SEC Command Format

^TnnnXXXX,XXXX,XXXX,,<CRC><cr>
Character Description Remark
^ Start bit
T Type P: PC Query command, S: Set command, D: Device Response
nnn Data length Include CRC and ending character, except"^Tnnn"
If the data is reserved, they will be filled nothing, so you
XXXXX Data
would see double "," connected.
Separate each data, please use "," to recognize the length of
, Seperator
data. If double "," continuing, that means this data is reserved.
Two byte of CRC result, the first byte is high 8 bits, second byte is
<CRC>
low 8 bits.

Query commands
^P005PI<CRC><cr>: Query protocol ID
Response: ^D00518<CRC><cr>

^P004T<CRC><cr>: Query current time


Response: ^D017YYYYMMDDHHFFSS<CRC><cr>
Data Description Remark
YYYY Year Y: 0~9
MM Month M: 0~9
DD Day D: 0~9
HH Hour H: 0~9
FF Minute F: 0~9
SS Second S: 0~9
For example:
^D01720160214201314 means the time of 2016-02-14, 20: 13: 14

^P005ET<CRC><cr>: Query total generated energy


查询总发电量
Response: ^D011NNNNNNNN<CRC><cr>
Data Description Remark
NNNNNNNN Generated energy N: 0~9, unit: KWh
^P009EYyyyy<CRC><cr>: Query generated energy of year
查询年发电量
Response: ^D011NNNNNNNN<CRC><cr>
Data Description Remark
yyyy Year y: 0~9
NNNNNNNN Generated energy N: 0~9, unit: KWh
^P011EMyyyymm<cr>: Query generated energy of month
查询月发电量
Response: ^D011NNNNNNNN<CRC><cr>
Data Description Remark
yyyy Year y: 0~9
mm Month m: 0~9
NNNNNNNN Generated energy N: 0~9, unit: KWh
^P013EDyyyymmdd<cr>: Query generated energy of day
查询天发电量
Response: ^D011NNNNNN<CRC><cr>
Data Description Remark
yyyy Year y: 0~9
mm Month m: 0~9
dd Day d: 0~9
NNNNNNNN Generated energy N: 0~9, unit: Wh

^P005ID<CRC><cr>: Query series number


Response: ^D025LLXXXXXXXXXXXXXXXXXXXX<CRC><cr>
X: 0~9, 20 unit X totally. LL: the available number of X.
Example: ^D0251401234567890123456789<CRC><cr>, it meas ID is 01234567890123.

^P006VFW<CRC><cr>: Query CPU version


Response: ^D020aaaaa,bbbbb,ccccc<CRC><cr>
Data Description Remark
aaaaa Main CPU version
bbbbb Slave 1 CPU version
ccccc Slave 2 CPU version

^P007PIRI<CRC><cr>: Query rated information


Response: ^D085AAAA,BBB,CCCC,DDD,EEE,FFFF,GGGG,HHH,III,JJJ,KKK,LLL,MMM,N,OO,PPP,Q,R,S,T,U,V,W,Z,a<CRC><cr>
Data Description Remark
AAAA AC input rating voltage A: 0~9, unit: 0.1V
BBB AC input rating current B: 0~9, unit: 0.1A
CCCC AC output rating voltage C: 0~9, unit: 0.1V
DDD AC output rating frequency D: 0~9, unit: 0.1Hz
EEE AC output rating current E: 0~9, unit: 0.1A
FFFF AC output rating apparent power F: 0~9, unit: VA
GGGG AC output rating active power G: 0~9, unit: W
HHH Battery rating voltage H: 0~9, unit: 0.1V
III Battery re-charge voltage I: 0~9, unit: 0.1V
JJJ Battery re-discharge voltage J: 0~9, unit: 0.1V
KKK Battery under voltage K: 0~9, unit: 0.1V
LLL Battery bulk voltage L: 0~9, unit: 0.1V
MMM Battery float voltage M: 0~9, unit: 0.1V
N Battery type N: 0: AGM, 1: Flooded, 2: User
OO Max AC charging current O: 0~9, unit: A
PPP Max charging current P: 0~9, unit: A
Q Input voltage range 0: Appliance, 1: UPS
R Output source priority 0: Solar-Utility-Battery, 1: Solar-Battery-Utility
S Charger source priority 0: Solar first, 1: Solar and Utility, 2: Only solar
T Parallel max num T: 0~9
U Machine type 0: Off-grid Tie, 1: Grid-Tie
V Topology 0: transformerless, 1: transformer
0: Single module, 1: parallel output, 2: Phase 1 of three phase
W Output model setting output,
3: Phase 2 of three phase output, 4: Phase 3 of three phase
Z Solar power priority 0: Battery-Load-Utility, 1: Load-Battery-Utility
a MPPT string a: 0~9

^P005GS<CRC><cr>: Query general status


Response: ^D106AAAA,BBB,CCCC,DDD,EEEE,FFFF,GGG,HHH,III,JJJ,KKK,LLL,
MMM,NNN,OOO,PPP,QQQQ,RRRR,SSSS,TTTT,U,V,W,X,Y,Z,a,b<CRC><cr>
Data Description Remark
AAAA Grid voltage A: 0~9, unit: 0.1V
BBB Grid frequency B: 0~9, unit: 0.1Hz
CCCC AC output voltage C: 0~9, unit: 0.1V
DDD AC output frequency D: 0~9, unit: 0.1Hz
EEEE AC output apparent power E: 0~9, unit: VA
FFFF AC output active power F: 0~9, unit: W
GGG Output load percent G: 0~9, unit: %
HHH Battery voltage H: 0~9, unit: 0.1V
III Battery voltage from SCC I: 0~9, unit: 0.1V
JJJ Battery voltage from SCC2 J: 0~9, unit: 0.1V
KKK Battery discharge current K: 0~9, unit: A
LLL Battery charging current L: 0~9, unit: A
MMM Battery capacity M: 0~9, unit: %
NNN Inverter heat sink temperature N: 0~9, unit: oC
OOO MPPT1 charger temperature O: 0~9, unit: oC
PPP MPPT2 charger temperature P: 0~9, unit: oC
QQQQ PV1 Input power Q: 0~9, unit: W
RRRR PV2 Input power R: 0~9, unit: W
SSSS PV1 Input voltage S: 0~9, unit: 0.1V
TTTT PV2 Input voltage S: 0~9, unit: 0.1V
U Setting value configuration state 0: Nothing changed, 1: Something changed
V MPPT1 charger status 0: abnormal, 1: normal but not charged, 2: charging
W MPPT2 charger status 0: abnormal, 1: normal but not charged, 2: charging
X Load connection 0: disconnect, 1: connect
Y Battery power direction 0: donothing, 1: charge, 2: discharge
Z DC/AC power direction 0: donothing, 1: AC-DC, 2: DC-AC
a Line power direction 0: donothing, 1: input, 2: output
b Local parallel ID a: 0~(parallel number - 1)

^P006MOD<CRC><cr>: Query working mode


Response: ^D005XX<CRC><cr>
Data Description Remark
0 Power on mode
1 Standby mode
2 Bypass mode
XX
3 Battery mode
4 Fault mode
5 Hybrid mode(Line mode, Grid mode)

^P005FWS<CRC><cr>: Query fault and warning status


^D034AA,B,C,D,E,F,G,H,I,J,K,L,M,N,O,P,Q<CRC><cr>
Data Description Remark
AA Fault code
B Line fail
C Output circuit short
D Inverter over temperature
E Fan lock
F Battery voltage high
G Battery low
H Battery under
I Over load
J Eeprom fail
K Power limit
L PV1 voltage high
M PV2 voltage high
N MPPT1 overload warning
O MPPT2 overload warning
P Battery too low to charge for SCC1
Q Battery too low to charge for SCC2
Fault code list
1 Fan is locked
2 Over temperature
3 Battery voltage is too high
4 Battery voltage is too low
5 Output short circuited or Over temperature
6 Output voltage is too high
7 Over load time out
8 Bus voltage is too high
9 Bus soft start failed
11 Main relay failed
51 Over current inverter
52 Bus soft start failed
53 Inverter soft start failed
54 Self-test failed
55 Over DC voltage on output of inverter
56 Battery connection is open
57 Current sensor failed
58 Output voltage is too low
60 Inverter negative power
71 Parallel version different
72 Output circuit failed
80 CAN communication failed
81 Parallel host line lost
82 Parallel synchronized signal lost
83 Parallel battery voltage detect different
84 Parallel Line voltage or frequency detect different
85 Parallel Line input current unbalanced
86 Parallel output setting different

^P007FLAG<CRC><cr>: Query enable/disable flag status


Response: ^D020A,B,C,D,E,F,G,H,I<CRC><cr>
Data Description Remark
A Enable/disable silence buzzer or open buzzer A: 0/1, 0: disable, 1: enable
B Enable/Disable overload bypass function B: 0/1, 0: disable, 1: enable
Enable/Disable LCD display escape to default page after 1min
C C: 0/1, 0: disable, 1: enable
timeout
D Enable/Disable overload restart D: 0/1, 0: disable, 1: enable
E Enable/Disable over temperature restart E: 0/1, 0: disable, 1: enable
F Enable/Disable backlight on F: 0/1, 0: disable, 1: enable
G Enable/Disable alarm on when primary source interrupt G: 0/1, 0: disable, 1: enable
H Enable/Disable fault code record H: 0/1, 0: disable, 1: enable
I Reserved

^P005DI<CRC><cr>: Query default value of changeable parameter


Response: ^D068AAAA,BBB,C,DDD,EEE,FFF,GGG,HHH,III,JJ,K,L,M,N,O,P,S,T,U,V,W,X,Y,Z<CRC><cr>
Data Description Remark
AAAA AC output voltage A: 0~9, unit: 0.1V
BBB AC output frequency B: 0~9, unit: 0.1Hz
C AC input voltage range 0: Appliance, 1: UPS
DDD Battery Under voltage D: 0~9, unit: 0.1V
EEE Charging float voltage E: 0~9, unit: 0.1V
FFF Charging bulk voltage F: 0~9, unit: 0.1V
GGG Battery default re-charge voltage G: 0~9, unit: 0.1V
HHH Battery re-discharge voltage H: 0~9, unit: 0.1V
III Max charging current I: 0~9, unit: A
JJ Max AC charging current J: 0~9, unit: A
K Battery type N: 0: AGM, 1: Flooded, 2: User
L Output source priority 0: Solar-Utility-Battery, 1: Solar-Battery-Utility
M Charger source priority 0: Solar first, 1: Solar and Utility, 2: Only solar
N Solar power priority 0: Battery-Load-Utility, 1: Load-Battery-Utility
O Machine type 0: Off-grid Tie, 1: Grid-Tie
0: Single module, 1: parallel output, 2: Phase 1 of three phase
P Output model setting output,
3: Phase 2 of three phase output, 4: Phase 3 of three phase
S Enable/disable silence buzzer or open buzzer 0: disable, 1: enable
T Enable/Disable overload restart 0: disable, 1: enable
U Enable/Disable over temperature restart 0: disable, 1: enable
V Enable/Disable LCD backlight on 0: disable, 1: enable
W Enable/Disable alarm on when primary source interrupt 0: disable, 1: enable
X Enable/Disable fault code record 0: disable, 1: enable
Y Enable/Disable overload bypass 0: disable, 1: enable
Enable/Disable LCD display escape to default page after 1min
Z 0: disable, 1: enable
timeout

^P009MCHGCR<CRC><cr>: Query Max. charging current selectable value


Response: ^D030AAA,BBB,CCC,DDD,EEE,FFF,GGG<CRC><cr>
Data Description Remark
AAA Max. charging current selectable value A: 0~9, unit: A
BBB Max. charging current selectable value B: 0~9, unit: A
CCC Max. charging current selectable value C: 0~9, unit: A
DDD Max. charging current selectable value D: 0~9, unit: A
EEE Max. charging current selectable value E: 0~9, unit: A
FFF Max. charging current selectable value F: 0~9, unit: A
GGG Max. charging current selectable value G: 0~9, unit: A

^P010MUCHGCR<CRC><cr>: Query Max. AC charging current selectable value


Response: ^D030AAA,BBB,CCC,DDD,EEE,FFF,GGG<CRC><cr>
Data Description Remark
AAA Max. charging current selectable value A: 0~9, unit: A
BBB Max. charging current selectable value B: 0~9, unit: A
CCC Max. charging current selectable value C: 0~9, unit: A
DDD Max. charging current selectable value D: 0~9, unit: A
EEE Max. charging current selectable value E: 0~9, unit: A
FFF Max. charging current selectable value F: 0~9, unit: A
GGG Max. charging current selectable value G: 0~9, unit: A

^P007PRIn<CRC><cr>: Query different rated information of parallel system


Response: ^D039A,BB,CCCCCCCCCCCCCCCCCCCC,D,EEE,FF,G<CRC><cr>
Data Description Remark
n Parallel system ID n: 0~(Parallel number - 1)
A Parallel ID connection status 0: Not existent, 1: existent
BB Serial Number valid length B: 0~9
CCCCCCCCC
CCCCCCCCC Serial Number C: 0~9
CC
D Charging source priority 0: Solar first, 1: Solar and Utility, 2: Only solar
EEE Max. charging current E: 0~9, unit: A
FF Max. AC charging current F: 0~9, unit: A
0: Single module, 1: parallel output, 2: Phase 1 of three phase
G Output model setting output,
3: Phase 2 of three phase output, 4: Phase 3 of three phase

^P007PGSn<CRC><cr>: Query general status of parallel system


Response: ^D113A,B,CC,DDDD,EEE,FFFF,GGG,HHHH,IIII,JJJJJ,KKKKK,LLL,
MMM,NNN,OOO,PPP,QQQ,MMM,RRRR,SSSS,TTTT,UUUU,V,W,X,Y,Z,a,bbb<CRC><cr>
Data Description Remark
n Parallel system ID n: 0~(Parallel number - 1)
A Parallel ID connection status 0: Not existent, 1: existent
B Work mode
CC Fault code
DDDD Grid voltage D: 0~9, unit: 0.1V
EEE Grid frequency E: 0~9, unit: 0.1Hz
FFFF AC output voltage F: 0~9, unit: 0.1V
GGG AC output frequency G: 0~9, unit: 0.1Hz
HHHH AC output apparent power H: 0~9, unit: VA
IIII AC output active power I: 0~9, unit: W
JJJJJ Total AC output apparent power J: 0~9, unit: VA
KKKKK Total AC output active power K: 0~9, unit: W
LLL Output load percent L: 0~9, unit: %
MMM Total output load percent M: 0~9, unit: %
NNN Battery voltage N: 0~9, unit: 0.1V
OOO Battery discharge current O: 0~9, unit: A
PPP Battery charging current P: 0~9, unit: A
QQQ Total battery charging current Q: 0~9, unit: A
MMM Battery capacity M: 0~9, unit: %
RRRR PV1 Input power R: 0~9, unit: W
SSSS PV2 Input power S: 0~9, unit: W
TTTT PV1 Input voltage T: 0~9, unit: 0.1V
UUUU PV2 Input voltage U: 0~9, unit: 0.1V
V MPPT1 charger status 0: abnormal, 1: normal but not charged, 2: charging
W MPPT2 charger status 0: abnormal, 1: normal but not charged, 2: charging
X Load connection 0: disconnect, 1: connect
Y Battery power direction 0: donothing, 1: charge, 2: discharge
Z DC/AC power direction 0: donothing, 1: AC-DC, 2: DC-AC
a Line power direction 0: donothing, 1: input, 2: output
bbb Max. Temperature b:0~9, unit: oC

^P005ACCT<CRC><cr>: Query AC charge time bucket


查询允许AC充电时间段
Response: ^D012AAAA,BBBB<CRC><cr>
Data Description Remark
AAAA Start time for enable AC charger working AAAA: HH:MM(hour : minute)
BBBB Ending time for enable AC charger working BBBB: HH:MM(hour : minute)

^P005ACLT<cr>: Query AC supply load time bucket


查询允许AC带载时间段
Response: ^D012AAAA,BBBB<CRC><cr>
Data Description Remark
AAAA Start time for enable AC supply the load AAAA: HH:MM(hour : minute)
BBBB Ending time for enable AC supply the load BBBB: HH:MM(hour : minute)

Set commands
^S007LONn<CRC><cr>: Set enable/disable machine supply power to the loads
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
n Enable/disable 0: disable, 1: enable
^1 Accept command
^0 Refuse command

^S006Pmn<CRC><cr>: Set enable/disable status


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m enable/disable E: enable, D: disable
A Silence buzzer or open buzzer
B Overload bypass function
C LCD display escape to default page after 1min timeout
D Overload restart
n E Over temperature restart
F Backlight on
G Alarm on when primary source interrupt
H Fault code record
I Machine type, enable: Grid-Tie, disable: Off-Grid Tie
^1 Accept command
^0 Refuse command

^S005PF<CRC><cr>: Set changeable parameter restore to default value


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
^1 Accept command
^0 Refuse command

^S013MCHGCm,nnn<CRC><cr>: Set battery maximum charge current


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Parallel machine ID m: 0~Parallel number, if single model, it should be 0
n: 0~9, unit: A, please check setable value by
nnn Battery maximum charge current
"^P009MCHGCR<CRC><cr>"
^1 Accept command
^0 Refuse command
^S014MUCHGCm,nnn<CRC><cr>: Set battery maximum AC charge current
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Parallel machine ID m: 0~Parallel number, if single model, it should be 0
n: 0~9, unit: A, please check setable value by
nnn Battery maximum charge current
"^P010MUCHGCR<CRC><cr>"
^1 Accept command
^0 Refuse command

^S006F50<CRC><cr>: Set AC output frequency to be 50Hz


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
^1 Accept command
^0 Refuse command

^S006F60<CRC><cr>: Set AC output frequency to be 60Hz


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
^1 Accept command
^0 Refuse command

^S015MCHGVmmm,nnn<CRC><cr>: Set battery maximum charge voltage


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
mmm Battery constant charge voltage(C.V.) mmm: 480~584, unit: 0.1V
nnn Battery float charge voltage nnn: 480~584, unit: 0.1V
^1 Accept command
^0 Refuse command

^S008Vnnnn<CRC><cr>: Set AC output rated voltage


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
nnnn voltage unit: 0.1V, nnnn: 2020,2080, 2200, 2300, 2400
^1 Accept command
^0 Refuse command

^S007POPm<CRC><cr>: Set output souce priority


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Output source priority 0: Solar-Utility-Battery, 1: Solar-Battery-Utility
^1 Accept command
^0 Refuse command

^S014BUCDmmm,nnn<cr>: Battery re-charged and re-discharged voltage when utility is available


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
mmm Battery re-charged voltage when utility is available m: 0~9, unit: 0.1V
12V unit: 11V/11.3V/11.5V/11.8V/12V/12.3V/12.5V/12.8V
Selectable
24V unit: 22V/22.5V/23V/23.5V/24V/24.5V/25V/25.5V
value
48V unit: 44V/45V/46V/47V/48V/49V/50V/51V
nnn Battery re-discharged voltage when utility is available n: 0~9, unit: 0.1V
12V unit: 00.0V/12V/12.3V/12.5V/12.8V/13V/13.3V/13.5V/13.8V/14V/14.3V/14.5
Selectable
24V unit: 00.0V/24V/24.5V/25V/25.5V/26V/26.5V/27V/27.5V/28V/28.5V/29V
value
48V unit: 00.0V/48V/49V/50V/51V/52V/53V/54V/55V/56V/57V/58V
^1 Accept command
^0 Refuse command

^S009PCPm,n<CRC><cr>: Set charging source priority


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Parallel machine ID m: 0~Parallel number, if single model, it should be 0
n Charging source priority 0: Solar first, 1: Solar and Utility, 2: Only solar
^1 Accept command
^0 Refuse command

^S007PSPm<CRC><cr>: Set solar power priority


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Solar power priority 0: Battery-Load-Utility, 1: Load-Battery-Utility
^1 Accept command
^0 Refuse command
^S007PGRm<CRC><cr>: Set AC input voltage range
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m AC input voltage range 0: Appliance, 1: UPS
^1 Accept command
^0 Refuse command

^S007PBTm<CRC><cr>: Set battery type


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Battery type N: 0: AGM, 1: Flooded, 2: User
^1 Accept command
^0 Refuse command

^S010POPMm,n<CRC><cr>: Set output model


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
m Parallel machine ID m: 0~Parallel number, if single model, it should be 0
0: Single module, 1: parallel output, 2: Phase 1 of three phase
n Output model output,
3: Phase 2 of three phase output, 4: Phase 3 of three phase
^1 Accept command
^0 Refuse command

^S010PSDVmmm<CRC><cr>: Set battery cut-off voltage


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
mmm battery cut-off voltage mmm:400~480, the unit is 0.1V
^1 Accept command
^0 Refuse command

^S027IDmmnnnnnnnnnnnnnnnnnnnn<CRC><cr>: Set solar configuration


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
mm valid serial number length mm: 01~20
n Serial number n: 0~9
^1 Accept command
^0 Refuse command

^S006CLE<cr>: Clear the all the data of generated energy


清除所有发电量
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
^1 Accept command
^0 Refuse command

^S018DATyymmddhhffss<cr>: Set date time


Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
yy Year Y: 0~9
mm Month M: 0~9
dd Day D: 0~9
hh Hour H: 0~9
ff Minute F: 0~9
ss Second S: 0~9
^1 Accept command
^0 Refuse command
^S014ACCTaaaa,bbbb<cr>: Set AC charge time bucket
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
aaaa Start time for enable AC charger working aaaa: HH:MM(hour : minute)
bbbb Ending time for enable AC charger working bbbb: HH:MM(hour : minute)
^1 Accept command
^0 Refuse command
^S014ACLTaaaa,bbbb<cr>: Set AC supply load time bucket
Response: ^1<CRC><cr> or ^0<CRC><cr>
Data Description Remark
aaaa Start time for enable AC supply the load aaaa: HH:MM(hour : minute)
bbbb Ending time for enable AC supply the load bbbb: HH:MM(hour : minute)
^1 Accept command
^0 Refuse command
CRC calculation

CRC source code.txt