You are on page 1of 10

2736 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO.

6, DECEMBER 2018

Distance Protection During Asymmetrical Power


Swings: Challenges and Solutions
Sayyed Mohammad Hashemi and Majid Sanaye-Pasand , Senior Member, IEEE

Abstract—It is commonly assumed that power swings are sym- Distance protection offers a reliable protection in transmis-
metrical phenomena that impose almost identical effects on the sion and meshed distribution networks [3]. The trajectory of
three-phase voltages and currents of the power system. However, impedance seen by a distance relay may enter its operating zones
there is another type of power swings which is asymmetrical and oc-
curs mainly during single-pole tripping. In the nowadays heavily during a power swing condition. Therefore, these relays are sus-
loaded power systems, the likelihood of occurrence of this phe- ceptible to undesirable trip due to mistaking a power swing for
nomenon is increased considerably. Although the effects of sym- a short-circuit fault. The conventional countermeasure against
metrical power swings on distance protection are widely analyzed distance relays maloperation is to block their operation as long
in the literature, asymmetrical power swings have been less stud- as power swings persist. Power swing blocking (PSB) functions
ied so far. This paper focuses on this type of power swings and
their effects on distance protection. Besides, two new techniques work traditionally based on the rate of change of impedance,
are proposed to detect faults during asymmetrical power swings which is slower in power swings than in faults. The main pur-
and enhance performance of power swing blocking schemes. The pose of a PSB function is to detect power swings and to block
first technique is based on the rate of change of zero sequence cur- distance relay tripping during power swings.
rent, while the second one is based on the magnitudes of voltage During a power swing, the power system is under stress. If a
and current in each phase, as well as their relative phase angle. The
presented analyses and proposed methods are validated using two second disturbance occurs in such a condition, large oscillations
benchmark test systems and promising results are obtained. the system would experience might also endanger the whole
system stability. As long as a distance relay remains blocked,
Index Terms—Asymmetrical power swing, distance protection,
single-pole tripping, transmission line.
it will not detect and clear short-circuit faults. Thus, faults that
occur during a power swing must be detected and cleared with
I. INTRODUCTION a high degree of selectivity and dependability.
In some relays, fault detection during power swings is carried
OWER systems are often prone to inevitable disturbances
P such as load variations, transmission line switchings, and
short-circuit faults. Such disturbances may cause oscillations in
out using the zero-sequence current [4]. However, this method
is not suitable for detecting symmetrical faults. In [5], symmet-
rical faults are detected during power swings by monitoring the
machine rotor angles during which, transmission lines might energy of high-frequency components of forward and backward
undergo significant fluctuations in their power flows commonly traveling waves induced by the fault. In [6], the rate of change of
referred to as power swings. Depending on the severity of the swing-center voltage is used to provide a power swing blocking
disturbance and the response of power system controllers, the protection. The wavelet transform is capable of decomposing
emerging power swings may be stable or unstable [1]. In the ma- signals into several frequency bands. This capability is used
jority of cases, power swings are low-magnitude well-damped in [7] for fault detection during power swings. In [8], the av-
oscillations subsequent to which the power system would effec- erage of current is used for power swing detection and fault
tively settle to a new operating point. However, under extreme identification during power swing. Some recent works on fault
conditions, a system disturbance may result in an unstable power detection techniques during power swings are based on intel-
swing of increasing magnitude, and loss of synchronism be- ligent training [9], phase-space mapping [10], support vector
tween generators or portions of the system. Large power swings, machine identification [11] and wavelet singular entropy [12].
stable or unstable, may cause unwanted operation of relays at Although their reported results are satisfactory, however, some
different locations. This would further aggravate the situation of these methods require time consuming training procedures
and might result in cascading outages or even blackouts [2]. or high sampling frequencies which are beyond the capabilities
of existing numerical relays.
Manuscript received October 28, 2017; revised January 25, 2018; accepted
March 9, 2018. Date of publication March 15, 2018; date of current version Calculation of impedance trajectory in numerical distance re-
November 20, 2018. This work was supported by the University of Tehran lays is based on voltage and current phasor estimation [13]. Os-
under Grant 8101064-1-11. Paper no. TPWRD-01316-2017. (Corresponding cillation of fundamental frequency phasors during power swings
author: Majid Sanaye-Pasand.)
The authors are with the School of Electrical and Computer Engineering, has led to the idea of dynamic phasor, rather than conventional
College of Engineering, University of Tehran, Tehran 14395-515, Iran (e-mail:, static phasors, to improve the accuracy of oscillation estimation
hashemi93@ut.ac.ir; msanaye@ut.ac.ir). [14]–[16]. The transient variation of dynamic phasors is used in
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. [17] as a criterion to discriminate symmetrical and asymmetri-
Digital Object Identifier 10.1109/TPWRD.2018.2816304 cal faults from power swings. In most cases, power swings are

0885-8977 © 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2737

symmetrical and three-phase active or reactive powers can be


used to distinguish between power swings and faults as pre-
sented in [18], [19].
Single-pole tripping and reclosing is a common practice for
enhancing power system transient stability. In weak areas of a
power system, power swings may occur after single-pole trip-
ping [1]. The resulting phenomenon is known as asymmetrical
power swing and is more likely to occur in long, heavily loaded
transmission lines for which the interruption of one phase will
Fig. 1. Investigation of a typical transmission line during single-pole tripping;
result in remarkable change of transferred power [1], [20], [21]. (a) Self and mutual impedances; (b) Voltage phasor diagram.
To deal with such a problem, PSB schemes should be able to
detect power swings on each phase independently.
arranged as:
This paper focuses on asymmetrical power swings and their
effects on distance protection. In this respect, performance of ΔVb = (Zs − Zm )Ib + Zm IE , ΔVc = (Zs − Zm )Ic + Zm IE
distance relays during single-pole tripping is elaborated at the (2)
beginning. Then, an analytic discussion is presented to show where the earth current IE is defined as:
when and where asymmetrical power swings are emerged. These
IE = 3I0 = Ia + Ib + Ic = Ib + Ic (3)
issues provide the required information to investigate the effects
of asymmetrical power swings on distance protection. After- Using the K0 factor defined in (4), the healthy phases currents
wards, two new techniques are proposed to enhance numeri- are obtained as (5). It should be noted that K0 is a complex value
cal distance protection in the presence of asymmetrical power with an angle close to zero and can be well-approximated as a
swings. Finally, simulation results are provided to support the real value.
presented analysis and evaluate the proposed solutions. In a nut- Zm Z0 − Z1
shell, the main contributions and features of this paper are listed K0 = = (4)
Z1 3Z1
as:
r Elaborating asymmetrical power swings and their impacts ΔVb ΔVc
Ib = − K0 IE , Ic = − K0 IE (5)
on distance protection. This type of power swings is less Z1 Z1
studied in detail in the literature. From (3) and (5), the currents can be described in terms of
r Analyzing the effects of single-pole tripping on distance voltage differences as
protection by extracting proper mathematical equations. ⎧    
r Presenting two new techniques to empower distance pro- 1+K 0
⎨ Ib = 1+2K ΔVb
− K0 ΔVc
0 Z1 1+2K 0 Z1
tection in counteracting asymmetrical power swings.     (6)
⎩I = 1+K Δ Δ
Z 1 − 1+2K 0
0 V c K 0 Vb
c 1+2K 0 Z1

II. EFFECTS OF SINGLE-POLE TRIPPING CONDITION ON Note that for K0 = 0 in (6), the line is considered as three
DISTANCE PROTECTION separated phases with no mutual coupling, whose currents are
simply obtained by dividing voltage over the impedance. This
A distance relay measures impedance to the fault in order
condition takes place when Z0 = Z1 or mathematically:
to protect the line against short-circuit faults. Six distance 
protection units, including three ground units and three phase K0 = 0 ΔVb ΔVc
if Z0 = Z1 ⇒ ⇒ Ib = , Ic = (7)
units, provide a comprehensive protection against all types Zm = 0 Zs Zs
of short-circuit faults. During single-pole tripping (SPT), the
From (3) and (6), IE is expressed as:
line is operating under unbalanced condition which may affect 
some protection functions. Before analyzing these effects on 1 1
IE = (ΔVb + ΔVc ) (8)
distance protection, the relationships between the currents of Z1 1 + 2K0
healthy phases during SPT condition are extracted as follows.
Now, assume that buses x and y in Fig. 1 have the same voltage
magnitudes with the phase difference of δ. The voltage across
A. Healthy Phases Currents During SPT each phase is generally expressed as:
During SPT, the power flow is established through two healthy ΔV = |V | ∠0 − |V | ∠ − δ (9)
phases of the line. Considering Fig. 1(a), the following equations
can be written. Taking phase a as the reference and α = 1 ∠ 120◦ :
ΔVb + ΔVc = (α2 + α)ΔV = −ΔV (10)
Vbx − Vby = Zs Ib + Zm Ic , Vcx − Vcy = Zs Ic + Zm Ib (1)
Before SPT, the currents of healthy phases are given as (11)
where Zs and Zm are the self and mutual impedances of trans- in which the subscript ‘ini’ denotes the initial value.
mission line, respectively, and the line is considered to be trans- ΔVb α2 ΔV ΔVc αΔV
posed. Since the positive and zero sequence impedances are Ib,in i = = = α2 I, Ic,in i = = = αI
Z1 Z1 Z1 Z1
defined as Z1 = Zs − Zm and Z0 = Zs + 2Zm , (1) can be (11)
2738 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018

Fig. 2. Variation of magnitude of IE with K 0 during SPT. Fig. 4. Variation of |Z/Z i n i | with K 0 for phase distance relays during SPT.

set longer than the dead time of reclosing scheme. Effect of this
current on distance protection is investigated in the subsequent
part.

B. Distance Protection During SPT


For a given phase L, the ground and phase units of a distance
relay calculate the following impedances:
V L 1 E −V L 2 E
ZL E = VL E
I L +K 0 I E , ZL 1L 2 = I L 1 −I L 2 (15)
where L1 and L2 are two given phases of the line. When the
system is operating under normal condition with no fault, the
impedance calculated by the distance relay is proportional to
the load power transfer across the line. An area near the R-axis
Fig. 3. Variation of I/Ii n i with K 0 during SPT for a typical transmission determines the load area. The longer the line, the more likely
line.
the load area encroachment on the relay characteristics.
Considering (12)−(15) and assuming that the voltages before
Accordingly, the expression of IE in (8) is developed as: and after SPT are similar, the impedance seen by the ground

1 ΔV 1 distance relay of phase b (ZbE ) during the SPT of phase a is
IE = − =− I (12) obtained as:
1 + 2K0 Z1 1 + 2K0
VbE α2 V V
Variation of magnitude of IE with K0 is shown in Fig. 2. It can ZbE = =  = (16)
be concluded that as the interphase mutual coupling increases, Ib + K0 IE Kb − 1+2K
K 0
I I
0
the magnitude of IE during SPT decreases. Meanwhile, the
currents of healthy phases in (6) are represented as: Under normal condition where IE is zero, ZbE turns to:

⎨ Ib = Kb I, Kb = (1+K 0 )α 2 −K 0 α VbE ,in i α2 V V
1+2K 0 ZbE ,in i = = 2 = (17)
(13) Ib,in i α I I
⎩ I = K I, K = (1+K 0 )α −K 0 α 2
c c c 1+2K 0 Hence, ZbE is equal to ZbE ,in i . A similar relationship is
established for phase c. In other words, the impedances seen
Fig. 3 represents variation of Ib /Ib,in i and Ic /Ic,in i ratios
by the ground distance relays of healthy phases during SPT are
both in magnitude and phase angle versus the K0 factor. Typical
similar to those during normal condition.
values of K0 in overhead lines are between 0.6 to 1 [3]. As
Moreover, it can be shown that the impedances of phase
mentioned earlier, zero K0 corresponds to Z0 = Z1 . Fig. 3
distance units during the SPT of phase a are described as:
demonstrates that as K0 increases, the magnitudes of Ib /Ib,in i
α2 V (α 2 −α )V
and Ic /Ic,in i decrease gradually. For K0 values between 0.6 to Zab = Kb I , Zbc = (K b −K c )I = V
I , Zca = αV
Kc I
(18)
1, the magnitudes of Ib and Ic during SPT are almost 85% of
their corresponding values before SPT. The trends of Ib and Ic These equations are related to their counterparts in normal
for larger values of K0 can be approximated as: condition as:
⎧ √  α2
⎪ 2
Za b
= , Zb c
= 1, Zc a
= α
(19)
⎨ lim Ib = lim Kb I = α 2−α I = 23 ∠ −90◦ I Za b , i n i Kb Zb c , i n i Zc a , i n i Kc
K 0 →∞ K 0 →∞
√  (14) As shown in Fig. 4, for typical K0 values of 0.6 to 0.1, the

⎩ lim Ic = lim Kc I = α −α
2
I = 3
∠ +90 ◦
I
K 0 →∞ K 0 →∞ 2 2 magnitudes of impedances seen by ab and ca phase distance
relays during SPT are almost 1.15 times greater than those of
The main result of this part is that during SPT, an inherent normal condition.
earth current (or zero sequence current) is generated due to the In numerical distance relays, the ground units are usually acti-
unbalanced system condition. Therefore, the protection func- vated if an earth fault is detected by monitoring the earth current
tions which are based on the value of zero-sequence current IE [3], [4]. During symmetrical operation of power system, due
have to be blocked during SPT or their time delay should be to the lack of zero sequence current, the ground distance units
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2739

are not activated. This condition is established during symmet-


rical power swings as well. However, the presence of IE during
asymmetrical conditions, like SPT, may result in unwanted ac-
tivation of ground distance relays.
It is worth mentioning that some modern relays employ more
sophisticated earth fault detection algorithms to prevent activat-
ing ground distance units by SPT [22]. Such algorithms are only
carried out during SPT and therefore, they need to know whether
or not the faulted line is tripped single-pole. The ground units
Fig. 5. Variation of |ΔP e /P e , i n i | with K 0 during SPT.
of these relays may be immune to activation during the SPT of
faulted line. However, the presence of IE can be seen by the
relays of adjacent lines as well and those relays should have where α = ζωn , ωn = (KE  /M )1/2 , ζ = D/ 2(KE  /M )1/2
the SPT data of the main faulted line which is not usually the and ϕ = cos−1 ζ. On the other hand, the output electrical power
case. Therefore, even using modern numerical distance relays, of a generator can be expressed as:
activation of ground distance relays during SPT is still likely.
As will be explained, the activated distance relays are exposed Pe = Pm ax sin δ (24)
to the risk of issuing false trip commands during power swings. For a small change in the electrical power:

III. ASYMMETRICAL POWER SWINGS AND THEIR EFFECTS ON Pe,in i + ΔPin i = Pm ax sin (δin i + Δδin i )
DISTANCE PROTECTION ≈ Pm ax sin δin i + (Pm ax cos δin i )Δδin i
As mentioned earlier, asymmetrical power swings occur dur- (25)
ing SPT. There are also some single-pole tripping and reclosing
From (24) and (25), it is concluded that:
practices without any considerable power swing. Thus, the ques-
tion is that when and where asymmetrical power swings take ΔPin i = (Pm ax cos δin i )Δδin i (26)
place. Proper equations are derived in this section to answer this
question. Equation (26) implies that any change in output electrical
power of a generator will be followed almost directly by a
A. Asymmetrical Power Swings: When/Where Taking Place? proportional change in rotor angle. According to (23), the value
of initial change of angle Δδin i determines the amplitude of
In a bulk power system, power swings are originated from the angle oscillations. The more the change in power, the more the
rotor angle oscillations of synchronous generators. The well- severity of disturbance and rotor angle oscillations.
known swing equation of a turbo-generator is written by using The electrical power transferred through a transmission line
the Newton’s second law of motion as: is calculated as:
dωm
J + Td = Tm − Te (20) Pe,in i = Pa,in i + Pb,in i + Pc,in i = 3 |V | |I| cos θ (27)
dt
where J is the inertia constant, ωm is the rotor speed, Tm is During the SPT of phase a, the transferred power is
the mechanical torque produced by the turbine, Te is the coun- yielded as:
teracting electromagnetic torque, and Td is the damping torque
Pe = Pb + Pc = |V | |I| (|Kb | + |Kc |) cos θ (28)
accounting the mechanical rotational loss due to windage and
friction [23]. It is approximately proportional to the rotor speed From (27) and (28), one can deduce that:
as Td = Dωm . The change in electromagnetic torque ΔTe is a
ΔPe
linear function of changes in rotor angle and flux linkages. After % = 1 − |Kb | + |Kc | × 100 (29)
Pe,in i 3
some manipulations [23], the swing equation can be expressed
in terms of change of angle as: Variation of (29) with K0 is illustrated in Fig. 5. As expected,
2
d Δδ dΔδ the single-phase interruption induced ΔP is smaller than that
M +D + KE  Δδ = 0 (21) induced by the three-phase interruption. For K0 > 0.5, ΔP
dt2 dt
is about 40%. In meshed and interconnected transmission net-
where M = Jωm and KE  is the transient synchronizing power
works, some part of this ΔP is imposed on other lines which
coefficient. Equation (21) is a second-order differential equation
provide alternative paths from the generators to the load cen-
with the initial conditions of (22).
ters. However, during the maintenance programs or in case of

Δδ|t=0 + = Δδin i , Δωm = Δδ̇ + = 0 (22) a single-circuit tie-line between two areas of the system, there
t=0 may be only one path for the power transfer from power plants to
During stable power swings, the rotor angle variation is un- loads. If so, the whole ΔP created by SPT affects the generators
derdamped and described as [23]: and it can be shown that:

Δδin i −α t Δδin i ΔPe
Δδ(t) = e sin(ωn t + ϕ) (23) ≈ (30)
1 − ζ2 δin i Pe,in i
2740 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018

For K0 > 0.5, the rotor angle variations during asymmetrical


power swings can be extracted from (23) and (30) as:

0.4
δ(t) = δin i + Δδ ≈ δin i × 1 + e−α t sin (ωn t + ϕ)
1 − ζ2
(31)
If the initial transferred power Pin i is relatively high, this
ΔP can also be high enough to create remarkable Δδ and thus,
severe power swings. On the other hand, these power swings are
harmful to distance protection only when they cause impedance
trajectory encroachment on the relay characteristic zones which
is more likely in long transmission lines. In summary, the oc-
currence of asymmetrical power swings is more likely in long
heavily loaded systems

B. Effects of Asymmetrical Power Swings on Distance


Protection
Investigation of distance protection performance during
asymmetrical power swings can be studied using Fig. 1(a),
where phase a is opened following a single-phase to ground
fault. For one of the healthy phases, say phase b, we can con-
clude from (1), (4) and (15) that:
Vbx = Vby + (Zs − Zm )Ib + Zm IE (32)
Vbx − Vby
Ib + K0 IE = (33)
Z1
Vbx 1
ZbE x = V b x −V b y
= Z1 |V b y |
(34) Fig. 6. Time evolution of phase angle and impedance during power swings;
Z1 1− |V b x | ∠ − δ(t) (a) Phase angles and their corresponding impedances; (b) 3-D representation of
impedance trajectory encroachment on the relay third zone for δi n i = 40◦ .
The right-hand side of (34) is based on the assumption that
the angle difference between the voltages of both line ends is
δ(t) and the flow direction is from bus x to bus y. Given that
Kv = |Vby |/|Vbx |, the Cartesian representation of (34) is:
1
ZbE x = Z1 (35)
1 − Kv (cos δ(t) + j sin δ(t))
The real and imaginary parts of ZbE x are yielded as:

⎨ Re(ZbE x ) = R 1 (1−K v cos δ (t))+X 1 K v2 sin δ (t)
1−2K v cos δ (t)+K v
(36)
⎩ Im(ZbE x ) = X 1 (1−K v cos δ (t))−R 1 K v sin δ (t)
1−2K v cos δ (t)+K v2

It is worth mentioning that in practice δin i is maintained below


44° (equal to 30% margin) due to the steady-state stability limit Fig. 7. Impedance trajectories during power swings.
of transmission lines [26], [27]. Fig. 6(a) shows time variation
of δ in (31) for 10◦ < δin i < 44◦ . In this figure, ϕ is π/6, α is pends on how long the related impedance trajectory remains
0.2 and ωn is 2π which equals to the swing frequency of 1 Hz. within the relay zone. This time is mainly affected by the swing
At the same time, the corresponding magnitudes of |ZB E x | are frequency and its severity. In other words, severe power swings
represented in Fig. 6(a) as well as the boundaries of zones 1, 2 whose related impedance trajectory encroaches the first zone of
and 3 for an arbitrary line with total impedance of 40 ohms. It distance relays may result in immediate maloperation of relay
is observed that as δin i increases, the impedance approaches to regardless of the swing frequency. However, for swings inside
the relay zones. Fig. 6(b) illustrates time evolution of impedance the second or third zones, only those slow frequency swings are
trajectory with respect to the relay third zone for δin i = 40◦ . problematic which remain inside the zone longer than the zone
As illustrated, the impedance may encroach several times on the delay time.
relay zone. Variations of ZbE x against power angle δ for different values
It should be noted that maloperation of a distance relay zone of Kv are depicted in Fig. 7, where the line impedance and relay
during either symmetrical or asymmetrical power swings de- characteristics belong to the system simulated in Section III. It is
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2741

observed in this figure that for some values of δ, the impedance


trajectory lies inside the relay characteristics and in the worst
case, it passes through the relay characteristics and proceeds to
the opposite side of RX plane which represent unstable power
swings. It should be noted that the majority of asymmetrical
power swings are stable. However, if a line which is exposed to
asymmetrical power swings operates under SPT condition for a
long dead-time, it may experience unstable swings.
For phase distance relays, it can be shown that during the SPT
of phase a, the impedance seen by phase bc distance relay is
calculated using (1), (13), (15) as:
ΔV
Vbx − Vcx = (α2 − α)V, Ib − Ic = (α2 − α) (37)
Z1
Vbx − Vcx V 1
Zbc = = Z1 = Z1
Ib − Ic ΔV 1 − Kv ∠ − δ(t)
(38)
Considering (18), the following relationships can be extracted
for phases ca and ab.
α2 Z1 α Z1
Zab = · , Zca = ·
Kb 1 − Kv ∠ − δ(t) Kc 1 − Kv ∠ − δ(t)
(39)
The main results of this discussion can be summarized as
follows:
r Since the value of IE in symmetrical power swings is al-
Fig. 8. Proposed earth fault detection algorithm for activating ground distance
most zero, the ground distance relays are not activated and relays; (a) Flowchart; (b) Logic diagram used for generating FDL signal.
thus, they are immune to mal-operation under symmetri-
cal power swings. However, since these relays are activated
during SPT, they may mal-operate in asymmetrical power earth faults by using only the zero sequence current in this con-
swings. dition. For this purpose, the absolute of rate of change of zero
r It can be deduced form (18), (39) and Fig. 4 that during the sequence current (|dI0 /dt|) can be an alternative option, since it
SPT of phase a, distance units of phases ab and ca would rises up suddenly when an earth fault occurs. However, it should
see larger impedances than normal condition and there- be deactivated at the instants of single-pole tripping and reclos-
fore, they are less affected by asymmetrical power swings. ing in which |dI0 /dt| may increase spuriously. The threshold of
However, phase bc distance relay is affected similar to the |dI0 /dt| can be set as equal to 10% of In per second where In is
ground distance relays of bE and cE. the nominal primary current of the line current transformers. In
r As an analogy, in symmetrical power swings, only phase order to increase the reliability of this fault detection technique,
distance relays are involved and it is sufficient to equip PSB function should be activated during asymmetrical power
them with PSB functions. However, in asymmetrical power swings and an abrupt change should occur at least in the current
swings, both phase and ground units are engaged and of one phase.
should have PSB functions. 2) Enhanced Earth Fault Detection Algorithm: Some mod-
ern numerical distance relays employ more sophisticated earth
C. Proposed Solutions to Enhance Distance Protection fault detection algorithms during the SPT condition to restrain
During Asymmetrical Power Swings against the presence of IE . Such an algorithm is introduced in
[22] which is activated when the line is tripped single-pole fol-
It is demonstrated so far that both ground and phase units lowing a single-phase to ground fault. Therefore, the algorithm
of distance relays are affected by asymmetrical power swings. requires to know which phase is opened during SPT. As men-
From the reliability viewpoint, distance relays should be secure tioned earlier, the presence of IE in asymmetrical power swings
to prevent maloperation during power swings and dependable may also affect some adjacent lines which are not tripped. In this
to prevent misoperation and detect the faults in any condition case, the algorithm of [22] is not efficient. To tackle this prob-
regardless of the presence of power swings. In this part, two lem, an enhanced earth fault detection algorithm is proposed as
solutions are proposed to enhance numerical distance protection Fig. 8 which can be used in any condition regardless of SPT.
during asymmetrical power swings. Before running the proposed algorithm, the appropriate phases
1) Fault Detection using the Rate of Change of Zero Se- for fault detection are gathered in a given set like S as:
quence Current: As mentioned earlier, due to the nonzero value
of IE in asymmetrical power swings, it is not secure to detect ∀x = 1, 2, 3 if |Ix | > Im in ⇒ x ∈ {S} (40)
2742 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018

Fig. 9. Modified Kundur’s four-machine system.

where Imin denotes the minimum current used for detecting any
phase opening and can be set as 0.1 × In . For the main faulted
line whose faulted phase (say a) is tripped, |Ia | becomes less Fig. 10. Performance of aE ground distance relays for an SLG fault on phase
than Imin and the corresponding phase a is eliminated from c; Reclosing dead time = (a) 800 ms, (b) 1000 ms.
set S. The maxima and minima of phase voltages and current
are compared with each other according to Fig. 8(a). If there
are considerable differences, an earth fault is detected and the
ground distance relays are activated. It should be noted that in
Fig. 8(a), the fault detection logic (FDL) signal is generated
according to the logic diagram shown in Fig. 8(b), wherein
the load angle criteria block checks the angle |(V{S} /I{S} )|
to see whether or not it is less than the maximum load angle,
typically 30°. Fig. 11. Phase and zero sequence currents during asymmetrical power swing.

IV. SIMULATION RESULTS AND DISCUSSION


In this section, two simulated systems are used to evaluate the
presented analyses. Each of two proposed solutions for distance
protection enhancement during asymmetrical power swings is
tested on one of the simulated systems as follows. Both sys-
tems are simulated in the DIgSILENT Power Factory software
[24] and the proposed methods are carried out in MATLAB
using a personal computer with Intel Core i7 CPU and 8 GB
RAM. Meanwhile, asymmetrical power swings are detected in
the simulated systems by conventional PSB functions used for
Fig. 12. Simulation results for an SLG fault on phase a during asymmetrical
both ground and phase distance relays [4]. For this purpose, in- power swing; (a) Impedance trajectory; (b) Phase and zero-sequence currents.
ner and outer blinders are defined as zone 3 and 1.2 times zone
3, respectively. If the impedance trajectory remains between the
relay operating zones once the faulty phase is opened. Moreover,
outer and inner blinders for more than 40 ms, PSB function is
following the SPT, the impedance trajectory proceeds towards
activated.
the relay operating zones. Fig. 10 demonstrates that power swing
will represent different features depending on the reclosing dead
A. Modified Kundur’s Four-Machine System time. For the shorter dead time, the power swing is likely to
In order to demonstrate the effect of asymmetrical power be stable and the impedance trajectory will exit the relay zones
swings on distance protection, the Kundur’s four-machine sys- after reclosing. However, if the dead time is further extended, the
tem shown in Fig. 9 is used for simulation studies [25] and its system may experience an unstable power swing. This is because
data are given in Appendix. Moreover, the values of loads L5 during the single-pole tripping period, the power angles at line
and L6 are changed to create a heavy load condition for line 5– end buses are moving further apart from each other. Although the
6. This line transfers almost 430 MW from bus 5 to bus 6. The angle difference increase in this case is smaller than that of three-
relay under study is located at beginning of the line on bus 5. pole tripping, it is still possible that such a phenomenon occurs
The simulation scenario is as follows. A single phase-to- in weak areas of the power system. Meanwhile, Fig. 11 shows
ground (SLG) fault with Rf = 0 Ω occurs at t = 1 s at the the magnitudes of currents measured by relay R. As shown,
middle of line 5–6 on phase c. To prevent system separation, similar to the SLG fault condition, there is a considerable zero-
SPT is necessary in this case. The faulty phase is opened at t = sequence current during single-pole tripping, which continues
1.06 s, meaning that the total time required for fault detection to increase.
and circuit breaker opening is assumed to be 60 ms. Then, the One of the main features of PSB functions is how to detect
fault is cleared at t = 1.08 s due to its temporary nature. Finally, faults during power swings. Fig. 12 shows the simulation re-
the opened phase is reclosed after a prescribed dead time. sults for an SLG fault occurring during an asymmetrical power
Fig. 10 shows the simulation results for two different dead swing. In this figure, an asymmetrical power swing appears after
times. In Fig. 10(a), the dead time is 800 ms, while in Fig. 10(b) single-pole tripping of phase c. During this condition, a perma-
it is 1 s. In both cases, the impedance trajectory approaches the nent SLG fault initiates at t = 1.5 s on phase a. Following this
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2743

Fig. 13. Variation of the rate of change of zero-sequence current.

Fig. 14. IEEE 39 Bus New-England System.

fault, the impedance abruptly moves into the relay operating Fig. 15. Simulation results for the IEEE 39 bus system; (a) Impedance seen
zone. This abrupt change is also observed in the zero-sequence by the relay of line 26–29; (b) Currents of line 25–26; (c) Voltages of line 25–26.
current depicted in Fig. 12(b). It can be concluded from Figs. 11
and 12(b) that the net value of zero-sequence current is not an
effective tool to detect earth faults during asymmetrical power
swings. However, Fig. 13 demonstrates that the rate of change Fig. 15(a) shows the impedance seen by the cE distance relay of
of zero-sequence current is able to serve this purpose quite line 26–29 located at bus 29, in which the impedance trajectory
well. As shown, this parameter detects any abrupt change due enters the relay zone due to the asymmetrical power swings
to fault or single-pole switching. Therefore, in order to make emerged after the fault removal.
it suitable to detect the faults that occur during asymmetrical In order to examine the second proposed earth fault detection
power swings, it can be logically combined with a power swing method, consider the three-phase voltages and currents of line
detection method. In other words, the mentioned faults are de- 25–26 which are measured at bus 25 and shown in Fig. 15(b)
tected if a power swing is detected and the rate of change of and (c). During the SPT of line 26–29, the zero sequence current
zero-sequence current exceeds a predetermined threshold. of line 25–26 is greater than zero which can result in starting
ground distance units. Using the proposed earth fault detec-
tion, max(|Ia |, |Ib |, |Ic |) is greater than 2 × min(|Ia |, |Ib |, |Ic |)
B. IEEE 39 Bus System
during SPT. However, at the same time max(|Va |, |Vb |, |Vc |) is
The IEEE 39 bus system, as shown in Fig. 14, contains 34 lines less than 1.5 × min(|Va |, |Vb |, |Vc |). Once an earth fault occurs
among which lines 26–29 and 26–28 are the longest ones and on phase a of line 25–26 at t = 2 s, max(|Va |, |Vb |, |Vc |) be-
line 26–28 is assumed to be out of service. Thus, generator G9 is comes greater than 1.5 × min(|Va |, |Vb |, |Vc |). Therefore, the
connected to the rest of the grid via line 26–29 which transfers proposed combination of current and voltage signals in earth
about 330 MW from bus 29 to 26. Under this condition, an fault detection method makes the relays of the main line and its
SLG fault on phase a with Rf = 0 Ω is applied at the middle adjacent lines immune to activation of earth fault units during
of line 26–29 at t = 1 s and this phase is opened at t = 1.1 s. SPT condition.
2744 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 6, DECEMBER 2018

TABLE I
EVALUATION OF EXISTING POWER SWING BLOCKING/UNBLOCKING SCHEMES
FOR ASYMMETRICAL POWER SWINGS APPLICATIONS

Methodology Applicable in Setting


Asymmetrical Free
Power Swings

Conventional blinder scheme [4] No No


Wavelet transform [7] Yes No
Traveling waves [5] No No
Moving window averaging [8] No Yes
Swing center voltage tracer [6] No Yes
Modified concentric characteristic [28] Yes No
Admittance circular trajectory [29] Yes No
SVM classifier [11] No No
Differential power [30] Yes No
Negative sequence current [31] No No
Dynamic phasor transient [17] Yes No
Taylor series [32] Yes No
Instantaneous active power [18] No No Fig. 17. Investigation of fault detection methods proposed in [18] and [19]
Change of active/reactive power [19] No No during SPT; (a) Magnitude of FFT of active power for line 17–27; (b) Rates of
Proposed dI0 /dt Method Yes No changes of active and reactive powers for line 17–27.
Proposed Earth Fault Detection Method Yes Yes

of fast Fourier transform (FFT) of three-phase active power


during normal condition and symmetrical power swings have
negligible variations; while following three-phase faults, it rises
considerably. A similar relationship has been used in [19] for the
rates of changes of three-phase active and reactive powers. Both
of these methods work well during symmetrical power swings.
However, during SPT and asymmetrical power swings, they may
cause undesired results. This issue is shown by evaluating these
methods during a simple SPT condition without remarkable
power swings. In doing so, line 26–28 in Fig. 14 is closed and
Fig. 16. Simulation results for SPT of line 17–27 following an SLG fault. line 17–27 as a medium length and lightly loaded line is selected
for study. During normal condition, this line is loaded by about
7%. An SLG fault is applied at t = 1 s at the middle of phase
C. Comparison With Other Methods
a of line 17–27 and removed at t = 1.1 s by SPT of the faulty
The presented simulation results demonstrated the better per- phase. The SPT condition is established until t = 2 s.
formance of proposed fault detection methods during asymmet- Fig. 16 shows the three-phase active and reactive powers of
rical power swings in comparison with some commercial relays. line 17–27 during pre-fault and post-fault conditions. As shown,
For instance, Figs. 12 and 13 showed that the zero sequence cur- these powers are almost fixed during pre-fault condition and rep-
rent, which is used in [4], is not an appropriate parameter for resent remarkable variations during SPT. Fig. 17(a) and (b) illus-
fault detection during asymmetrical power swings, but its rate trate the magnitude of FFT of active power and rates of changes
of change is proper for this purpose. Moreover, it was shown in of active and reactive powers, respectively. As observed, both
Fig. 15 that the second proposed method can effectively detect of these variables have considerable variations during SPT. It
earth faults during asymmetrical power swings in the faulty line should be noted that these variations are mainly due to the open-
and its adjacent lines which is more beneficial than the method ing of one phase, since the created asymmetrical power swings
used in [22]. in this case are negligible. Consequently, these methods may
Table I presents results of evaluating some existing power Result in relay maloperation during SPT and asymmetrical
swing blocking/unblocking schemes for using in case of asym- power swings.
metrical power swings. As shown, some methods are not effi-
cient for asymmetrical power swings applications due to relying
on all phases data or using zero sequence current. Meanwhile, V. CONCLUSION
some methods including the second proposed method are set- In this paper, effects of asymmetrical power swings on dis-
ting free, while others require settings. The procedure of setting tance protection were analyzed in detail. It was shown that in
calculation in some methods like the first proposed method is heavily loaded power systems, single-pole tripping of faulty
simple. However, some methods like [17], [18] and [32] need phase may induce power swings on healthy phases. During this
simulation studies for setting calculations. period, since one phase of transmission line is out of service,
For more investigation, performances of two worthy methods there would be a zero-sequence current flow under non-faulted
introduced in [18] and [19] are examined. Method [18] is based conditions. This circumstance makes it difficult to detect earth
on the three-phase active power. It is shown that the magnitude faults which might occur during asymmetrical power swings.
HASHEMI AND SANAYE-PASAND: DISTANCE PROTECTION DURING ASYMMETRICAL POWER SWINGS: CHALLENGES AND SOLUTIONS 2745

TABLE A-I [6] G. Benmouyal, D. Tziouvaras, and D. Hou, “Zero-setting power-swing


PARAMETERS OF THE MODIFIED KUNDUR’S FOUR-MACHINE SYSTEM blocking protection,” in Proc. 31st Annu. Western Protective Relay Conf.,
Spokane, WA, USA, Oct. 19–21, 2004, pp. 1–31.
[7] S. Brahma, “Distance relay with out of step blocking function using
Parameter Value Parameter Value wavelet transform,” IEEE Trans. Power Del., vol. 22, no. 3, pp. 1360–
1366, Jul. 2007.
G1 to G4: T1 to T4:
[8] J. G. Rao and A. K. Pradhan, “Power-swing detection using moving win-
X l (p.u.) 0.14 Ratio (KV) 20/230
dow averaging of current signals,” IEEE Trans. Power Del., vol. 30, no. 1,
X d (p.u.) 2.01 S n (MVA) 2 × 450
pp. 368–376, Feb. 2015.
X q (p.u.) 1.89 L5:
[9] S. Das, R. Dubey, B. Panigrahi, and S. Samantaray, “Secured zone-3 pro-
X d (p.u.) 0.21 P n (MW) 967
tection during power swing and voltage instability: an online approach,”
X q (p.u.) 0.34 Q n (MVAr) 100 IET Gener. Transmiss. Distrib., vol. 11, no. 2, pp. 437–446, 2017.
X d (p.u.) 0.16 L6: [10] R. Dubey, S. R. Samantaray, B. K. Panigrahi, and V. G. Venkoparao,
“Phase-space-based symmetrical fault detection during power swing,” IET
X q (p.u.) 0.17 P n (MW) 1810 Gener. Transmiss. Distrib., vol. 10, no. 8, pp. 1947–1956, 2016.
T d (s) 1.08 Q n (MVAr) 100 [11] N. Chothani, B. Bhalja, and U. Parikh, “New support vector machine-
T q (s) 0.18 Lines: based digital relaying scheme for discrimination between power swing
and fault,” IET Gener. Transmiss. Distrib., vol. 8, no. 1, pp. 17–25, 2014.
T d (s) 0.018 Z 1 (Ω/km) 0.061 + j0.402 [12] R. Dubey and S. Samantaray, “Wavelet singular entropy-based symmet-
T q (s) 0.018 Capacitors: rical fault-detection and out-of-step protection during power swing,” IET
H (s) 5 Q C 5 (MVAr) 200 Gener. Transmiss. Distrib., vol. 7, no. 10, pp. 1123–1134, 2013.
S n (MVA) 4 × 255 Q C 6 (MVAr) 350 [13] A. Mahari, M. Sanaye-Pasand, and S. M. Hashemi, “Adaptive phasor es-
timation algorithm to enhance numerical distance protection,” IET Gener.
Transmiss. Distrib., vol. 11, no. 5, pp. 1170–1178, 2017.
Meanwhile, ground distance relays may be activated due to [14] J. A. de la O Serna, “Dynamic phasor estimates for power system os-
cillations,” IEEE Trans. Instrum. Meas., vol. 56, no. 5, pp. 1648–1657,
the presence of mentioned zero sequence current and operate Oct. 2007.
spuriously following the impedance trajectory variations dur- [15] R. K. Mai, L. Fu, Z. Y. Dong, K. P. Wong, Z. Q. Bo, and H. B. Xu, “Dy-
ing asymmetrical power swings. Therefore, a more inclusive namic phasor and frequency estimators considering decaying DC compo-
nents,” IEEE Trans. Power Syst., vol. 27, no. 2, pp. 671–681, May 2012.
power swing blocking function suitable for both symmetrical [16] S. Vejdan, M. Sanaye-Pasand, and O. P. Malik, “Accurate dynamic pha-
and asymmetrical power swings should be implemented on each sor estimation based on the signal model under off-nominal frequency
phase independently. To be as reliable as possible, this function and oscillations,” IEEE Trans. Smart Grid, vol. 8, no. 2, pp. 708–719,
Mar. 2017.
should detect faults using features other than the net value of [17] J. Khodaparast and M. Khederzadeh, “Three-phase fault detection during
zero-sequence current. power swing by transient monitor,” IEEE Trans. Power Syst., vol. 30,
The main achievements of this paper are summarized as: no. 5, pp. 2558–2565, Sep. 2015.
r Ground distance relays might undesirably get started and [18] B. Mahamedi and J. Zhu, “A novel approach to detect symmetrical faults
occurring during power swings by using frequency components of instan-
operate during asymmetrical power swings. Therefore, taneous three-phase active power,” IEEE Trans. Power Del., vol. 27, no. 3,
these relays should be equipped by PSB functions as well. pp. 1368–1376, Jul. 2012.
r To detect power swing condition caused by the SPT of [19] X. Lin, Y. Gao, and P. Liu, “A novel scheme to identify symmetrical faults
occurring during power swings,” IEEE Trans. Power Del., vol. 23, no. 1,
transmission lines, PSB functions should be implemented pp. 73–78, Jan. 2008.
on each phase independently. There would be no symmetry [20] D. A. Tziouvaras and D. Hou, “Out-of-step protection fundamentals and
advancements,” in Proc. 30th Annu. Western Protective Relay Conf.,
in the voltage and current oscillations of all three phases Oct. 2003, pp. 1–27.
during asymmetrical power swings. [21] T. J. E. Miller, Reactive Power Control in Electric Systems. New York,
r It was shown that the change of rate of zero-sequence NY, USA: Wiley, 1982.
[22] SIEMENS AG, “Distance Protection 7SA522 V4.74: Manual,” 2016.
current is a good index for detection of earth faults dur- [23] J. Machowski, J. W. Bialek, and J. R. Bumby, Power System Dynamics,
ing asymmetrical power swings. Moreover, a new fault Stability and Control, 2nd ed. Chichester, U.K.: Wiley, 2008.
detection method is proposed which can reliably detect [24] DIgSILENT GmbH, “DIgSILENT Power Factory,” Version 15, 2014.
[25] P. Kundur, Power System Stability and Control. New York, NY, USA:
earth faults in any condition including asymmetrical power McGraw-Hill, 1994.
swings. [26] R. D. Dunlop, R. Gutman, and P. P. Marchenko, “Analytical development
of loadability characteristics for EHV and UHV transmission lines,” IEEE
Trans. Power App. Syst., vol. PAS-98, no. 2, pp. 606–613, Mar. 1979.
APPENDIX [27] D. Lauria, G. Mazzanti, and S. Quaia, “The loadability of overhead trans-
mission lines—Part I: analysis of single circuits,” IEEE Trans. Power Del.,
Parameters of the modified Kundur’s four machine system vol. 29, no. 1, pp. 29–37, Feb. 2014.
are given in Table A-I. [28] X. Lin, Z. Li, S. Ke, and Y. Gao, “Theoretical fundamentals and im-
plementation of novel self-adaptive distance protection resistant to power
swings,” IEEE Trans. Power Del., vol. 25, no. 3, pp. 1372–1383, Jul. 2010.
REFERENCES [29] R. Jafari, N. Moaddabi, M. Eskandari-Nasab, G. B. Gharehpetian, and M.
S. Naderi, “A novel power swing detection scheme independent of the rate
[1] “Power swing and out-of-step considerations on transmission lines,” IEEE of change of power system parameters,” IEEE Trans. Power Del., vol. 29,
PSRC WG D6, Jul. 2005. [Online]. Available: www.pes-psrc.org no. 3, pp. 1192–1202, Jun. 2014.
[2] NERC, “Protection system response to power swing,” Aug. 2013. [On- [30] J. G. Rao and A. K. Pradhan, “Differential power-based symmetrical fault
line]. Available: www.nerc.com detection during power swing,” IEEE Trans. Power Del., vol. 27, no. 3,
[3] G. Ziegler, Numerical Distance Protection: Principles and Applications, pp. 1557–1564, Jul. 2012.
4th ed. New York, NY, USA: Wiley, 2011. [31] P. K. Nayak, A. K. Pradhan, and P. Bajpai, “A fault detection technique
[4] ABB Power Technologies, “Technical reference manual: Line distance for the series-compensated line during power swing,” IEEE Trans. Power
protection terminal REL 521∗2.5,” Dec. 2006. Del., vol. 28, no. 2, pp. 714–722, Apr. 2013.
[5] C. Pang and M. Kezunovic, “Fast distance relay scheme for detecting [32] I. G. Tekdemir and B. Alboyaci, “A novel approach for improvement of
symmetrical fault during power swing,” IEEE Trans. Power Del., vol. 25, power swing blocking and deblocking functions in distance relays,” IEEE
no. 4, pp. 2205–2212, Oct. 2010. Trans. Power Del., vol. 32, no. 4, pp. 1986–1994, Aug. 2017.

You might also like