Professional Documents
Culture Documents
Multi-Circuit Installation Guide English For information on basic meter setup, refer to the PM5350PB/PM5350IB User Guide.
EAV25860-07 12/2019 You can download the user guides and other documentation from our website at
www.schneider-electric.com. Type PM5350PB or PM5350IB in the search field.
SAFETY PRECAUTIONS
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E in the USA or applicable local standards.
• Only qualified electrical workers should install this equipment. Such work should
be performed only after reading this entire set of instructions.
• NEVER work alone.
• Do not exceed the device’s ratings for maximum limits.
• Do not use this device for critical control or protection applications where human
or equipment safety relies on the operation of the control circuit.
• Before performing visual inspections, tests, or maintenance on this equipment,
disconnect all sources of electric power. Assume that all circuits are live until they
have been completely de-energized, tested, and tagged. Pay particular attention
to the design of the power system. Consider all sources of power, including the
possibility of backfeeding.
• Turn off all power supplying this device before working on it.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• Before closing all covers and doors, carefully inspect the work area for tools and
objects that may have been left inside the equipment.
• Use caution while removing or installing panels so that they do not extend into the
energized bus; avoid handling the panels, which could cause personal injury.
• The successful operation of this equipment depends upon proper handling,
installation, and operation. Neglecting fundamental installation requirements may
To install the meter into a non-multi-circuit application, lead to personal injury as well as damage to electrical equipment or other property.
• NEVER bypass external fusing.
refer to the PM5350 Installation Guide, part number • NEVER short the secondary of a PT or VT.
63230-401-202. • NEVER open circuit a CT; use the shorting block to short circuit the leads of the
CT before removing the connection from the power meter.
• Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which
For California residents only the power meter is installed, disconnect all input and output wires to the power
meter. High voltage testing may damage electronic components contained in the
power meter.
• The power meter should be installed in a suitable electrical enclosure.
• Always use grounded external CTs for current inputs.
• All external CT’s and PT’s should have reinforced insulation.
1. Turn off all power supplying this device before working on it.
2. Always use a properly rated voltage sensing device to confirm that all power is off.
Only the meters with firmware (F/W) versions 3.00 and above can be used in a multi-
circuit application. Refer to the product label on the rear of the meter or on the meter PM5350IB PM5350PB
13
carton to verify the firmware version. (0.51) 13
(0.51)
44 96 44
(1.73) 96
FW: 3.10 (3.78) (1.73) (3.78)
FW: 3.10
96 96
92 +0.8 (3.78) 92 +0.8
–0.0 (3.78)
–0.0
(3.62) (3.62)
+0.8
+0.8
92 +0.8
INSTALLATION
92–0.0
–0.0
(3.62) (3.62)
These instructions are only for installing the PM5350PB/PM5350IB meter in a multi-
circuit configuration.
mm 6.4
Box Contents mm
(in.) 6.4
(0.25)
(in.) (0.25)
• One (1) power meter with retainer clips attached • One (1) certificate of calibration max.
• One (1) set of installation guides • Two (2) screws (spare screws for CTs)
Figure 3: Mounting
• One (1) RS-485 terminator (MCT2W)
• One (1) panel gasket
PM5350IB PM5350PB
Figure 1: Parts of PM5350PB and PM5350IB (rear panel door removed)
PM5350IB PM5350PB
B
A B
H
H
H
C
C
G F E D
G F E D
1
Mounting Instructions Table 1: Wiring Specifications
Measurement Category
UL:
WARNING 20 to 480 Vac L-L, CAT III
HAZARD OF UNINTENDED OPERATION PM5350PB IEC:
• Do not excessively bend, twist, or pull the wiring during installation. 20 to 480 Vac L-L; 20 to 277 Vac L-N, CAT III
20 to 690 Vac L-L; 20 to 400 Vac L-N, CAT II
Failure to follow this instruction can result in death, serious injury, or Voltage Inputs
UL:
equipment damage.
20 to 300 Vac L-L, CAT III
PM5350IB IEC:
1. Remove retainer clips from the power meter and set aside.
2. Insert the power meter through the panel cut-out. 20 to 480 Vac L-L; 20 to 277 Vac L-N, CAT III
NOTE: Remove adhesive backing from the panel gasket before inserting the power 20 to 690 Vac L-L; 20 to 400 Vac L-N, CAT II
meter. Control Power CAT III, up to 277 Vac or 300 Vdc
1
3. Attach the retainer clips to the power meter. Wire ferrules recommended. Wire ferrule determines stripping length.
2
Current inputs (CTs) must have spade or ring terminal connections.
Installation Considerations
Figure 4: Three-Phase Power System Configurations
When choosing a mounting location, consider the following points:
• Allow for easy access to all parts of the power meter. Allow extra space for wiring,
fuse disconnects, shorting blocks, accessories, or other components. Route the
wires so that they do not cover the back of the unit or cooling vents on the power
meter.
• Install the power meter on a flat surface of a protective enclosure (for example, in
3PH3W Delta Corner 3PH3W Delta 3PH3W Wye 3PH3W Wye
USA, use a Type 1 rated enclosure or better). Resistance Grounded
Grounded Ungrounded Ungrounded
(3PH3W Dlt Crnr Gnd) (3PH3W Dlt Ungnd) (3PH3W Wye Ungnd) (3PH3W Wye Res Gnd)
WIRING
See the label inside the rear panel door of the meter for wiring connections. Terminal N N
Table 1: Wiring Specifications 3PH4W Open Delta 3PH4W Delta 3PH4W Wye 3PH4W Wye
Center-Tapped Center-Tapped Grounded Resistance Grounded
Wire Strip (3PH4W Opn Dlt Ctr Tp) (3PH4W Dlt Ctr Tp) (3PH4W Wye Gnd) (3PH4W Wye Res Gnd)
Connector Wire Size Torque
Length
1 2
Control Power 14 AWG 1.91 mm 0.28 in. 7mm 4.4 - 5.3 in-lbf 0.5 - 0.6 N•m
Voltage PM5350IB 14 AWG 1.91 mm2 0.28 in. 7mm 4.4 - 5.3 in-lbf 0.5 - 0.6 N•m
Inputs1 PM5350PB 14 AWG 1.91 mm2 0.39 in. 10mm 4.4 - 7.1 in-lbf 0.5 - 0.8 N•m
Current Inputs2 14 AWG 1.91 mm2 — — 4.4 - 5.3 in-lbf 0.5 - 0.6 N•m
RS-485 Communications,
Digital Outputs1, and Digital 16 AWG 1.34 mm2 0.24 in. 6 mm 4.4 - 5.3 in-lbf 0.5 - 0.6 N•m
Inputs
This is the safety alert symbol. It is used to alert you to potential personal Wiring for VTs
injury hazards. Obey all safety messages that follow this symbol to avoid CKT Circuit
possible injury or death.
S1 S2
L1 S1 S2
L1
L2 L2
L3 L3
N
Figure 7: MULTI-1CKT-LLN System Figure 8: MULTI-CKT-WYE System Figure 11: MULTI-2CKT / Figure 12: MULTI-3CKT-LN System
Type Type MULTI-2CKT-LL-DELT Type
One 2-phase LLN Circuit Breaker on L1-L2 One 3-phase Wye Circuit Breaker with Neutral Common
System Type
Two 2-phase LL Circuit Breaker on L1-L3, L2-L3 Three 1-phase LN Circuit Breaker on L1, L2, L3
V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 ) V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 )
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 )
S1 S2 S1 S2 S1 S2
V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 )
S1 S2 S1 S2 S1 S2
L1-L2-N L1-L3
CKT 1 CKT 2
L1-N
L1-L2-L3-N CKT 1
L2-L3
CKT 1
CKT 1
S1 S2 L2-N
CKT 2
S1 S2 S1 S2 L3-N
L1 S1 S2 L1 CKT 3
S1 S2 S1 S2
L2 L2 L1 S1 S2 L1
S1 S2 S1 S2
L3 L3 L2 L2
N L3 S1 S2
N L3
N
Figure 9: MULTI-1CKT-WYE-NN Figure 10: MULTI-2CKT-LN System
System Type Type Figure 13: Direct Connect Control Figure 14: Direct Connect Control
Power (Phase to Phase) Power (Phase to Neutral)
One 3-phase Wye Circuit Breaker with no Neutral Common Two 1-phase LN Circuit Breaker on L1-L2
L1L2L3 N L1L2L3
V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 ) V1 V2 V3 VN ( I1 ) ( I2 ) ( I3 )
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
- + - +
L1-N
CKT 1
L2-N
L1-L2-L3 CKT 2
CKT 1
• Phase to Phase only when voltage • Phase to Neutral only when voltage
L1
S1 S2
85 Vac < V < 277 Vac 85 Vac < V < 277 Vac
S1 S2
L1
S1 S2
L2 • See Table 2. • See Table 2.
S1 S2 L3
L2
L3
S1 S2 N Figure 15: Direct Connect Control Figure 16: Control Power Transformer
Power (DC Control Power) (CPT) Connection
N L1 L2 L3
- +
- +
NOTE: Refer to the PM5350PB/PM5350IB User Guide for a complete set of wiring and
phase configurations.
3
INPUT/OUTPUT COMMUNICATIONS CAPABILITIES
WARNING DANGER
UNINTENDED EQUIPMENT OPERATION HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not use this device for critical control or protection applications where human • Do not attempt to service the power meter. CT and PT or VT inputs may contain
or equipment safety relies on the operation of the control action. hazardous currents and voltages.
• Do not rely solely on device data to determine if your power system is functioning • Only authorized service personnel from the manufacturer should service the
correctly or meeting all applicable standards and compliances. power meter.
• Do not use device control for time-critical functions because delays can occur • Shield conductors may be energized if not properly connected.
between the time a control action is initiated and when that action is applied. • Shield wire should be installed per the device’s installation instructions and
• Do not use digital inputs for voltage sensing applications over 36 Vdc. grounded at one end only.
Failure to follow this instruction can result in death, serious injury, or Failure to follow these instructions will result in death or serious injury.
equipment damage.
Table 5: RS-485 Communications Distances
The PM5350PB/PM5350IB has four (4) digital inputs and two (2) digital mechanical
relay outputs. The digital inputs have two (2) control modes: Normal and Demand sync. Maximum Communication Distances - 1 to 32 Devices
Baud Rate
The digital outputs have three (3) control modes: External Control (default), Demand Feet Meters
sync and Alarm mode. When configured in Alarm mode, the meter can control the digital 9600 8,000 2,438
output in response to an alarm condition. 19200 6,000 1,829
Figure 17: I/O Connections 38400 2,500 762
NOTE: Distances listed should be used as a guide only and cannot be guaranteed for
Whetting voltage non-PowerLogic devices. Refer to the master device’s documentation for any
additional distance limitations.
Relay outputs
D1 D2 Digital inputs Daisy-chaining Devices to the Power Meter
(load control)
D0- D1+ + -/C S1 S2 S3 S4 The RS-485 communications port allows the power meter to be connected in a daisy
13 14 15 16 18 19 20 21 22 23 24 25 26 chain with up to 31, 2-wire devices. In this document, communications link refers to a
30 Vdc, 5A chain of devices that are connected by a communications cable.
250 Vac, 8A Cos Φ = 1 Figure 18: Daisy-chaining 2-wire Devices
250 Vac, 6A Cos Φ = 0.4
RS-485 Belden 9841 or equivalent MCT2W-RS485 terminator
(100 ohm, 1/4 Watt, 1% resistor)
Overcurrent on the last device of the daisy cha
1
protective device
(not supplied)
LOAD
~ (+)
LOAD 20 D1
Digital input wiring shown for
internal voltage source
19 (-) D0
1
18
The overcurrent protective device must be rated for the short-circuit current at the connection point.
Power Meter PM5350PB/PM5350IB or other PowerLogic 2-wire compatible devices
NOTE: Do not use the whetting voltage power supply as a power source for other
devices. • If the power meter is the last device on the daisy chain, terminate it with the
terminator provided.
• See Table 4 for the maximum daisy-chain communications distances for 2-wire
devices.
• The terminal’s voltage and current ratings are compliant with the requirements of the
EIA RS-485 communications standard.