POWER TRANSFORMERS DATE: 08/07/19
VICEPRESIDENCY OF TECHNOLOGY
ELECTRIC SPECIFICATION OF
PAD-MOUNTED TRANFORMER
APPROVED BY
TAG No. DATE OBSERVATIONS GERENCIA INGENIERIA Y
PROYECTOS
319-03-511-02 29/02/24 TRANSFORMER 1000 KA EDL / FFR
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 2/10
POWER TRANSFORMERS DATE: 08/07/19
CONTENTS
100 GENERAL 3
200 COOLING 3
300 WINDINGS 3
700 NAMEPLATES 4
800 WIRING 4
900 ACCESSORIES 5
1100 TESTING 6
1200 OIL 6
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 3/10
POWER TRANSFORMERS DATE: 08/07/19
100. GENERAL
Three-phase LV power transformers for unit substations must be built for outdoor service, maximum size up to 3000 kVA
and meet ANSI/IEEE C57.12.26 and NEC standards.
200. COOLING
1. The insulating liquid may be silicon or mineral oil certified (NMX-J-123) to contain no detectable PCB´s.
(CONTAIN less than 2 p.p.pm.)and comply with the following; Non-toxic, Biodegradable.
2. Cooling radiator shall be welded to the tank
3. Transformers shall have OA/FA operation with provisions for future fans with three-phase 220 VAC motors.
300. WINDINGS
1. The transformer design shall be capable of frequency, winding average temperature rise
operating above rated voltage or below rated by resistance shall not exceed 55°C and
frequency in accordance with ANSI C57.12.00. hottest-spot winding temperature rise shall not
exceed 65°C, over ambient 40°C.
400. BUSHINGS,
1. Primary nozzles must have well or integral and secondary bushings shall be epoxy porcelain with sword terminal.
2. Bushings rating and location shall be specified in the CEMEX Data Sheet. Neutral bushings shall be provided.
3. Cable connectors shall be provided for all terminal bushings. Cable size shall be specified in the CEMEX Data Sheet.
700. NAMEPLATES
1. Transformers shall be furnished with a stainless 2. Nameplates shall contain all connection and
steel diagrammatic nameplate permanently rating information in accordance with ANSI
attached with non-corrosive hardware. C57.12.00
2. the interior of the cabinet’s door should carry a stainless steel plate.
900. ACCESSORIES
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 5/10
POWER TRANSFORMERS DATE: 08/07/19
1. The transformer shall be equipped with a complete set of accessories as indicated in ANSI C57.12. The following
standard accessories shall be supplied located according to ANSI standards.
Dial type gauges, valves and tap shall be located for Globe-type combination drain and The sampling
easy accessibility and maintenance. valve will be located so as to allow draining or
sampling from the bottom surface of the tank.
Wells for thermometer bulbs shall be outside the main
tank so as not to require removal for un-tanking. Globe type upper filter valve 25.5 mm diameter
Dial-type oil thermometer gauge. Lifting eyes for lifting core and coils assembly from
the tank.
Interlock for de-energized tap changer. Cover-mounted mechanical pressure relief device
Pressure relief auto-regenerative device. with automatic resealing/resetting operation and
mechanical signal to serve as a device operation
Overpressure valve with rotatory case. indicator.
In case it is necessary, conservative tank made of All gasket must have the characteristics of table 12
carbon steel with paint application at the exterior and according to NM-J-285-1996 or later.
interior
If necessary, conservative tank made of carbon steel
with a minimum thickness of 4.55mm and the front of
5.88 mm plus the application of paint on exterior and
interior
1110. TESTING
1. The transformer must receive all routine tests required by ANSI C57.12.00 and perform as specified in ANSI C57.12.90.
Additional tests will be indicated in the CEMEX Data Sheet.
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 6/10
POWER TRANSFORMERS DATE: 08/07/19
1200. OIL
1. The oil used in the transformers must have the following specifications:
DATASHEET
Load Center Power Transformers
Equipment Identification 95 KV
4. Quantity 1 piece
12. Secondary BIL
30 KV
5. Application RADIAL
Transformer 1000 kva for Process plant 13. Tap above rated voltage (quantity and %Vn)
+ 2 , 2.5%
Requirements
14. Taps below rated voltage (quantity and %Vn)
1. Transformer Type Pad-Mounted -2.5 , 2.5 %
ANSI segment
b. OA/FA KVA
b. LV
✘ At walls At cover
4. Frequency 60 Hz
ANSI segment
1. HV Bushings
b. Other
a. Connection to:
✘ Cooper Cable
7. Primary Voltage (HV) 13,800 VOLTS
Cooper Bus Bar
8. Primary Winding Connection
DELTA, with WINDINGS ALUMINUM b. Cable Size: 2/0 awg ,EPR,15kv,133%
c. Wired /Phases: 4/3 2. Spare Parts for start-up and two years operation
Yes ✘ No
Additional Accessories
2. Max. Temperature 45 °C
3. Terminal Chamber for LV Bushings
Yes ✘ No 3. Min. Temperature 04 °C
4. Relative Humidity 48 %