tension anchor) = 119.3 kN

☞ Tension (Nsa') for Side-Face Blowout Check


119.3 x 2 ea = 238.5 kN

Apply bolt ( 2 ea ) for Side-Face Blowout Check Use

☞ Determine Nominal Concrete Side-Face Blow-out Strength of a headed anchor in tension(Nsb,Nsbg)


For single headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef)
Min. spacing = 300 mm < 6ca1. So, it's considered as a group anchor
0.4hef = 140 mm < ca1. So, blow-out failure is not considered.
ca2/ca1 = 1.0
λa = 1.0

Nsb = {(1+ca2/ca1)/4} · 13 · ca1 · Abrg^0.5 · λa ·f'c^0.5, where 1.0 ≤ ca2/ca1 ≤ 3.0


= N.A
= N.A kN

For multiple headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef) and
anchor spacing(s) < 6·ca1,
Nsbg = (1+s2 / 6·ca1)·Nsb = N.A kN

Not Applicable

E) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 358 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K


☞ Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 240 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 267 mm

of fresh concrete is cast in the member below the


hef = 350 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.36

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 72.5 mm ( Hoof Dia= D13 )


□ Required Development Length = 325 x 0.36 = 117 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 350 - (150 - 60/2 - 72.5) x tan 35 - 50
= 267 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 241 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 286 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 95 kN

□ AVc / AVco = 1.7


AVco = 4.5·ca12 = 101,250 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 168,750 mm , Avc ≤ n·Avco

□ Vb = 0.66 · (ℓe/do)0.2 · (do)(1/2) · λa · (fc')(1/2) · ca1(1.5)


= 0.66 x ( 160 / 20 )^(0.2) x 20^(1/2) x 1 x 30^(1/2) x 150 ^(1.5)
= 45 kN
ℓe = 8 do = 160 < 350

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.90 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 477 = 954 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 242 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 286 /( 0.75 x 390 )x 1000
= 225 mm

2
= 978 mm
1.5xCa1

As,prov. = Use 9 - D D13


2
= 1197 mm

As,req./As,prov = 0.82 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM210)
= 24 kN

Min (φVsa, φVcbg, φVcpg) = 186 kN


Vua = 24 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 243 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9) Pedestal identification = FD FAN(1)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 2155 x 1043


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 24 mm
1 in.
□ Number of anchors in group n = 3 Nos.
Arrangement = 3 x 1
□ Anchor spacing s1 = 1000 mm ( 2@ 500 )
s2 = 0 mm ( 0@ #DIV/0!
□ Effective cross sectional area Ase = 391 mm
2

□ Effective embedment depth hef = 385 mm


□ Edge distance ca1 = 578 mm
if Ca ≥ 1.5·hef, ca2 = 465 mm
value of Ca is 1.5·hef (= 577.5 ) ca3 = 578 mm
ca4 = 578 mm
□ Bearing area of the hook of anchor eh = 80 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 244 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 469 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 656 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 385 mm
□ ANc / ANco = 1.7
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 1,334,025 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 2,246,588 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 385 ^(1.5)
= 414 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.94 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg > Nsa, ∴ OK

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 156 kN
Np = 0.9·fc'·eh·do = 51.84 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 469 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1603 mm2 fy = 390 Mpa

Used : 0 - D 16 ---------- As = - mm2


Additional : 26 - D 16 ---------- As = 5,226 mm2
As,prov.= 5226 mm2 (∴ As,req./As,prov= 0.31 )

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 245 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 87 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 230 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.31


a=150 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 710 x 0.31 = 220 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 385 - 150 x tan 35 - 50
= 230 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 246 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

□ Development Length ldh for Deformed Bars in Tension


f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa α D10 D13 D16 D19 D22 D25 D29 D32
1.3 450 580 710 840 1200 1370 1580 1750
a
1.0 340 450 550 650 930 1050 1220 1350
ld
1.3 670 860 1060 1260 1860 2110 2450 2700
b
1.0 510 670 820 970 1430 1620 1880 2080

Case a : Clear spacing of bars being developed or spliced not less than db, clear cover
not less than db, and stirrups or ties throughout ld not less than the code
minimum, or clear spacing of bars being developed or spliced not less than
2db and clear cover not less than db

Case b : All other cases, except for case a

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 247 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 281 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 449 kN

□ AVc / AVco = 1.0


AVco = 4.5·ca12 = 1,500,778 mm2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 1,500,778 mm2 , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 192 / 24 )^(0.2) x 24^(1/2) x 1 x 30^(1/2) x 577.5 ^(1.5)
= 373 kN
ℓe = 8 do = 192 < 385

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.86 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg > Vsa ∴ OK

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 469 = 938 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 248 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 26.00 kN

Min (φVsa, φVcbg, φVcpg) = 183 kN


Vua = 26 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 249 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

10) Pedestal identification = FD FAN(2)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 978 x 1855


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 24 mm
1 in.
□ Number of anchors in group n = 5 Nos.
Arrangement = 2 + 3
□ Anchor spacing s1 = 200 mm ( 1@ 200 )
s2 = 700 mm ( 2@ 350 )
□ Effective cross sectional area Ase = 391 mm
2

□ Effective embedment depth hef = 385 mm


□ Edge distance ca1 = 200 mm
if Ca ≥ 1.5·hef, ca2 = 578 mm
value of Ca is 1.5·hef (= 577.5 ) ca3 = 578 mm
ca4 = 578 mm
□ Bearing area of the hook of anchor eh = 80 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 250 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 782 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 452 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 385 mm
□ ANc / ANco = 1.4
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 1,334,025 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 1,813,263 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 385 ^(1.5)
= 414 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.80 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 782 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2674 mm2 fy = 390 Mpa

Used : 12 - D 16 ---------- As = 2,412 mm2


Additional : 12 - D 16 ---------- As = 2,412 mm2
As,prov.= 4824 mm2 (∴ As,req./As,prov= 0.55 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 259 kN
Np = 0.9·fc'·eh·do = 51.84 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 251 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 782 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2674 mm2 fy = 390 Mpa

Used : 12 - D 16 ---------- As = 2,412 mm2


Additional : 12 - D 16 ---------- As = 2,412 mm2
As,prov.= 4824 mm2 (∴ As,req./As,prov= 0.55 )

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 146 kN


Nua ( ≤0, compression) = 25.9 kN factored tension Load(LCOM215)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 364 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.55

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 71.0 mm ( Hoof Dia= D13 )


□ Required Development Length = 273 x 0.55 = 150 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 385 - (80 - 100/2 - 71) x tan 35 - 50
= 364 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 252 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

In this section, the development length is checked for the additional vertical reinforcement of pedestal
which is expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 195 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.55


a=200 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 273 x 0.55 = 150 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 385 - 200 x tan 35 - 50
= 195 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 253 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 469 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 230 kN

□ AVc / AVco = 2.2


AVco = 4.5·ca12 = 180,000 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 390,000 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 192 / 24 )^(0.2) x 24^(1/2) x 1 x 30^(1/2) x 200 ^(1.5)
= 76 kN
ℓe = 8 do = 192 < 385

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 1.00 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 782 = 1,564 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 254 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 469 /( 0.75 x 390 )x 1000
= 300 mm

2
= 1603 mm
1.5xCa1

As,prov. = Use 12 - D 16
2
= 2412 mm

As,req./As,prov = 0.66 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM226)
= 23.00 kN

Min (φVsa, φVcbg, φVcpg) = 305 kN


Vua = 23 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 255 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

11) Pedestal identification = FD FAN(3)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 2155 x 1043


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 24 mm
1 in.
□ Number of anchors in group n = 3 Nos.
Arrangement = 3 x 1
□ Anchor spacing s1 = 1000 mm ( 2@ 500 )
s2 = 0 mm ( 0@ #DIV/0!
□ Effective cross sectional area Ase = 391 mm
2

□ Effective embedment depth hef = 385 mm


□ Edge distance ca1 = 578 mm
if Ca ≥ 1.5·hef, ca2 = 465 mm
value of Ca is 1.5·hef (= 577.5 ) ca3 = 578 mm
ca4 = 578 mm
□ Bearing area of the hook of anchor eh = 80 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 256 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 469 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 656 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 385 mm
□ ANc / ANco = 1.7
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 1,334,025 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 2,246,588 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 385 ^(1.5)
= 414 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.94 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg > Nsa, ∴ OK

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 156 kN
Np = 0.9·fc'·eh·do = 51.84 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 469 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1603 mm2 fy = 390 Mpa

Used : 0 - D 16 ---------- As = - mm2


Additional : 26 - D 16 ---------- As = 5,226 mm2
As,prov.= 5226 mm2 (∴ As,req./As,prov= 0.31 )

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 257 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 87 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 230 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.31


a=150 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 710 x 0.31 = 220 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 385 - 150 x tan 35 - 50
= 230 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 258 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

□ Development Length ldh for Deformed Bars in Tension


f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa α D10 D13 D16 D19 D22 D25 D29 D32
1.3 450 580 710 840 1200 1370 1580 1750
a
1.0 340 450 550 650 930 1050 1220 1350
ld
1.3 670 860 1060 1260 1860 2110 2450 2700
b
1.0 510 670 820 970 1430 1620 1880 2080

Case a : Clear spacing of bars being developed or spliced not less than db, clear cover
not less than db, and stirrups or ties throughout ld not less than the code
minimum, or clear spacing of bars being developed or spliced not less than
2db and clear cover not less than db

Case b : All other cases, except for case a

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 259 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 281 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 449 kN

□ AVc / AVco = 1.0


AVco = 4.5·ca12 = 1,500,778 mm2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 1,500,778 mm2 , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 192 / 24 )^(0.2) x 24^(1/2) x 1 x 30^(1/2) x 577.5 ^(1.5)
= 373 kN
ℓe = 8 do = 192 < 385

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.86 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg > Vsa ∴ OK

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 469 = 938 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 260 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM218)
= 26.00 kN

Min (φVsa, φVcbg, φVcpg) = 183 kN


Vua = 26 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 261 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

12) Pedestal identification = FD FAN(4)

(1) Design information

A) Anchor bolt Property

L'

B'

□ Pedestal Size B' x L' = 978 x 1855


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 24 mm
1 in.
□ Number of anchors in group n = 5 Nos.
Arrangement = 2 + 3
□ Anchor spacing s1 = 200 mm ( 1@ 200 )
s2 = 700 mm ( 2@ 350 )
□ Effective cross sectional area Ase = 391 mm
2

□ Effective embedment depth hef = 385 mm


□ Edge distance ca1 = 200 mm
if Ca ≥ 1.5·hef, ca2 = 578 mm
value of Ca is 1.5·hef (= 577.5 ) ca3 = 578 mm
ca4 = 578 mm
□ Bearing area of the hook of anchor eh = 80 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa
Because of overturning moment due to the horizontal seismic force acting at C.G, a half part is in tension
and the other part is in compression. So the check of concrete breakout failure should be performed
focused on this point. Considering only tension part, the area ANc for concrete breakout failure check is
calculated as expressed in "Tension Check. B" in next page.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 262 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 782 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 452 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 385 mm
□ ANc / ANco = 1.4
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 1,334,025 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 1,813,263 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 385 ^(1.5)
= 414 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.80 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 782 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2674 mm2 fy = 390 Mpa

Used : 12 - D 16 ---------- As = 2,412 mm2


Additional : 12 - D 16 ---------- As = 2,412 mm2
As,prov.= 4824 mm2 (∴ As,req./As,prov= 0.55 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 259 kN
Np = 0.9·fc'·eh·do = 51.84 kN (for single hooked bolt)
where 3·do≤eh≤4.5·do
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn < Nsa, ∴ NG

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 263 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

☞ Determine Additional Reinforcement


As,req. = Nsa/φ·fy = 782 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 2674 mm2 fy = 390 Mpa

Used : 12 - D 16 ---------- As = 2,412 mm2


Additional : 12 - D 16 ---------- As = 2,412 mm2
As,prov.= 4824 mm2 (∴ As,req./As,prov= 0.55 )

D) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 146 kN


Nua ( ≤0, compression) = 25.9 kN factored tension Load(LCOM215)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K

E) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 364 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.55

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 71.0 mm ( Hoof Dia= D13 )


□ Required Development Length = 273 x 0.55 = 150 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 385 - (80 - 100/2 - 71) x tan 35 - 50
= 364 mm ----- O.K

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 264 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

In this section, the development length is checked for the additional vertical reinforcement of pedestal
which is expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 195 mm

of fresh concrete is cast in the member below the


hef = 385 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.55


a=195 mm

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Required Development Length = 273 x 0.55 = 150 mm


□ Used Development Length = hef - a·tan35 -Top Con'c Cover
= 385 - 200 x tan 35 - 50
= 195 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 265 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 469 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 230 kN

□ AVc / AVco = 2.2


AVco = 4.5·ca12 = 180,000 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 390,000 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 192 / 24 )^(0.2) x 24^(1/2) x 1 x 30^(1/2) x 200 ^(1.5)
= 76 kN
ℓe = 8 do = 192 < 385

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 1.00 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 782 = 1,564 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 266 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 469 /( 0.75 x 390 )x 1000
= 300 mm

2
= 1603 mm
1.5xCa1

As,prov. = Use 12 - D 16
2
= 2412 mm

As,req./As,prov = 0.66 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM226)
= 23.00 kN

Min (φVsa, φVcbg, φVcpg) = 305 kN


Vua = 23 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 267 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

13) Pedestal identification = FD FAN(5)

(1) Design information

A) Anchor bolt Property

ca2 s2 ca4

ca3

s1
B'
hef

ca1

L'

□ Pedestal Size B' x L' = 950 x 850


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 20 mm
7/8 in.
□ Number of anchors in group n = 4 Nos.
Arrangement = 2 x 2
□ Anchor spacing s1 = 560 mm ( 1@ 560 )
s2 = 350 mm ( 1@ 350 )
□ Effective cross sectional area Ase = 298 mm
2

□ Effective embedment depth hef = 260 mm


□ Edge distance ca1 = 195 mm
if Ca ≥ 1.5·hef, ca2 = 250 mm
value of Ca is 1.5·hef (= 390 ) ca3 = 195 mm
ca4 = 250 mm
□ Bearing area of the head of anchor Abrg = 3148
mm
2

Bearing plate size, W : 60 mm x 60 mm (=60 x 60 - 0.25 x π x 24^2)


Sleeve diameter, SD : D 24 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 268 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 477 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 327 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 187 mm
□ ANc / ANco = 2.6
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 314,721 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) - (Bshear x Lshear) = 807,500 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 187 ^(1.5)
= 140 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 0.91 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 477 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1631 mm2 fy = 390 Mpa

Used : 34 - D 19 ---------- As = 9,656 mm2


Additional : 22 - D 16 ---------- As = 4,422 mm2
As,prov.= 14078 mm2 (∴ As,req./As,prov= 0.12 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 3,022 kN
Np = 8·Abrg·fc' = 755 kN (for single headed stud & bolt)
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn > Nsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 269 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Check for Concrete Side-Face Blow-out Strength of a headed anchor in tension


(ACI318-14 Chapter 17.4.4)

☞ Tension per Anchor Bolt


Nsa / n (Tension anchor) = 119.3 kN

☞ Tension (Nsa') for Side-Face Blowout Check


119.3 x 2 ea = 238.5 kN

Apply bolt ( 2 ea ) for Side-Face Blowout Check Use

☞ Determine Nominal Concrete Side-Face Blow-out Strength of a headed anchor in tension(Nsb,Nsbg)


For single headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef)
Min. spacing = 350 mm < 6ca1. So, it's considered as a group anchor
0.4hef = 104 mm < ca1. So, blow-out failure is not considered.
ca2/ca1 = 1.3
λa = 1.0

Nsb = {(1+ca2/ca1)/4} · 13 · ca1 · Abrg^0.5 · λa ·f'c^0.5, where 1.0 ≤ ca2/ca1 ≤ 3.0


= N.A
= N.A kN

For multiple headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef) and
anchor spacing(s) < 6·ca1,
Nsbg = (1+s2 / 6·ca1)·Nsb = N.A kN

Not Applicable

E) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 358 kN


Nua ( ≤0, compression) = 1,367 kN factored tension Load(LCOM430)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≤ Nua, ∴ N.G


☞ Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 270 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


of fresh concrete is cast in the member below the
ldh = 107 mm
hef = 260 mm

development length or splice : 1.3

35 deg Other reinforcement : 1.0

Excess reinforcement = 0.12

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 72.5 mm ( Hoof Dia= D13 )


□ Required Development Length = 325 x 0.12 = 101 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 260 - (250 - 60/2 - 72.5) x tan 35 - 50
= 107 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 271 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 286 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 143 kN

□ AVc / AVco = 1.6


AVco = 4.5·ca12 = 171,113 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 273,488 mm , Avc ≤ n·Avco

0.2 (1/2)
□ Vb = 0.66 · (ℓe/do) · (do) · λa · (fc')(1/2) · ca1(1.5)
= 0.66 x ( 160 / 20 )^(0.2) x 20^(1/2) x 1 x 30^(1/2) x 195 ^(1.5)
= 67 kN
ℓe = 8 do = 160 < 260

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.96 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 477 = 954 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 272 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 286 /( 0.75 x 390 )x 1000
= 293 mm

2
= 978 mm
1.5xCa1

As,prov. = Use 24 - D 13
2
= 3192 mm

As,req./As,prov = 0.31 < 1.0 -------> ∴ OK

D> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM209)
= 1 kN

Min (φVsa, φVcbg, φVcpg) = 186 kN


Vua = 1 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 273 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

14) Pedestal identification = FD FAN(6)

(1) Design information

A) Anchor bolt Property

ca2 s2 ca4

ca3

s1
B'
hef

ca1

L'

□ Pedestal Size B' x L' = 600 x 600


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 20 mm
7/8 in.
□ Number of anchors in group n = 4 Nos.
Arrangement = 2 x 2
□ Anchor spacing s1 = 300 mm ( 1@ 300 )
s2 = 300 mm ( 1@ 300 )
□ Effective cross sectional area Ase = 298 mm
2

□ Effective embedment depth hef = 350 mm


□ Edge distance ca1 = 150 mm
if Ca ≥ 1.5·hef, ca2 = 150 mm
value of Ca is 1.5·hef (= 525 ) ca3 = 150 mm
ca4 = 150 mm
□ Bearing area of the head of anchor Abrg = 3148
mm
2

Bearing plate size, W : 60 mm x 60 mm (=60 x 60 - 0.25 x π x 24^2)


Sleeve diameter, SD : D 24 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 274 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 477 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 219 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 100 mm
□ ANc / ANco = 4.0
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 90,000 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) = 360,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 100 ^(1.5)
= 55 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 1.00 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 477 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1631 mm2 fy = 390 Mpa

Used : 16 - D 19 ---------- As = 4,544 mm2


Additional : 0 - D 16 ---------- As = - mm2
As,prov.= 4544 mm2 (∴ As,req./As,prov= 0.36 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 3,022 kN
Np = 8·Abrg·fc' = 755 kN (for single headed stud & bolt)
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn > Nsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 275 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Check for Concrete Side-Face Blow-out Strength of a headed anchor in tension


(ACI318-14 Chapter 17.4.4)

☞ Tension per Anchor Bolt


Nsa / n (Tension anchor) = 119.3 kN

☞ Tension (Nsa') for Side-Face Blowout Check


119.3 x 2 ea = 238.5 kN

Apply bolt ( 2 ea ) for Side-Face Blowout Check Use

☞ Determine Nominal Concrete Side-Face Blow-out Strength of a headed anchor in tension(Nsb,Nsbg)


For single headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef)
Min. spacing = 300 mm < 6ca1. So, it's considered as a group anchor
0.4hef = 140 mm < ca1. So, blow-out failure is not considered.
ca2/ca1 = 1.0
λa = 1.0

Nsb = {(1+ca2/ca1)/4} · 13 · ca1 · Abrg^0.5 · λa ·f'c^0.5, where 1.0 ≤ ca2/ca1 ≤ 3.0


= N.A
= N.A kN

For multiple headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef) and
anchor spacing(s) < 6·ca1,
Nsbg = (1+s2 / 6·ca1)·Nsb = N.A kN

Not Applicable

E) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 358 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K


☞ Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 276 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 267 mm

of fresh concrete is cast in the member below the


hef = 350 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.36

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 72.5 mm ( Hoof Dia= D13 )


□ Required Development Length = 325 x 0.36 = 117 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 350 - (150 - 60/2 - 72.5) x tan 35 - 50
= 267 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 277 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 286 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 95 kN

□ AVc / AVco = 1.7


AVco = 4.5·ca12 = 101,250 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 168,750 mm , Avc ≤ n·Avco

□ Vb = 0.66 · (ℓe/do)0.2 · (do)(1/2) · λa · (fc')(1/2) · ca1(1.5)


= 0.66 x ( 160 / 20 )^(0.2) x 20^(1/2) x 1 x 30^(1/2) x 150 ^(1.5)
= 45 kN
ℓe = 8 do = 160 < 350

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.90 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 477 = 954 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 278 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 286 /( 0.75 x 390 )x 1000
= 225 mm

2
= 978 mm
1.5xCa1

As,prov. = Use 9 - D D13


2
= 1197 mm

As,req./As,prov = 0.82 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM219)
= 29 kN

Min (φVsa, φVcbg, φVcpg) = 186 kN


Vua = 29 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 279 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

15) Pedestal identification = DUCT & PLATFORM

(1) Design information

A) Anchor bolt Property

ca2 s2 ca4

ca3

s1
B'
hef

ca1

L'

□ Pedestal Size B' x L' = 600 x 600


□ Material of anchor bolt = ASTM A36
□ Yield strength fya = 250 Mpa
□ Tensile strength futa = 400 Mpa
□ Diameter do = 20 mm
7/8 in.
□ Number of anchors in group n = 4 Nos.
Arrangement = 2 x 2
□ Anchor spacing s1 = 300 mm ( 1@ 300 )
s2 = 300 mm ( 1@ 300 )
□ Effective cross sectional area Ase = 298 mm
2

□ Effective embedment depth hef = 350 mm


□ Edge distance ca1 = 150 mm
if Ca ≥ 1.5·hef, ca2 = 150 mm
value of Ca is 1.5·hef (= 525 ) ca3 = 150 mm
ca4 = 150 mm
□ Bearing area of the head of anchor Abrg = 3148
mm
2

Bearing plate size, W : 60 mm x 60 mm (=60 x 60 - 0.25 x π x 24^2)


Sleeve diameter, SD : D 24 mm

B) Concrete Property
□ Compressive strength of concrete f'c = 30 MPa

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 280 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

(2) Tension check

A) Check for Strength of Anchor in Tension (ACI318-14 Chapter 17.4.1.2)


☞ Determine Nominal Strength of Anchor in Tension (Nsa)
Nsa = n·Ase·futa = 477 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B) Check for Concrete Breakout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.2)
☞ Determine Nominal Concrete Breakout Strength of Anchor in Tension (Ncb, Ncbg)
Ncbg = ANc/ANco·ψec,N·ψed,N·ψc,N·ψcp,N·Nb = 219 kN
where, anchors are located less than 1.5·hef from three or more edges,
the value of hef shall be greater of ca,max /1.5 and 1/3 of max. spacing of group anchor.
Therefore, hef = 100 mm
□ ANc / ANco = 4.0
ANco = 2·(1.5·hef)·2·(1.5·hef) = 9·hef2 = 90,000 mm2
ANc = (ca1+s1+ca3)·(ca2+s2+ca4) = 360,000 mm2 , Anc ≤ n·Anco

(1/2) (1.5)
□Nb = kc·λa·(fc') ·hef = 10 x 1 x 30^(1/2) x 100 ^(1.5)
= 55 kN
kc = 10 λa = 1.0 modification factor lightweight
10 for cast-in anchor concrete for cast-in anchor
7 for post-installed anchor

□ ψec,N = 1 for no eccentricity in the connection


ψ
□ ed,N = 1.00 for modification of edge effects
ψed,N = 1 ca,min ≥ 1.5·hef
ψed,N = 0.7+0.3·ca,min / (1.5·hef) ca,min < 1.5·hef
□ ψc,N = 1
ψc,N = 1.25 for cast-in anchors, when analysis indicates no cracking at service load
ψc,N = 1.4 for post-installed anchor, when analysis indicates no cracking
at service load
ψc,N = 1 when analysis indicates cracking at service load
□ cp,N =
ψ 1 for cast-in anchors

Ncbg < Nsa, ∴ NG. So, additional reinforcement shall be provided

☞ Determine Additional Reinforcement (ACI318-14 Chapter 17.4.2.9)


As,req. = Nsa/φ·fy = 477 /( 0.75 x 390 )x 1000 , where φ = 0.75
= 1631 mm2 fy = 390 Mpa

Used : 16 - D 19 ---------- As = 4,544 mm2


Additional : 0 - D 16 ---------- As = - mm2
As,prov.= 4544 mm2 (∴ As,req./As,prov= 0.36 )

C) Check for Pullout Strength of Anchor in Tension (ACI318-14 Chapter 17.4.3)


☞ Determine Nominal Pullout Strength of Anchor in Tension (Npn)
Npn = n·ψc,P·Np = 3,022 kN
Np = 8·Abrg·fc' = 755 kN (for single headed stud & bolt)
ψc,P = 1
ψc,P = 1.4 when analysis indicates no cracking at service load
ψc,P = 1 when analysis indicates cracking at service load

Npn > Nsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 281 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D) Check for Concrete Side-Face Blow-out Strength of a headed anchor in tension


(ACI318-14 Chapter 17.4.4)

☞ Tension per Anchor Bolt


Nsa / n (Tension anchor) = 119.3 kN

☞ Tension (Nsa') for Side-Face Blowout Check


119.3 x 2 ea = 238.5 kN

Apply bolt ( 2 ea ) for Side-Face Blowout Check Use

☞ Determine Nominal Concrete Side-Face Blow-out Strength of a headed anchor in tension(Nsb,Nsbg)


For single headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef)
Min. spacing = 300 mm < 6ca1. So, it's considered as a group anchor
0.4hef = 140 mm < ca1. So, blow-out failure is not considered.
ca2/ca1 = 1.0
λa = 1.0

Nsb = {(1+ca2/ca1)/4} · 13 · ca1 · Abrg^0.5 · λa ·f'c^0.5, where 1.0 ≤ ca2/ca1 ≤ 3.0


= N.A
= N.A kN

For multiple headed anchor w/ deep embedment close to an edge (ca1 < 0.4·hef) and
anchor spacing(s) < 6·ca1,
Nsbg = (1+s2 / 6·ca1)·Nsb = N.A kN

Not Applicable

E) Comparison of Factored Tension with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)

☞ Factored tension (Nua) by load combination would be compared with reduced anchor strength
(Nsa, Ncbg, Npn, Nsbg, calculated in clause A>, B>, C>, D>) by equation as follow.

Min (φNsa, 0.75φNcbg, 0.75φNpn, 0.75φNsbg) ≥ Nua

where, φ = 0.75 (tension)

Min (φNsa, 0.75φNpn, 0.75φNsbg) = 358 kN


Nua ( ≤0, compression) = 0 kN factored tension Load(LCOM225)

Min (φNsa, 0.75φNpn, 0.75φNsbg) ≥ Nua, ∴ O.K


☞ Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 282 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

F) Check for development length of deformed bars in tension

In this section, the development length is checked for the main vertical reinforcement of pedestal which is
expressed as "Used" in section 'B>' above.

□ Modification Factor
Reinforcement Location Factor, α = 1.00

Horizontal reinforcement so placed that more than 300mm


ldh = 267 mm

of fresh concrete is cast in the member below the


hef = 350 mm

development length or splice : 1.3


35 deg Other reinforcement : 1.0

Excess reinforcement = 0.36

Where anchorage or development for fy is not specifically


required, reinforcement in excess of that required by
analysis : As,required / As,provided

□ Concrete Cover = 72.5 mm ( Hoof Dia= D13 )


□ Required Development Length = 325 x 0.36 = 117 mm
□ Used Development Length = hef - (ca2 - W/2 - Con'c Cover) tan35 -Top Con'c Cover
= 350 - (150 - 60/2 - 72.5) x tan 35 - 50
= 267 mm ----- O.K

□ Development Length ldh for Deformed Bars in Tension (ACI318-14 Chapter 25.4.3)
f'c = 30MPa, fy = 390MPa, Unit= mm
f'c = 30MPa D10 D13 D16 D19 D22 D25 D29 D32
ldh 171 222 273 325 376 427 496 547

0.24 fy ψe ψc ψr
ldh = ( ) db
λ √fc'

Where, ψe : Modification factor by uncoated reinforcement 1.0


ψc : Modification factor by bars size (Other) 1.0
ψr : Modification factor by confining reinforcement (Other) 1.0
λ : Modification factor by nomalweight 1.0

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 283 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

■ SHEAR CHECK

A> Check for Strength of Anchor in Shear (ACI318-14 Chapter 17.5.1)


☞ Determine Nominal Strength of Anchor in Shear (Vsa)
Vsa = n·0.6·Ase·futa = 286 kN , where futa ≤ Min (1.9·fya, 860 Mpa)

B> Check for Concrete Breakout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.2)

☞ Determine Nominal Concrete Breakout Strength of Anchor in Shear (Vcb, Vcbg)


Vcbg = AVc/AVco·ψec,V·ψed,V·ψc,V·ψh,V·Vb = 95 kN

□ AVc / AVco = 1.7


AVco = 4.5·ca12 = 101,250 mm2
2
AVc = (1.5ca1+s2+1.5ca1)·(1.5ca1) = 168,750 mm , Avc ≤ n·Avco

□ Vb = 0.66 · (ℓe/do)0.2 · (do)(1/2) · λa · (fc')(1/2) · ca1(1.5)


= 0.66 x ( 160 / 20 )^(0.2) x 20^(1/2) x 1 x 30^(1/2) x 150 ^(1.5)
= 45 kN
ℓe = 8 do = 160 < 350

□ ψec,V = 1.00 for no eccentricity in the connection

□ ψed,V = 0.90 for modification of edge effects


ψed,N = 1 ca2 ≥ 1.5·ca1
ψed,N = 0.7+0.3·ca2 / .(1.5·ca1) ca2 < 1.5·ca1

□ ψc,V = 1.40
ψc,V = 1.0 for anchors in cracked concrete with no supplementary
reinforcement or edge reinforcement smaller than a No. 13 bar.
ψc,V = 1.2 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge.
ψc,V = 1.4 for anchors in cracked concrete with supplementary reinforcement
of a No. 13 bar or greater between the anchor and the edge,
and with the supplementary reinforcement enclosed
within stirrups spaced at not more than 10cm.

Vcbg < Vsa ∴ NG. So, additional reinforcement shall be provided

C> Check for Pryout Strength of Anchor in Shear (ACI318-14 Chapter 17.5.3)
☞ Determine Nominal Pullout Strength of Anchor in Shear (Vcp or Vcpg)
Vcpg = kcp Ncbg ( ≥ Nsa ) = kcp Nsa = 2.0 x 477 = 954 kN for a group of anchors
Where, Ncbg would be lager than Nsa, when considering additional reinforcement would be placed.

kcp = 2.0
kcp = 1.0 for hef < 64mm(2.5in.)
kcp = 2.0 for hef ≥ 64mm(2.5in.)

Vcpg > Vsa, ∴ OK

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 284 -
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

D> Determine Supplementary Reinforcement for Shear (ACI318-14 Chapter 17.5.2.9)

Use SNI 07-2052 BjTS 40 fy = 390 Mpa


As,req. = Vs / φ·fy Where, φ=0.75
= 286 /( 0.75 x 390 )x 1000
= 225 mm

2
= 978 mm
1.5xCa1

As,prov. = Use 9 - D D13


2
= 1197 mm

As,req./As,prov = 0.82 < 1.0 -------> ∴ OK

E> Comparison of Factored Shear with Reduced Anchor Strength applied Reduction Factor
(ACI318-14 Chapter 17.3.1.1)
☞ Factored shear (Vua) by load combination would be compared with reduced anchor strength
(Vsa, Vcbg, Vcpg, calculated in clause A>, B>, C>) by equation as follow.

Min (φVsa, φVcbg, φVcpg) ≥ Vua

where, φ = 0.65 (shear)


Vua = factored Shear Load (LCOM201)
= 55 kN

Min (φVsa, φVcbg, φVcpg) = 186 kN


Vua = 55 kN

Min (φVsa, , φVcpg) ≥ Vua, ∴ O.K


☞ Vcbg would be lager than Vsa, when considering additional reinforcement would be placed.

DOCUMENT No. : IKCP0-UHA-C-06-0001


- 285 -
[ ATTACHMENTS ]

#1. Equipment Vendor Data


[ ATTACHMENTS ]

#2. Foundation Check for Vibration Machinery (P.A FAN)


2-1. P.A FAN (UNIT#1A,2A)
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.0 CONCRETE AND SOIL PARAMETERS

γs 1.96 3
1) UNIT WEIGHT OF SUBGROUND = ton/m (From clause 8.0)
(CLAY LAYER)

2) DYNAMIC SHEAR MODULUS OF SUGBROUND Gds = 1119.9 kg/cm2 (From clause 8.0)
(CLAY LAYER)

3) DYNAMIC POISSON'S RATIO OF SUBGROUND νds = 0.330 (From clause 8.0)


(CLAY LAYER)

4) SOIL INTERNAL DAMPING RATIO = 0.05

3
5) UNIT WEIGHT OF FOUNDATION CONCRETE = 2.50 ton/m

2.0 MACHINE PARAMETERS (BY VENDOR INFORMATION)

1) MACHINE WEIGHT (UNIT : KG)

STATIC WEIGHT DYNAMIC FORCES

LOCATION VERTICAL HORIZONTAL LOCATION VERTICAL HORIZONTAL

Y-DIR. X-DIR. Z-DIR. Y-DIR. X-DIR. Z-DIR.

A 7200 0 0 A 7200 290 290


Motar Motar
Bed Bed
SUB Ⅰ 7200 0 0 SUB Ⅰ 7200 290 290

B 1950 0 0 B 1050 72 72
B'RG B'RG
Housing C 1950 0 0 Housing C 1050 42 42
Bed Bed
SUB Ⅱ 3900 0 0 SUB Ⅱ 2100 114 114

D 3450 0 0 D 0 74 74

E 2850 0 0 E 0 74 74

Casing Casing
F 2550 0 0 F 0 74 74
Bracket Bracket

G 950 0 0 G 0 74 74

SUB Ⅲ 9800 0 0 SUB Ⅲ 0 296 296

DAMPER H 440 0 0 DAMPER H 0 0 0


ACTUATO ACTUATO
R BED SUB Ⅳ 440 0 0 R BED SUB Ⅳ 0 0 0

TOTAL 20900 0 0 TOTAL 9300 700 404

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.0 FOUNDATION SIZE CHECK

1) FOUNDATION WEIGHT
(UNIT : ton, m)

FOUNDATION SIZE TOTAL

COMPONENT WIDTH LENGTH AREA HEIGHT WEIGHT

Bf Lf Af Hf Wf

F1 1.150 0.800 0.92 1.910 4.39

F2 3.600 1.100 3.96 1.910 18.91

F3 3.600 0.800 2.88 1.910 13.75

F4 3.600 1.950 7.02 1.650 28.96

F5 2.800 2.250 6.30 1.650 25.99

F6 1.200 1.200 1.44 0.250 0.90

F7 1.800 1.200 2.16 1.100 5.94

F8 3.600 8.430 30.35 1.100 83.46

TOTAL 55.03 182.30

2) MACHINE WEIGHT Wm = 20.9 ton

3) MASS RATIO = Wc / Wm = 182.30 ÷ 20.9

= 8.72 > 3 ∴ O.K

4) MASS RATIO OF ROTOR


MASS RATIO = Wc / ROTOR WEIGHT
= 182.3 ÷ 7.2

= 25.32 > 25 ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) OPERATING FREQUENCY : fo = 1480 RPM

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4.0 CALCULATION OF C.G. OF MACHINE & FOUNDATION

4.1 CENTER OF GRAVITY IN STATIC CONDITION


1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD
Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My
A 7.200 0.000 0.000 5.407 38.930 2.100 15.120 2.800 0.000

B 1.950 0.000 0.000 3.720 7.254 2.100 4.095 3.060 0.000

C 1.950 0.000 0.000 1.610 3.140 2.100 4.095 3.060 0.000

D 3.450 0.000 0.000 3.680 12.696 1.350 4.658 3.060 0.000

E 2.850 0.000 0.000 1.650 4.703 1.350 3.848 3.060 0.000

F 2.550 0.000 0.000 3.680 9.384 2.850 7.268 3.060 0.000

G 0.950 0.000 0.000 1.650 1.568 2.850 2.708 3.060 0.000

H 0.440 0.000 0.000 1.322 0.582 4.800 2.112 1.400 0.000

TOTAL 21.34 0.00 0.00 78.3 43.90 0.00

2) CENTER OF GRAVITY FOR FOUNDATION


WEIGHT MASS X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (t·sec2/m) X(m) Mz Z(m) Mx Y(m) My
F1 4.39 0.448 0.400 1.76 3.025 13.28 2.055 9.02

F2 18.91 1.928 1.350 25.53 1.800 34.04 2.055 38.86

F3 13.75 1.402 3.830 52.66 1.800 24.75 2.055 28.26

F4 28.96 2.952 5.205 150.74 1.800 52.13 1.925 55.75

F5 25.99 2.649 7.305 189.86 2.200 57.18 1.925 50.03

F6 0.90 0.092 1.322 1.19 4.800 4.32 1.225 1.10

F7 5.94 0.606 1.322 7.85 4.500 26.73 0.550 3.27

F8 83.46 8.508 4.190 349.70 1.800 150.23 0.550 45.90

TOTAL 182.30 18.58 779.28 362.65 232.19

3) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA

Mcx = Af x Czi

Mcz = Af x Cxi

FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F8,F9 3.600 8.430 32.508 1.979 4.023 64.33 130.78

TOTAL 32.51 64.33 130.78

Xf = ∑Mcz / ∑Af = 130.78 / 32.51 = 4.02 m

Zf = ∑Mcx / ∑Af = 64.33 / 32.51 = 1.98 m

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) CENTER OF GRAVITY OF MACHINE & FOUNDATION

Xcg = Mz(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 779.28 + 78.26 )/( 182.30 + 21.34 ) = 4.211 m

Zcg = Mx(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 362.65 + 43.90 )/( 182.30 + 21.34 ) = 1.996 m

Ycg = My(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 232.19 + 0.00 )/( 182.30 + 21.34 ) = 1.140 m

5) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 4.02 - 4.21 | / 8.43 x 100
= 2.27 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 1.98 - 2.00 | / 3.60 x 100
= 0.44 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.0 CENTER OF GRAVITY IN OPERATING CONDITION

1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 7.200 0.000 0.000 5.407 38.930 2.100 15.120 2.800 0.000

B 1.950 0.000 0.000 3.720 7.254 2.100 4.095 2.800 0.000

C 1.950 0.000 0.000 1.610 3.140 2.100 4.095 2.800 0.000

D 3.450 0.000 0.000 3.680 12.696 1.350 4.658 2.800 0.000

E 2.850 0.000 0.000 1.650 4.703 1.350 3.848 2.800 0.000

F 2.550 0.000 0.000 3.680 9.384 2.850 7.268 2.800 0.000

G 0.950 0.000 0.000 1.650 1.568 2.850 2.708 2.800 0.000

H 0.440 0.000 0.000 1.322 0.582 4.800 2.112 2.800 0.000

TOTAL 20.90 0.00 0.00 21.40 77.7 14.70 41.79 19.6 0.00

2) CENTER OF GRAVITY FOR MACHINE DYNAMIC LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 7.200 0.290 0.290 5.407 39.742 2.100 15.932 2.800 2.177

B 1.050 0.072 0.072 3.720 4.108 2.100 2.407 2.800 0.419

C 1.050 0.042 0.042 1.610 1.808 2.100 2.323 2.800 0.156

D 0.000 0.074 0.074 3.680 0.207 1.350 0.207 2.800 0.372

E 0.000 0.074 0.074 1.650 0.207 1.350 0.207 2.800 0.222

F 0.000 0.074 0.074 3.680 0.207 2.850 0.207 2.800 0.483

G 0.000 0.074 0.074 1.650 0.207 2.850 0.207 2.800 0.333

TOTAL 9.30 0.70 0.70 46.49 21.49 4.16

3) CENTER OF GRAVITY FOR FOUNDATION


WEIGHT MASS X-DIR Z-DIR Y-DIR
COMPONENT
2
(TON) (t·sec /m) X(m) Mz Z(m) Mx Y(m) My

F1 4.39 0.448 0.400 1.76 3.025 13.28 2.055 9.02

F2 18.91 1.928 1.350 25.53 1.800 34.04 2.055 38.86

F3 13.75 1.402 3.830 52.66 1.800 24.75 2.055 28.26

F4 28.96 2.952 5.205 150.74 1.800 52.13 1.925 55.75

F5 25.99 2.649 7.305 189.86 2.200 57.18 1.925 50.03

F6 0.90 0.092 1.322 1.19 4.800 4.32 1.225 1.10

F7 5.94 0.606 1.322 7.85 4.500 26.73 0.550 3.27

F8 83.46 8.508 4.190 349.70 1.800 150.23 0.550 45.90

TOTAL 182.30 18.583 779.28 362.65 232.19

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA


Mcx = Af x Czi
Mcz = Af x Cxi
FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F8,F9 3.600 8.430 32.508 1.979 4.023 64.33 130.78

TOTAL 32.51 64.33 130.78

Xf = ∑Mcz / ∑Af = 130.78 / 32.51 = 4.02 m


Zf = ∑Mcx / ∑Af = 64.33 / 32.51 = 1.98 m

5) CENTER OF GRAVITY OF MACHINE & FDN. IN DYNAMIC CONDITION

Xcg = Mz(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 779.28 + 77.67 + 46.49 )
/ ( 182.30 + 21.34 + 9.30 ) = 4.243 m

Zcg = Mx(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 362.65 + 41.79 + 21.49 )
/ ( 182.30 + 21.34 + 9.30 ) = 2.000 m

Ycg = My(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 232.19 + 0.00 + 4.16 )
/ ( 182.30 + 21.34 + 9.30 ) = 1.110 m

6) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 4.02 - 4.24 | / 8.43 x 100
= 2.65 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 1.98 - 2.00 | / 3.60 x 100
= 0.56 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.0 SPRING CONSTANT CALCULATION


6.1 Vertical direction
1) SINGLE PILE SPRING CONSTANT
Ep·A
KZ1 = · fz1
r0p
3354866 x 0.157
= x 0.092 = 161,526 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


= ( Gds / ρs )0.5 = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 32900000 kpa = 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
A = CROSS-SECTION AREA OF PILE = 0.157 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22 m
∴ L/r0p = 22 / 0.3 = 73.3333
fz1 = VALUE OF FUNCTION = 0.092
Ep/Gsp
L/r0p
250 299.568 500
fw1 0.0980 0.092 0.0700 73.3333

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT


∑n·KZ1 6 x 161,526
KZg1 = = = 314,865 ton/m (FOR PILE)
αa 3.078

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 22 / ( 2 x 0.3 ) = 36.667
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αa = INTERACTION FACTOR = 3.078
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
S/2r0p or αa
S(m) REMARKS
2r0p/S νs = 0.00 νs = 0.32 νs = 0.50
P1 0.000 - - 1.000 - REFERENCE PILE
P2 2.665 4.442 0.527 0.486 0.464
P3 5.330 0.113 0.397 0.346 0.318
P4 2.500 4.167 0.542 0.501 0.479
P5 3.654 0.164 0.464 0.417 0.391
P6 5.887 0.102 0.378 0.328 0.300

∑ 3.08

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.2 Horizontal direction (Parrel to PA Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m4
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22 m
∴ L/r0p = 22 / 0.3 = 73.3333
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 73

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 6 x 24,937
KHg1 = = = 59,403 ton/m (FOR PILE)
αpf 2.52

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 22 / ( 2 x 0.3 ) = 36.667
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.52
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
4
= 3354866 x 0.00329 /( 29,599 x 22 )
= 1.59E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - 90.00 1.00 1.00 1.00
P2 2.665 0.000 2.665 4.442 0.225 0.00 0.43 0.29 0.43
P3 5.330 0.000 5.330 8.883 0.113 0.00 0.27 0.16 0.27
P4 0.000 2.500 2.500 4.167 0.240 90.00 0.47 0.31 0.31
P5 2.665 2.500 3.654 6.090 0.164 43.17 0.33 0.21 0.27
P6 5.330 2.500 5.887 9.812 0.102 25.13 0.26 0.15 0.23
Sum of interaction factor for horizontal direction 2.52

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.3 Horizontal direction (Transverse to PA Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
= 0.26 t·sec2/m4
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22 m
∴ L/r0p = 22 / 0.3 = 73.3333
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 73

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 6 x 24,937
KHg1 = = = 63,345 ton/m (FOR PILE)
αpf 2.36

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 22 / ( 2 x 0.3 ) = 36.667
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.36
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
4
= 3354866 x 0.00329 /( 29,599 x 22 )
= 1.59E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - - 1 1 1 Reference pile
P2 2.665 0.000 2.665 4.442 0.225 90.00 0.43 0.29 0.29
P3 5.330 0.000 5.330 8.883 0.113 90.00 0.27 0.16 0.16
P4 0.000 2.500 2.500 4.167 0.240 - 0.47 0.31 0.47
P5 2.665 2.500 3.654 6.090 0.164 46.83 0.33 0.21 0.27
P6 5.330 2.500 5.887 9.812 0.102 64.87 0.26 0.15 0.18
Sum of interaction factor for horizontal direction 2.36

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 DAMPING RATIO


7.1 Vertical direction
1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ap 3354866 x 0.157


CZ1 = · fw2 = x 0.055
Vs 237

= 122.4 t·sec/m (FOR PILE)

From clause 6, ∴ Ep/Gds= 3354866 / 11,199 = 299.57


∴ L/r0p = 22 / 0.3 = 73.3333

fz2 : VALUE OF FUNCTION = 0.055


Ep/Gds
L/r0p
250 299.568 500
fw2 0.059 0.055 0.041 73

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CZ1 6 x 122.423
CZg1 = = = 238.641 t·sec/m
αa 3.078

Where, n = NUMBER OF PILE = 6 EA


αa = 3.078 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CZg1 238.641
DZ = = = 0.047
2· KZg1·m 2x 314,865 x 20.7

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 2.1 + 18.6 = 20.7 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

Dtz = Dz + Di = 0.047 + 0.05 = 0.097

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.2 Horizontal direction (Parrel to PA Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 73

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 6 x 74.63
CHg1 = = = 177.781 t·sec/m
αpf 2.52

Where, n = NUMBER OF PILE = 6 EA


αpf = 2.52 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 177.781
DH = = = 0.08
2· KHg1·m 2x 59,403 x 20.7

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 2.1 + 18.6 = 20.7 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.08 + 0.05 = 0.13

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.3 Horizontal direction (Transverse PA Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 73.3333

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 6 x 74.63
CHg1 = = = 189.579 t·sec/m
αpf 2.36

Where, n = NUMBER OF PILE = 6 EA


αpf = 2.36 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 189.579
DH = = = 0.083
2· KHg1·m 2x 63,345 x 20.7

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT]/9.81 + FDN WEIGHT/9.81
2
= 2.1 + 18.6 = 20.7 t·sec /m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.083 + 0.05 = 0.133

8.0 NATURAL AND RESONANCE FREQUANCE CALCULATION AND REVIEW


8.1 Vertical direction
1) UNDAMPED NATURAL FREQUENCY
60 Kz 60 314,865
fnZ = · = x = 1177.35 rpm
2·π m 2xπ 20.7

Where, m = LUMPED MASS = 2.1 + 18.6 = 20.7 t·sec2/m


KZ = SPRING CONSTANT = 314,864.7 ton/m

2) RESONANCE FREQUENCY

fmZ = fnZ x 1/ ((1-2Dt2) 0.5


2
= 1177.35 x 1/((1-2* 0.097 )0.5 = 1,189 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 950.9 1426.3 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.2 Horizontal direction (Parrel to PA fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 59,403
fnH = · = x = 511.39 rpm
2·π m 2xπ 20.7

Where, m = LUMPED MASS = 2.1 + 18.6 = 20.7 t·sec2/m


KH = SPRING CONSTANT = 59,403 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 511.39 x 1/((1-2* 0.13 )0.5 = 520 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 416.2 624.3 OUT OF RANGE

8.3 Horizontal direction (Transverse to PA fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 63,345
fnH = · = x = 528.08 rpm
2·π m 2xπ 20.7

Where, m = LUMPED MASS = 2.1 + 18.6 = 20.7 t·sec2/m


KH = SPRING CONSTANT = 63,345 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 528.08 x 1/((1-2* 0.133 )0.5 = 538 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 430.1 645.2 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9.0 The determinatin of dynamic Gds and νds for clay layer
From Soil Investigation Report (clause 3.9, down hole test results),
the dynamic Shear modulus and poisson ratio for clay layer would be summarided as below table.
Density Vp Vs Ed Gds νds
Sort REMARK
t/m3 m/s m/s kg/cm2 kg/cm2 -
1 1.96 417 179 1500 1000 0.39
2 1.96 500 221 1607 1021 0.38
3 1.96 500 253 1714 1043 0.33
4 1.96 500 257 1821 1064 0.32
5 1.96 556 289 1929 1086 0.31
6 1.96 625 291 2036 1107 0.31
7 1.96 625 330 2143 1129 0.31
8 1.96 625 331 2250 1150 0.31 BH-03
9 1.96 625 332 2357 1171 0.30
10 1.96 455 237 2464 1193 0.31
11 1.96 455 237 2571 1214 0.31
12 1.96 455 237 2679 1236 0.31
13 1.96 714 384 2786 1257 0.30
14 1.96 714 374 2893 1279 0.30
15 1.96 714 384 3000 1300 0.30
1 1.95 454.6 195.68 1500 1000 0.39
2 1.95 454.6 220.53 1636 1027 0.35
3 1.95 500 252.85 1773 1055 0.33
4 1.95 500 256.82 1909 1082 0.32
5 1.95 454.6 234.22 2045 1109 0.32
6 1.95 454.6 235.31 2182 1136 0.32
BH-13
7 1.95 454.6 236 2318 1164 0.31
8 1.95 454.6 236.46 2455 1191 0.31
9 1.95 454.6 236.78 2591 1218 0.31
10 1.95 500 236.97 2727 1245 0.31
11 1.95 500 262.17 2864 1273 0.31
12 1.95 500 262.32 3000 1300 0.31

For safety side review, dynamic shear modulus at lower 5% and poisson ratio at higher 5% would be adopted.
And, the density for clay layer would be 1.96 ton/m3 for resonance frequency check.

Dynamic shear modulus (kg/cm2, Gds) for layer 1


Average(=m) 1150
Variance 9036
The confidence interval90% (=δ) 30
Higher5% limitation(=m+δ) 1180
Lower5% limitation(=m+δ) 1120

Dynamic Poisson ratios (νds) for layer 1


Average(=m) 0.321
Variance 0.001
The confidence interval90% (=δ) 0.008
Higher5% limitation(=m+δ) 0.330
Lower5% limitation(=m+δ) 0.313

DOCUMENT No. : IKCP0-UHA-C-06-0002


2-2. P.A FAN (UNIT#1B,2B)
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.0 CONCRETE AND SOIL PARAMETERS

γs 1.96 3
1) UNIT WEIGHT OF SUBGROUND = ton/m (From clause 8.0)
(CLAY LAYER)
2) DYNAMIC SHEAR MODULUS OF SUGBROUND Gds = 1119.9 kg/cm2 (From clause 8.0)
(CLAY LAYER)
3) DYNAMIC POISSON'S RATIO OF SUBGROUND νds = 0.330 (From clause 8.0)
(CLAY LAYER)
4) SOIL INTERNAL DAMPING RATIO = 0.05
5) UNIT WEIGHT OF FOUNDATION CONCRETE = 2.50 ton/m3

2.0 MACHINE PARAMETERS (BY VENDOR INFORMATION)

1) MACHINE WEIGHT (UNIT : KG)

STATIC WEIGHT DYNAMIC FORCES

LOCATION VERTICAL HORIZONTAL LOCATION VERTICAL HORIZONTAL

Y-DIR. X-DIR. Z-DIR. Y-DIR. X-DIR. Z-DIR.

A 7200 0 0 A 7200 290 290


Motar Motar
Bed Bed
SUB Ⅰ 7200 0 0 SUB Ⅰ 7200 290 290

B 1950 0 0 B 1050 72 72
B'RG B'RG
Housing C 1950 0 0 Housing C 1050 42 42
Bed Bed
SUB Ⅱ 3900 0 0 SUB Ⅱ 2100 114 114

D 3450 0 0 D 0 74 74

E 2850 0 0 E 0 74 74
Casing Casing
F 2550 0 0 F 0 74 74
Bracket Bracket
G 950 0 0 G 0 74 74

SUB Ⅲ 9800 0 0 SUB Ⅲ 0 296 296

DAMPER H 440 0 0 DAMPER H 0 0 0


ACTUATO ACTUATO
R BED SUB Ⅳ 440 0 0 R BED SUB Ⅳ 0 0 0

B1 6700.0 270.0 -10.0 B1 0 0 0

B2 6790.0 -250.0 10.0 B2 0 0 0

B3 15220.0 250.0 40.0 B3 0 0 0


SILENCER SILENCER
B4 14060.0 -350.0 30.0 B4 0 0 0
SUPPORT SUPPORT
B5 9150.0 200.0 -60.0 B5 0 0 0

B6 7300.0 -120.0 0.0 B6 0 0 0

SUB Ⅴ 59220 0.0 10 SUB Ⅴ 0 0 0

TOTAL 80560 0 10 TOTAL 9300 700 700

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) OPERATING FREQUENCY : fo = 1480 RPM

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.0 FOUNDATION SIZE CHECK

1) FOUNDATION WEIGHT
(UNIT : ton, m)

FOUNDATION SIZE TOTAL

COMPONENT WIDTH LENGTH AREA HEIGHT Q'ty WEIGHT

Bf Lf Af Hf Wf

F1 1.150 0.800 0.92 1.910 1 4.39

F2 3.600 1.100 3.96 1.910 1 18.91

F3 3.600 0.800 2.88 1.910 1 13.75

F4 3.600 1.950 7.02 1.650 1 28.96

F5 2.800 2.250 6.30 1.650 1 25.99

F6 1.200 1.200 1.44 0.250 1 0.90

F7-1~F7-6 0.600 0.600 0.36 0.050 6 0.27

F8 6.500 12.130 78.85 0.800 1 157.69

TOTAL 101.73 250.86

2) MACHINE WEIGHT Wm = 80.6 ton

3) MASS RATIO = Wc / Wm = 250.86 ÷ 80.56

= 3.11 > 3 ∴ O.K

4) MASS RATIO OF ROTOR


MASS RATIO = Wc / ROTOR WEIGHT
= 250.86 ÷ 7.2

= 34.84 > 25 ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4.0 CALCULATION OF C.G. OF MACHINE & FOUNDATION

4.1 CENTER OF GRAVITY IN STATIC CONDITION


1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD
Ver.(Z) Hori.(X) Hori.(Y) X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My
A 7.200 0.000 0.000 6.307 45.410 3.200 23.040 2.450 0.000

B 1.950 0.000 0.000 4.620 9.009 3.200 6.240 2.710 0.000

C 1.950 0.000 0.000 2.510 4.895 3.200 6.240 2.710 0.000

D 3.450 0.000 0.000 4.580 15.801 2.450 8.453 2.710 0.000

E 2.850 0.000 0.000 2.550 7.268 2.450 6.983 2.710 0.000

F 2.550 0.000 0.000 4.580 11.679 3.950 10.073 2.710 0.000

G 0.950 0.000 0.000 2.550 2.423 3.950 3.753 2.710 0.000

H 0.440 0.000 0.000 2.222 0.978 5.900 2.596 1.050 0.000

B1 6.700 0.270 -0.010 11.830 79.491 5.500 36.842 0.850 1.367

B2 6.790 -0.250 0.010 11.830 80.113 0.300 2.046 0.850 0.043

B3 15.220 0.250 0.040 4.630 70.681 5.500 83.744 0.850 1.560

B4 14.060 -0.350 0.030 4.630 64.800 0.300 4.244 0.850 0.034

B5 9.150 0.200 -0.060 0.300 2.915 5.500 50.274 0.850 1.082

B6 6.790 -0.250 0.010 0.300 1.825 0.300 2.046 0.850 -0.072

TOTAL 80.05 -0.13 0.02 397.3 246.57 4.01

2) CENTER OF GRAVITY FOR FOUNDATION


WEIGHT MASS X-DIR Z-DIR Y-DIR
COMPONENT
2
(TON) (t·sec /m) X(m) Mz Z(m) Mx Y(m) My
F1 4.39 0.448 1.300 5.71 4.125 18.11 1.755 7.70

F2 18.91 1.928 2.250 42.55 2.900 54.84 1.755 33.19

F3 13.75 1.402 4.730 65.04 2.900 39.88 1.755 24.13

F4 28.96 2.952 6.105 176.80 2.900 83.98 1.625 47.06

F5 25.99 2.649 8.205 213.25 3.300 85.77 1.625 42.23

F6 0.90 0.092 2.222 2.00 5.900 5.31 0.925 0.83

F7-1 0.27 0.028 11.830 3.19 5.500 1.49 0.825 0.22

F7-2 0.27 0.028 11.830 3.19 0.300 0.08 0.825 0.22

F7-3 0.27 0.028 4.630 1.25 5.500 1.49 0.825 0.22

F7-4 0.27 0.028 4.630 1.25 0.300 0.08 0.825 0.22

F7-5 0.27 0.028 0.300 0.08 5.500 1.49 0.825 0.22

F7-6 0.27 0.028 0.300 0.08 0.300 0.08 0.825 0.22

F9 157.69 16.074 6.065 956.39 3.250 512.49 0.400 63.08

TOTAL 252.21 25.71 1470.78 805.07 219.56

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2
3) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA

Mcx = Af x Czi

Mcz = Af x Cxi

FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F9 6.500 12.130 78.845 3.250 6.065 256.25 478.19

TOTAL 78.85 256.25 478.19

Xf = ∑Mcz / ∑Af = 478.19 / 78.85 = 6.07 m

Zf = ∑Mcx / ∑Af = 256.25 / 78.85 = 3.25 m

4) CENTER OF GRAVITY OF MACHINE & FOUNDATION

Xcg = Mz(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 1470.78 + 397.29 )/( 252.21 + 80.05 ) = 5.622 m

Zcg = Mx(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 805.07 + 246.57 )/( 252.21 + 80.05 ) = 3.165 m

Ycg = My(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 219.56 + 4.01 )/( 252.21 + 80.05 ) = 0.673 m

5) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 6.07 - 5.62 | / 12.13 x 100
= 3.69 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 3.25 - 3.17 | / 6.50 x 100
= 1.31 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.0 CENTER OF GRAVITY IN OPERATING CONDITION

1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 7.200 0.000 0.000 6.307 45.410 3.200 23.040 2.450 0.000

B 1.950 0.000 0.000 4.620 9.009 3.200 6.240 2.710 0.000

C 1.950 0.000 0.000 2.510 4.895 3.200 6.240 2.710 0.000

D 3.450 0.000 0.000 4.580 15.801 2.450 8.453 2.710 0.000

E 2.850 0.000 0.000 2.550 7.268 2.450 6.983 2.710 0.000

F 2.550 0.000 0.000 4.580 11.679 3.950 10.073 2.710 0.000

G 0.950 0.000 0.000 2.550 2.423 3.950 3.753 2.710 0.000

H 0.440 0.000 0.000 2.222 0.978 5.900 2.596 1.050 0.000

B1 6.700 0.270 -0.010 11.830 79.491 5.500 36.842 0.850 1.367

B2 6.790 -0.250 0.010 11.830 80.113 0.300 2.046 0.850 0.043

B3 15.220 0.250 0.040 4.630 70.681 5.500 83.744 0.850 1.560

B4 14.060 -0.350 0.030 4.630 64.800 0.300 4.244 0.850 0.034

B5 9.150 0.200 -0.060 0.300 2.915 5.500 50.274 0.850 1.082

B6 7.300 -0.120 0.000 0.300 2.088 0.300 2.190 0.850 -0.036

TOTAL 80.56 0.00 0.01 397.5 246.71 4.05

2) CENTER OF GRAVITY FOR MACHINE DYNAMIC LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 7.200 0.290 0.290 6.307 46.121 3.200 23.751 2.450 2.757

B 1.050 0.072 0.072 4.620 5.046 3.200 3.555 2.710 0.563

C 1.050 0.042 0.042 2.510 2.749 3.200 3.474 2.710 0.240

D 0.000 0.074 0.074 4.580 0.201 2.450 0.201 2.710 0.520

E 0.000 0.074 0.074 2.550 0.201 2.450 0.201 2.710 0.370

F 0.000 0.074 0.074 4.580 0.201 3.950 0.201 2.710 0.631

G 0.000 0.074 0.074 2.550 0.201 3.950 0.201 2.710 0.481

TOTAL 9.30 0.70 0.70 54.72 31.58 5.56

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) CENTER OF GRAVITY FOR FOUNDATION

WEIGHT MASS X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (t·sec2/m) X(m) Mz Z(m) Mx Y(m) My

F1 4.39 0.448 1.300 5.71 4.125 18.11 1.755 7.70

F2 18.91 1.928 2.250 42.55 2.900 54.84 1.755 33.19

F3 13.75 1.402 4.730 65.04 2.900 39.88 1.755 24.13

F4 28.96 2.952 6.105 176.80 2.900 83.98 1.625 47.06

F5 25.99 2.649 8.205 213.25 3.300 85.77 1.625 42.23

F6 0.90 0.092 2.222 2.00 5.900 5.31 0.925 0.83

F7-1 0.27 0.028 11.830 3.19 5.500 1.49 0.825 0.22

F7-2 0.27 0.028 11.830 3.19 0.300 0.08 0.825 0.22

F7-3 0.27 0.028 4.630 1.25 5.500 1.49 0.825 0.22

F7-4 0.27 0.028 4.630 1.25 0.300 0.08 0.825 0.22

F7-5 0.27 0.028 0.300 0.08 5.500 1.49 0.825 0.22

F7-6 0.27 0.028 0.300 0.08 0.300 0.08 0.825 0.22

F9 157.69 16.074 6.065 956.39 3.250 512.49 0.400 63.08

TOTAL 252.21 25.709 1470.78 805.07 219.56

4) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA


Mcx = Af x Czi
Mcz = Af x Cxi
FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F9 6.500 12.130 78.845 3.250 6.065 256.25 478.19

TOTAL 78.85 256.25 478.19

Xf = ∑Mcz / ∑Af = 478.19 / 78.85 = 6.07 m


Zf = ∑Mcx / ∑Af = 256.25 / 78.85 = 3.25 m

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) CENTER OF GRAVITY OF MACHINE & FDN. IN DYNAMIC CONDITION

Xcg = Mz(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 1470.78 + 397.55 + 54.72 )
/ ( 252.21 + 80.05 + 9.30 ) = 5.630 m

Zcg = Mx(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 805.07 + 246.71 + 31.58 )
/ ( 252.21 + 80.05 + 9.30 ) = 3.172 m

Ycg = My(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 219.56 + 4.05 + 5.56 )
/ ( 252.21 + 80.05 + 9.30 ) = 0.671 m

6) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 6.07 - 5.63 | / 12.13 x 100
= 3.63 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 3.25 - 3.17 | / 6.50 x 100
= 1.2 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.0 SPRING CONSTANT CALCULATION


6.1 Vertical direction
1) SINGLE PILE SPRING CONSTANT
Ep·A
KZ1 = · fz1
r0p
3354866 x 0.157
= x 0.092 = 161,526 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


= ( Gds / ρs )0.5 = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
= 1,120 kg/cm2 = 11,199 ton/m2
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 32900000 kpa = 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
A = CROSS-SECTION AREA OF PILE = 0.157 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.3 m
∴ L/r0p = 22.3 / 0.3 = 74.3333
fz1 = VALUE OF FUNCTION = 0.092
Ep/Gsp
L/r0p
250 299.568 500
fw1 0.0980 0.092 0.0700 74.3333

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT


∑n·KZ1 9 x 161,526
KZg1 = = = 416,781 ton/m (FOR PILE)
αa 3.488

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.3 / ( 2 x 0.3 ) = 37.167
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αa = INTERACTION FACTOR = 3.488
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
S/2r0p or αa
S(m) REMARKS
2r0p/S νs = 0.00 νs = 0.32 νs = 0.50
P1 0.000 - - 1.000 - REFERENCE PILE
P2 5.315 0.113 0.397 0.346 0.318
P3 10.630 0.056 0.268 0.229 0.207
P4 2.500 4.167 0.542 0.501 0.479
P5 5.874 0.102 0.379 0.328 0.300
P6 10.920 0.055 0.263 0.224 0.203
P7 5.000 0.120 0.408 0.357 0.329
P8 7.297 0.082 0.338 0.290 0.264
P9 11.747 0.051 0.250 0.213 0.193

∑ 3.49

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.2 Horizontal direction (Parrel to PA Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
= 0.26 t·sec2/m4
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m4
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.3 m
∴ L/r0p = 22.3 / 0.3 = 74.3333
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 74

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 9 x 24,937
KHg1 = = = 86,472 ton/m (FOR PILE)
αpf 2.60

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.3 / ( 2 x 0.3 ) = 37.167
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.60
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
4
= 3354866 x 0.00329 /( 29,599 x 22.3 )
= 1.51E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - 90.00 1.00 1.00 1.00
P2 5.315 0.000 5.315 8.858 0.113 0.00 0.28 0.16 0.28
P3 10.630 0.000 10.630 17.717 0.056 0.00 0.16 0.09 0.16
P4 0.000 2.500 2.500 4.167 0.240 90.00 0.47 0.31 0.31
P5 5.315 2.500 5.874 9.789 0.102 25.19 0.26 0.15 0.23
P6 10.630 2.500 10.920 18.200 0.055 13.23 0.16 0.08 0.15
P7 0.000 5.000 5.000 8.333 0.120 90.00 0.28 0.17 0.17
P8 5.315 5.000 7.297 12.162 0.082 43.25 0.23 0.12 0.18
P9 10.630 5.000 11.747 19.579 0.051 25.19 0.15 0.08 0.13
Sum of interaction factor for horizontal direction 2.60

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.3 Horizontal direction (Transverse to PA Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5 0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
= 2
I = Moment inertia 0.00329 m
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.3 m
∴ L/r0p = 22.3 / 0.3 = 74.3333
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 74

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 9 x 24,937
KHg1 = = = 88,226 ton/m (FOR PILE)
αpf 2.54

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.3 / ( 2 x 0.3 ) = 37.167
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.54
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
4
= 3354866 x 0.00329 /( 29,599 x 22.3 )
= 1.51E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - - 1 1 1 Reference pile
P2 5.315 0.000 5.315 8.858 0.113 90.00 0.28 0.16 0.16
P3 10.630 0.000 10.630 17.717 0.056 90.00 0.16 0.09 0.09
P4 0.000 2.500 2.500 4.167 0.240 - 0.47 0.31 0.47
P5 5.315 2.500 5.874 9.789 0.102 64.81 0.26 0.15 0.18
P6 10.630 2.500 10.920 18.200 0.055 76.77 0.16 0.08 0.09
P7 0.000 5.000 5.000 8.333 0.120 - 0.28 0.17 0.28
P8 5.315 5.000 7.297 12.162 0.082 46.75 0.23 0.12 0.17
P9 10.630 5.000 11.747 19.579 0.051 64.81 0.15 0.08 0.10
Sum of interaction factor for horizontal direction 2.54

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 DAMPING RATIO


7.1 Vertical direction
1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ap 3354866 x 0.157


CZ1 = · fw2 = x 0.055
Vs 237

= 122.4 t·sec/m (FOR PILE)

From clause 6, ∴ Ep/Gds= 3354866 / 11,199 = 299.57


∴ L/r0p = 22.3 / 0.3 = 74.3333

fz2 : VALUE OF FUNCTION = 0.055


Ep/Gds
L/r0p
250 299.568 500
fw2 0.059 0.055 0.041 74

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CZ1 9 x 122.423
CZg1 = = = 315.885 t·sec/m
αa 3.488

Where, n = NUMBER OF PILE = 9 EA


αa = 3.488 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CZg1 315.885
DZ = = = 0.042
2· KZg1·m 2x 416,781 x 33.8

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 8.2 + 25.6 = 33.8 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

Dtz = Dz + Di = 0.042 + 0.05 = 0.092

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.2 Horizontal direction (Parrel to PA Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 74

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 9 x 74.63
CHg1 = = = 258.794 t·sec/m
αpf 2.60

Where, n = NUMBER OF PILE = 9 EA


αpf = 2.60 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 258.794
DH = = = 0.076
2· KHg1·m 2x 86,472 x 33.8

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 8.2 + 25.6 = 33.8 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.076 + 0.05 = 0.126

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.3 Horizontal direction (Transverse PA Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 74.3333

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 9 x 74.63
CHg1 = = = 264.042 t·sec/m
αpf 2.54

Where, n = NUMBER OF PILE = 9 EA


αpf = 2.54 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 264.042
DH = = = 0.076
2· KHg1·m 2x 88,226 x 33.8

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT]/9.81 + FDN WEIGHT/9.81
= 8.2 + 25.6 = 33.8 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.076 + 0.05 = 0.126

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.0 NATURAL AND RESONANCE FREQUANCE CALCULATION AND REVIEW


8.1 Vertical direction
1) UNDAMPED NATURAL FREQUENCY
60 Kz 60 416,781
fnZ = · = x = 1060.65 rpm
2·π m 2xπ 33.8

2
Where, m = LUMPED MASS = 8.2 + 25.6 = 33.8 t·sec /m
KZ = SPRING CONSTANT = 416,780.5 ton/m

2) RESONANCE FREQUENCY

fmZ = fnZ x 1/ ((1-2Dt2) 0.5


2
= 1060.65 x 1/((1-2* 0.092 )0.5 = 1,070 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 855.8 1283.7 OUT OF RANGE

8.2 Horizontal direction (Parrel to PA fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 86,472
fnH = · = x = 483.12 rpm
2·π m 2xπ 33.8

Where, m = LUMPED MASS = 8.2 + 25.6 = 33.8 t·sec2/m


KH = SPRING CONSTANT = 86,472 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 483.12 x 1/((1-2* 0.126 )0.5 = 491 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 392.8 589.2 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.3 Horizontal direction (Transverse to PA fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 88,226
fnH = · = x = 487.99 rpm
2·π m 2xπ 33.8

Where, m = LUMPED MASS = 8.2 + 25.6 = 33.8 t·sec2/m


KH = SPRING CONSTANT = 88,226 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 487.99 x 1/((1-2* 0.126 )0.5 = 496 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 396.7 595.1 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9.0 The determinatin of dynamic Gds and νds for clay layer
From Soil Investigation Report (clause 3.9, down hole test results),
the dynamic Shear modulus and poisson ratio for clay layer would be summarided as below table.
Density Vp Vs Ed Gds νds
Sort REMARK
t/m3 m/s m/s kg/cm2 kg/cm2 -
1 1.96 417 179 1500 1000 0.39
2 1.96 500 221 1607 1021 0.38
3 1.96 500 253 1714 1043 0.33
4 1.96 500 257 1821 1064 0.32
5 1.96 556 289 1929 1086 0.31
6 1.96 625 291 2036 1107 0.31
7 1.96 625 330 2143 1129 0.31
8 1.96 625 331 2250 1150 0.31 BH-03
9 1.96 625 332 2357 1171 0.30
10 1.96 455 237 2464 1193 0.31
11 1.96 455 237 2571 1214 0.31
12 1.96 455 237 2679 1236 0.31
13 1.96 714 384 2786 1257 0.30
14 1.96 714 374 2893 1279 0.30
15 1.96 714 384 3000 1300 0.30
1 1.95 454.6 195.68 1500 1000 0.39
2 1.95 454.6 220.53 1636 1027 0.35
3 1.95 500 252.85 1773 1055 0.33
4 1.95 500 256.82 1909 1082 0.32
5 1.95 454.6 234.22 2045 1109 0.32
6 1.95 454.6 235.31 2182 1136 0.32
BH-13
7 1.95 454.6 236 2318 1164 0.31
8 1.95 454.6 236.46 2455 1191 0.31
9 1.95 454.6 236.78 2591 1218 0.31
10 1.95 500 236.97 2727 1245 0.31
11 1.95 500 262.17 2864 1273 0.31
12 1.95 500 262.32 3000 1300 0.31

For safety side review, dynamic shear modulus at lower 5% and poisson ratio at higher 5% would be adopted.
And, the density for clay layer would be 1.96 ton/m3 for resonance frequency check.

Dynamic shear modulus (kg/cm2, Gds) for layer 1


Average(=m) 1150
Variance 9036
The confidence interval90% (=δ) 30
Higher5% limitation(=m+δ) 1180
Lower5% limitation(=m+δ) 1120

Dynamic Poisson ratios (νds) for layer 1


Average(=m) 0.321
Variance 0.001
The confidence interval90% (=δ) 0.008
Higher5% limitation(=m+δ) 0.330
Lower5% limitation(=m+δ) 0.313

DOCUMENT No. : IKCP0-UHA-C-06-0002


[ ATTACHMENTS ]

#3. Foundation Check for Vibration Machinery


3-1. F.D FAN (UNIT#1A,2A)
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.0 CONCRETE AND SOIL PARAMETERS

γs 1.96 3
1) UNIT WEIGHT OF SUBGROUND = ton/m (From clause 8.0)
(CLAY LAYER)

2) DYNAMIC SHEAR MODULUS OF SUGBROUND Gds = 1119.9 kg/cm2 (From clause 8.0)
(CLAY LAYER)

3) DYNAMIC POISSON'S RATIO OF SUBGROUND νds = 0.330 (From clause 8.0)


(CLAY LAYER)

4) SOIL INTERNAL DAMPING RATIO = 0.05

3
5) UNIT WEIGHT OF FOUNDATION CONCRETE = 2.50 ton/m

2.0 MACHINE PARAMETERS (BY VENDOR INFORMATION)

1) MACHINE WEIGHT (UNIT : KG)

STATIC WEIGHT DYNAMIC FORCES

LOCATION VERTICAL HORIZONTAL LOCATION VERTICAL HORIZONTAL

Y-DIR. X-DIR. Z-DIR. Y-DIR. X-DIR. Z-DIR.

A 3000 0 0 A 3000 0 0
Motar Motar
Bed Bed
SUB Ⅰ 3000 0 0 SUB Ⅰ 3000 0 0

B 1300 0 0 B 850 0 0
B'RG B'RG
Housing C 1950 0 0 Housing C 1050 0 0
Bed Bed
SUB Ⅱ 3250 0 0 SUB Ⅱ 1900 0 0

D 1200 0 0 D 0 0 0

E 1000 0 0 E 0 0 0

Casing Casing
F 1050 0 0 F 0 0 0
Bracket Bracket

G 950 0 0 G 0 0 0

SUB Ⅲ 4200 0 0 SUB Ⅲ 0 0 0

DAMPER H 300 0 0 DAMPER H 0 0 0


ACTUATO ACTUATO
R BED SUB Ⅳ 300 0 0 R BED SUB Ⅳ 0 0 0

TOTAL 10750 0 0 TOTAL 4900 0 0

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) OPERATING FREQUENCY : fo = 1480 RPM

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.0 FOUNDATION SIZE CHECK

1) FOUNDATION WEIGHT
(UNIT : ton, m)

FOUNDATION SIZE TOTAL

COMPONENT WIDTH LENGTH AREA HEIGHT WEIGHT

Bf Lf Af Hf Wf

F1 1.350 0.800 1.08 1.350 3.65

F2 3.400 1.400 4.76 1.350 16.07

F3 3.400 0.600 2.04 1.455 7.42

F4 3.400 1.750 5.95 1.455 21.64

F5 2.600 1.750 4.55 1.455 16.55

F6 0.950 0.850 0.81 0.250 0.50

F7 1.350 0.850 1.15 1.450 4.16

F8 3.400 8.680 29.51 1.450 106.98

TOTAL 49.85 176.97

2) MACHINE WEIGHT Wm = 10.8 ton

3) MASS RATIO = Wc / Wm = 176.97 ÷ 10.75

= 16.46 > 3 ∴ O.K

4) MASS RATIO OF ROTOR


MASS RATIO = Wc / ROTOR WEIGHT
= 176.97 ÷ 3

= 58.99 > 25 ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4.0 CALCULATION OF C.G. OF MACHINE & FOUNDATION

4.1 CENTER OF GRAVITY IN STATIC CONDITION


1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD
Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My
A 3.000 0.000 0.000 2.636 7.908 0.800 2.400 2.850 0.000

B 1.300 0.000 0.000 3.830 4.979 1.600 2.080 2.955 0.000

C 1.950 0.000 0.000 6.750 13.163 1.600 3.120 2.955 0.000

D 1.200 0.000 0.000 3.935 4.722 0.800 0.960 2.955 0.000

E 1.000 0.000 0.000 6.645 6.645 0.800 0.800 2.955 0.000

F 1.050 0.000 0.000 3.935 4.132 2.400 2.520 2.955 0.000

G 0.950 0.000 0.000 6.645 6.313 2.400 2.280 2.955 0.000

H 0.300 0.000 0.000 7.038 2.111 4.275 1.283 1.750 0.000

TOTAL 10.75 0.00 0.00 50.0 15.44 0.00

2) CENTER OF GRAVITY FOR FOUNDATION


WEIGHT MASS X-DIR Z-DIR Y-DIR
COMPONENT
2
(TON) (t·sec /m) X(m) Mz Z(m) Mx Y(m) My
F1 3.65 0.372 8.280 30.22 2.725 9.95 2.125 7.76

F2 16.07 1.638 7.180 115.38 1.700 27.32 2.125 34.15

F3 7.42 0.756 3.800 28.20 1.700 12.61 2.178 16.16

F4 21.64 2.206 2.625 56.81 1.700 36.79 2.178 47.12

F5 16.55 1.687 0.750 12.41 1.300 21.52 2.178 36.04

F6 0.50 0.051 7.038 3.52 4.275 2.14 1.575 0.79

F7 4.16 0.424 7.038 29.28 4.075 16.95 0.725 3.02

F8 106.98 10.905 4.340 464.29 1.700 181.87 0.725 77.56

TOTAL 176.97 18.04 740.11 309.14 222.58

3) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA

Mcx = Af x Czi

Mcz = Af x Cxi

FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F7, F8 3.400 8.680 30.660 1.789 4.441 54.85 136.16

TOTAL 30.66 54.85 136.16

Xf = ∑Mcz / ∑Af = 136.16 / 30.66 = 4.44 m

Zf = ∑Mcx / ∑Af = 54.85 / 30.66 = 1.79 m

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) CENTER OF GRAVITY OF MACHINE & FOUNDATION

Xcg = Mz(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 740.11 + 49.97 )/( 176.97 + 10.75 ) = 4.209 m

Zcg = Mx(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 309.14 + 15.44 )/( 176.97 + 10.75 ) = 1.729 m

Ycg = My(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 222.58 + 0.00 )/( 176.97 + 10.75 ) = 1.186 m

5) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 4.44 - 4.21 | / 8.68 x 100
= 2.66 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 1.79 - 1.73 | / 3.40 x 100
= 1.79 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.0 CENTER OF GRAVITY IN OPERATING CONDITION

1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 3.000 0.000 0.000 2.636 7.908 0.800 2.400 2.850 0.000

B 1.300 0.000 0.000 3.830 4.979 1.600 2.080 2.850 0.000

C 1.950 0.000 0.000 6.750 13.163 1.600 3.120 2.850 0.000

D 1.200 0.000 0.000 3.935 4.722 0.800 0.960 2.850 0.000

E 1.000 0.000 0.000 6.645 6.645 0.800 0.800 2.850 0.000

F 1.050 0.000 0.000 3.935 4.132 2.400 2.520 2.850 0.000

G 0.950 0.000 0.000 6.645 6.313 2.400 2.280 2.850 0.000

TOTAL 10.45 0.00 0.00 47.9 14.16 0.00

2) CENTER OF GRAVITY FOR MACHINE DYNAMIC LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 3.000 0.000 0.000 2.636 7.908 0.800 2.400 2.850 0.000

B 0.850 0.000 0.000 3.830 3.256 1.600 1.360 2.850 0.000

C 1.050 0.000 0.000 6.750 7.088 1.600 1.680 2.850 0.000

TOTAL 4.90 0.00 0.00 18.25 5.44 0.00

3) CENTER OF GRAVITY FOR FOUNDATION

WEIGHT MASS X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (t·sec2/m) X(m) Mz Z(m) Mx Y(m) My

F1 3.65 0.372 8.280 30.22 2.725 9.95 2.125 7.76

F2 16.07 1.638 7.180 115.38 1.700 27.32 2.125 34.15

F3 7.42 0.756 3.800 28.20 1.700 12.61 2.178 16.16

F4 21.64 2.206 2.625 56.81 1.700 36.79 2.178 47.12

F5 16.55 1.687 0.750 12.41 1.300 21.52 2.178 36.04

F6 0.50 0.051 7.038 3.52 4.275 2.14 1.575 0.79

F7 4.16 0.424 7.038 29.28 4.075 16.95 0.725 3.02

F8 106.98 10.905 4.340 464.29 1.700 181.87 0.725 77.56

TOTAL 176.97 18.040 740.11 309.14 222.58

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA


Mcx = Af x Czi
Mcz = Af x Cxi
FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F7, F8 3.400 8.680 30.660 1.789 4.441 54.85 136.16

TOTAL 30.66 54.85 136.16

Xf = ∑Mcz / ∑Af = 136.16 / 30.66 = 4.44 m


Zf = ∑Mcx / ∑Af = 54.85 / 30.66 = 1.79 m

5) CENTER OF GRAVITY OF MACHINE & FDN. IN DYNAMIC CONDITION

Xcg = Mz(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 740.11 + 47.86 + 18.25 )
/ ( 176.97 + 10.75 + 4.90 ) = 4.186 m

Zcg = Mx(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 309.14 + 14.16 + 5.44 )
/ ( 176.97 + 10.75 + 4.90 ) = 1.707 m

Ycg = My(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 222.58 + 0.00 + 0.00 )
/ ( 176.97 + 10.75 + 4.90 ) = 1.156 m

6) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 4.44 - 4.19 | / 8.68 x 100
= 2.93 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 1.79 - 1.71 | / 3.40 x 100
= 2.44 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.0 SPRING CONSTANT CALCULATION


6.1 Vertical direction
1) SINGLE PILE SPRING CONSTANT
Ep·A
KZ1 = · fz1
r0p
3354866 x 0.157
= x 0.092 = 161,526 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


= ( Gds / ρs )0.5 = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 32900000 kpa = 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
A = CROSS-SECTION AREA OF PILE = 0.157 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 21.65 m
∴ L/r0p = 21.65 / 0.3 = 72.1667
fz1 = VALUE OF FUNCTION = 0.092
Ep/Gsp
L/r0p
250 299.568 500
fw1 0.0980 0.092 0.0700 72.1667

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT


∑n·KZ1 6 x 161,526
KZg1 = = = 308,549 ton/m (FOR PILE)
αa 3.141

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 21.65 / ( 2 x 0.3 ) = 36.083
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αa = INTERACTION FACTOR = 3.141
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
S/2r0p or αa
S(m) REMARKS
2r0p/S νs = 0.00 νs = 0.32 νs = 0.50
P1 0.000 - - 1.000 - REFERENCE PILE
P2 2.790 4.650 0.517 0.476 0.453
P3 5.580 0.108 0.388 0.338 0.309
P4 1.900 3.167 0.609 0.565 0.540
P5 3.376 0.178 0.478 0.434 0.409
P6 5.895 0.102 0.378 0.328 0.300

∑ 3.141

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.2 Horizontal direction (Parrel to FD Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m4
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 21.65 m
∴ L/r0p = 21.65 / 0.3 = 72.1667
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 72

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 6 x 24,937
KHg1 = = = 55,010 ton/m (FOR PILE)
αpf 2.72

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 21.65 / ( 2 x 0.3 ) = 36.083
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.72
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
= 3354866 x 0.00329 /( 29,599 x 21.65 4)
= 1.7E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - 90.00 1.00 1.00 1.00
P2 2.790 0.000 2.790 4.650 0.215 0.00 0.41 0.27 0.41
P3 5.580 0.000 5.580 9.300 0.108 0.00 0.27 0.15 0.27
P4 0.000 1.900 1.900 3.167 0.316 90.00 0.85 0.51 0.51
P5 2.790 1.900 3.376 5.626 0.178 34.26 0.35 0.22 0.30
P6 5.580 1.900 5.895 9.824 0.102 18.80 0.26 0.15 0.24
Sum of interaction factor for horizontal direction 2.72

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.3 Horizontal direction (Transverse to FD Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
= 0.26 t·sec2/m4
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 21.65 m
∴ L/r0p = 21.65 / 0.3 = 72.1667
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 72

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 6 x 24,937
KHg1 = = = 55,030 ton/m (FOR PILE)
αpf 2.72

Where, n = NUMBER OF PILE = 6 EA


∴ L/2r0p = 21.65 / ( 2 x 0.3 ) = 36.083
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.72
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
= 3354866 x 0.00329 /( 29,599 x 21.65 4)
= 1.7E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - - 1 1 1 Reference pile
P2 2.790 0.000 2.790 4.650 0.215 90.00 0.41 0.27 0.27
P3 5.580 0.000 5.580 9.300 0.108 90.00 0.27 0.15 0.15
P4 0.000 1.900 1.900 3.167 0.316 - 0.85 0.51 0.85
P5 2.790 1.900 3.376 5.626 0.178 55.74 0.35 0.22 0.27
P6 5.580 1.900 5.895 9.824 0.102 71.20 0.26 0.15 0.17
Sum of interaction factor for horizontal direction 2.72

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 DAMPING RATIO


7.1 Vertical direction
1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ap 3354866 x 0.157


CZ1 = · fw2 = x 0.055
Vs 237

= 122.4 t·sec/m (FOR PILE)

From clause 6, ∴ Ep/Gds= 3354866 / 11,199 = 299.57


∴ L/r0p = 21.65 / 0.3 = 72.1667

fz2 : VALUE OF FUNCTION = 0.055


Ep/Gds
L/r0p
250 299.568 500
fw2 0.059 0.055 0.041 72

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CZ1 6 x 122.423
CZg1 = = = 233.855 t·sec/m
αa 3.141

Where, n = NUMBER OF PILE = 6 EA


αa = 3.141 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CZg1 233.855
DZ = = = 0.048
2· KZg1·m 2x 308,549 x 19.1

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 1.1 + 18.0 = 19.1 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

Dtz = Dz + Di = 0.048 + 0.05 = 0.098

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.2 Horizontal direction (Parrel to FD Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 72

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 6 x 74.63
CHg1 = = = 164.632 t·sec/m
αpf 2.720

Where, n = NUMBER OF PILE = 6 EA


αpf = 2.72 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 164.632
DH = = = 0.08
2· KHg1·m 2x 55,010 x 19.1

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 1.1 + 18.0 = 19.1 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.08 + 0.05 = 0.13

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.3 Horizontal direction (Transverse FD fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 72.1667

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 6 x 74.63
CHg1 = = = 164.695 t·sec/m
αpf 2.719

Where, n = NUMBER OF PILE = 6 EA


αpf = 2.72 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 164.695
DH = = = 0.08
2· KHg1·m 2x 55,030 x 19.1

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT]/9.81 + FDN WEIGHT/9.81
= 1.1 + 18.0 = 19.1 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.080 + 0.05 = 0.13

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.0 NATURAL AND RESONANCE FREQUANCE CALCULATION AND REVIEW


8.1 Vertical direction
1) UNDAMPED NATURAL FREQUENCY
60 Kz 60 308,549
fnZ = · = x = 1212.59 rpm
2·π m 2xπ 19.1

2
Where, m = LUMPED MASS = 1.1 + 18.0 = 19.1 t·sec /m
KZ = SPRING CONSTANT = 308,549.4 ton/m

2) RESONANCE FREQUENCY

fmZ = fnZ x 1/ ((1-2Dt2) 0.5


2
= 1212.59 x 1/((1-2* 0.098 )0.5 = 1,224 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 979.5 1469.3 OUT OF RANGE

8.2 Horizontal direction (Parrel to FD fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 55,010
fnH = · = x = 512 rpm
2·π m 2xπ 19.1

Where, m = LUMPED MASS = 1.1 + 18.0 = 19.1 t·sec2/m


KH = SPRING CONSTANT = 55,010 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 512 x 1/((1-2* 0.13 )0.5 = 521 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 416.7 625.1 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.3 Horizontal direction (Transverse to FD fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 55,030
fnH = · = x = 512.1 rpm
2·π m 2xπ 19.1

Where, m = LUMPED MASS = 1.1 + 18.0 = 19.1 t·sec2/m


KH = SPRING CONSTANT = 55,030 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 512.1 x 1/((1-2* 0.13 )0.5 = 521 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 416.8 625.2 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9.0 The determinatin of dynamic Gds and νds for clay layer
From Soil Investigation Report (clause 3.9, down hole test results),
the dynamic Shear modulus and poisson ratio for clay layer would be summarided as below table.
Density Vp Vs Ed Gds νds
Sort REMARK
t/m3 m/s m/s kg/cm2 kg/cm2 -
1 1.96 417 179 1500 1000 0.39
2 1.96 500 221 1607 1021 0.38
3 1.96 500 253 1714 1043 0.33
4 1.96 500 257 1821 1064 0.32
5 1.96 556 289 1929 1086 0.31
6 1.96 625 291 2036 1107 0.31
7 1.96 625 330 2143 1129 0.31
8 1.96 625 331 2250 1150 0.31 BH-03
9 1.96 625 332 2357 1171 0.30
10 1.96 455 237 2464 1193 0.31
11 1.96 455 237 2571 1214 0.31
12 1.96 455 237 2679 1236 0.31
13 1.96 714 384 2786 1257 0.30
14 1.96 714 374 2893 1279 0.30
15 1.96 714 384 3000 1300 0.30
1 1.95 454.6 195.68 1500 1000 0.39
2 1.95 454.6 220.53 1636 1027 0.35
3 1.95 500 252.85 1773 1055 0.33
4 1.95 500 256.82 1909 1082 0.32
5 1.95 454.6 234.22 2045 1109 0.32
6 1.95 454.6 235.31 2182 1136 0.32
BH-13
7 1.95 454.6 236 2318 1164 0.31
8 1.95 454.6 236.46 2455 1191 0.31
9 1.95 454.6 236.78 2591 1218 0.31
10 1.95 500 236.97 2727 1245 0.31
11 1.95 500 262.17 2864 1273 0.31
12 1.95 500 262.32 3000 1300 0.31

For safety side review, dynamic shear modulus at lower 5% and poisson ratio at higher 5% would be adopted.
And, the density for clay layer would be 1.96 ton/m3 for resonance frequency check.

Dynamic shear modulus (kg/cm2, Gds) for layer 1


Average(=m) 1150
Variance 9036
The confidence interval90% (=δ) 30
Higher5% limitation(=m+δ) 1180
Lower5% limitation(=m+δ) 1120

Dynamic Poisson ratios (νds) for layer 1


Average(=m) 0.321
Variance 0.001
The confidence interval90% (=δ) 0.008
Higher5% limitation(=m+δ) 0.330
Lower5% limitation(=m+δ) 0.313

DOCUMENT No. : IKCP0-UHA-C-06-0002


3-2. F.D FAN (UNIT#1B,2B)
KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

1.0 CONCRETE AND SOIL PARAMETERS

γs 1.96 3
1) UNIT WEIGHT OF SUBGROUND = ton/m (From clause 8.0)
(CLAY LAYER)

2) DYNAMIC SHEAR MODULUS OF SUGBROUND Gds = 1119.9 kg/cm2 (From clause 8.0)
(CLAY LAYER)

3) DYNAMIC POISSON'S RATIO OF SUBGROUND νds = 0.330 (From clause 8.0)


(CLAY LAYER)

4) SOIL INTERNAL DAMPING RATIO = 0.05

3
5) UNIT WEIGHT OF FOUNDATION CONCRETE = 2.50 ton/m

2.0 MACHINE PARAMETERS (BY VENDOR INFORMATION)

1) MACHINE WEIGHT (UNIT : KG)

STATIC WEIGHT DYNAMIC FORCES

LOCATION VERTICAL HORIZONTAL LOCATION VERTICAL HORIZONTAL

Y-DIR. X-DIR. Z-DIR. Y-DIR. X-DIR. Z-DIR.

Motar A 3000 0 0 Motar A 3000 0 0


Bed SUB Ⅰ 3000 0 0 Bed
SUB Ⅰ 3000 0 0

B 1300 0 0 B 850 0 0
B'RG B'RG
Housing C 1950 0 0 Housing C 1050 0 0
Bed Bed
SUB Ⅱ 3250 0 0 SUB Ⅱ 1900 0 0

D 1200 0 0 D 0 0 0

E 1000 0 0 E 0 0 0
Casing Casing
F 1050 0 0 F 0 0 0
Bracket Bracket
G 950 0 0 G 0 0 0

SUB Ⅲ 4200 0 0 SUB Ⅲ 0 0 0

DAMPER H 300 0 0 DAMPER H 0 0 0


ACTUATO ACTUATO
R BED SUB Ⅳ 300 0 0 R BED SUB Ⅳ 0 0 0

C1 7490 160 1750 C1 0 0 0

C2 7330 -140 1710 C2 0 0 0

C3 4850 140 30 C3 0 0 0
SILENCER SILENCER
C4 5130 -180 30 C4 0 0 0
SUPPORT SUPPORT
C5 9340 100 -1790 C5 0 0 0

C6 9210 -80 -1740 C6 0 0 0

SUB Ⅴ 43350 0.0 -10 SUB Ⅴ 0 0 0

TOTAL 10450 0 0 TOTAL 4900 0 0

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) OPERATING FREQUENCY : fo = 1480 RPM

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3.0 FOUNDATION SIZE CHECK

1) FOUNDATION WEIGHT
(UNIT : ton, m)

FOUNDATION SIZE TOTAL

COMPONENT WIDTH LENGTH AREA HEIGHT Q'ty WEIGHT

Bf Lf Af Hf Wf

F1 1.350 0.800 1.08 1.350 1 3.65

F2 3.400 1.400 4.76 1.455 1 17.31

F3 3.400 0.600 2.04 1.455 1 7.42

F4 3.400 1.750 5.95 1.455 1 21.64

F5 2.600 1.750 4.55 1.455 1 16.55

F6 0.950 0.850 0.81 0.250 1 0.50

F7-1~F7-6 0.600 0.600 0.36 0.050 6 0.27

F8 5.850 11.665 68.24 1.000 1 170.60

TOTAL 87.79 237.94

2) MACHINE WEIGHT Wm = 10.5 ton

3) MASS RATIO = Wc / Wm = 237.94 ÷ 10.45

= 22.77 > 3 ∴ O.K

4) MASS RATIO OF ROTOR


MASS RATIO = Wc / ROTOR WEIGHT
= 237.94 ÷ 3

= 79.31 > 25 ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

4.0 CALCULATION OF C.G. OF MACHINE & FOUNDATION

4.1 CENTER OF GRAVITY IN STATIC CONDITION


1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD
Ver.(Y) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My
A 3.000 0.000 0.000 6.220 18.660 3.150 9.450 2.350 0.000

B 1.300 0.000 0.000 5.028 6.536 3.150 4.095 2.455 0.000

C 1.950 0.000 0.000 2.108 4.111 3.150 6.143 2.455 0.000

D 1.200 0.000 0.000 4.923 5.908 4.065 4.878 2.455 0.000

E 1.000 0.000 0.000 2.213 2.213 4.065 4.065 2.455 0.000

F 1.050 0.000 0.000 4.923 5.169 2.235 2.347 2.455 0.000

G 0.950 0.000 0.000 2.213 2.102 2.235 2.123 2.455 0.000

H 0.300 0.000 0.000 1.820 0.546 0.475 0.143 1.300 0.000

C1 7.490 0.160 1.750 11.365 85.292 5.550 43.407 1.050 20.777

C2 7.330 -0.140 1.710 11.365 83.158 0.750 7.293 1.050 19.329

C3 4.850 0.140 0.030 6.300 30.702 5.550 26.949 1.050 0.966

C4 5.130 -0.180 0.030 6.300 32.130 0.750 3.879 1.050 0.054

C5 9.340 0.100 -1.790 0.300 2.907 5.500 49.491 1.050 0.013

C6 9.210 -0.080 -1.740 0.300 2.679 0.750 5.081 1.050 -0.582

TOTAL 54.10 0.00 -0.01 282.1 169.34 40.56

2) CENTER OF GRAVITY FOR FOUNDATION


WEIGHT MASS X-DIR Z-DIR Y-DIR
COMPONENT
(TON) (t·sec2/m) X(m) Mz Z(m) Mx Y(m) My
F1 3.65 0.372 0.578 2.11 2.025 7.39 1.675 6.11

F2 17.31 1.765 1.678 29.05 3.050 52.80 1.728 29.90

F3 7.42 0.756 5.058 37.53 3.050 22.63 1.728 12.82

F4 21.64 2.206 6.233 134.88 3.050 66.00 1.728 37.38

F5 16.55 1.687 7.983 132.12 2.450 40.55 1.728 28.59

F6 0.50 0.051 1.820 0.91 0.475 0.24 1.125 0.56

F7-1 0.27 0.028 11.365 3.07 5.550 1.50 1.025 0.28

F7-2 0.27 0.028 11.365 3.07 0.750 0.20 1.025 0.28

F7-3 0.27 0.028 6.300 1.70 5.550 1.50 1.025 0.28

F7-4 0.27 0.028 6.300 1.70 0.750 0.20 1.025 0.28

F7-5 0.27 0.028 0.300 0.08 5.500 1.49 1.025 0.28

F7-6 0.27 0.028 0.300 0.08 0.750 0.20 1.025 0.28

F8 170.60 17.390 5.832 994.94 2.925 499.01 0.500 85.30

TOTAL 239.29 24.39 1341.24 693.70 202.33

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2
3) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA

Mcx = Af x Czi

Mcz = Af x Cxi

FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F8 5.850 11.665 68.240 2.925 5.832 199.60 397.98

TOTAL 68.24 199.60 397.98

Xf = ∑Mcz / ∑Af = 397.98 / 68.24 = 5.83 m

Zf = ∑Mcx / ∑Af = 199.60 / 68.24 = 2.93 m

4) CENTER OF GRAVITY OF MACHINE & FOUNDATION

Xcg = Mz(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 1341.24 + 282.11 )/( 239.29 + 54.10 ) = 5.533 m

Zcg = Mx(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 693.70 + 169.34 )/( 239.29 + 54.10 ) = 2.942 m

Ycg = My(FDN. + MACHINE DEAD) / ∑WEIGHT(FDN. + MACHINE)

= ( 202.33 + 40.56 )/( 239.29 + 54.10 ) = 0.828 m

5) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 5.83 - 5.53 | / 11.67 x 100
= 2.55 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 2.93 - 2.94 | / 5.85 x 100
= 0.21 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5.0 CENTER OF GRAVITY IN OPERATING CONDITION

1) CENTER OF GRAVITY FOR MACHINE DEAD LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 3.000 0.000 0.000 6.220 18.660 3.150 9.450 2.350 0.000

B 1.300 0.000 0.000 5.028 6.536 3.150 4.095 2.455 0.000

C 1.950 0.000 0.000 2.108 4.111 3.150 6.143 2.455 0.000

D 1.200 0.000 0.000 4.923 5.908 4.065 4.878 2.455 0.000

E 1.000 0.000 0.000 2.213 2.213 4.065 4.065 2.455 0.000

F 1.050 0.000 0.000 4.923 5.169 2.235 2.347 2.455 0.000

G 0.950 0.000 0.000 2.213 2.102 2.235 2.123 2.455 0.000

C1 7.490 0.160 1.750 11.365 85.292 5.550 43.407 1.050 20.777

C2 7.330 -0.140 1.710 11.365 83.158 0.750 7.293 1.050 19.329

C3 4.850 0.140 0.030 6.300 30.702 5.550 26.949 1.050 0.966

C4 5.130 -0.180 0.030 6.300 32.130 0.750 3.879 1.050 0.054

C5 9.340 0.100 -1.790 0.300 2.907 5.500 49.491 1.050 0.013

C6 9.210 -0.080 -1.740 0.300 2.679 0.750 5.081 1.050 -0.582

TOTAL 53.80 0.00 -0.01 281.6 169.20 40.56

2) CENTER OF GRAVITY FOR MACHINE DYNAMIC LOAD

Ver.(Z) Hori.(X) Hori.(Z) X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (TON) (TON) X(m) Mz Z(m) Mx Y(m) My

A 3.000 0.000 0.000 6.220 18.660 3.150 9.450 2.350 0.000

B 0.850 0.000 0.000 5.028 4.274 3.150 2.678 2.455 0.000

C 1.050 0.000 0.000 2.108 2.213 3.150 3.308 2.455 0.000

TOTAL 4.90 0.00 0.00 25.15 15.44 0.00

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

3) CENTER OF GRAVITY FOR FOUNDATION

WEIGHT MASS X-DIR Z-DIR Y-DIR


COMPONENT
(TON) (t·sec2/m) X(m) Mz Z(m) Mx Y(m) My

F1 3.65 0.372 0.578 2.11 2.025 7.39 1.675 6.11

F2 17.31 1.765 1.678 29.05 3.050 52.80 1.728 29.90

F3 7.42 0.756 5.058 37.53 3.050 22.63 1.728 12.82

F4 21.64 2.206 6.233 134.88 3.050 66.00 1.728 37.38

F5 16.55 1.687 7.983 132.12 2.450 40.55 1.728 28.59

F6 0.50 0.051 1.820 0.91 0.475 0.24 1.125 0.56

F7-1 0.27 0.028 11.365 3.07 5.550 1.50 1.025 0.28

F7-2 0.27 0.028 11.365 3.07 0.750 0.20 1.025 0.28

F7-3 0.27 0.028 6.300 1.70 5.550 1.50 1.025 0.28

F7-4 0.27 0.028 6.300 1.70 0.750 0.20 1.025 0.28

F7-5 0.27 0.028 0.300 0.08 5.500 1.49 1.025 0.28

F7-6 0.27 0.028 0.300 0.08 0.750 0.20 1.025 0.28

F8 170.60 17.390 5.832 994.94 2.925 499.01 0.500 85.30

TOTAL 239.29 24.392 1341.24 693.70 202.33

4) CENTER OF SUBGROUND CONTACTED FOUNDATION AREA


Mcx = Af x Czi
Mcz = Af x Cxi
FOUNDATION SIZE

COMPONENT WIDTH LENGTH AREA Czi Cxi Mcx Mcz

Bz Lx Af

F6 5.850 11.665 68.240 2.925 5.832 199.60 397.98

TOTAL 68.24 199.60 397.98

Xf = ∑Mcz / ∑Af = 397.98 / 68.24 = 5.83 m


Zf = ∑Mcx / ∑Af = 199.60 / 68.24 = 2.93 m

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

5) CENTER OF GRAVITY OF MACHINE & FDN. IN DYNAMIC CONDITION

Xcg = Mz(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 1341.24 + 281.57 + 25.15 )
/ ( 239.29 + 54.10 + 4.90 ) = 5.525 m

Zcg = Mx(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 693.70 + 169.20 + 15.44 )
/ ( 239.29 + 54.10 + 4.90 ) = 2.945 m

Ycg = My(FDN. + MACHINE DEAD + MACHINE DYNAMIC)


/ ∑WEIGHT(FDN. + MACHINE + MACHINE DYNAMIC)
= ( 202.33 + 40.56 + 0.00 )
/ ( 239.29 + 54.10 + 4.90 ) = 0.814 m

6) ECCENTRICITY
● X - AXIS
ex = |Xf - Xcg | / Lx x 100 = | 5.83 - 5.53 | / 11.67 x 100
= 2.61 % < 5.00 % ∴ O.K
● Z - AXIS
ez = |Zf - Zcg | / Bz x 100 = | 2.93 - 2.95 | / 5.85 x 100
= 0.26 % < 5.00 % ∴ O.K

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.0 SPRING CONSTANT CALCULATION


6.1 Vertical direction
1) SINGLE PILE SPRING CONSTANT
Ep·A
KZ1 = · fz1
r0p
3354866 x 0.157
= x 0.092 = 161,526 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


= ( Gds / ρs )0.5 = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
= 1,120 kg/cm2 = 11,199 ton/m2
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 32900000 kpa = 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
A = CROSS-SECTION AREA OF PILE = 0.157 m2
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.1 m
∴ L/r0p = 22.1 / 0.3 = 73.6667
fz1 = VALUE OF FUNCTION = 0.092
Ep/Gsp
L/r0p
250 299.568 500
fw1 0.0980 0.092 0.0700 73.6667

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT


∑n·KZ1 9 x 161,526
KZg1 = = = 398,064 ton/m (FOR PILE)
αa 3.652

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.1 / ( 2 x 0.3 ) = 36.833
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αa = INTERACTION FACTOR = 3.652
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
S/2r0p or αa
S(m) REMARKS
2r0p/S νs = 0.00 νs = 0.32 νs = 0.50
P1 0.000 - - 1.000 - REFERENCE PILE
P2 5.083 0.118 0.405 0.354 0.326
P3 10.165 0.059 0.276 0.236 0.213
P4 2.000 3.333 0.598 0.554 0.529
P5 5.462 0.110 0.392 0.341 0.313
P6 10.360 0.058 0.273 0.233 0.210
P7 4.000 0.150 0.448 0.399 0.373
P8 6.468 0.093 0.361 0.311 0.284
P9 10.924 0.055 0.263 0.224 0.203

∑ 3.652

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.2 Horizontal direction (Parrel to FD Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


0.5
= ( Gds / ρs ) = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
= 0.26 t·sec2/m4
∴ Ep/Gds= 3354866 / 11199 = 299.5684
I = Moment inertia = 0.00329 m4
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.1 m
∴ L/r0p = 22.1 / 0.3 = 73.6667
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 74

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 9 x 24,937
KHg1 = = = 78,938 ton/m (FOR PILE)
αpf 2.84

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.1 / ( 2 x 0.3 ) = 36.833
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.84
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
4
KR = (EI)PILE / (Ed,s*L )
4
= 3354866 x 0.00329 /( 29,599 x 22.1 )
= 1.56E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - 90.00 1.00 1.00 1.00
P2 5.083 0.000 5.083 8.471 0.118 0.00 0.28 0.16 0.28
P3 10.165 0.000 10.165 16.942 0.059 0.00 0.17 0.09 0.17
P4 0.000 2.000 2.000 3.333 0.300 90.00 0.75 0.45 0.45
P5 5.083 2.000 5.462 9.103 0.110 21.48 0.27 0.16 0.24
P6 10.165 2.000 10.360 17.266 0.058 11.13 0.17 0.09 0.16
P7 0.000 4.000 4.000 6.667 0.150 90.00 0.32 0.20 0.20
P8 5.083 4.000 6.468 10.780 0.093 38.20 0.25 0.14 0.20
P9 10.165 4.000 10.924 18.206 0.055 21.48 0.16 0.08 0.14
Sum of interaction factor for horizontal direction 2.84

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

6.3 Horizontal direction (Transverse to FD Fan shaft)


1) SINGLE PILE SPRING CONSTANT
Ep·Ip
KH1 = 3
· fx1
r0p
3354866 x 0.00329
= 3
x 0.061 = 24,937 ton/m
0.3

Where, Vs = SHEAR WAVE VELOCITY IN THE SOIL


= ( Gds / ρs )0.5 = ( 11199 / 0.2 )0.5
= 237 m/sec
Gds = DYNAMIC SHEAR MODULUS OF SUB SOIL
2 2
= 1,120 kg/cm = 11,199 ton/m
ρs = MASS DENSITY OF SOIL = γs / g = 1.96 / 9.81
2 4
= 0.2 t·sec /m
Ep = YOUNG'S MODULUS OF PILE
2
= 3354866 ton/m
ρp = MASS DENSITY OF PILE = γp / g = 2.50 / 9.81
2 4
= 0.26 t·sec /m
∴ Ep/Gds= 3354866 / 11199 = 299.5684
= 2
I = Moment inertia 0.00329 m
r0p = RADIUS OF PILE = 60 / 2
= 30 cm = 0.3 m
L = PILE LENGTH = 22.1 m
∴ L/r0p = 22.1 / 0.3 = 73.6667
fx1 = VALUE OF FUNCTION = 0.061
Ep/Gsp
L/r0p
250 299.568 500
fx1 0.0659 0.061 0.0395 74

* Note. Although νs would be 0.321, the fx1 for [ν=0.25] would be taken for consevative side review.

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

2) GROUP PILE SPRING CONSTANT

∑n·KH1 9 x 24,937
KHg1 = = = 77,881 ton/m (FOR PILE)
αpf 2.88

Where, n = NUMBER OF PILE = 9 EA


∴ L/2r0p = 22.1 / ( 2 x 0.3 ) = 36.833
νs = DYNAMIC POISON'S RATIO OF SUBSOIL = 0.321
αpf = INTERACTION FACTOR FOR HORIZONTAL DIR. = 2.88
S = DISTANCE FROM REFERENCE PILE TO EACH PILE
Ed,s = DYNAMIC ELEASTIC MODULUS OF SUB SOIL = Gds*2*(1+νs)
= 2,960 kg/cm2 = 29,599 ton/m2
KR = (EI)PILE / (Ed,s*L4)
4
= 3354866 x 0.00329 /( 29,599 x 22.1 )
= 1.56E-06 (For conservative side review, use αpf under KR=10-3)
β = Horizontal load departure angle based on reference pile

DX DY S β αpf, β=0° αpf, β=90°


Sort S/2Ro 2R0/S αpf, β° Remark
(m) (m) (m) (°) (°) (°)
P1 0.000 0.000 0.000 - - - 1 1 1 Reference pile
P2 5.083 0.000 5.083 8.471 0.118 90.00 0.28 0.16 0.16
P3 10.165 0.000 10.165 16.942 0.059 90.00 0.17 0.09 0.09
P4 0.000 2.000 2.000 3.333 0.300 - 0.75 0.45 0.75
P5 5.083 2.000 5.462 9.103 0.110 68.52 0.27 0.16 0.18
P6 10.165 2.000 10.360 17.266 0.058 78.87 0.17 0.09 0.10
P7 0.000 4.000 4.000 6.667 0.150 - 0.32 0.20 0.32
P8 5.083 4.000 6.468 10.780 0.093 51.80 0.25 0.14 0.18
P9 10.165 4.000 10.924 18.206 0.055 68.52 0.16 0.08 0.10
Sum of interaction factor for horizontal direction 2.88

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.0 DAMPING RATIO


7.1 Vertical direction
1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ap 3354866 x 0.157


CZ1 = · fw2 = x 0.055
Vs 237

= 122.4 t·sec/m (FOR PILE)

From clause 6, ∴ Ep/Gds= 3354866 / 11,199 = 299.57


∴ L/r0p = 22.1 / 0.3 = 73.6667

fz2 : VALUE OF FUNCTION = 0.055


Ep/Gds
L/r0p
250 299.568 500
fw2 0.059 0.055 0.041 74

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CZ1 9 x 122.423
CZg1 = = = 301.7 t·sec/m
αa 3.652

Where, n = NUMBER OF PILE = 9 EA


αa = 3.652 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CZg1 301.7
DZ = = = 0.048
2· KZg1·m 2x 398,064 x 25.3

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 1.1 + 24.3 = 25.3 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

Dtz = Dz + Di = 0.048 + 0.05 = 0.098

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.2 Horizontal direction (Parrel to FD Fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 74

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 9 x 74.63
CHg1 = = = 236.246 t·sec/m
αpf 2.843

Where, n = NUMBER OF PILE = 9 EA


αpf = 2.84 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 236.246
DH = = = 0.084
2· KHg1·m 2x 78,938 x 25.3

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT] / 9.81 + FDN WEIGHT / 9.81
= 1.1 + 24.3 = 25.3 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.084 + 0.05 = 0.134

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

7.3 Horizontal direction (Transverse FD fan shaft)


1) GEOMETRICAL DAMPING CALCULATION
a) DAMPING CONSTANT FOR SINGLE PILE

Ep·Ip 3354866 x 0.00329


CH1 = · fx2 = x 0.144
r0p2Vs 0.3 2
x 237

= 74.6 t·sec/m (FOR PILE)

fx2 : VALUE OF FUNCTION = 0.144


Ep/Gds
L/r0p
250 299.568 500
fx2 0.1556 0.144 0.0953 73.6667

b) DAMPING CONSTANT FOR GROUP PILE

∑n·CH1 9 x 74.63
CHg1 = = = 233.082 t·sec/m
αpf 2.882

Where, n = NUMBER OF PILE = 9 EA


αpf = 2.88 (From clause 6.0)

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

c) DAMPING RATIO CALCULATION

CHg1 233.082
DH = = = 0.083
2· KHg1·m 2x 77,881 x 25.3

Where, m = LUMPED MASS


= [WEIGHT OF MACHINE&EQUIPMENT]/9.81 + FDN WEIGHT/9.81
= 1.1 + 24.3 = 25.3 t·sec2/m

2) SOIL INTERNAL DAMPING

Di = 0.05

3) TOTAL DAMPING

DtH = DH + Di = 0.083 + 0.05 = 0.133

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.0 NATURAL AND RESONANCE FREQUANCE CALCULATION AND REVIEW


8.1 Vertical direction
1) UNDAMPED NATURAL FREQUENCY
60 Kz 60 398,064
fnZ = · = x = 1197.33 rpm
2·π m 2xπ 25.3

2
Where, m = LUMPED MASS = 1.1 + 24.3 = 25.3 t·sec /m
KZ = SPRING CONSTANT = 398,064.2 ton/m

2) RESONANCE FREQUENCY

fmZ = fnZ x 1/ ((1-2Dt2) 0.5


2
= 1197.33 x 1/((1-2* 0.098 )0.5 = 1,209 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 967.2 1450.8 OUT OF RANGE

8.2 Horizontal direction (Parrel to FD fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 78,938
fnH = · = x = 533.19 rpm
2·π m 2xπ 25.3

Where, m = LUMPED MASS = 1.1 + 24.3 = 25.3 t·sec2/m


KH = SPRING CONSTANT = 78,938 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 533.19 x 1/((1-2* 0.134 )0.5 = 543 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 434.4 651.6 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

8.3 Horizontal direction (Transverse to FD fan shaft)


1) UNDAMPED NATURAL FREQUENCY
60 KH 60 77,881
fnH = · = x = 529.61 rpm
2·π m 2xπ 25.3

2
Where, m = LUMPED MASS = 1.1 + 24.3 = 25.3 t·sec /m
KH = SPRING CONSTANT = 77,881 ton/m

2) RESONANCE FREQUENCY

fmH = fnH x 1/ ((1-2Dt2) 0.5


2
= 529.61 x 1/((1-2* 0.133 )0.5 = 539 rpm

3) THE OPERATING FREQUENCY OF THE MACHINE SHOULD HAVE AT LEAST A DIFFERENCE OF ±


20.0% WITH THE RESONANCE FREQUENCIES:
⇔ [ f < 0.80 fm ] or [ f > 1.20 fm ]

Operating 0.80 * fm 1.20 * fm


Review result
frequency(RPM) (RPM) (RPM)
1480.0 431.4 647.1 OUT OF RANGE

DOCUMENT No. : IKCP0-UHA-C-06-0002


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

9.0 The determinatin of dynamic Gds and νds for clay layer
From Soil Investigation Report (clause 3.9, down hole test results),
the dynamic Shear modulus and poisson ratio for clay layer would be summarided as below table.
Density Vp Vs Ed Gds νds
Sort REMARK
t/m3 m/s m/s kg/cm2 kg/cm2 -
1 1.96 417 179 1500 1000 0.39
2 1.96 500 221 1607 1021 0.38
3 1.96 500 253 1714 1043 0.33
4 1.96 500 257 1821 1064 0.32
5 1.96 556 289 1929 1086 0.31
6 1.96 625 291 2036 1107 0.31
7 1.96 625 330 2143 1129 0.31
8 1.96 625 331 2250 1150 0.31 BH-03
9 1.96 625 332 2357 1171 0.30
10 1.96 455 237 2464 1193 0.31
11 1.96 455 237 2571 1214 0.31
12 1.96 455 237 2679 1236 0.31
13 1.96 714 384 2786 1257 0.30
14 1.96 714 374 2893 1279 0.30
15 1.96 714 384 3000 1300 0.30
1 1.95 454.6 195.68 1500 1000 0.39
2 1.95 454.6 220.53 1636 1027 0.35
3 1.95 500 252.85 1773 1055 0.33
4 1.95 500 256.82 1909 1082 0.32
5 1.95 454.6 234.22 2045 1109 0.32
6 1.95 454.6 235.31 2182 1136 0.32
BH-13
7 1.95 454.6 236 2318 1164 0.31
8 1.95 454.6 236.46 2455 1191 0.31
9 1.95 454.6 236.78 2591 1218 0.31
10 1.95 500 236.97 2727 1245 0.31
11 1.95 500 262.17 2864 1273 0.31
12 1.95 500 262.32 3000 1300 0.31

For safety side review, dynamic shear modulus at lower 5% and poisson ratio at higher 5% would be adopted.
And, the density for clay layer would be 1.96 ton/m3 for resonance frequency check.

Dynamic shear modulus (kg/cm2, Gds) for layer 1


Average(=m) 1150
Variance 9036
The confidence interval90% (=δ) 30
Higher5% limitation(=m+δ) 1180
Lower5% limitation(=m+δ) 1120

Dynamic Poisson ratios (νds) for layer 1


Average(=m) 0.321
Variance 0.001
The confidence interval90% (=δ) 0.008
Higher5% limitation(=m+δ) 0.330
Lower5% limitation(=m+δ) 0.313

DOCUMENT No. : IKCP0-UHA-C-06-0002


[ ATTACHMENTS ]

#4. RECOMMENDED PARMETER OF SOIL


PT. TIGENCO GRAHA PERSADA
Geodesy – Topography – Hydrography – Oceanography – Cadastral Survey-
Soil Investigation –Engineering Design

simplicity sake and because it is mixed with clay therefore it will be neglected except for
liquefaction analysis later. The stratigraphy of the site will follow 4 layers: top fill, soft clay,
stiff clay and claystone. The lab testing is mainly done on top fill layer and soft clay layer. The
consolidable layer is mostly the top fill and soft clay layer.

The parameters recommended for this area is taken as:

Table 4-4Recommended Parameters for Powerblock Area

Pre
Comp Conso
Undrained Soil consol
Depth (m) Thick Unit ression lidation eo
Assumed Shear Str. Modulus idation
No ness Soil Type Weight Coefficient Coefficient
SPT Pressure
(m) (gr/cm3)
Cv (cm2/ Pc
from to Su (kPa) E (Mpa) Cc
sec) (kg/cm2)
1 0 6 6 CLAY 1.9 50 15.00 0.5 5.00E-03 1.2 1.1
2 6 15 9 CLAY 1.9 8 15 4.50 0.5 5.00E-03 1.2 1.1
3 15 19 4 STIFF CLAY 2.1 35 234.5 70.35
stiff - very hard
4 19 40 21 CLAYSTONE 2.2 50 335 150.00

TRUBA JAYA ENGINEERING - Geotechnical Investigation Kalselteng- 2 CFSPP Project 109


[ ATTACHMENT ]

#5. PILE QUANTITY ANALYSIS COMPARED TO CONTRACT SCHEDULE


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Pile Quantity Analysis Compared to Contract Schedule


(Boiler Foundation Area)
1) General

- For pile diameter & total length, the variation between schedule 1.2 in Contract and detail design is
compared as per the Owner's request.
2) Comparison Table
Total Pile Length Remark
Schedule 1.2 Detail Difference
Structures Pile Dia
in Contract Design (B-A)
(A)* (B)
Boiler House Area D600 15630 m 14792 m -838 m
* (A) is based on Contrat Book I, Attachment 2, Detail Price Schedule 1.2 which is estimated by PLN
during bidding stage.
3) Reason For Change
- Total pile length is decreased around 5% at the detail design compared to contract data.

- This detail design is performed based on actual super-structure's loading data provided by Suppiler.
- In this design, pile reaction is considering up to max. 98.8% compared to allowable pile capacity.
- Therefore, pile design of boiler house area is really optimized according to actual supplier's information
and fixed plot plan as above-mentioned, not assumption by uncertain data during the bidding stage.

- Pile Compression Capacity Check for Coal Bunker Area

Allowable Pile capacity = 135 ton, by pile load test result

- Pile Compression Capacity Check for Boiler Main Foundation

Allowable Pile capacity = 135 ton, by pile load test result


KALSELTENG-2 COAL FIRED STEAM POWER PROJECT
DESIGN CALCULATION FOR OTHERS FOUNDATION FOR BOILER AREA REV.2

Contrat Book I, Attachment 2, Detail Price Schedule 1.2

You might also like