1. Push the button for at least 5 [sec], then I/P converter changes to configuration mode.
CONFIDENTIAL
Auto Calibration Procedure (SI-Part)
CONFIDENTIAL
Auto Calibration Procedure (SI-Part)
3. Press the ‘+’ button for at least 5 [sec] to start the initialization. SIPART will run the “Automatic Initi
alization Program” With 5 step.
CONFIDENTIAL
Auto Calibration Procedure (SI-Part)
4. When the display shows ‘Finish’, the Automatic Initialization Program” is done.
CONFIDENTIAL
Auto Calibration Procedure (SI-Part)
5. Do simulation with LDU. (* All the shutdown must be cancelled to do this simulation test)