ABLEREX
MSII 10KVA
PARALLEL SETTING
GUIDE
WITH MTBS

Page 1 of 6
Ablerex Electronics (S) Pte Ltd
No.23 New Industrial Road
#05-03 Solstice Business Center
Singapore 536209
Tel: +65 6282 6535 Fax: +65 6282 6343
Co. Reg. No.: 200203197Z

A: Parallel Communication Cable Connection

1) Connect the unit as per diagram above.


2) Connect the RJ-45 in ring configuration as below and ensure the cables are secured with
the parallel kit fixing plate.

Page 2 of 6
Ablerex Electronics (S) Pte Ltd
No.23 New Industrial Road
#05-03 Solstice Business Center
Singapore 536209
Tel: +65 6282 6535 Fax: +65 6282 6343
Co. Reg. No.: 200203197Z

3) Behind the MSII-RT 10KVA, ensure the micro switch is at [ON] position on both unit.

Page 3 of 6
Ablerex Electronics (S) Pte Ltd
No.23 New Industrial Road
#05-03 Solstice Business Center
Singapore 536209
Tel: +65 6282 6535 Fax: +65 6282 6343
Co. Reg. No.: 200203197Z

B: MSII-RT 10KVA UPS Setting


1) Turn on the AC input.
2) Turn on the Circuit Breaker at the back of MSII 10K

3) To enter Setting Mode, press the [ON] + [↓] Button at the same time for 3 second until
the unit giving out 2 beep sound.

Page 4 of 6
Ablerex Electronics (S) Pte Ltd
No.23 New Industrial Road
#05-03 Solstice Business Center
Singapore 536209
Tel: +65 6282 6535 Fax: +65 6282 6343
Co. Reg. No.: 200203197Z

4) Press [↓] until it shows as the picture below in RED CIRCLE.

5) Set [Id01] for the first unit of MSII 10KVA and [Id02] for the second MSII 10KVA.
Press [↑] to change the setting if required.

Page 5 of 6
Ablerex Electronics (S) Pte Ltd
No.23 New Industrial Road
#05-03 Solstice Business Center
Singapore 536209
Tel: +65 6282 6535 Fax: +65 6282 6343
Co. Reg. No.: 200203197Z

6) Press [↓] again to set the Parallel Function on to [P 02] on both unit.

Press [↑] to change the setting if required.

7) Press [↓] followed by [ ] button to save the changed setting.

* Any changed setting without press [ ] during save will resulted in unchanged setting
after unit power cycle.
8) Turn off and then turn on the AC input for both UPS to enable the new saved setting to
be applied.

Page 6 of 6