You are on page 1of 6

Wavelet Based Energy Function for

Symmetrical Fault Detection during Power


Swing
Rahul.Dubey, S.R.Samantaray ,Ashok Tripathy, B. Chitti Babu, and Muhammad Ehtesham
with knowledge of the likely speed of movement of the
Abstract— Fault during power swing is one of the challenging impedance during the. Power swing. However, with this
task for the distance relay functioning. This paper focuses on setting, the relay fails to block if the apparent impedance
developing Wavelet Energy (WE) based function for symmetrical moves fast during power swing. Moreover, the relay may not
fault detection during power swing. The process starts at respond to genuine faults. Occurring during the power
retrieving the current signal samples during power swing and
swing period since it is blocked from operation [4, 5].
processes it through Wavelet Transform to derive detailed
coefficient of wavelet d1 to d7, used to find out energy of the This will inevitably delay the operation of relay when a fault
signal, and called Wavelet Energy (WE). In the case study, the occurs during the power swings. Therefore, fault detection
three-phase symmetrical fault is created in the transmission line during power swing is an important and critical issue for the
and proposed algorithm detects the fault with in one and half distance relays [6].
cycles for 60 Hz system. Simulation results demonstrate the For a fault occurring during the power swing, the distance
effectiveness of the proposed approach under time-varying relay should be able to detect the fault and operate correctly.
conditions. The power swing center voltage (SCV), defined as the voltage
at the location of a two-source equivalent system where the
Keywords — Power Swing, Symmetrical Fault, Wavelet Energy,
Wavelet Transform (WT). voltage value is zero and the angles between the two sources
are 1800 apart, is used to distinguish faults from power swing
I. INTRODUCTION [7].However, it is difficult to set the threshold, especially
when a fault arc is considered. It is easy to detect the

P ower swing are caused by sudden removal of faults, loss


of synchronism or changes in direction of power flow as a
result of switching and creates oscillations in power flow.
unsymmetrical fault and unblock the distance relay during
power swing with the negative and zero sequence
components, which do not exist during stable power swing [3]
During power swing, the appearance impedance measured by .Some symmetrical fault detectors, are based on the
a distance relay may move in to the tripping zone of the superimposed components or the rate of change of measured
distance relay characteristics, causing unwanted trip [1]. To impedance [8].
ensure the reliable operation of the distance relay, power These detectors are fast, but cannot operate sensitively for
swing blocking function is employed in most of the modern those faults that cause very small superimposed components,
distance relays to block the operation during pure power such as those faults that occur at the power swing center when
swing [2, 3]. the power angle is close to 180°.Thus, the issue becomes more
The most conventional power swing blocking method is. challenging in case of symmetrical faults during power
Based on speed (timing) at which the impedance locus travels swing, because both, power swing and symmetrical
in to the operating zones of the relay characteristics. the fault faults are balanced phenomena, resulting blocking of the relay
conditions the apparent impedance trajectory travels faster for faults during power swing.
compared to the speed of the locus during power swing Distinguishing faults from power swing by monitoring the
conditions. This happens as this rate depends on the slip voltage phase angle at the relay location [9, 10], has been
frequency during power swing and is much slower found during suitable. However, only the single-phase faults
than the fault case. Generally, the relay takes hundreds of have been simulated and the method has not been applied to
milliseconds before approaching the relaying zones during symmetrical and other unsymmetrical faults. Research
power swing. Thus, the time delay is one of the indices for on building intelligent schemes for blocking power swings
discriminating fault from power swing and that has to be set using adaptive, neuro-fuzzy inference systems
(ANFIS) [11] has been reported. However, neuro-fuzzy
Rahul Dubey is with Department of Electrical Engineering, National
Institute of Technology, Rourkela-769008, India (email:
systems require huge numbers of training patterns in
rahul.dubey2011@gmail.com). achieving a reliable relay function. Moreover, it might need
S.R.Samantaray is with School of Electrical Sciences, Indian Institute of re-training for use in different power systems.
Technology, Bhubaneswar-751 013, India (email: sbh_samant@yahoo.co.in) Advanced signal processing technique such as Wavelet
B. Chitti Babu is with the Department of Electrical Engineering, National
Institute of Technology, Rourkela-769008, India (email:
transform [12,13] is an effective tool for power system
bcbabunitrkl@gmail.com). transient analysis and feature extraction The Wavelet
Muhammad Ehtesham is with Department of Electrical Engineering, transform is a time-frequency transform, retaining the time
National Institute of Technology, Rourkela-769008, India (email: information of the frequency spectrum, an added advantage
mdehtesham87@gmail.com).
Ashok Tripathy is with Department of Electrical Engineering, Silicon
over Fourier Transform and basically a series of band pass
Institute of Technology, Bhubaneswar-751024, India (email: filters. However, in achieving a good location in time, it loses
tripathy_1948@sify.com). frequency location and provides such information in

978-1-4673-0455-9/12/$31.00 ©2012 IEEE


frequency bands [14, 15]. Thus it has become a potential tool 2.1 Discrete Wavelet Transform
for fault detection during power swing as the frequency of the The base functions are generated discretely to avoid redundant
system varies over a range around the nominal frequency m m
during power swings and a fault gives rise to transients. Information by selecting a = a 0 and b = nb0 a 0 [21]. Thus,
The proposed technique uses current signal samples and discrete wavelet transform (DWT) is defined as
process it though Wavelet Transform (db-4) and find out the
detailed coefficients at different level. Using the detailed −m
∗ ⎛ t − n2 ⎞
m
coefficients, the Wavelet Energy is calculated. Further, the DWT (m, n) = 2 2
∑∑ x ( n ) Ψ ⎜
⎜ 2 m ⎟⎟ (2)
out-of-step blocking function is defined for final decision m n ⎝ ⎠
making process which is used for distinguish symmetrical Where, the discretized mother wavelet is
fault from power swing. This paper is organized as
follows. In Section II, symmetrical fault (LLL) detection
1 ⎛ t − nb0 a0m ⎞
methodology is analyzed. The proposed wavelet energy Ψm ,n (t ) = Ψ⎜⎜ m
⎟⎟ (3)
functions for fault detection in presence of power swing are m a
a0 ⎝ 0 ⎠
described in Section III. Section IV describes modeling and
the simulation results. Section V reveals the general a0 ,b0 Are fixed constant with a0 > 1, b0 > 1 m, n € Z where
conclusions followed by the references. Z is set of integers.
20
In discrete case, to analyze the signal at different scales filters
10 of different cut-off frequencies are used. Signal is passed
through a series of high-pass filter (HPF) and low-pass filter
Pinst(p.u)

0
(LPF) to analyze the high frequency and low frequency
-10
components respectively.
-20
B. Multiresolution Analysis (MRA)
-30
0 0.5 1 1.5 2 2.5 3 MRA allows the signal to decompose into various levels of
time(second)
Fig. 1 Instantaneous power (per unit) during power swing resolution. Course resolution level contains approximate
10 Information about low frequency components and retains the
0
main features of original signal. Detailed information
about the high frequency components are retained
Pmean(p.u)

-10
from the level with finer resolution [20] this is an effective
-20
method in which a signal is decomposed into scales with
different frequency and time resolutions and can be
-30
0 0.5 1 1.5
time(second)
2 2.5 3
implemented by using only two filters, one HPF and
Fig. 2 Mean power (per unit) during power swing Another LPF. Then the results are down sampled by a factor
of two and same two filters are applied to the output of LPF
II. DETECTION METHODOLOGY from the previous stage. From the mother wavelet,
Wavelet Theory is the mathematics, which deals with non- the HPF derived and measures the details in a particular
stationary signals, using a set of components that look like input. On the other hand, the LPF delivers a smooth
small waves, called wavelets. It provides multiple resolutions version of the input signal and this filter is derived
in both time and frequency. It is a linear transformation like from the mother wavelet scaling function.
the Fourier transform with one important difference: it allows
Time localization of a given signal with different frequency d1 d2 d7
components.
A. Continuous Wavelet Transform g(n) g(n) g(n)
Continuous Wavelet Transform (CWT) of a signal x x(n)
(t) is defined as

−∞ h(n) h(n) h(n)


1 ∗⎛ t − b ⎞
20 kHz
CWT (a, b) =

∫ x(t ) ∗ a
∗Ψ ⎜
⎝ a ⎠
⎟dt (1)
10 kHz 5 kHz 0.156 kHz
Where ψ (t) is the base function or mother wavelet, ‘*’ Fig. 3. MRA using Wavelet Transform
denotes a complex conjugate and a, b Є R, are the
translation parameters, respectively. R is the real
number system. [20]
A sampling rate of 20 kHz is selected in this study. are many known solutions available for implementing the
Daubechies wavelet db4 is used as the mother wavelet since it antialiasing filters; hence, no further discussion is given.
has given good performance for power system transient
analysis [18], [19]. Based on the sampling rate, the Table-I
current/voltage signal can be fully decomposed into seven Wavelet level and their corresponding frequency bands for a sampling
rate of 20 kHz
levels as shown in Table I [16], [17]. It is expected that the
transient energy will be captured in levels d1–d4 and the
energy in level d7 will track the variations of current with Wavelet Frequency Center
frequency around the nominal frequency. WT will decompose Level Band Frequency
the signal into 7 levels d1–d7 as shown in Table I, each level (Hz) (Hz)
having detail coefficients. The total energy “D” in each level d1 5000-10000 7500
“d” can be calculated using the Frobenius norm as d2 2500-5000 3750
N d3 1250-2500 1875
D= ∑[d (i)]
i =1
2
(4) d4
d5
625-1250
312.5-625
937.5
468.75
The total energy of levels of interest—D7 for the current d6 156.25-312.5 234.375
signal and D1 through D4 for the voltage signal are calculated d7 78.125-156.25 117.1875
and tracked. The reason for selecting the voltage signal to
track the energy of transients is because faults give rise to
more transients in the voltage than in the currents. Start

A Line-1 C
300KM
Current signal at relaying point
(Phase- A current)

S
Relay B ∞
Processing through wavelet
Transform
Line-2 Fault

Fig. 4 System studied for power swing classification.


Compute the energy of the signals
Ed6

III. PROPOSED WAVELET ENERGY FUNCTION FOR FAULT


DETECTION IN PRESENCE OF POWER SWING

The diagram of the proposed symmetrical fault


detection method based on the energy function technique
and wavelet transform is conceptually shown in Fig. 3 Ed6 > threshold??
A. Data Acquisition
The proposed symmetrical fault detection in presence of
power swing requires data acquisition for all three phase
currents. Those data can be obtained directly from No
measurement units of advanced digital relays. Most wavelet
transform based methods require high frequency sampling Yes
rate. The detection method proposed in this paper can be used
in a wide range of sampling rates. Considering advanced
digital relays using sampling rate of 10 kHz, the Fault detected Power swing

same sampling rate is selected in this study, which can satisfy


Fig. 5 flow chart for the proposed energy function for fault detection in
the requirements of the wavelet transform proposed in this presence of power swing
scheme with good results. In order to avoid aliasing due to the
fault transients and low sampling rate, an analog antialiasing
filter needs to be employed before the sampling of the input B. Wavelet Transform
waveforms coming from instrument transformers. There The samples are fed to the relay at a reduced rate of 10 kHz,
because higher sampling rate is not required for normal relay
functions. The samples of the three-phase current of any one and current signals of power swing (a-b-c fault at 80 km from
phase(say IA) are processed with WT. Using (1), the indices the line, fault resistance RF=10Ω, δ = 45 0 ).
D1,D2,D3,D4,D5,D6 and D7 are formed for current(IA).
1
C. Wavelet Energy

d1
0
After processing through WT. We get indices D1 to -1
D7 and cross ponding that we get Ed1 to Ed7 i.e. shown in 0 0.5 1 1.5 2 2.5 3
Table-III. Clearly.
2
D. symmetrical Fault Detection (LLL-G) 0

d2
After calculating the energy(Ed) for each indices then -2
0 0.5 1 1.5 2 2.5 3
Comparing Ed6 with Eth (power swing) so fault is detected.
(Ed6>Eth) 5
0

d3
IV. SIMULATION RESULT -5
0 0.5 1 1.5 2 2.5 3
The studied power system is developed using MATLAB time(second)
(SIMULINK) software package, is shown in Fig.2. The
complete power system includes parallel transmission lines Fig. 8. D1 to D3 fault during power swing
(distributed model) of 300 km each (AB and BC are 150 km
each) and connected to the source (600 MVA) and 5
infinite bus, respectively, at both ends. The relaying
0

d4
point ‘R’, where voltage and current signal samples (per unit)
are retrieved, is as is shown in Fig.2. The operating voltage -5
and frequency of the transmission system are 400kV and the 0 0.5 1 1.5 2 2.5 3
5
sampling rate is 20 kHz on 60 Hz base frequency (333
samples per cycle). The system details are given in the d5
0
Appendix-I.
-5
2 0 0.5 1 1.5 2 2.5 3
5
1.5
0
d6

1
-5
v o lta g e (p .u )

0 0.5 1 1.5 2 2.5 3


0.5
time(second)
0 Fig. 9. D4 to D6 fault during power swing
-0.5

-1
50
c u r r e n t ( p .u )

-1.5
0 0.5 1 1.5 2 2.5 3
time(second)
Fig. 6. Phase-A voltage waveforms during power swing. 0

-50
20 0 0.5 1 1.5 2 2.5 3
10
5
c u r r e n t(p .u )

0
d5

-10

-20
-5
-30
0 0.5 1 1.5 2 2.5 3
0 0.5 1 1.5
time(second)
2 2.5 3
time(second)
Fig. 7. Phase- current waveforms during power swing
Fig. 10. Phase-A current and D5 LLL-fault during power swing
Initially, a three-phase fault is created on line-2 and after 15
cycles (0.25 sec) the fault is cleared by opening the respective
circuit breakers at both end of line-2. This sends
the power system into power swing. Fig 4 shows the voltage
APPENDIX-I
Table –II
Energy of the signals for different wavelet level d1 to d7 The parameter of the system used for simulation (Fig.2) is as
(delta=450, LLL-faults) given below.
Equivalent Generator G: 600 MVA, 22 kV, 60 Hz,
Energy of the Without faults With faults inertia constant 4.4 MW/MVA.
signals Transformer: 600 MVA, 22/400 kV, 60 Hz, Δ Υ
Ed1 0 0 Transmission lines Parameter:-
Ed2 0.0001 0.001 Zero sequence impedance: ZL0 =96.45 + j 335.26 ohms
Ed3 0.0007 0.0159 Positive sequence impedance: ZL1 =9.78 + j 110.23 ohms
Ed4 0.0018 0.0243 Source impedance: Z S = 6 + j 28.5 ohms
Ed5 0.0341 0.1033 Source voltages: E S = 400∠δ kV
Ed6 0.4036 0.8584 Where δ = load angle in degrees.
Ed7 6.4198 9.0941
REFERENCES
[1] Xu Zhengya. “New distance relay for transmission line”, China
TABLE-III
water and hydroelectricity press, 2002.
FAULT SITUATIONS TESTED USING THE PROPOSED
[2] AREVA, “MiCOMho P443 fast multifunction distance protection”,
WAVELET ENERGY FUNCTION
AREVA T&D Automation & Information Systems.
[3] NARI-Relays electric limited company. “RCS-901A/B EHV
Fault Fault Fault Fault Power Response transmission line distance protection”.
Types resistance location inception angle time [4] P. J. Moore and A. T. Johns, “New method of power swing
(ohm) (km) angle (degree) (cycles) blocking for digital distance protection” Proc. Inst. Elect. Eng.,
(degree) Gen., Transm.Distrib., vol. 143, no. 1, pp. 19–26, Jan. 1996.
[5] X. Lin, Y. Gao, and P. Liu, “A novel scheme to identify
symmetrical faults occurring during power swings” IEEE Trans.
a-b-c 10 60 30 45 1.53 on Power. Del., vol. 23, no. 1, pp. 73–78, Jan. 2008.
[6] S. Jiao, Z. Bo, W. Liu, and Q. Yang, “New principles to detect
100 170 45 60 1.54 faults during power swing” in Proc. Inst. Elect. Eng.,
a-b-c- 20 50 45 60 1.55 Developments in PowerSystem Protectio 7th Int. Conf.,
g Amsterdam, The Netherlands, 2001, pp. 515–518.
100 160 60 45 1.53 [7] G. Benmouyal, D. Hou, and D. Tziouvaras, “Zero-setting power-
swing blocking protection”, 31st Annu. Western Protective Relay
a-b-g 10 85 90 60 1.55 Conf., Spokane, WA, Oct. 2004.
[8] Zhu Shengshi, “Theories and techniques of the protection in high
b-c-g 50 120 45 45 1.55
voltage power system”, China electrical power press, 1995.
c-a-g 100 180 60 60 1.54 [9] A. Mechraoui and D. W. P. Thomas, “A new blocking principle
with phase and earth fault detection during fast power swings for
a-b 20 30 45 45 1.54 distance protection”, IEEE Trans. on Power. Del., vol. 10, no. 3,
b-c 50 90 60 60 1.54 pp. 1242–1248, Jul. 1995.
[10] A. Mechraoui and D. W. P. Thomas, “A new principle for high
c-a 100 160 30 45 1.53 resistance earth fault detection during fast power swings for
distance protection”, IEEE Trans. on Power. Del., vol. 12, no. 4,
a-g 0 20 30 45 1.54
pp. 1452–1457, Oct. 1997.
b-g 50 130 60 45 1.54 [11] H. K. Zadeh and Z. Li, “A novel power swing blocking scheme
using adaptive neuro-fuzzy inference system”, Electric Power
c-g 100 180 30 60 1.55 Syst. Res., vol. 78, pp. 1138–1146, 2008.
[12] J. Faiz and S. Lotfi-Fard, “A novel wavelet-based algorithm for
discrimination of internal faults from magnetizing inrush currents
V. CONCLUSIONS in power transformers,” IEEE Trans. Power. Del., vol. 21, no. 4,
A new technique for detecting symmetrical fault (LLL) in pp. 1989–1996, Oct. 2006.
[13] N. Zhang and M. Kezunovic, “Transmission line boundary
presence of a power swing has been obtained by analyzing the protection using wavelet transform and neural network”, IEEE
current signal at relay end. the effectiveness of a new and Trans. on Power. Del., vol. 22, no. 2, pp. 859–869, Apr. 2007.
reliable approach for the characterization of symmetrical fault [14] C. Parameswariah and M. Cox, “Frequency characteristics of
(LLL) during a power swing in time varying condition. the wavelets” IEEE Trans. on Power Del., vol. 17, no. 3, pp. 800–804,
Jul. 2002.
proposed approach is based on an optimized use of the DWT [15] D. C. Robertson, O. I. Camps, J. S. Mayer, and W. B. Gish,
by a simple pre-processing of the variables to be analyzed. In “Wavelets and electromagnetic power system transient” , IEEE
the case study, the three-phase fault is created in the LINE-2 Trans. on Power Del., vol. 11, no. 2, pp. 1050–1058, Apr. 1996.
and proposed algorithm detects the fault with in one and half [16] C. Parameswariah and M. Cox, “Frequency
characteristics of wavelets,” IEEE Trans. Power Del., vol. 17, no.
cycles for 60Hz system. A new diagnostic method based on 3, pp. 800–804, Jul.2002
the current modulating signals (LINE-1) pre-processing by [17] D. C. Robertson, O. I. Camps, J. S. Mayer, and W. B.
Discrete Wavelet Transform (DWT) thereby is here proposed Gish, “Wavelets and electromagnetic power system transient,”
to detect faults during power swing dynamically over time. IEEE Trans. Power Del. vol. 11, no. 2, pp. 1050–1058, Apr. 1996.
Simulation results demonstrate the effectiveness of the [18] S. Santoso, E. J. Powers, W. M. Grady, and P.
Hofmann, “Power quality assessment via wavelet transform
proposed approach under time- varying conditions.
analysis,” IEEE Trans. Power Del., vol. 11, no. 2, pp. 924–930,
Apr. 1996.
[19] A. Osman and O. P. Malik, “Transmission line
distance protection based on wavelet transform,” IEEE Trans.
Power Del., vol. 19, no. 2,pp. 515 –523, Apr. 2004.
[20] J . Upender, C. P. Gupta and G. K. Singh, “Discrete wavelet
transformand probabilistic neural network based
algorithmfor classification of fault on transmission systems,”
in India conf. IEEE,INDICON 2008,11-13 Dec,2008, Vol.1, pp.
206-211.
[21] L. H. Hansen, L. Helle, F. Blaabjerg, E. Ritche, S. Munk-
Nielsen, H. Bindner, P. Sorensen, and B. Bak-Jensen, “Conceptual
survey of generators and power electronics for wind turbines,”
Risø Nat. Lab., Rockilde, Denmark, Dec. 2001.

You might also like