Auto Calibration Procedure (SI-Part)

1. Push the button for at least 5 [sec], then I/P converter changes to configuration mode.

CONFIDENTIAL
Auto Calibration Procedure (SI-Part)

2. By keep clicking go to parameter 4 – ‘Initialization of SIPART’.

CONFIDENTIAL
Auto Calibration Procedure (SI-Part)

3. Press the ‘+’ button for at least 5 [sec] to start the initialization. SIPART will run the “Automatic Initi
alization Program” With 5 step.

CONFIDENTIAL
Auto Calibration Procedure (SI-Part)

4. When the display shows ‘Finish’, the Automatic Initialization Program” is done.

CONFIDENTIAL
Auto Calibration Procedure (SI-Part)

5. Do simulation with LDU. (* All the shutdown must be cancelled to do this simulation test)

1) Open “Scavenge air –EWG’ in LDU


2) Select the 1 ‘manual control mode’
3) Check the EWG control mode display
‘Manual’
4) Select the 2 ‘Activate manual
command’ and input ‘command value’
in the 3 .
5) Compare the manual set-point 3 and
actual command feedback 4

CONFIDENTIAL