You are on page 1of 10

SPECIFICATION PAD-MOUNTED REVISION: 0

Page 1/10
POWER TRANSFORMERS DATE: 08/07/19

VICEPRESIDENCY OF TECHNOLOGY

ELECTRIC SPECIFICATION OF
PAD-MOUNTED TRANFORMER

APPROVED BY
TAG No. DATE OBSERVATIONS GERENCIA INGENIERIA Y
PROYECTOS
319-03-511-02 29/02/24 TRANSFORMER 1000 KA EDL / FFR
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 2/10
POWER TRANSFORMERS DATE: 08/07/19

THE CONTENT OF THIS SPECIFICATION IS CEMEX’S PROPERTY


INFORMATION CONTAINED HERE MUST NOT BE COPIED, REWRITTEN, OR REPRODUCED, PARTIALY OR FULLY,
WITHOUT THE PRIOR WRITTEN CONSENT OF CEMEX.

CONTENTS

SECTION DESCRIPTION PAGE

100 GENERAL 3

200 COOLING 3

300 WINDINGS 3

400 BUSHINGS, TERMINAL CHAMBER 4

500 TAP CHANGER 4

600 GROUNDING CONNECTIONS 4

700 NAMEPLATES 4

800 WIRING 4

900 ACCESSORIES 5

1000 EXTERIOR FINISH 5

1100 TESTING 6

1200 OIL 6
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 3/10
POWER TRANSFORMERS DATE: 08/07/19

100. GENERAL

Three-phase LV power transformers for unit substations must be built for outdoor service, maximum size up to 3000 kVA
and meet ANSI/IEEE C57.12.26 and NEC standards.

1.-) Dead front


2.-) Outdoor service, Nema 4
3.-) Connection Radial type system

200. COOLING

1. The insulating liquid may be silicon or mineral oil certified (NMX-J-123) to contain no detectable PCB´s.
(CONTAIN less than 2 p.p.pm.)and comply with the following; Non-toxic, Biodegradable.
2. Cooling radiator shall be welded to the tank
3. Transformers shall have OA/FA operation with provisions for future fans with three-phase 220 VAC motors.

300. WINDINGS

2. At full capacity and with rated voltage and


SPECIFICATION PAD-MOUNTED REVISION: 0
Page 4/10
POWER TRANSFORMERS DATE: 08/07/19

1. The transformer design shall be capable of frequency, winding average temperature rise
operating above rated voltage or below rated by resistance shall not exceed 55°C and
frequency in accordance with ANSI C57.12.00. hottest-spot winding temperature rise shall not
exceed 65°C, over ambient 40°C.

400. BUSHINGS,
1. Primary nozzles must have well or integral and secondary bushings shall be epoxy porcelain with sword terminal.
2. Bushings rating and location shall be specified in the CEMEX Data Sheet. Neutral bushings shall be provided.
3. Cable connectors shall be provided for all terminal bushings. Cable size shall be specified in the CEMEX Data Sheet.

4. For dimensions and bushings separations see NMX-J-285-1996 and later.


5. In transformer greater than 150 kva to supply a connection and type B connector for ground.
6. Bushings shall have an orange silicone (brand Silidriel) coating. This coating will be applied once the bushings are
installed in the transformer.

500. TAP CHANGER

600. GROUNDING PROVISIONS

1. All non-energized metallic transformer components shall be grounded.


2. The doors and the lid must be connected to Ground through a flexible conductor.

700. NAMEPLATES

1. Transformers shall be furnished with a stainless 2. Nameplates shall contain all connection and
steel diagrammatic nameplate permanently rating information in accordance with ANSI
attached with non-corrosive hardware. C57.12.00

Table 2: Nameplates characteristics

800. CONTROL CABINET AND WIRING

1. The cabinet door shall be padlockable.

2. the interior of the cabinet’s door should carry a stainless steel plate.

900. ACCESSORIES
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 5/10
POWER TRANSFORMERS DATE: 08/07/19

1. The transformer shall be equipped with a complete set of accessories as indicated in ANSI C57.12. The following
standard accessories shall be supplied located according to ANSI standards.

 Dial type gauges, valves and tap shall be located for  Globe-type combination drain and The sampling
easy accessibility and maintenance. valve will be located so as to allow draining or
sampling from the bottom surface of the tank.
 Wells for thermometer bulbs shall be outside the main
tank so as not to require removal for un-tanking.  Globe type upper filter valve 25.5 mm diameter

 Dial-type oil thermometer gauge.  Lifting eyes for lifting core and coils assembly from
the tank.
 Interlock for de-energized tap changer.  Cover-mounted mechanical pressure relief device
 Pressure relief auto-regenerative device. with automatic resealing/resetting operation and
mechanical signal to serve as a device operation
 Overpressure valve with rotatory case. indicator.
 In case it is necessary, conservative tank made of  All gasket must have the characteristics of table 12
carbon steel with paint application at the exterior and according to NM-J-285-1996 or later.
interior
 If necessary, conservative tank made of carbon steel
with a minimum thickness of 4.55mm and the front of
5.88 mm plus the application of paint on exterior and
interior

Table 3: Accessories to include for the transformer.

1000. EXTERIOR FINISH

1110. TESTING
1. The transformer must receive all routine tests required by ANSI C57.12.00 and perform as specified in ANSI C57.12.90.
Additional tests will be indicated in the CEMEX Data Sheet.
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 6/10
POWER TRANSFORMERS DATE: 08/07/19

 Resistance on Windings Test.


 Ratio Test on all tap connections.
 Polarity and Phase Relation Test
 No-Load Losses Test
 Exciting Current Test.
 Impedance and Load Loss Test
 Applied Potential Test.
 Induced Potential Test.
 Insulation Resistance in Windings Test
 Winding Power Factor Test.
 Capacitance and Power Factor at Capacitive Bushings Test
 Frequency Response Test
 Dispersion Reactance Test

1200. OIL

1. The oil used in the transformers must have the following specifications:

Table 4: Oil Specifications


SPECIFICATION PAD-MOUNTED REVISION: 0
Page 7/10
POWER TRANSFORMERS DATE: 08/07/19

DATASHEET
Load Center Power Transformers

Equipment Identification 95 KV

1. Equipment No. 319-03-511-02


10. Secondary Voltage (LV) 480/277 V
2. Plant TORREON
11. Secondary Winding Connection
3. Project No. C141500-22-C02 STAR, with WINDINGS ALUMINUM

4. Quantity 1 piece
12. Secondary BIL
30 KV
5. Application RADIAL

Transformer 1000 kva for Process plant 13. Tap above rated voltage (quantity and %Vn)
+ 2 , 2.5%

Requirements
14. Taps below rated voltage (quantity and %Vn)
1. Transformer Type Pad-Mounted -2.5 , 2.5 %

2. Cooling Class ONAN


15. Bushing Location

3. 3-ph power rating a. HV


a. OA 1000 KVA ✘ At walls At cover

ANSI segment
b. OA/FA KVA
b. LV
✘ At walls At cover
4. Frequency 60 Hz
ANSI segment

5. Type Enclosure 3R 16. Insulating Fluid System


✘ Mineral Oil Silicone
6. Impedance
a. ANSI Standard STD Provision for Bushing Connection LV and HV

1. HV Bushings
b. Other
a. Connection to:
✘ Cooper Cable
7. Primary Voltage (HV) 13,800 VOLTS
Cooper Bus Bar
8. Primary Winding Connection
DELTA, with WINDINGS ALUMINUM b. Cable Size: 2/0 awg ,EPR,15kv,133%

9. Primary BIL 2. LV Bushings


SPECIFICATION PAD-MOUNTED REVISION: 0
Page 8/10
POWER TRANSFORMERS DATE: 08/07/19

9. Oil temperature indicator


a. Connection to: ✘ Yes No
✘ Cooper Cable

Cooper Bus Bar Miscellaneous

1. Start-Up Technical Service


b. Cable Size: 4 C # 500 kcm / fhase + 2c #500
kcm neutral Yes ✘ No

c. Wired /Phases: 4/3 2. Spare Parts for start-up and two years operation
Yes ✘ No
Additional Accessories

1. Terminal Chamber for HV Bushings.


Yes ✘ No
Environment Data
2. Throat for HV Bushings.
Yes ✘ No 1. Altitude 1,200 msnm

2. Max. Temperature 45 °C
3. Terminal Chamber for LV Bushings
Yes ✘ No 3. Min. Temperature 04 °C

4. Relative Humidity 48 %

5. Seismic Zone zona A


4. Throat for LV Bushings
Yes ✘ No
6. City TORREON
5. Bus-duct type throat for LV Bushing
Factory Tests
Yes ✘ No
1. Routine Tests
6. Disconnector bushings AT ✘ Yes No
✘ Yes No
2. Witness Tests
7. Expulsion fuses Yes ✘ No
✘ Yes No
8. Oil level indicator 3. Special Tests
✘ Yes No Yes ✘ No
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 9/10
POWER TRANSFORMERS DATE: 08/07/19
SPECIFICATION PAD-MOUNTED REVISION: 0
Page 10/10
POWER TRANSFORMERS DATE: 08/07/19