Model: 1381 and 1381V

Description
Type 1381 and 1381V pressure switches are used for monitoring
pressure to sound an alarm, operate a warning light or cut off an
electrical supply as soon as the pressure rises to the set point. Each
unit contains one double pole switch (common, normally open
and normally closed connections) activated by a diaphragm.
‘Standard Pressure Switch Wiring Instructions’ data sheet supplied
with each unit.

Pressure Range
Pressure Range Hysteresis Typical

-1 to +1 bar 0.04 bar

0.2 to 4 bar 0.07 bar

0.5 to 11 bar 0.3 bar

0.7 to 14 bar 0.4 bar

2 to 28 bar 0.6 bar

2 to 42 bar 0.8 bar

Temperature
44 106
Temperature Range -10ºC to +85ºC
22
58
Approvals
x1.5
LPCB, CE marked to EN 60730-1 (low voltage directive) M20
19.5

Material Specification
Part Name Material

105
Type 1381 Factory set @ 0.8 Bar rising,
(Non Variable) Resets @ 0.4 Bar.
24
Type 1381V Factory set @ 5 Bar rising,
(Variable) Resets @ 0.4 Bar.

Accuracy ± 2% of range 23

Enclosure IP65 1/2" BSPP


78
Weight 0.9 Kg

Diaphragm Beryllium Copper

Seal Glass Filled PTFE

Base / Connection Brass

Housing Aluminium/Zinc diecast

Cover Glass filled nylon with nitrile seal

10A @ 250V AC
Contact Rating
1A @ 30V DC

Manufactured by Bailey & Mackey who holds the LPCB and CE certificates

DS: 2.02 Rapidrop Global Ltd


Issue D T: +44 (0) 1733 847 510 F: +44 (0) 1733 553 958
08/03/2022 e: rapidrop@rapidrop.com
© 2022 Rapidrop w: www.rapidrop.com Page 1 of 3

Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development
Data Sheet 2.02
Issue D CERT/LPCB/ ref. 085a/01

Pressure Switch
Model: 1381 and 1381V

Non-Variable Pressure Switch 1381

Set point adjustment


M3 Nylon Nut (5.5 Socket)

• Remove the four switch lid screws


• Remove the red electrical cover
• Tighten the nylon nut clockwise to reduce the pressure set point
• Loosen the nylon nut anticlockwise to increase the pressure set
point
• When the set point is achieved replace the red cover and re-fit
the lid
• Please write on the label the new set point and the re-set point

Clockwise
(-) Pressure

NC NC Anticlockwise
(+) Pressure

Set Point
COMMON NORMALLY CLOSED
NO NO
Pressure decreasing

NORMALLY OPEN
Pressure increasing

COMMON NORMALLY CLOSED

NORMALLY OPEN

GROUND

Manufactured by Bailey & Mackey who holds the LPCB and CE certificates

DS: 2.02 Rapidrop Global Ltd


Issue D T: +44 (0) 1733 847 510 F: +44 (0) 1733 553 958
08/03/2022 e: rapidrop@rapidrop.com
© 2022 Rapidrop w: www.rapidrop.com Page 2 of 3

Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development
Data Sheet 2.02
Issue D CERT/LPCB/ ref. 085a/01

Pressure Switch
Model: 1381 and 1381V

Variable Pressure Switch 1381V


Set point adjustment
M3 Nylon Nut (5.5 Socket)

• Remove the four switch lid screws


• Remove the red electrical cover
• Tighten the nylon nut clockwise to reduce the pressure set point
• Loosen the nylon nut anticlockwise to increase the pressure set
point

Clockwise
(-)Pressure

Anticlockwise
(+) Pressure

Reset point adjustment


NC NC
Set the set point as above and then set the reset point as follows:
Set Point
• Rotate the adjusting gear clockwise to reduce the pressure
differential
• Rotate the adjusting gear anticlockwise to increase the pressure
differential
• Always do one final check as sometimes the set point can move
Reset Point slightly when moving the wheel
• When the set point achieved replace the red cover and re-fit
the lid
NO NO
• Please write on the label the new set point and the re-set point
Pressure decreasing
Pressure increasing

Clockwise
(-) Pressure differential

COMMON NORMALLY CLOSED

NORMALLY OPEN

COMMON NORMALLY CLOSED Anticlockwise


(+) Pressure differential
NORMALLY OPEN

GROUND

Manufactured by Bailey & Mackey who holds the LPCB and CE certificates

DS: 2.02 Rapidrop Global Ltd


Issue D T: +44 (0) 1733 847 510 F: +44 (0) 1733 553 958
08/03/2022 e: rapidrop@rapidrop.com
© 2022 Rapidrop w: www.rapidrop.com Page 3 of 3

Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development

You might also like