1. Air enters a fan through a duct at a velocity of 6.3 m/s and an
inlet static pressure of 2.5 cm of water less than atmospheric. The air leaves the fan through a duct at a velocity of 11.25 m/s and a discharge static pressure of 7.62 cm of water above the atmospheric pressure. If the specific weight of the air is 1.20 kg/m3 and the fan delivers 9.45 m3/s, what is the fan efficiency when the power input to the fan is 13.75 kW at the coupling? 2. A fan described in a manufacturer’s table is rated to deliver 500m3/min at a static pressure (gage) of 254 cm of water when running at 250 rpm and requiring 3.6 kW. If the fan speed is changed to 305 rpm and air handled is at 65 0C instead of the standard 210C, find the capacity in m3/min, static pressure in cm of wg, and the power in kW.