Professional Documents
Culture Documents
6, DECEMBER 2018
Abstract—It is commonly assumed that power swings are sym- Distance protection offers a reliable protection in transmis-
metrical phenomena that impose almost identical effects on the sion and meshed distribution networks [3]. The trajectory of
three-phase voltages and currents of the power system. However, impedance seen by a distance relay may enter its operating zones
there is another type of power swings which is asymmetrical and oc-
curs mainly during single-pole tripping. In the nowadays heavily during a power swing condition. Therefore, these relays are sus-
loaded power systems, the likelihood of occurrence of this phe- ceptible to undesirable trip due to mistaking a power swing for
nomenon is increased considerably. Although the effects of sym- a short-circuit fault. The conventional countermeasure against
metrical power swings on distance protection are widely analyzed distance relays maloperation is to block their operation as long
in the literature, asymmetrical power swings have been less stud- as power swings persist. Power swing blocking (PSB) functions
ied so far. This paper focuses on this type of power swings and
their effects on distance protection. Besides, two new techniques work traditionally based on the rate of change of impedance,
are proposed to detect faults during asymmetrical power swings which is slower in power swings than in faults. The main pur-
and enhance performance of power swing blocking schemes. The pose of a PSB function is to detect power swings and to block
first technique is based on the rate of change of zero sequence cur- distance relay tripping during power swings.
rent, while the second one is based on the magnitudes of voltage During a power swing, the power system is under stress. If a
and current in each phase, as well as their relative phase angle. The
presented analyses and proposed methods are validated using two second disturbance occurs in such a condition, large oscillations
benchmark test systems and promising results are obtained. the system would experience might also endanger the whole
system stability. As long as a distance relay remains blocked,
Index Terms—Asymmetrical power swing, distance protection,
single-pole tripping, transmission line.
it will not detect and clear short-circuit faults. Thus, faults that
occur during a power swing must be detected and cleared with
I. INTRODUCTION a high degree of selectivity and dependability.
In some relays, fault detection during power swings is carried
OWER systems are often prone to inevitable disturbances
P such as load variations, transmission line switchings, and
short-circuit faults. Such disturbances may cause oscillations in
out using the zero-sequence current [4]. However, this method
is not suitable for detecting symmetrical faults. In [5], symmet-
rical faults are detected during power swings by monitoring the
machine rotor angles during which, transmission lines might energy of high-frequency components of forward and backward
undergo significant fluctuations in their power flows commonly traveling waves induced by the fault. In [6], the rate of change of
referred to as power swings. Depending on the severity of the swing-center voltage is used to provide a power swing blocking
disturbance and the response of power system controllers, the protection. The wavelet transform is capable of decomposing
emerging power swings may be stable or unstable [1]. In the ma- signals into several frequency bands. This capability is used
jority of cases, power swings are low-magnitude well-damped in [7] for fault detection during power swings. In [8], the av-
oscillations subsequent to which the power system would effec- erage of current is used for power swing detection and fault
tively settle to a new operating point. However, under extreme identification during power swing. Some recent works on fault
conditions, a system disturbance may result in an unstable power detection techniques during power swings are based on intel-
swing of increasing magnitude, and loss of synchronism be- ligent training [9], phase-space mapping [10], support vector
tween generators or portions of the system. Large power swings, machine identification [11] and wavelet singular entropy [12].
stable or unstable, may cause unwanted operation of relays at Although their reported results are satisfactory, however, some
different locations. This would further aggravate the situation of these methods require time consuming training procedures
and might result in cascading outages or even blackouts [2]. or high sampling frequencies which are beyond the capabilities
of existing numerical relays.
Manuscript received October 28, 2017; revised January 25, 2018; accepted
March 9, 2018. Date of publication March 15, 2018; date of current version Calculation of impedance trajectory in numerical distance re-
November 20, 2018. This work was supported by the University of Tehran lays is based on voltage and current phasor estimation [13]. Os-
under Grant 8101064-1-11. Paper no. TPWRD-01316-2017. (Corresponding cillation of fundamental frequency phasors during power swings
author: Majid Sanaye-Pasand.)
The authors are with the School of Electrical and Computer Engineering, has led to the idea of dynamic phasor, rather than conventional
College of Engineering, University of Tehran, Tehran 14395-515, Iran (e-mail:, static phasors, to improve the accuracy of oscillation estimation
hashemi93@ut.ac.ir; msanaye@ut.ac.ir). [14]–[16]. The transient variation of dynamic phasors is used in
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. [17] as a criterion to discriminate symmetrical and asymmetri-
Digital Object Identifier 10.1109/TPWRD.2018.2816304 cal faults from power swings. In most cases, power swings are
0885-8977 © 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2737
II. EFFECTS OF SINGLE-POLE TRIPPING CONDITION ON Note that for K0 = 0 in (6), the line is considered as three
DISTANCE PROTECTION separated phases with no mutual coupling, whose currents are
simply obtained by dividing voltage over the impedance. This
A distance relay measures impedance to the fault in order
condition takes place when Z0 = Z1 or mathematically:
to protect the line against short-circuit faults. Six distance
protection units, including three ground units and three phase K0 = 0 ΔVb ΔVc
if Z0 = Z1 ⇒ ⇒ Ib = , Ic = (7)
units, provide a comprehensive protection against all types Zm = 0 Zs Zs
of short-circuit faults. During single-pole tripping (SPT), the
From (3) and (6), IE is expressed as:
line is operating under unbalanced condition which may affect
some protection functions. Before analyzing these effects on 1 1
IE = (ΔVb + ΔVc ) (8)
distance protection, the relationships between the currents of Z1 1 + 2K0
healthy phases during SPT condition are extracted as follows.
Now, assume that buses x and y in Fig. 1 have the same voltage
magnitudes with the phase difference of δ. The voltage across
A. Healthy Phases Currents During SPT each phase is generally expressed as:
During SPT, the power flow is established through two healthy ΔV = |V | ∠0 − |V | ∠ − δ (9)
phases of the line. Considering Fig. 1(a), the following equations
can be written. Taking phase a as the reference and α = 1 ∠ 120◦ :
ΔVb + ΔVc = (α2 + α)ΔV = −ΔV (10)
Vbx − Vby = Zs Ib + Zm Ic , Vcx − Vcy = Zs Ic + Zm Ib (1)
Before SPT, the currents of healthy phases are given as (11)
where Zs and Zm are the self and mutual impedances of trans- in which the subscript ‘ini’ denotes the initial value.
mission line, respectively, and the line is considered to be trans- ΔVb α2 ΔV ΔVc αΔV
posed. Since the positive and zero sequence impedances are Ib,in i = = = α2 I, Ic,in i = = = αI
Z1 Z1 Z1 Z1
defined as Z1 = Zs − Zm and Z0 = Zs + 2Zm , (1) can be (11)
2738 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018
Fig. 2. Variation of magnitude of IE with K 0 during SPT. Fig. 4. Variation of |Z/Z i n i | with K 0 for phase distance relays during SPT.
set longer than the dead time of reclosing scheme. Effect of this
current on distance protection is investigated in the subsequent
part.
III. ASYMMETRICAL POWER SWINGS AND THEIR EFFECTS ON Pe,in i + ΔPin i = Pm ax sin (δin i + Δδin i )
DISTANCE PROTECTION ≈ Pm ax sin δin i + (Pm ax cos δin i )Δδin i
As mentioned earlier, asymmetrical power swings occur dur- (25)
ing SPT. There are also some single-pole tripping and reclosing
From (24) and (25), it is concluded that:
practices without any considerable power swing. Thus, the ques-
tion is that when and where asymmetrical power swings take ΔPin i = (Pm ax cos δin i )Δδin i (26)
place. Proper equations are derived in this section to answer this
question. Equation (26) implies that any change in output electrical
power of a generator will be followed almost directly by a
A. Asymmetrical Power Swings: When/Where Taking Place? proportional change in rotor angle. According to (23), the value
of initial change of angle Δδin i determines the amplitude of
In a bulk power system, power swings are originated from the angle oscillations. The more the change in power, the more the
rotor angle oscillations of synchronous generators. The well- severity of disturbance and rotor angle oscillations.
known swing equation of a turbo-generator is written by using The electrical power transferred through a transmission line
the Newton’s second law of motion as: is calculated as:
dωm
J + Td = Tm − Te (20) Pe,in i = Pa,in i + Pb,in i + Pc,in i = 3 |V | |I| cos θ (27)
dt
where J is the inertia constant, ωm is the rotor speed, Tm is During the SPT of phase a, the transferred power is
the mechanical torque produced by the turbine, Te is the coun- yielded as:
teracting electromagnetic torque, and Td is the damping torque
Pe = Pb + Pc = |V | |I| (|Kb | + |Kc |) cos θ (28)
accounting the mechanical rotational loss due to windage and
friction [23]. It is approximately proportional to the rotor speed From (27) and (28), one can deduce that:
as Td = Dωm . The change in electromagnetic torque ΔTe is a
ΔPe
linear function of changes in rotor angle and flux linkages. After % = 1 − |Kb | + |Kc | × 100 (29)
Pe,in i 3
some manipulations [23], the swing equation can be expressed
in terms of change of angle as: Variation of (29) with K0 is illustrated in Fig. 5. As expected,
2
d Δδ dΔδ the single-phase interruption induced ΔP is smaller than that
M +D + KE Δδ = 0 (21) induced by the three-phase interruption. For K0 > 0.5, ΔP
dt2 dt
is about 40%. In meshed and interconnected transmission net-
where M = Jωm and KE is the transient synchronizing power
works, some part of this ΔP is imposed on other lines which
coefficient. Equation (21) is a second-order differential equation
provide alternative paths from the generators to the load cen-
with the initial conditions of (22).
ters. However, during the maintenance programs or in case of
Δδ|t=0 + = Δδin i , Δωm = Δδ̇ + = 0 (22) a single-circuit tie-line between two areas of the system, there
t=0 may be only one path for the power transfer from power plants to
During stable power swings, the rotor angle variation is un- loads. If so, the whole ΔP created by SPT affects the generators
derdamped and described as [23]: and it can be shown that:
Δδin i −α t Δδin i ΔPe
Δδ(t) = e sin(ωn t + ϕ) (23) ≈ (30)
1 − ζ2 δin i Pe,in i
2740 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018
where Imin denotes the minimum current used for detecting any
phase opening and can be set as 0.1 × In . For the main faulted
line whose faulted phase (say a) is tripped, |Ia | becomes less Fig. 10. Performance of aE ground distance relays for an SLG fault on phase
than Imin and the corresponding phase a is eliminated from c; Reclosing dead time = (a) 800 ms, (b) 1000 ms.
set S. The maxima and minima of phase voltages and current
are compared with each other according to Fig. 8(a). If there
are considerable differences, an earth fault is detected and the
ground distance relays are activated. It should be noted that in
Fig. 8(a), the fault detection logic (FDL) signal is generated
according to the logic diagram shown in Fig. 8(b), wherein
the load angle criteria block checks the angle |(V{S} /I{S} )|
to see whether or not it is less than the maximum load angle,
typically 30°. Fig. 11. Phase and zero sequence currents during asymmetrical power swing.
fault, the impedance abruptly moves into the relay operating Fig. 15. Simulation results for the IEEE 39 bus system; (a) Impedance seen
zone. This abrupt change is also observed in the zero-sequence by the relay of line 26–29; (b) Currents of line 25–26; (c) Voltages of line 25–26.
current depicted in Fig. 12(b). It can be concluded from Figs. 11
and 12(b) that the net value of zero-sequence current is not an
effective tool to detect earth faults during asymmetrical power
swings. However, Fig. 13 demonstrates that the rate of change Fig. 15(a) shows the impedance seen by the cE distance relay of
of zero-sequence current is able to serve this purpose quite line 26–29 located at bus 29, in which the impedance trajectory
well. As shown, this parameter detects any abrupt change due enters the relay zone due to the asymmetrical power swings
to fault or single-pole switching. Therefore, in order to make emerged after the fault removal.
it suitable to detect the faults that occur during asymmetrical In order to examine the second proposed earth fault detection
power swings, it can be logically combined with a power swing method, consider the three-phase voltages and currents of line
detection method. In other words, the mentioned faults are de- 25–26 which are measured at bus 25 and shown in Fig. 15(b)
tected if a power swing is detected and the rate of change of and (c). During the SPT of line 26–29, the zero sequence current
zero-sequence current exceeds a predetermined threshold. of line 25–26 is greater than zero which can result in starting
ground distance units. Using the proposed earth fault detec-
tion, max(|Ia |, |Ib |, |Ic |) is greater than 2 × min(|Ia |, |Ib |, |Ic |)
B. IEEE 39 Bus System
during SPT. However, at the same time max(|Va |, |Vb |, |Vc |) is
The IEEE 39 bus system, as shown in Fig. 14, contains 34 lines less than 1.5 × min(|Va |, |Vb |, |Vc |). Once an earth fault occurs
among which lines 26–29 and 26–28 are the longest ones and on phase a of line 25–26 at t = 2 s, max(|Va |, |Vb |, |Vc |) be-
line 26–28 is assumed to be out of service. Thus, generator G9 is comes greater than 1.5 × min(|Va |, |Vb |, |Vc |). Therefore, the
connected to the rest of the grid via line 26–29 which transfers proposed combination of current and voltage signals in earth
about 330 MW from bus 29 to 26. Under this condition, an fault detection method makes the relays of the main line and its
SLG fault on phase a with Rf = 0 Ω is applied at the middle adjacent lines immune to activation of earth fault units during
of line 26–29 at t = 1 s and this phase is opened at t = 1.1 s. SPT condition.
2744 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018
TABLE I
EVALUATION OF EXISTING POWER SWING BLOCKING/UNBLOCKING SCHEMES
FOR ASYMMETRICAL POWER SWINGS APPLICATIONS