Professional Documents
Culture Documents
LP superheater
Auxiliary boiler
HAD10
HAD50
LP evaporator reheater process steam GHC
HAD80
LP LAA
LBG M MBL70
MAW
IP superheater
Deionat
tank
IP evaporator
IP LP bypass station
HP bypass station
LBG
M
HP superheater IP bypass station
LBG
HP economizer
M
IP economizer
M
M
LBG
M
LDK
level to be
controlled
Condenser Level Control Slow process
GHC
FL calculated limit
M
CL CL CL
setpoint change
target value
reached
required values
Condensate Preheater Inlet Temperature Control Slow process
adjustable condensate
recirculation via
preheater inlet
additional pumps
temperature setpoint as
cold bypass function of sulfur content
at fuel (natural gas)
recirculation via
feedwater pumps
temperature to
be controlled
lp steam pressure
Step 03 > 4,8 bar Step 04 > 5,8 bar Step 05 > 6,8 bar
ip boiler drum
overflow control valve
IP Drum level Control fast process
drum filling to
overflow setpoint start up level
drum level drum wall
temperature
level setpoint
ip feedwater flow
IP Drum level Control during cold start of CCPP fast process
Start with screen shot : 20110111_104829_CJA25_bef_SGC_HAD80
SGC manual related stop of CJA sequence – reset of SGC’s required
overflow first evaporation – drum wall
setpoint drum wall temperature
temperature >105°C
interstage
temperature to
desuperheater is be controlled
supporting the final
desuperheater
(influence to
efficiency and ASME)
final desuperheater for max.
hp steam temperature control
upstream steam turbine
interstage
desuperheater for
max. hp steam
superheater outlet
temperature control
HP Steam Temperature Control upstream Steam Turbine fast process
- LAE11 – increase of heat transfer due to high dT but exergy losses for hp evaporator
- LAE20 – risk of water droplets upstream of steam turbine (ASME; additional drains required)
HP Steam Temperature Control upstream Steam Turbine fast process
Start with screen shot : 20110727_113024_350MW_KEPRI
Setpoint of LBA10DT002 / 216016 change from 566°C to 530°
fast process
delayed setpoint
decrease (setpoint steam temperatures
change) downstream LAE20
opening of final
HP Evaporator Enthalpy Control slow process
superheated to
be controlled
enthalpy set point
feedwater pump
speed control
HP Evaporator Enthalpy Control slow process