02
Issue D CERT/LPCB/ ref. 085a/01
Pressure Switch
Model: 1381 and 1381V
Description
Type 1381 and 1381V pressure switches are used for monitoring
pressure to sound an alarm, operate a warning light or cut off an
electrical supply as soon as the pressure rises to the set point. Each
unit contains one double pole switch (common, normally open
and normally closed connections) activated by a diaphragm.
‘Standard Pressure Switch Wiring Instructions’ data sheet supplied
with each unit.
Pressure Range
Pressure Range Hysteresis Typical
Temperature
44 106
Temperature Range -10ºC to +85ºC
22
58
Approvals
x1.5
LPCB, CE marked to EN 60730-1 (low voltage directive) M20
19.5
Material Specification
Part Name Material
105
Type 1381 Factory set @ 0.8 Bar rising,
(Non Variable) Resets @ 0.4 Bar.
24
Type 1381V Factory set @ 5 Bar rising,
(Variable) Resets @ 0.4 Bar.
Accuracy ± 2% of range 23
10A @ 250V AC
Contact Rating
1A @ 30V DC
Manufactured by Bailey & Mackey who holds the LPCB and CE certificates
Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development
Data Sheet 2.02
Issue D CERT/LPCB/ ref. 085a/01
Pressure Switch
Model: 1381 and 1381V
Clockwise
(-) Pressure
NC NC Anticlockwise
(+) Pressure
Set Point
COMMON NORMALLY CLOSED
NO NO
Pressure decreasing
NORMALLY OPEN
Pressure increasing
NORMALLY OPEN
GROUND
Manufactured by Bailey & Mackey who holds the LPCB and CE certificates
Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development
Data Sheet 2.02
Issue D CERT/LPCB/ ref. 085a/01
Pressure Switch
Model: 1381 and 1381V
Clockwise
(-)Pressure
Anticlockwise
(+) Pressure
Clockwise
(-) Pressure differential
NORMALLY OPEN
GROUND
Manufactured by Bailey & Mackey who holds the LPCB and CE certificates
Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development