Professional Documents
Culture Documents
transformer nameplate
information
Table of Contents:
1. Minimum nameplate requirements
2. Manufacturer’s information
3. Cooling class, number of phases, and operating frequency
4. Transformer voltage ratings
5. KVA or MVA ratings
6. Winding connection diagram
7. Transformer-phasor or vector diagram
8. Weights and oil capacity
9. Operating pressure range
10. Transformer impedance
11. Basic insulation level (BIL)
12. Nameplate layout
1. Minimum nameplate
requirements
There are hundreds of thousands of transformer nameplates installed out there
with differences in size and information displayed. However, the minimum
information to be shown on a transformer nameplate depends on the
transformer’s KVA rating as specified in the standards.
Name of manufacturer
Serial number
Month/year of manufacture
Cooling class
Where the class of transformer involves more than one rating, all
ratings are shown. Windings having different ratings have their
individual KVA ratings described. If the transformer has more than
one temperature rating, these ratings are shown on the nameplate.
Provisions for future cooling equipment are indicated.
Number of phases
Frequency
KVA or MVA rating
Voltage ratings. The voltage ratings of a transformer or
autotransformer windings are separated by a dash (-).
Tap voltages. The tap voltages of an individual winding are
separated by a slash (/).
Rated temperature rise, °C
Polarity (single-phase transformers)
Phasor or vector diagram (polyphase transformers)
Percent impedance. The percent impedance is specified between
each pair of windings with the voltage connection and the KVA base
stated. The percent impedance shall be tested.
Basic lightning impulse insulation levels (BIL). The BIL of each
winding and each bushing are specified.
Approximate mass of the core and coils, tank and fittings, insulating
oil, total weight, and heaviest piece.
Connection diagram
The connection diagram shows all winding terminations with a
schematic plan view showing all fixed accessories. The
schematic plan view generally shows the low-voltage side of the
transformer at the bottom . The location and polarity shall be shown
for all current transformers used for metering, relaying, or drop
compensation.
Installation and operating instructions references
The word ‘‘transformer’’ or ‘‘autotransformer’’
Suitability for step-up operation. Since the MVA rating is generally
specified at the output winding at the nominal output winding
voltage, the MVA rating for step-up operation will generally be
different than the MVA rating for step-down operation, unless
specified.
Maximum positive and negative operating pressures of the oil
preservation system, kPa or psi
Maximum negative pressure of the tank for vacuum filling
Liquid level below the top surface of the highest point of the highest
manhole flange at 25°C
Change in liquid level per 10°C change in liquid level
Oil volume of each transformer compartment
Type of insulating liquid. The nameplate shall also have the
following note: ‘‘Contains no detectable level of PCB (less than 2
PPM) at the time of manufacture.’’
Conductor material of each winding
Figure
1 – Part of a transformer’s nameplate showing the voltage ratings, MVA ratings,
percent impedances, connection diagram, physical layout, vector diagram, tap
connections, CT connections, and BIL ratings
2. Manufacturer’s information
The manufacturer’s name usually appears prominently at the top of the
nameplate. Just below the manufacturer’s name is a unique serial number or
shop order number to identify the particular unit so its manufacturing and
design records can be traced.
4. Voltage ratings
The voltage rating of the transformer is specified in terms of both the lineto-line
system voltages and the winding voltages. For example, a 230 kV Grd.Y to 69
kV Grd.Y transformer with a 12.47 kV tertiary would have the following voltage
rating on its nameplate:
The hyphens separate the voltage ratings of one winding from the voltage
ratings of the other windings. In this illustration, 230000 GR.Y / 132800 is the
rating of the high-voltage winding, 69000 GR.Y / 39840 is the rating of the low-
voltage winding, and 12470 is the rating of the tertiary winding. The voltage
ratings are always given in volts.
When a slash is shown in the voltage rating of a winding, this indicates that the
winding is Y-connected with the phase-to-phase system voltage appearing first
followed by the slash and then the winding voltage. The winding voltage is the
phase-to-neutral voltage of the system. If a designator GR.Y, GRD.Y,
or Grd.Y appears, this indicates that the neutral end of the winding is intended
to be grounded, which probably means that there is reduced insulation near the
neutral end of the winding. In this case, operating the winding ungrounded may
not be safe.
The example 230000 GR.Y / 132800-69000 GR.Y / 39840-12470 designates
the 12,470 V tertiary winding by a single number without a slash appearing
because the winding ratings and the line-to-line voltage of the system are the
same. In other words, the windings are connected phase-to-phase in a ∆.
Therefore, these transformers were built to the ‘‘standard’’ KVA ratings for
55°C temperature rise but could be operated at higher KVA ratings at 65°C
temperature rise, so both sets of ratings were shown. Today, most
transformer nameplates omit the 55°C ratings entirely and are built for standard
KVA ratings at 65°C temperature rise.
Certain high-performance insulating materials such as Nomex and silicone
fluids allow operation at 75°C rise or even higher temperatures. The nameplate
ratings would reflect the KVA ratings at the higher temperature rise.
For two-winding transformers, there is usually only one set of KVA or MVA
values shown, because it is understood that the primary and secondary
windings must have the same KVA capabilities. This is not true for three-
winding transformers, however, since the tertiary is often not designed to the
same KVA capabilities as the primary and secondary windings.
The connection diagram usually also gives the general physical layout of the
transformer, showing the placement of the bushings and the locations of
current transformers (CTs) and a schematic representation of the load tap
changing equipment, including the preventative autotransformer, moving
contacts, arcing contacts, transfer switch, and reversing switch.
The nameplate can also contain a layout sketch showing the physical
locations of the bushings, the load tap changing compartment and the
operating handle for the tap changer at deenergized conditions. The load tap
changer is represented schematically in the connection diagram.
Note the terminals labeled P1, P2, and P3. These terminals correspond to the
connections to the preventative autotransformer. The two series arcing contacts
per phase that are in series with the movable contacts are shown as well.
The vector diagram on the nameplate shown in Figure 5 shows the standard
phase angle displacement of 0° for a Y-Y connected transformer.
Figure 5 – Standard phase angle
displacement of 0° for a Y-Y connected transformer as shown in Figure 4
There is also information showing the internal oil level at 25°C that is used to
properly fill the transformer, plus an indication of the change in oil level per
change in temperature. Figure 6 shows the manner in which this information is
typically shown on actual nameplates.
Figure 6 – Part of a transformer’s nameplate showing weights, oil capacities, oil
level, and operating pressure range
Example #1
A transformer is to be loaded onto a rail car after the oil is drained from
the main tank and the LTC compartment. A 150 T crane is available. Using
the information in Figure 6 above, is the crane’s capacity adequate?
The untanking weight of the unit (core and coils) is 118,000 lb and the weight of
the tank and fittings is 88,000 lb. Thus, the net weight of the transformer without
oil is 118,000 lb + 88,000 lb = 206,000 lb = 103 T. The capacity of the crane is
adequate to lift the transformer without oil. Note that when the transformer is
filled with oil, the total weight is 306,200 lb = 153.1 T, which exceeds the
capacity of the crane.
Example #2
The oil level of a particular transformer is shown in Figure 6. The
transformer is being filled with oil at a substation at an ambient
temperature of 30°C (86°F). Where should the oil level be after when the
filling is complete?
According to Figure 6, the oil level at 25°C is 12.6 in. below the top of the
manhole. The change in oil level is 1.17 in. per 10°C change in oil temperature.
Since the ambient temperature is 5°C the reference temperature, the change in
oil level is one-half of 1.17 in., or 0.585 in. above the reference point of 12.6
in.
Therefore, the proper oil level is 12.6 in − 0.585 in. = 12.015 in. below the top
of the manhole.
The nominal atmospheric pressure is 14.7 psi at sea level. Thus, when the
transformer contains a perfect vacuum, the negative pressure on the tank will
be approximately 15 psi at sea level, and slightly less at higher elevations.
10. Impedance
The transformer impedance, sometimes referred to as ‘‘impedance volts’’ on
the nameplate, is specified for each of pair of windings as a percent value on a
specific KVA base. For two-winding transformers, only one value of impedance
is given, corresponding to the high-to-low voltage series impedance at a KVA
base that usually corresponds to the KVA rating of the primary and secondary
windings.
Therefore, the percent impedances are usually stamped on the nameplate just
before the transformer is shipped from the factory.