LOAD SETTING
1. STVF Duplex
1) Load sensor installation
2 sensors 1 sensor
Normally, when we install Load sensor it is consist of 2pieces.
on on on off
A B
LS
BOARD
Cn1 Cn2 Cn1 Cn2
B` A`
Keep Jumper(JU1)
CC54
<Platform
position>
CN5
-1-
LOAD SETTING
1. STVF Duplex
2) MCU board setting
1. Put control panel TNP board’s SW1(AUTO/INS) on INS to make manual mode.
2. Door should be fully OPENED (Door open limit(DOL) Signal OFF)
3. Gate, Interlock SW should be turn OFF.
PARAMETER SETTING(MCU BOARD – H8 Connector) <H8 Connector>
Menu Description
Load sensor device selection (Use : "Enable")
20a LS Use * After set "Enable", Press reset button of MCU Board for setting the following
31a. General sub menu
31b. Field
Load set up (0%, 50%, zero point alignment)
Load Set : 0% (0% set up : at no load in car)
ESC UP DN ENT 20b Load Setting Load Set : 50% (50% set up: at 50% loads in car)
Load Align : (zero point alignment at no load)
SetEnd Data : (no use)
A19. Init TrvlLen Current load data display
A20. Load Sensor LS Data : %
20c Sensing Data percentage data (0% ~ 120%)
LS Data : A/D
ESC UP DN ENT Analog to digital decimal value data
-2-
LOAD SETTING
1. STVF Duplex
2) MCU board setting
Set the LS setting
MCU BOARD RESET
20a. LS Use LS USE : LS USE :
20b. Load setting no use Enable
Sensor’s suppression is normal if “LS Data: A/D” value is 9,000~10,000 when no load
This value can change pressed amount of sensor by inserting liners
F58 Error : disconnection with LS board.
F59 Error : abnormal state of LS board’s setting.
-3-
LOAD SETTING
1. STVF Duplex
2) MCU board setting
Setting No Load(0%)
Make car of no load. If there was a load, displace it and wait for 10 minutes.
ESC UP DN ENT
ESC UP DN ENT
-4-
LOAD SETTING
1. STVF Duplex
2) MCU board setting
Setting No Load(50%)
Load weight that is 50% of the car maximum load then wait for 10 minutes to make stable condition.
Load Set : 50 %
Can’t Settable Recheck the setting condition
ESC UP DN ENT
Load Set : 50 %
Yes Wait for 10 seconds
(Need for measuring load)
ESC UP DN ENT
-5-
LOAD SETTING
1. STVF Duplex
2) MCU board setting
Check setting status
After setting 50%, do not displace the weight and go to ‘20c Sensing Data’ menu.
If 50% data is correct, LS Data : % If it shows ‘0%’ when no load, every setting is completed.
1. displace the weight 0% Sensing Data may vary ±1~2% depending on the weight.
2. check if ‘LS Data : % is 0%. but it is normal.
ESC UP DN ENT
-6-
LOAD SETTING
1. STVF Duplex
3) Inverter board setting
Setting inverter menu
After all check the load data, please connect the HHT on Inverter board(HIVD board)
2. WBVF Duplex
1) Potential meter installation
Normally, when we install potential meter, it is consist of 2 pieces.
When installing the potential meter, insert the liners so that the sensor is pressed by 1~3mm.
A B
B` A`
liners
<Platform position>
2. WBVF Duplex
2) LoadCell board connection
SENSOR
LC 1
2 LC : Load cell
PM : Potential meter
PM 3
1
T-RES
2
3
Make sure that the both jumper pins are used to the PM side and T-RES side.
Connect the terminal of potential meter to LoadCell B’d.
Connect the CN5 connector of the Loadcell B’d to the CN_T21 or CN_T23 of the CTC-3 board.
Check the LED status.
Power Supply (PWR 24V : ON)
Potential Meter (PM : Blink)
<Potential meter> Can Communication (CAN : Blink)
-9-
LOAD SETTING
2. WBVF Duplex
3) LoadCell parameter
Auto_Drive 5 Auto_Drive 5
Door_Closed Door_Closed
01 INVERTER MENU 01 I/O SIGNAL
02 SYSTEM MENU 02 FAULT ANALYSIS
Auto_Drive 5 Auto_Drive 5
Door_Closed Door_Closed
03 CAR CAN DATA 15 EXT IO DATA
04 HALL CAN DATA 16 LOAD DATA
-10-
LOAD SETTING
2. WBVF Duplex
3) LoadCell parameter
How to check Load data & Load pulse
Check the CPM LS PORT 1, 2 Value. In no load state, adjust the liners so that the load-data value is between 3500~3800.
Check if the load Pulse value is between 100 ~ 200 in no-load state.
-11-
LOAD SETTING
2. WBVF Duplex
3) LoadCell parameter
How to setting LS DATA
-12-
LOAD SETTING
2. WBVF Duplex
3) LoadCell parameter
How to setting LS DATA
Middle floor
E-
Auto Ins LAMP S/W
STOP