You are on page 1of 1

02/08/2007

FDVMI100
INPUT MODULE
- Installation instructions -

DESCRIPTION CONNECTIONS EXAMPLE


A connections example is following showed:
FDVMI100 is an input micro-module useful to interface external devices with a addressable analogic
detection line. It’s relevant characteristics are following described.
• The micro-module is addressable (from user) using FD P100 programmer tool. Input module line distingue detect the following states:
• With monitored input line, is possibile to interface ON/OFF signals • FAULT: cut or short circuit on input monitored line (end of line resistor Reol=27kΩ)
• The module is compatible exclusively with Teledata panels. • ALARM: using Rsw=10kΩ resistorin parallel connected to end of line resistor (Reol=27kΩ)
• An integrated insulator is provided for every module

TECHNICAL SPECIFICATION
Power supply.............................................................................................................15-40Vdc
Standby consuption ...................................................................................................0,15 mA-
Optical visualisation .................................................................................................green / yellow / red led
Led fixed on consuption ............................................................................................6 mA-
Addressing ................................................................................................................With FD P100
Operating temperature range ..................................................................................(-30 ÷ +70) °C
Operating humidity ...................................................................................................(5 ÷ 85) % .R.H.
Dimentions (HxPxL) ................................................................................................75 x 55 x 30 mm

CONNECTIONS
Loop+ Loop+ to next device

Connection Description
Loop - Loop – to next device
1 Loop + (input)
2 Loop + (output)
3 Loop - (input)
4 Loop – (output)
5 monitored on/off + input
6 monitored on/off - input
Rsw
7 -12 Not used

1 12

Reol

TELEDATA srl. - VIA Giulietti 8 - 20132 Milano - +39 02.27201352 -  +39 02.2593704 - e - mai l : te l e d ata@ te l e d ata- i . c o m