Professional Documents
Culture Documents
net/publication/321731148
CITATIONS READS
0 242
3 authors, including:
All content following this page was uploaded by Eduardo Mojica-Nava on 11 December 2017.
40 40 DOI: 10.17533/udea.redin.n85a05
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
This work presents a state estimation algorithm for DS The probability distribution function of each component of
and distributed generation feeding an external network η is usually assumed as a normal distribution. In addition,
41
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
it is assumed that the measurements are random and The minimum is obtained when Eq. (9) is satisfied.
independent. To estimate the unknown state vector x,
a weighted least squares function, presented in Eq. (2), ui = φ−1
i yi , i = 1, . . . , n (9)
must be minimized (13).
Finally, from (9) and the definition u = V T ∆x, multiplying
by V and using the orthogonality of V Eq. (10) is obtained.
∑
m
[zi − hi (x)]
2
min J(x) = (2) ∆x = V ui (10)
x
i=1
σi2
Here, J(x) is the weighted measurement residual, σi is
the standard deviation of each measurement and reflects 3. Numerical Observability in
meter accuracy (14). A linearized matrix formulation of (2) Distribution Systems
is given by Eq. (3),
The observability analysis ensures that the system state
min J(x) = ||W − 2 (z − Hx)||2
1
42
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
In DS, it is assumed that X ≈ R. This, at first glance, The S phasor can be rotated on the complex plane by using
suggests that it is not possible to decouple the active the transformation matrix. Applying the matrix T to (14)
power from the reactive power, as it is often done in large and (15), are obtained Eqs. (20) and (21):
power systems (12). However, using an orthogonal linear
′
rotational transformation matrix T , it is possible to obtain Z Pkl
sin δkl = , (20)
a decoupled relationship between the state variables and Vk Vl
power flows (17). This can be applied in DS. In this sense,
the cosine is eliminated from (12) and (13), obtaining Eq.
ZQ′kl
Vk − Vl cos δkl = . (21)
(14): Vk Vl
In (20) and (21) it may be seen that the active modified
XPkl − RQkl power flow could be decoupled from the reactive modified
sin δkl = . (14)
Vk Vl power flow. This suggests that the observability analysis
In the same way, the sine can be eliminated, obtaining Eq. for DS’s can be done in a similar way as in high voltage
(15): systems. To implement the observability analysis the
transformation matrix T must be applied on each node of
RPkl + XQkl the DS, because the angle δkl varies for each one.
Vk − Vl cos δkl = . (15)
Vk
To linearize the observability analysis, the decoupled (DC)
In Figure 2, S ′ is the orthogonal linear rotational state estimation can be used. The DCSE has the same
transformation for complex power S . DC load flow’s features (12; 13). For the DCSE in DS it is
assumed:
Im Im
′ • A flat voltage profile: V = 1.0 p.u. and δ = 0◦ .
(−Pkl , Q′kl )
(R, X)
• The impedance magnitude is Z = 1.0 p.u..
ϕ − δkl
′
Pkl = −S ′ sin(ϕ − δkl ), (18) min J(x) = [z − [H]x]T [W −1 ][z − [H]x] (25)
x
43
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
the DS is unobservable. Using Eq. (26) one iteration of the The DS shown in Figure 3a is numerically observable
DCSE is calculated (12; 19). because there are five state variables which are linearly
independent. However, the solution is not unique due to
G0δ δ = HPT ′ δ WP−1
′ zP ′ (26) nonlinearity.
The SE for DS has an unique solution if, and only if, Eq. (26)
is satisfied for δ , which is the same as G0δ is nonsingular. 3.3 Phasor Measurement Units
Then a radial DS is observable if the decoupled gain matrix
has full rank as in Eq. (27). The voltage and branch current phasors can be measured
with a PMU (22). The branch current phase angle αln
(Gδ ) > n − 1 (27) is measured with respect to the voltage phase angle at
slack node k . The PMU is synchronized respect to cosine
function at the system’s nominal frequency (7).
3.2 Branch Current Measurements
In large power systems, the SE uses power flow, power In radial DS, shown in Figure 4a, branch
injection and voltage magnitude measurements (14). The current
[ phasors are chosen ] as state variables:
line current magnitude measurements are commonly αkl αlm αln Ikl Ilm Iln . To measure a
used to increase redundancy. In DS, branch current branch current phasor, a PMU is used. With conventional
magnitude measurements are widely used, instead of measurements and the PMU, this DS is numerically
power measurements. observable because there are as many independent pairs
of measurements of P and Q as branches. Here the PMU
When only magnitude measurements are available, the increases the redundancy.
system can have multiple solutions for some state
variables (20; 21). In the DS shown in Figure 3a, it is In the DS shown in Figure 4b, it is assumed that the power
assumed that the region of system inside the ellipse is flow measurement at node n has been removed and the
observable by using power flow measurements. Thus PMU is placed at node l. Thus, the active and reactive
the angle δl is unknown and can be estimated using power injections at node l are known. Then the Jacobian
current and voltage magnitude measurements. The matrix becomes in Eq. (28):
phasor diagram for the DS is shown in Figure 3b. Points
p1 and p2 are two possible solutions for the voltage phasor P n Qn
Iln ∠αln n PMU
Ṽk . In the same way, the phase angle δl has two possible
solutions. Vk ∠δk
k l m
Pk Qk Pm Qm
l Ikl
k
(a) PMU as a redundant measurement
Vl
Iln ∠αln n
m Vk ∠δk PMU
V oltage magnitude meter. k l m
Branch current magnitude meter. P k Qk P l Ql
(a) Distribution system
(b) PMU as a critical measurement
Vk ∂P ∂Pk
∂αkl
k
0 0 ∂Ikl 0 0
0 ∂Pl ∂Pl ∂Pl ∂Pl
I˜kl Z̃kl 0 ∂Iln
∂Qk ∂αlm ∂αln ∂Ilm
0 0 ∂Qk
0 0
p2 Hα,I = ∂αkl ∂Ikl
∂Ql
,
Ṽl 0 ∂Ql ∂Ql
0 ∂Ql
∂αlm ∂αln ∂Ilm ∂Iln
0 0 1 0 0 0
0 0 0 0 0 1
(b) Phasor diagram (28)
and the system gain matrix is the Eq. (29).
Figure 3 DS and SE with two possible solutions (20)
44
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
( )2 ( )2
∂Pk ∂Qk ∂Pk ∂Pk ∂Qk ∂Qk
∂αkl + ∂αkl 0 0 ∂αkl ∂Ikl + ∂αkl ∂Ikl 0 0
( )2 ( )2
∂Pl ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql
0 ∂αlm + ∂αlm +1 ∂αlm ∂αln + ∂αlm ∂αln 0 ∂αlm ∂Ilm + ∂αlm ∂Ilm ∂αlm ∂Iln + ∂αlm ∂Iln
( )2 ( )2
∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql
0 + + 0 + ∂αln ∂Iln + ∂αln ∂Iln
∂αlm ∂αln ∂αlm ∂αln ∂αln ∂αln ∂αln ∂Ilm ∂αln ∂Ilm
Gα,I =
( )2 ( )2
(29)
∂Pk ∂Pk
∂α ∂I + ∂Qk ∂Qk
0 0 ∂Pk
+ ∂Ql
0 0
kl kl ∂αkl ∂Ikl ∂Ikl ∂Ikl
( )2 ( )2
∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql
0 ∂αlm ∂Ilm + ∂αlm ∂Ilm ∂αln ∂Ilm + ∂αln ∂Ilm 0 ∂Ilm + ∂Ilm +1 ∂Ilm ∂Iln + ∂Ilm ∂Iln
( )2 ( )2
∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Pl ∂Ql ∂Ql ∂Pl ∂Ql
0 ∂αlm ∂Iln + ∂αlm ∂Iln ∂αln ∂Iln + ∂αln ∂Iln 0 ∂Ilm ∂Iln + ∂Ilm ∂Iln ∂Iln + ∂Iln
The gain matrix (Gα,I ), is nonsingular, because its • Branch power measurements
determinant is not zero, as can be checked in Eq. (30).
Pkl +jQkl = Vk Ikl [cos(δk − αkl ) + j sin(δk − αkl )] .
(31)
( )2 ( )2 • Power injection measurements
det(Gα,I ) = ∂Pk ∂Qk
− ∂Pk ∂Qk ∂Pl ∂Ql
− ∂Pl ∂Ql
∂αkl ∂Ikl ∂Ikl ∂αkl ∂Iln ∂αln ∂αln ∂Iln
( )∗
(30) ∑
m ∑
n
Pk + jQk = Ṽk I˜ik − I˜ki . (32)
i=1 i=m+1
The branch current magnitude and phase angle are linearly
independent such as the power injection measurements
• Voltage magnitude measurements
at the nodes k and l. Consequently, the system is
numerically observable and the branch current phasor is ∑
n+1
a critical measurement. If the PMU is removed from the Ṽn+1 = Ṽ0 − I˜i−1,i Z̃i−1,i . (33)
measurement set, the system will be unobservable (22). i=1
In short, the solution for the SE is unique when the branch • Branch current phasor measurements
current phase angle αkl is known. See the dashed phasor
in the phasor diagram shown in Figure 3b. Ikl ∠αkl = Ikl ∠αkl . (34)
45
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
were simulated and the results averaged. The DS used is Power Measurements
the IEEE 13 nodes test feeder, to which a DGEN can be
The branch current phasors were estimated with a set
connected. In the simulation, different measurements sets
formed by n pairs of power measurements and power
were used and observability analysis results were applied.
pseudo-measurements. In Figure 6a, a histogram for the
The load flow solution for the DS and DGEN was run in
voltage magnitude errors is shown. The absolute error is
PSE ®. This solution is taken as the real value of the state
less than 0.5% for all nodes of the system.
variables. The data of the IEEE 13 nodes test feeder were
used as measurements, by adding a random noise signal.
In the test system, the voltage angle is very small (ie.
The noise is the simulated error in measurements and was
assumed normally distributed. For the measurements,
−2◦ ≤ δ ≤ 0◦ ), thus the difference between real and
estimated values can result in large errors, mainly in
the maximum error can be up to ±6% of the exact value.
those nodes where the voltage phase angle is close to 0◦ .
For the pseudo-measurements, the maximum error can be
In Figure 6b it is shown the histogram of the difference
up to ±45% of the exact value. All the algorithms were
between real and estimated voltage phase angles. This
simulated in Matlab ®.
difference is less than |0.25|◦ .
The single phase diagram for the DS and the DGEN is 500
redundancy.
(a) Voltage magnitude error
5 MVA
4.16 kV 600
1 650
4 3 5 6
1 500
5
3 2 4
2 632
6
300
9 8 12 13
8 7 11 12 200
7 671
9
611 10 684 692 675 100
11 652 10 680
RC
0
−0.25 −0.2 −0.15 −0.1 −0.05 0 0.05 0.1 0.15 0.2 0.25
(δ−δest) [deg]
2 MVA
2 MVA 13 0.48 kV
4.16/0.48 kV
15 16 G
14 15 (b) Voltage phase angle difference
14 19
17
16 17
18 18 Figure 6 Histogram, n pairs of power measurements and
pseudo-measurements
46
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
the histogram for the voltage magnitude error and the in the system; in consequence, all measurements are
voltage phase angle difference. Despite the fact that the critical. In figure 5, a PMU has been connected at node
measurement set has fewer measures than in the previous 2. In nodes 5 and 6 it is assumed that there are no
case, the results are similar since the voltage magnitude measurements or pseudo-measurements. The Figure 8
error is less than |0.5|% (Figure 7a), and the difference shows the histogram for the voltage magnitude error and
between real and estimated voltage phase angle is less voltage phase angle difference.
than |0.25|◦ (Figure 7b).
600
600
500
500
400
400
Frequency
Frequency
300
300
200
200
100
100
0
0 −0.3 −0.2 −0.1 0 0.1 0.2 0.3
−0.5 −0.4 −0.3 −0.2 −0.1 0 0.1 0.2 0.3 0.4 0.5
Error [%]
Error [%]
700
700
600
600
500
500
400
Frequency
400
Frequency
300
300
200
200
100
100
0
0 −0.2 −0.15 −0.1 −0.05 0 0.05 0.1 0.15 0.2
−0.25 −0.2 −0.15 −0.1 −0.05 0 0.05 0.1 0.15 0.2 0.25 (δ−δest) [deg]
(δ−δest) [deg]
(b) Voltage phase angle difference (b) Voltage phase angle difference
Figure 7 Histogram, (n − 1) pairs of power measurements and Figure 8 Histogram, PMU in the measurements set
pseudo-measurements
When the PMU is included, the accuracy of the SE
increases, because the voltage magnitude error decreased
Phasor Measurements Units from |0.5|% to |0.3|% and the difference in voltage phase
angle is in the range −0.15◦ ≤ δ − δest ≤ 0.20◦ . Table
From the observability analysis in a radial DS, two pairs 1 shows the maximum absolute average error when the
of P and Q measurements can be replaced by a PMU, if PMU is used. This reduction is, undoubtedly, due mainly
it is located in the previous node (l), see Figure 4b. Thus, to the fact that the PMU has a lower inherent error, with a
the PMU must measure both, the power injected and the standard deviation σmag = 0.00067 and σang = 0.00097,
branch current phasor in one of the existing branches compared to the values of the conventional measurement
between node (l) and downstream nodes (m or n). that has σ = 0.0125. Nevertheless, the errors are smaller.
By adding a PMU to measure the branch current phasor, To study the influence of the PMU location in the SE
there exist as many pairs of measurements as branches performance, the location was changed, keeping the
47
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
δ 5 0.4355
0.6
Error [%]
measurements and pseudo-measurements was increased 0.2
to values close to the maximum allowed ±6% and ±45%
respectively. The maximum error is summarized in the 0
Table 2.
−0.2
nodes (9 and 11) have the greater errors for the voltage
0 2 4 6 8 10 12 14 16 18 20
Node
5.2 State Estimation Applications to Figure 9 Error when PMU location is changed
Distributed Generation
The SE outputs are used to compute the system total
operation is re-synchronization with an external system
losses. Thus, the DS behavior could be assessed when
(25). This is a necessary condition to change operation
DGEN is connected as a new load. In the same way, the SE
from off-grid to grid mode. If voltages at the PCC are not
data are used to implement another proposed algorithm to
synchronized when the switch is closed, high currents can
re-synchronize the DGEN to the DS, this algorithm can be
occur, affecting the power quality in both DS and DG grid
used as a MG self-healing function.
(8; 6). For the simulation, the DG is composed by a Diesel
generator. In off-grid mode the DG feeds an external
Prediction of Losses network (DGEN).
The total DS losses can be estimated using the SE results.
Figure 10 shows the total DS loss histogram. Active To re-synchronize the DGEN to the DS, it is assumed that
and reactive power loss errors are less than 8%. This the DGEN was connected to the DS. Next, the DGEN is
percentage is an acceptable value especially taking into removed from the DS and starts to operate in off-grid
account that the pseudo-measurement error can be as mode. Then, the DGEN can be re-synchronized to the
large as ±45%. DS. Under these conditions the DGEN re-synchronization
is carried out at the PCC.
48
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
Vref
25
20 Vf ie sTC +1 1
0 KA Vf ie
KA sTB +1 sTA +1
15
Frequency
1
sTR +1 Vsta Ista
10
12
DGEN and DS. It is observed that restrictions were
Frequency
0
−8 −6 −4 −2 0 2 4 6 For reference, Figure 15a shows the branch current and
8
were taken from (26). The generator impedances were When the DGEN and DS are coupled, the system reliability
adjusted to 60 Hz. The automatic voltage regulator improves. For example, if the generator in the DGEN has
(AVR) is a modification of IEEE AC4 model. For each enough capacity, it is possible to export active and reactive
controller, block diagrams are shown in Figures 11 and power to DS. This task can be fulfilled with the
12. In the synchronization, the AVR reference is modified synchronous machine control in the DGEN. The active and
in accordance with the estimated state variables. The reactive power in both sides of the system are shown in
governor holds the frequency in the DGEN constant. Figure 16b. After the connection, both sources continue
feeding their own loads. When the voltage phase
reference in the AVR is changed to 1.0 p.u., the DGEN
Figure 13a shows the voltage magnitude and angle at the
exports reactive power to DS. Similarly, an increase in
PCC, in the DS and the DGEN sides (see Figure 5). The
active power generation in the DGEN can be exported to
voltage magnitude difference is Vkl = 0.0615 p.u., and the
DS. These changes in the reference parameters for the
voltage phase angle difference is δkl > 10◦ . For the DG
generation in the DGEN, lead to an improved voltage
rating, the restrictions of the Standard IEEE 1547 (27) are
profile of the system, as shown in Figure 16a.
not satisfied. Since, for a 2 [MVA] generator the maximum
allowed differences are Vkl < 3% and δkl < 10◦ . The
synchronous machine variables in off-gride mode are 6. Conclusions
shown in Figure 13b, the voltage magnitude is 1.0 p.u. and
phase angle is 0◦ . With the use of PMUs in radial DS, the system observability
can be ensured, if there are enough pairs of P and
The re-synchronization process is described as follows: Q measurements.
49
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
sT3 +1 sT4 +1 1 1
e−sTD
wref K Pmec
s2 T1 T2 +sT1 +1 sT5 +1 sT6 +1 s
−
b
∆w
|V| [p.u.]
0.9865 0.924
0 2 4 6 8 10 12 14 16 18 20
Volltage phase angle PCC DGEN side
0.922
29.35
Deg
0.92
0 5 10 15 20 25 30 35 40
29.3
0 2 4 6 8 10 12 14 16 18 20
Voltage magnitude PCC DS side
0.925 Phase angle difference
−3.4
p.u.
0.925
−3.6
0.925
0 2 4 6 8 10 12 14 16 18 20 −3.8
Deg
Volltage phase angle PCC DS side
−3.7438 −4
−3.7438
Deg
−4.2 DGEN
−3.7438 DS
−3.7438 −4.4
0 2 4 6 8 10 12 14 16 18 20 0 5 10 15 20 25 30 35 40
Time Time
1 1
1 0.9995
0 2 4 6 8 10 12 14 16 18 20 0 5 10 15 20 25 30 35 40
Mechanical Power Mechanical Power
0.4564 0.458
0.4564 0.4575
p.u.
p.u.
0.4564 0.457
0.4564 0.4565
0 2 4 6 8 10 12 14 16 18 20 0 5 10 15 20 25 30 35 40
Field Voltage Field Voltage
2.4
2.2668
2.35
2.2668
V
V
2.2668 2.3
2.2668 2.25
0 2 4 6 8 10 12 14 16 18 20 0 5 10 15 20 25 30 35 40
Stator Voltage Stator Voltage
1 0.94
p.u.
p.u.
1 0.935
1 0.93
0 2 4 6 8 10 12 14 16 18 20 0 5 10 15 20 25 30 35 40
Time Time
50
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
12 0.96
|V| [p.u.]
0.95
10 0.94
0.93
Branch current [A]
DGEN
8 DS
0.92
0 5 10 15 20 25 30 35 40 45 50
6
Phase angle at PCC
0
4 −1
−2
Deg
2
−3
−4 DGEN
0 DS
0 5 10 15 20 25 30 35 40
−5
Time 0 5 10 15 20 25 30 35 40 45 50
Time
P [p.u].
0.15
60.02
0.1
60.015
Frequency [Hz]
0.05
60.01 0 5 10 15 20 25 30 35 40 45 50
60.005
0.15 DGEN
60 Q [p.u.] DS
59.995 0.1
59.99
0.05
59.985
0 2 4 6 8 10 12 14 16 18 20
Time 0 5 10 15 20 25 30 35 40 45 50
Time
7. References
[1] C. M. Colson, M. H. Nehrir, and R. W. Gunderson, “Distributed [8] C. Cho, J. H. Jeon, J. Y. Kim, S. Kwon, K. Park, and S. Kim, “Active
multi-agent microgrids: a decentralized approach to resilient power synchronizing control of a microgrid,” IEEE Transactions on Power
system self-healing,” in 4th International Symposium on Resilient Electronics, vol. 26, pp. 3707–3719, 2011.
Control Systems, Boise, USA, 2011, pp. 83–88. [9] F. Mahmood, H. Hooshyar, J. Lavenius, A. Bidadfar, P. Lund,
[2] A. Gómez-Expósito, A. Abur, A. de la Villa Jaen, and C. Gómez-Quiles, and L. Vanfretti, “Real-time reduced steady-state model synthesis
“A multilevel state estimation paradigm for smart grids,” of active distribution networks using pmu measurements,” IEEE
Proceedings of the IEEE, vol. 99, pp. 952–976, 2011. Transactions on Power Delivery, vol. 32, pp. 546–555, 2017.
[3] S. Choi and A. P. S. Meliopoulos, “Effective real-time operation [10] S. R. Samantaray, I. Kamwa, and G. Joos, “Phasor measurement
and protection scheme of microgrids using distributed dynamic unit based wide-area monitoring and information sharing between
state estimation,” IEEE Transactions on Power Delivery, vol. 32, pp. micro-grids,” IET Generation, Transmission Distribution, vol. 11, pp.
504–514, 2017. 1293–1302, 2017.
[4] Y. F. Huang, S. Werner, J. Huang, N. Kashyap, and V. Gupta, [11] R. E. Larson, W. F. Tinney, and J. Peschon, “State estimation in power
“State estimation in electric power grids: Meeting new challenges systems part i: Theory and feasibility,” IEEE Transactions on Power
presented by the requirements of the future grid,” IEEE Signal Apparatus and Systems, vol. PAS-89, pp. 345–352, 1970.
Processing Magazine, vol. 29, pp. 33–43, 2012. [12] A. Monticelli and F. F. Wu, “Network observability: Theory,” IEEE
[5] D. A. Haughton and G. T. Heydt, “A linear state estimation Power Engineering Review, vol. PER-5, no. 5, pp. 1042–1048, 1985.
formulation for smart distribution systems,” IEEE Transactions on [13] A. J. Wood and B. F. Wollenberg, Power generation, operation, and
Power Systems, vol. 28, pp. 1187–1195, 2013. control, 1st ed. New York, USA: John Wiley & Sons, 1984, pp.
[6] Z. Wang, B. Chen, J. Wang, and C. Chen, “Networked microgrids for 391–426.
self-healing power systems,” IEEE Transactions on Smart Grid, vol. 7, [14] A. Abur and A. Gómez Expósito, Power system state estimation: theory
pp. 310–319, 2016. and implementation, 1st ed. New York, USA: Marcel Dekker, Inc.,
2004.
[7] G. N. Korres and N. M. Manousakis, “State estimation and
observability analysis for phasor measurement unit measured
systems,” IET Generation, Transmission Distribution, vol. 6, pp.
902–913, 2012.
51
F.A. Bermúdez-Calderón et al., Revista Facultad de Ingeniería, No. 85, pp. 40-52, 2017
52
View publication stats